Вы находитесь на странице: 1из 18

Installation and Maintenance Manual IM 835

Group: Applied Systems

Part Number: IM 835

Date: March 2006

Enthalpy Energy Recovery Wheel Option


McQuay Applied RoofPak™ Systems
Heating and Cooling Units and Rooftop Air Handlers

Type RPR/RFR/RDR 015C-075C, RAR 800C-802C and 47C

© 2006 McQuay International


Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Drive Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Drive Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Variable Frequency Controller . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wheel Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Purge and Pressurization . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Enthalpy Wheel Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Drive Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Frost Protection Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Variable Speed Frequency Control . . . . . . . . . . . . . . . . . . . . . 4 MicroTech II Sequence of Operation . . . . . . . . . . . . . . 9
Alternate Frost Protection Measures . . . . . . . . . . . . . . . . . . . . 4 Enthalpy Wheel Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Exhaust Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Startup and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Energy Recovery Bypass Damper Control . . . . . . . . . . . . . . 11
Prestartup Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Servicing Control Panel Components . . . . . . . . . . . . . . . . . . . 6 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Power Twister Belt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

McQuay and MicroTech are registered trademarks of McQuay International.


DesignFlow, Hi-F, Protocol Selectability, RoofPak, SelectTools, SpeedTrol, SuperMod, UltraSeal, and VaneTrol
are trademarks of McQuay International.
Microsoft is a registered trademark of Microsoft Corporation.
Windows is a trademark of Microsoft Corporation.
Copyright © 2006 McQuay International. All rights reserved throughout the world.
Introduction

Introduction
This manual provides installation and maintenance General installation amd maintenance information on the rest
information about the enthalpy energy recovery wheel option of the unit is found in the following manuals:
(“enthalpy wheel”) featured on the following McQuay • IM 738 for Packaged Heating and Cooling Units
Applied RoofPak™ models:
• IM 487 for Rooftop Air Handlers
1 RPR/RFR/RDE 015C - 075C Packaged Heating and
Cooling Units • IM 696 for MicroTech™ II Controls

2 RAR 800C - 802C and 47C Rooftop Air Handlers • OM 137 for discharge air control for MicroTech II
Controls
• OM 138 for space comfort for MicroTech II Controls

Figure 1: General Layout - (Approximate dimensions which vary with options)

Top

McQuay IM 835 1
Introduction

Arrangements arrangement is available on sizes 015 - 040C and 800 -


802C only.
Three arrangements are offered for the enthalpy wheel:
3 Dual enthalpy wheel without economizer (100% outdoor
1 Single enthalpy wheel with economizer and bypass (see air unit) for airflow exceeding about 7000 CFM (see
Figure 2). This arrangement is available for all units. Figure 3). This arrangement is available on sizes 015 -
2 Single enthalpy wheel without economizer (100% outdoor 040C and 800 - 802C only.
air unit) for airflow up to about 7000 CFM. This

Figure 2: Arrangement #1

OA Filter Rack Enthalpy


Wheel

Return Air
Economizer
Dampers

EA Filter Rack

Exhaust Air (EA)


(at negative pressure)

Figure 3: Arrangement #3

OA Hood OA Dampers
(2) Enthalpy
Wheels

OA Filter
Rack

Side EA
Economizer
Dampers
(not shown)
Plenum EA Fan

EA Filter Rack

2 McQuay IM 835
System Description

System Description
When a unit is equipped with an optional enthalpy wheel (see Latent energy - Latent energy, in the context of enthalpy
Figure 2), energy recovery is provided by drawing outside air wheel discussions, is the work done by the wheel to transfer
across half of the enthalpy wheel and drawing exhaust air moisture from one air stream to another. Latent work is
across the other half. Latent heat and sensible heat are accompanied by humidity changes in the air streams.
transferred from the hotter and moist exhaust air to the colder
Media - The chemical composite part of the enthalpy wheel
and dry outside air during winter conditions. Latent heat and
which actually performs the latent and sensible exchange.
sensible heat are transferred from the hotter and moist
outside air to the cooler and dry exhaust air during summer Outdoor air - The air stream that is brought in from the
conditions. Energy recovery control consists of starting and outside. Outdoor air becomes supply air after going through
stopping an exhaust fan, modulating the speed of the exhaust the enthalpy wheel.
fan, starting and stopping an enthalpy wheel, optionally
Purge - A small segment of supply air defined by the gap
controlling the speed of the enthalpy wheel and opening and
between the inner seal on the outdoor air edge of the center
closing a set of bypass dampers. The outdoor dampers are
post and the supply air edge of the center post. The purge
controlled in the normal manner. For more information, refer
angle is adjustable. The purge captures the small amount of
to OM 137 or OM 138. Also see “MicroTech II Sequence of
supply air captive in the enthalpy wheel when the wheel
Operation” on page 9.
moves from return to supply and routes it to return to
minimize cross contamination.
Wheel Construction
Return air - The air stream that is returned from the
Your McQuay enthalpy wheel is delivered completely building. Return air becomes exhaust air after going through
assembled and ready to run. The wheel is built to provide the enthalpy wheel.
many years of trouble free service following proper
installation and performance of the minimal maintenance Rotor - The part of an enthalpy wheel that performs the
requirements. energy exchange and consists of the wheel media, hub,
spokes and band.
Definitions Sensible heat - Sensible energy, in the context of enthalpy
The following are descriptions of various components related wheel discussion, is the work done by the enthalpy wheel to
to the enthalpy wheel construction (see Figure 4): transfer heat from one air stream to another. Sensible work is
accompanied by temperature changes in the air stream.
Bearing, external - The wheel and bearing rotate on the
shaft, no field lubrication is required. Spoke - Flat metal member used to support the enthalpy
wheel radially.
Brush seal - The seal used for both the circumferential seal
and the inner seal in the cassettes. They are constructed of Supply air - The air stream that is supplied to the building
nylon brush and configured to seal against the enthalpy space. Supply air is outdoor air that has been run through the
wheel band in the case of the circumferential seal, and enthalpy wheel.
against the wheel face in the case of the inner seal. These Figure 4: Wheel Construction (Side-by-Side)
seals are full contact seals, have an integral clip, and they are Hub
clipped to the cassette face panel cutout (concumferential) or Spoke Brush Seal
to the (inner) post.
Cassette - The steel structure that houses the rotor. Cassettes Media
are of punched sheet metal panelized construction.
Enthalpy wheel - A generic name for an energy
conservation wheel. The term “enthalpy” refers to an air Over-Under
stream’s total energy (temperature and humidity level). Configuration
Purge Location1
Exhaust air - The air stream that is exhausted to the outside.
Drive Belt
Exhaust air is building return air that has been run through
the enthalpy wheel.
Motor
Heat wheel - Synonymous with an enthalpy wheel, energy Sheave
conservation wheel, or total energy recovery wheel. Some Enthalpy Wheel Side-by-Side Cassette
heat wheels are sensible only wheels and should not be Configuration
confused with McQuay total energy recovery wheels. Purge Location 1
(1) Currently, only the Over-Under configuration is offered on McQuay rooftop
Hub - The center support of an enthalpy wheel. systems and air handlers.

McQuay IM 835 3
System Description

Purge and Pressurization Frost Protection Option


Pressurization is critical to minimize crossover from exhaust to During extremely cold winter conditions, exhaust air stream
supply and to allow the purge to operate. frost formation becomes a possibility. Frost formation will act
to plug or reduce air flow but it will not hurt the enthalpy
Figure 5: Purge and Pressurization
wheel itself.
Outside Air at
Atmospheric Pressure Supply Air To circumvent this frost possibility, McQuay offers a factory
installed frost protection option (MicroTech II VFD system)
that will control the speed of the enthalpy wheel for you (see
Any leakage must occur “Variable Speed Frequency Control” below). The sequence of
from outside to Exhaust Air Adjustable Purge
due to pressure gradient (See Detail) operation is detailed in “Variable Speed Enthalpy Wheel” on
page 9.
Exhaust Air
Variable Speed Frequency Control
A variable frequency drive is included with the frost protection
option and it controls the speed of the enthalpy wheel. The unit
Plenum Exhaust Fan has also been programmed for the recommended range of
draws a negative pressure NOTE: wheel speed operation. Typical wheel speed is 45 RPM, but
Maintain the pressure gradient to
prevent cross contamination from the the programming can allow for wheel speeds above or below
Exhaust to Outside Supply Air 45 RPM. Check all factory settings to make sure they are
consistent with the application.
Figure 6: Purge Detail Enthalpy wheel speed will be controlled by exhaust
temperature measurement.

Adjust purge in this Alternate Frost Protection Measures


direction to decrease
OUTSIDE AIR capacity and increase If you choose not to have the frost protection option factory
purge
installed by McQuay, other frost protection measures must be
considered.
Enthalpy wheel speed control functions to limit frost formation
by reducing wheel performance to a level where the exhaust
EXHAUST AIR
air temperature is kept above the dew point. Proper dew point
control of exhaust air is determined by using psychrometrics
(see Figure 8 on page 9):
1 Locate the winter design return air condition and outdoor
air condition and connect the two points on a psychrometric
chart.
2 Determine the dry bulb temperature at which this line
intercepts the saturation curve.
Drive Motor 3 Add 2°F and set dew point control at this point and vary
The enthalpy wheel comes standard with a constant speed enthalpy wheel speed downward to control at or above this
drive motor which is prewired to turn in the proper direction. point.
4 Audit performance of the enthalpy wheel during actual
operation. If frost formation is never evident, it may be
because design conditions are never reached. In such a
case, it may be possible to gradually work dew point
control down.

4 McQuay IM 835
Startup and Operation

Startup and Operation


Prestartup Checks 5 Is the optional frost control provided? If not, be aware that
enthalpy wheel capacity and air pressure drop suffer if frost
Before starting the unit, check the following: forms on the wheel.
1 Is the motor rotation correct? This can be checked by 6 If optional frost control is provided, check the following:
bumping the motor and observing the direction of rotation.
The sheave should be rotating in the direction such that the a Check the power supply for proper rating.
enthalpy wheel will rotate per the exterior markings. If not, b Make sure that the proper jumper orientation is used for
rewire the motor. specific control input.
2 Does the air flow orientation match up to design? See the c Make sure that the unit is programmed for proper input
identification markings on the cassette and/or refer to the voltage and output voltage.
general arrangement drawing to check the four duct Note – Variable speed units are provided only with the
connections to the unit. optional frost protection feature.
3 Are the belts on correctly and sufficiently tight? For more 7 Has the construction dirt been cleaned? If filters are used to
information, see “Appendix” on page 13. clean the duct system, leave the exhaust fan off and just
4 Check if seals are making good contact and adjust by recirculate air through the main filters with the supply fan.
moving the brushes closer to the wheel as necessary.

McQuay IM 835 5
Maintenance

Maintenance
Seals
CAUTION
The seals are designed to be durable and require no
Installation and maintenance must be performed only by maintenance other than adjustment. If seals become worn or
qualified personnel who are experienced with this type of damaged they may easily be replaced. The seals are made to
equipment and familiar with local codes and regulations.
clip onto the cassette or metal post easily.

WARNING
Variable Frequency Controller
Moving machinery and electrical power hazards. Can cause
severe personal injury or death. Disconnect and lock off all No maintenance should be required on the VFD. Should
power before servicing equipment. problems with the VFD develop, consult the VFD service
manual that accompanied your order.
CAUTION
Sharp edges are inherent to sheet metal parts, screws, clips, Wheel
and similar items. Contact with these edges may cause
personal injury. Exercise caution when servicing equipment.
The enthalpy wheel is designed to last the life of the
equipment. It is protected by an ASHRAE 30% filter to keep
Servicing Control Panel Components dust and dirt from the heat transfer surface. The wheel is
somewhat self cleaning through its normal action of rotating
Disconnect all electric power to the unit when servicing in and out of countercurrent air flow streams. If the wheel
control panel components. Before servicing, always inspect becomes dirty, it may be cleaned by blowing out the unit with
units for multiple disconnects to ensure all power is removed compressed air (20 psig maximum). In cases of severe dirt,
from the control panel and its components. the wheel may be removed from the cassette and washed
with water following wheel removable procedures outlined
DANGER below.
Hazardous voltage. Will cause severe injury or death.
Disconnect electric power before servicing equipment. More Enthalpy Wheel Removal
than one disconnect may be required to de-energize the unit.
The following enthalpy wheel removal procedure is for a
dual wheel design (although much of the procedure is
Replacement Parts applicable for a single wheel design).The dual wheel is only
Replacement parts can be obtained by contacting McQuay at offered for small cabinet 100% O.A. High Flow applications
1-800-37-PARTS or at www.mcquay.com. When contacting (no economizer or bypass dampers). There are two removal
McQuay for service or replacement parts, refer to the model procedures depending on the weight of the wheel (see
number and serial number of the unit as stamped on the Table 1) These are described below:
nameplate attached to the unit.
Procedure (size 800 - 802C or 015 - 040C)
Bearings 1 Disconnect electrical power.
2 Put a safety cover over the bottom return opening.
Enthalpy wheels are provided with "no maintenance" inboard
bearings, requiring no maintenance during the life of the 3 Remove divider panels and blockoffs.
equipment. 4 Remove filter rack and optional inverter mount.
5 Remove cross channel between uprights.
Drive Motor
6 Support the wheel from the bottom.(See Table1)
The drive motor should require no maintenance. 7 Remove end panels from energy wheel cassette.
8 Loosen motor and uncouple the belt.
Drive Belts
9 Remove enthalpy wheel supports and bearing from
Belts are multilink with individual links constructed of a high cassette.
performance polyurethane elastomer, reinforced with
multiple plies of polyester fabric. This belt provides a strong,
yet flexible belting. The multilink feature provides easy
servicing or replacement. See “Appendix” on page 13 for
belt repair/replacement instructions.

6 McQuay IM 835
Maintenance

Note – If the unit is equipped with an external flanged 12 Reinstall the enthalpy wheel using the reverse procedure,
bearing, loosen the allen screws in the bearing Run the unit. It may take several hours for the desiccant to
housing that keeps the shaft affixed in the horizontal
plane on both bearings, front and back. Remove the dry and for the wheel to perform normally.
shaft clips at the face of the hub from both sides of the Table 1: Weight of the wheel less sheet metal cassette
shaft. Unbolt one post completely and remove post
with the bearing completely out. Remove the shaft. Unit Size Weight
Roll the wheel carefully out. 55" tall cabinet 300 Lbs.
10 Slide wheel out the front of the cassette. 73" tall cabinet, 6" wide wheel 800 Lbs.

11 With the enthalpy wheel out, wash the media carefully with 73" tall cabinet, 12" wide wheel 1000 Lbs.
water. Allow wheel to dry completely for several hours.
Figure 7: Enthalpy Wheel Removal Components

Wheel Cassette
Cassette Supports/ End
End Bearing (#8) Panel (#6)
Panel (#6) Cross
Wheel (#9) Channel (#4) Divider
Panels/Blockoffs (#2)

Divider
Panels/Blockoffs (#2)
Cross Motor (#7)
Channel (#4)
Filter Rack/
Optional Inverter
Mount (#3)

Procedure (size 47C or 45 - 75C) blocking the drain pan. Clean the wheel with water
while it is in place, but care must be taken that the water
The enthalpy wheels in these larger units are too heavy and
does not splash outside the drain pan.
wheel removal, as described above for smaller units, is usually
not practical. If a need arises to remove an enthalpy wheel d If the wheel cannot be sufficiently cleaned while in
from a size 47C or 45-75C, then there are two choices to place, then the roof will have to be removed so a crane
consider, depending on the reason for removal: can be used to lift out and re-install the wheel. Follow
steps 1-8, 10 and 11 (from the above procedure for size
1 Disconnect electrical power.
800-802C or 015-040C) for loosening and reinstalling
2 If the primary need is to clean the wheel: the wheel.
a Normally the wheel can be cleaned with compressed air 3 If the wheel must be replaced:
(20 psig maximum) while in place.
a Cut the wheel into pieces that can be easily handled and
b If the wheel cannot be cleaned with compressed air, then replace the wheel.
water can be used. A drain pan is provided under the
b If using a crane and removing the unit’s roof is not
wheel for collecting the water.
practical, then replace the existing wheel with a
c To clean the wheel with water, first remove the lower segmented wheel.
baffle located between the bypass damper and the wheel

McQuay IM 835 7
Maintenance

Troubleshooting Check air flow and compare to design.


Check filters and clean/replace as necessary.
The following table may be used as a quick-reference for High Pressure Drop
Check media for plugging and clean per cleaning
identifying common symptoms and possible causes related to instructions (see “Enthalpy Wheel Removal” on
the recovery wheel. page 6).
Check seals and adjust as necessary.
SYMPTOM CAUSE
Check the bearings for source of noise.
Check wheel rotation speed (see “Variable Speed Noise
Frequency Control” on page 4). Check the belt for slippage (see “Power Twister Belt”
on page 13).
Check for wheel integrity and adjust seals or replace
worn seals (see “Prestartup Checks” on page 5 and Check all electrical connections.
“Seals” on page 6).
If MicroTech II controls are provided, make sure the
Inadequate Wheel Wheel Will Not
Check entering air conditions and compare to building pressure is above setpoint such that the
Performance Operate
design (see “Prestartup Checks” on page 5). EAF turns on. The wheel does not operate unless
the EAF is on (see “Exhaust Fan Control” on page
Check ducting for leakage and fix any leaks. 10).
Check media for dirt and clean per cleaning instruc-
tions (see“Wheel” on page 6 and “Enthalpy Wheel
Removal” on page 6).
Check drive belts for engagement with sheave.
Check drive motor.
Improper Wheel
Rotation Check drive motor wiring for proper voltage.
Check VFD programming (provided with optional
frost protection).

8 McQuay IM 835
MicroTech II Sequence of Operation

MicroTech II Sequence of Operation


When a unit is equipped with an optional enthalpy wheel, Variable Speed Enthalpy Wheel
energy recovery is provided by drawing outside air across half
When the unit is equipped with the enthalpy wheel frost
of the enthalpy wheel and drawing exhaust air across the other
protection option, it has a variable speed enthalpy wheel. The
half. Latent and sensible heat is transferred from the hotter
wheel is driven to maximum speed whenever the enthalpy
moist exhaust air to the colder dry outside air in winter. Latent
wheel is on. The speed of the wheel may be modulated as
and sensible heat is transferred from the hotter moist outside
described below to prevent wheel frosting.
air to the cooler dry exhaust air in summer. Energy recovery
control consists of starting and stopping an exhaust fan, When there is a threat of frost on the enthalpy wheel, the wheel
modulating the speed of the exhaust fan, starting and stopping is slowed down or stopped so that less enthalpy transfer occurs
an enthalpy wheel, optionally controlling the speed of the and frosting of the wheel is avoided. Frosting can occur on the
enthalpy wheel and opening and closing a set of bypass enthalpy wheel when the exhaust air leaving the wheel is
dampers. The outdoor dampers are controlled in the normal saturated. This condition occurs when two lines intersect on a
manner. Refer to OM 137 or OM 138.The following sections psychrometric chart, and it does not occur when these two
describe the control of the enthalpy wheel, exhaust fan and lines do not intersect (see Figure 8). One of these lines is the
bypass dampers. Humidity Ratio versus the dry bulb temperature for saturated
air. The other line is the exhaust air process line. The exhaust
Enthalpy Wheel Control air process is defined by two points on a psychrometric chart.
The first point on this line is the outdoor air temperature at
Table 2, below, lists the programmable parameters on the 95% relative humidity (point 1 in Figure 8) and the second
MicroTech II keypad that affect the operation of the enthalpy point on the line is the return air temperature at the return air
wheel. relative humidity (point 2 in Figure 8). One exhaust air process
line showing frosting conditions and another showing no frost
Table 2: Enthalpy Wheel Programmable Parameters
conditions is shown in Figure 8.
Keypad/Display ID
Parameter Name Figure 8: Variable Speed Enthalpy Wheel Frost Protection -
Menu Name Item Name Psychrometric Chart
Effective Minimum
OA Damper Eff Min OA Pos= ___% Outdoor Damper Position
Saturated Air Enthalpy Wheel
Set Point Exhaust Air
(Frost
Energy Energy Recovery Control
Energy Rec= No Conditions)
Recovery Flag Saturation
2
Temperature

Humidity Ration
Minimum Temperature (Intersection Point) ST
Min ExhT Diff= 2°F 2
Difference Enthalpy Wheel
Exhaust Air (No
Maximum Temperature Frost Conditions)
Max ExhT Diff= 6°F
Energy Rec Difference 2

Setup Enthalpy Wheel Stage


Stage Time= 5 min
Time
Enthalpy Wheel ST 1
Min Off Time= 20 min
Minimum Off Time
Saturated Air
1

When the Energy Recovery Control Flag is set to “Yes”, the


enthalpy wheel is turned on whenever the unit exhaust fan is Dry Bulb Temperature
on and the current OA Damper Pos= parameter in the OA The controller makes a continuous calculation to determine if
Damper menu indicates a value within 3% of the Effective and at what temperatures the saturated air and exhaust air
Minimum Outdoor Damper Position Set Point. It is turned off process lines intersect. When they do not intersect, the
when the exhaust fan is turned off or the OA Damper Pos= enthalpy wheel runs at full speed. When they do intersect, the
value is greater than the Effective Minimum Outdoor Damper enthalpy wheel is controlled to a slower speed to maintain the
Position Set Point by more than 3% (as when the unit is in the dry bulb temperature of the exhaust air leaving the enthalpy
Econo operating state). wheel above the higher of the two intersecting dry bulb
temperatures (point ST2 in Figure 8). This is referred to as the
Constant Speed Enthalpy Wheel “Intersection Point.” This prevents the wheel from operating
When the unit is equipped with a constant speed enthalpy under frosting conditions.
wheel, the wheel is driven to maximum speed whenever the
enthalpy wheel is on.

McQuay IM 835 9
MicroTech II Sequence of Operation

The following describes the details involved in the frost Table 3: Exhaust Fan Programmable Parameters
protection function that affect the speed and start/stop of the Keypad/Display ID
enthalpy wheel. Parameter Name
Menu Name Item Name
• When the enthalpy wheel has been operating at maximum Building Static
speed for at least the Enthalpy Wheel Stage Time and the BldgSP Spt= 1.00 “WC
Pressure Set Point
exhaust air temperature leaving the wheel (ER ExhT=) drops Bldg Pressure
Building Static
below the Intersection Point plus the Minimum Temperature BSP Db= 0.080 “WC
Pressure Dead Band
Difference, the enthalpy wheel will be slowed to its Effective Minimum
minimum speed. OA Damper Eff Min OA Pos=___% Outdoor Damper
Position Set Point
• If the enthalpy wheel has been operating at minimum speed
Building Static
for at least the Enthalpy Wheel Stage Time and the exhaust
BSP Propbd= 0.400 “WC Pressure Proportional
air temperature leaving the wheel (ER ExhT=) is still below Band
the Intersection Point plus the Minimum Temperature Building Static P Building Static
Difference, the enthalpy wheel will be stopped. Setup BSP IntTime= 2.0 sec Pressure Integral
• If the exhaust air temperature leaving the wheel (ER ExhT=) Time
then rises above the Intersection Point plus the Maximum Building Static
BSP Period= 2.0 sec
Pressure Period
Temperature Difference and the enthalpy wheel has been off
for longer than the Enthalpy Wheel Minimum Off Time, the Exhaust Fan Minimum
EF Min Cap= 5%
Capacity Value
wheel will be restarted and will run at its minimum speed.
Energy Recovery
• If the enthalpy wheel has been at minimum speed for longer Energy Rec= No
Control Flag
than the Enthalpy Wheel Stage Time and the exhaust air Energy Recovery
Minimum Exhaust Fan
Min Exh On= 120 sec
temperature leaving the wheel (ER ExhT=) is still above the On Timer
Intersection Point plus the Maximum Temperature Minimum Exhaust Fan
Min Exh Off= 120 sec
Difference, the wheel will be increased to its maximum Off Timer
speed. Second Pressure
2nd P Sensor= None
Sensor Present Flag

Exhaust Fan Control Return/Exhaust Fan


RF/EF Ctrl= Tracking
Unit Configuration Capacity Control Flag
When a unit is equipped with a 0 - 100% modulating Remote Return/
economizer or is 100% OA with a variable capacity discharge Rem RF/EF Cap= 25% Exhaust Fan Capacity
fan, the energy recovery option includes a variable capacity Set Point
exhaust fan equipped with a VFD. The MicroTech II
parameters that control the exhaust fan are shown in Table 3 1) Building Pressure Control

There are two different methods for controlling the exhaust fan When the Energy Recovery Control Flag is set to “Yes”, the
capacity, as described below. Return/Exhaust Fan Capacity Control Flag is set to “BldgPres”
and the Second Pressure Sensor Present Flag is set to “Bldg”,
the exhaust fan is controlled based on the building static
pressure. The exhaust fan is turned on when the discharge fan
is running and the Bldg Press= parameter value is above the
Building Static Pressure Set Point high by more than half the
Building Static Pressure Dead Band for longer than the
Minimum Exhaust Fan Off Timer.
Note – If the unit is 100% OA with a constant volume discharge
fan, the exhaust fan is turned on whenever the outdoor air
dampers are open.

The exhaust fan remains on until either of the following occur:


a The Bldg Press= parameter value drops below the
Building Static Pressure Set Point by more than half the
Building Static Pressure Deadband and the RF/EF Fan
Cap= value has been at the Exhaust Fan Minimum
Capacity Value for longer than the Minimum Exhaust
Fan On Timer.
b The discharge fan is turned off.

10 McQuay IM 835
MicroTech II Sequence of Operation

When the exhaust fan is on, its capacity is modulated to b The discharge fan is turned off.
maintain the Bldg Press= parameter value at the Building Note – If the unit is 100% OA with a constant volume
Static Pressure Set Point using three PID control loop discharge fan, the exhaust fan is turned on whenever
parameters. These are the Building Static Pressure the outdoor air dampers are open.
Proportional Band, Building Static Pressure Integral Time and
Building Static Pressure Period. Although these parameters Energy Recovery Bypass Damper Control
can be adjusted, for most applications, the factory default
values for these parameters provide the best control. For When a unit is equipped with a 0-100% modulating
detailed information regarding tuning PID control loop economizer, the energy recovery option includes a set of
parameters, refer to “MicroTech II DDC Features” in OM 137. bypass dampers (see Figure 9) that allow air to bypass the
energy recovery wheel when the wheel is not operating. The
2) Direct Position Control dampers are driven closed for 2 minutes whenever the energy
recovery wheel is turned on, forcing the entering and leaving
When the Energy Recovery Control Flag is set to “Yes” and air to go through the wheel. When the outdoor air dampers are
the Return/Exhaust Fan Capacity Control Flag is set to driven more than 3% above the effective Minimum Outdoor
“Position”, the exhaust fan is controlled based on Remote Damper Position Set Point (as when the unit enters the
Return/Exhaust Fan Capacity Set Point. This set point can be Economizer operating state the wheel is shut off and the
adjusted via a network signal. The exhaust fan is turned on bypass dampers are driven open for 2 minutes allowing the
when the discharge fan is running and the exhaust fan capacity entering and leaving air to bypass the wheel.
is commanded above the Exhaust Fan Minimum Capacity
Value for longer than the Minimum Exhaust Fan Off Timer. Table 4: Programmable Parameters
The exhaust fan remains on until either of the following occur: Keypad/Display ID
Parameter Name
a The Remote Return/Exhaust Fan Capacity Set Point is Menu Name Item Name
commanded to the Exhaust Fan Minimum Capacity Effective Minimum
Value for longer than the Minimum Exhaust Fan On OA Damper Eff MinOA Pos= ___% Outdoor Damper
Position Set Point
Timer.

Figure 9: Bypass Damper Control

O A D a m p e rs B y p a s s D a m p e r ( O p tio n a l)

A tm o s p h e r ic
S u p p ly
P re s s u re
A ir

O u td o o r
A ir
N e g a tiv e
E A a n d O A P re s s u re
P r e - F ilte r s E x h a u s t A ir R e tu rn
A ir
P le n u m E A F
R A E c o n o m iz e r
D a m p e r s ( O p tio n a l)

McQuay IM 835 11
Typical Wiring Diagram

Typical Wiring Diagram


The following is a common wiring diagram for the enthalpy
wheel.
W h e e l E n e rg y
P B 1 1 C B 6 0 V F D W h e e l
1 2 -L 1 H 9 0 3 -1 H 9 0 3 -1 M o to r
L 1 -1 2 L 1 T 1 U 1 U 2 T 1
1 2 -L 2 L 1 H 9 0 4 -1 H 9 0 4 -1 M T R 9 3 4
L 2 -1 2 L 2 T 2 V 1 V 2 T 2
1 2 -L 3 L 2 H 9 0 5 -1 G N D H 9 0 5 -1
L 3 -1 2 L 3 T 3 W 1 W 2 T 3
L 3
H 9 0 6 -1
G N D 1

N o r m a l E c o n o m iz e r
T 1 _ 1 1 5 V A C /1 .6 8 T 2 _ 2 4 V A C /2 .6 4 T 3 _ C O M T 2 _ C O M /2 .4 7 T 1 _ N /1 .6 8
C o n tro l O u tp u ts
S R C jp r s + N B
M C B A C T 3 P L 1 1
1 -8 9 1 2 A B 0 5 2 4 V S R C 9 1 2 B H 9 1 2 -7 H 9 1 2 -8 3 0 3 B
4 (O A D A M P E R ) 1
5 5 N O C C W
2 0 7 (C L O S E D ) 9 1 2 A H 9 1 3 -6 C O M
2
M C B jp r s 2 4 V (W IT H C C W S P R IN G
B 0 6 2 4 V S R C 9 1 2 A H 9 1 4 -1 0
3 R E T U R N C L O S E D )
6 6 N O C W
2 0 7 (O P E N )
+ N B
A C T 4
H 9 1 3 -0 H 9 1 2 -8
2 (R A D A M P E R ) 1
2 4 V C O M
H 9 1 2 -7
4
C C W
H 9 1 4 -1 0 (W IT H C W S P R IN G
3
R E T U R N O P E N )
C W

2 4 V 2 4 C
J 1 0 N 2 2 0 9 C W H T
N 2 + N 2 + A /2 .1 1
B U S N 2 2 1 0 C B L K N 2 + A /2 .1 2
J U M P E R S R E F 2 1 1 C D R N
B I7 B 0 1
R E F A /2 .1 2
E N A B L E D IS A B L E + P P
B I9 B 0 2 J 8
E N A B L E D IS A B L E P L 2 4
9 2 4 C W H T H 9 2 4 -1 O p tio n a l
B I1 0 A I1 1 + N B
(J U M P E R 9 2 5 C B L K H 9 2 5 -2 E A T
L O C A T E D
C O M D R N 2 D R N 4 (E X H A U S T A IR S E N S O R
J U S T U N D E R
C O M M . C A R D ) 4 L E A V IN G W H E E L )
B I8 S V D C
E n e rg y
B I1 1 R e c o v e ry A I2
B o a rd
B I1 2 C O M
E R B 1 + P P
A I6 P L 2 3
9 3 0 C W H T H 9 3 0 -1
IN P U T S 1 + N B
A I3
B I= B IN A R Y 9 3 1 C B L K H 9 3 1 -2 E A T
A I= A N A L O G C O M D R N 2 D R N 4 (L E A V IN G A IR S E N S O R
4 O U T D O O R A IR
L E A V IN G W H E E L )
S V D C L 1 (A U X IL IA R Y C O N T A C T O N T H E
+ N B W H E E L M O T O R O P E N S W H E N
(C O M P R # 1 ) B O 1 M T R 1 T H E M O T O R IS O F F ) R 6 0
1 P L 1 2 P L 1 2
9 3 4 C H 9 3 4 -1 H 9 3 4 -2
3 C O M N O 1 2 7 8
9 0 3
2
B O 2
(B Y P A S S D A M P E R S O P E N
5 C O M N O 4 D U R IN G E C O N O M IZ E R
T 3 _ 2 4 V + N B T 3 _ C O M
O P E R A T IO N )
6 B O 3 A C T 1 2
(B Y P A S S D A M P E R )
8 C O M N O 7 P L 2 2
H 9 3 9 -4 H 9 3 9 -3
B O 4 C L O S E C O M
9 4 0 C P L 2 2 C C W 3
4
3 0 3 A

9 C O M N O 1 0
B O 5
3 0 3 B

9 4 1 C P L 2 2 C W
O P E N
C O M N O B O 6 1 1 2 H 9 4 1 -2
(S P E E D U P A N D S L O W
1 2 B O 6 C O M N O 1 3 D O W N O U T P U T R E L A Y S
R 5 8 _ 5 9 F O R T H E V F D )
C O M N C B O 7 1 4
9 4 4 C H 1 D N
1 56 C O M N O 1 5
H 1 C
B O 8
9 4 6 C H 1 U P
1 7 C O M N O 1 8
9 6 1
(C O M P R # 2 ) B O 9

1 9 C O M N O 2 0

+ N B
A F D 6 0

V D F F o r T h e E n e rg y
R e c o v e ry W h e e l
9 0 3

1 3 1 1 1 4
8 1 0 6 1 2 9

O P E N S A N D F O R C E S
H 9 5 7 -1 2
H 9 5 7 -8

T H E V F D T O L O W
H 9 5 7 -9

H 9 5 7 -7

S P E E D W H E N T H E
W H E E L M O T O R
IS O F F T H R O U G H R 6 0
( lin e 9 3 4 )
P L 1 2 8 1 2 P L 1 2 P L 1 2 9 7 P L 1 2
R 6 0
9 5 8 B 9 5 9 A
9 5
9 5 8 A

9 5 8 A 9 3 4

H 2 U P H 2 V H 2 D N
R 5 8 _ 5 9
(S P E E D U P A N D S L O W D O W N
O U T P U T R E L A Y S F O R T H E V F D )
9 4 4

12 McQuay IM 835
Appendix

Appendix
Power Twister Belt 3 Rotate belt end with tab 90°.

The following Power Twist® Belt information offers


instruction on how to measure, disassemble, assemble, and
install the belt.

Belt Length Measurement


The following steps give the correct installed belt length and
will provide optimum belt tension when running.
4 Pull belt end through two links.
1 Pull belt tight around sheaves to check hand tight length,
overlapping the last two tabs with two holes in matching
links as shown below.

Belt Assembly
1 Hold belt with tabs pointing outward.

2 Count the number of links and remove one link for every
24 links.
Note – Every tenth link is designated with an arrow.

Belt Disassembly 2 Place end tab through two links at once.

1 Hold belt upside down. Bend back as far as possible; hold


with one hand. Twist one tab 90° parallel with slot.

3 Flex belt further and insert second tab through end link by
twisting tab with thumb.

2 Pull end of link over tab.

McQuay IM 835 13
Appendix

4 Ensure tab returns to position across belt. Reverse belt so Alternative Belt Installation Method
tabs run inside. 1 Set motor to mid position of adjustment range and mark
base clearly.

2 Determine required belt length (see “Belt Length


Belt Installation Measurement” on page 13).
1 Disconnect electrical power. 3 Push motor forward to minimum center distance.
2 Turn belt with tabs to the inside before installing. 4 Install belts as in (see “Belt Installation”).
3 Determine direction of the drive rotation. 5 Pull motor back to previously marked mid position.
4 Align belt directional arrow with drive rotation.
5 Fit belt in nearest groove of smaller sheave.
6 Roll belt onto larger sheave, turning the drive slowly. Belt
may seem very tight, this is okay; DO NOT JOG MOTOR.

Retensioning
Like all high performance V-belts, PowerTwist Plus V-Belts
require the maintenance of correct drive tension to operate
efficiently. Experience indicates that drive tension should be
checked after the first 24 hours running at full load. A
retension may be necessary depending on the severity of the
7 Roll belt onto larger sheave, turning the drive slowly. Belt
drive. Any initial belt stretch is then taken up. Subsequently,
may seem very tight, this is okay; DO NOT JOG MOTOR.
belt tension should be checked periodically and adjusted when
8 Check to see that all tabs are still in their correct position necessary.
and are not twisted out of alignment.

14 McQuay IM 835
McQuay Training and Development

Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority.
For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or
call 540-248-9646 and ask for the Training Department.

Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product
Warranty. Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your
local McQuay Representative, go to www.mcquay.com.

This document contains the most current product information as of this printing. For the most up-to-date product
information, please go to www.mcquay.com.

13600 Industrial Park Boulevard, Minneapolis, MN 55441 USA (612) 553-5330

Вам также может понравиться