Вы находитесь на странице: 1из 6

IAV

Time Delay Voltage

For AC and DC circuit applications.

Features and Benefits Protection and Control


■ Frequency compensation (optional) ■ Generator overvoltage
■ Target seal-in unit (most units) ■ Feeder under and overvoltage
■ Instantaneous units (optional) ■ Ground detection

Applications
■ AC Generators (including Hydro)
■ Distribution feeder
■ Time delay pickup or dropout

GE Multilin 1
IAV Time Delay Voltage

Description Application Fig. 3 Typical external for ground fault


protection 3-phase; ungrounded system
The IAV relays are single phase IAV512D

induction disk relays designed to Overvoltage Relays AC bus


1
IAV overvoltage relays are used 2 (+) Trip bus
respond, with time delay, to 3
either an increasing or a decreas- for protection against simple
59
ing voltage, or both. Some overvoltage, but other applica- SI
1
models are frequency compen- tions are also common. They are Potential 59
Transformer
sated, and some include an applied to ground detection, both 2
52
instantaneous unit (hinged arma- on feeders and on ac generators, 59 52
a

ture type). Most models listed in and they are also used in timed 5
59
TC
52 6
the Selection Guide include a switching arrangements, where C
(-)
target seal-in unit on all contacts. their dependability and accuracy Generator

The basic mechanism of all make them preferable to purely


models is an induction-disk unit mechanical timing relays. For the circuit of Figure 3, use
with either a tapped coil or a For protection against overvolt- IAV51D, a low pickup relay which
tapped resistor for setting pickup. age in a three-phase system, use has its operating circuit tuned to
the IAV51A relay (Fig. 1). For the rated frequency. The potential
(In the overvoltage models, the
instantaneous protection as well transformers used in this circuit
relay is calibrated on increasing
as time delay, use the IAV71B. are connected grounded-Y
voltage to close the normally
primary, broken- delta secondary.
open contact at tap setting. The For the detection of grounds on
The primaries should have
time dial adjusts the angle ungrounded three-phase
ratings equal to the line-to-line
through which the disk rotates systems, two methods are in
voltage of the system, and the
and, hence, the time delay.) general use. One measures the
secondaries can have ratings of
In the undervoltage models, the zero sequence potential (Fig. 3),
either 67 or 115 V.
relay is calibrated on decreasing and the other measures the actu-
al voltage between the system Select a relay model with a
voltage to close the normally
neutral and ground (Fig. 5). continuous rating of three times
closed contact at tap setting. The
the potential transformer second-
time dial adjusts the angle Fig. 1. Typical external for IAV51A used for ary voltage. This is necessary
through which the disk rotates at overvoltage protection
AC bus
because, when a ground occurs,
voltages above tap setting. 1 (+) Trip bus the zero sequence voltage may
2
In the combined overvoltage and 3 be up to three times the normal
undervoltage models, the relay is 1 59
transformer secondary voltage.
SI
calibrated on increasing voltages 52 Thus, with a potential trans-
to close the normally open 59
former secondary rated 67 V, use
2
contacts at tap setting and on 5 59 52 a 199-V relay coil. For ground
6 a
decreasing voltages to close the Potential 52 fault protection of ac rotating
normally closed contacts at vari- Transformer TC
machines, use a circuit similar to
ous percentages of tap setting. that shown in Figure 5 applying
Generator (-)
For the undervoltage and IAV51D or IAV51K relays. These
combined undervoltage and are low-pickup relays whose coil
overvoltage relays, the two Fig. 2 Typical time voltage curve for IAV51A, circuits are tuned by capacitors to
71 and 72
connecting plug S2 case is used their rated frequencies. The
to prevent false tripping when the circuits are thus rendered only
relay is removed or replaced. one-eighth as sensitive to the
Either plug completes the coil third harmonic as they are to the
circuit and thus opens the rated frequency.
normally closed contact used
with undervoltage operation.
Both plugs are needed to
complete the contact circuits.

2 www.GEindustrial.com/Multilin
IAV Time Delay Voltage

Fig. 4 Typical time voltage curve for IAV51D Fig. 6. Typical time voltage curve for IAV53K, 53L, 73A and 73B
and 51K

Fig. 5. Typical external for ground fault


protection of an AC rotating machine IAV51D
or 51K
AC bus
(+) Trip bus
IAV51D

59
C 59
52 6 59 SI
R 59
5
59
59
SI
IAV51K
2 Undervoltage Relays generators, where the frequency
6 59
59 Trip
For simple undervoltage protec- tends to increase when faults 5
3 or
Generator C 59 Alarm tion, select the IAV relay occur. Frequency compensation
C
5 4 according to the time voltage is provided by an R-C circuit
86 When used characteristic required. across the wound shading coils
6 for alarm
59 of the induction disk operating
In a typical automatic-preferred
Distribution 5 coil and core unit.
Transformer emergency throwover scheme,
the undervoltage contacts of the
In Figure 5, a distribution trans- IAV54E relay are used to trip the Characteristics
former is connected between the circuit break er in the normal
machine neutral of the generator IAV relays will continuously with-
source circuit, and the auxiliary
and ground. Normally there is no stand rated voltage on all taps,
switch (52b) of this normal source
voltage on the transformer but and tap voltage on all taps above
breaker permits the voltage clos-
during a fault, there is a voltage rated voltage. For the minimum
ing contacts of an IAV51A relay in
with a wor st-case magnitude and maximum taps shown in the
the emergency source to close its
equal to the phase-to-ground list below, the following interme-
circuit breaker.
value. diate taps are available:

Greater sensiti vity can be Combined Undervoltage and


Tap Range Taps Available
obtained by choosing a distribu- Overvoltage Relays
5.4-20 5.4, 7.5, 12.5, 20
tion transformer with higher IAV53, IAV69, IAV70, and IAV73 10-40 10, 15, 25, 40
secondary voltage. In such a relays are time-delay, over- and 16-64 16, 24, 40, 64
case, the relay will not carry the undervoltage relays having two 28-112 28, 42, 70, 112
fault voltage continuously, and contacts, one of which closes on 55-140 55, 64, 70, 82, 93, 105, 120, 140
110-280 110, 128, 140, 164, 186, 210, 240, 280
provision must be made to de- overvoltage and the other on 220-560 220, 256, 280, 328, 372, 420, 480, 560
energize the operating coil using undervoltage.
an auxiliary relay. The short-time
Frequency Compensation The overvoltage relays and the
rating for both IAV51D and
undervoltage relays are provided
IAV51K is 360 V for 10 sec. The following IAV relays are
with time dials for adjustment of
The IAV51M relay may be used frequency compensated:
time delay.
for a definite time delay and the n Overvoltage relays-IAV71, IAV72
The combined under- and over-
time is adjustable from 3 to 30 n Undervoltage relays-IAV74A
voltage relays are made both
sec by means of a time dial. n Undervoltage and Overvoltage with and without time delay
Operating time is defined as the relays IAV73A, IAV73B
adjustment. Models IAV53,
time to close the contacts with These relays have uniform char- -69, and -73 have time delays
voltage suddenly raised from acteristics over a frequency range which are functions of the setting
zero to the rated value. of 30-90 Hz. A typical application of the undervoltage contacts.
is on systems supplied by hydro- Model IAV70 has a time dial

www.GEindustrial.com/Multilin 3
IAV Time Delay Voltage

which permits adjustment of time unit and by the tap used on the
delay independently of the volt- seal-in coil. Without a seal-in unit
age settings. the relay contacts will close and
carry 30 A for tripping duty and 2
Tripping Circuits and A continuously at control volt-
Contact Ratings ages of 250 vdc or less. Refer to
The current carrying rating of the the GE Multilin CD or Home Page
contact circuit is determined by for data on target seal-in units.
whether the relay has a seal-in

Selection Guide
Approx. Wt.
General Rated Tap Range Volts Target Model Numbers Case in lbs (kg)
Description VAC Seal-in Contacts Size
Min Max 60 Hz 50 Hz Net Ship
OVERVOLTAGE (DEVICE No. 59)
115 55 140 IAV51A1A IAV51A4A
General duty, overvoltage and 208 70 140 A7A A9A
control switching. Time delay 1 to 0.2/2 1-N.O.
10 sec at 1.6 times tap setting. 230 110 280 A2A A5A
12 15
460 220 560 A3A A11A S1
(5.4) (6.8)
Same as IAV51A except 115 55 140 IAV52A1A IAV52A4A
2-N.O. Contacts 199 70 140 0.2/2 2-N.O.
. A7A A9A
1 - Target Seal-in 230 110 280 A2A A5A
LOW PICK-UP
Ground detection on 3-phase 115 ➀ 10 40 IAV51D2A IAV51D5A
systems and on generator stator 199 ➀ 16 64 D1A D4A S1 12 (5.4) 15 (6.8)
windings. Time delay 0.75 to 7.5 sec 1-N.O.
at 200% of tap setting, or 4 sec on 345 ➀ 28 112 D9A D10A
0.2/2
N.O. 10 TDs. 67 ➀ 5.4 20 IAV51K1A IAV51K2A S1➁ 13 (5.9) 16 (7.3)
Same as IAV51D or IAV51K except 199 ➀ 16 64 IAV52D1A ---- S1 12 (5.4) 15 (6.8)
2-N.O.
2 N.O. Contacts 67 ➀ 5.4 20 IAV52K1A IAV52K2A S1➁ 13 (5.9) 16 (7.3)
TIMING APPLICATIONS
Single circuit closes with time delay. 115 55 IAV51M1A IAV51M2A
12 15
Fixed pickup voltage. Time delay: 208 100 0.2/2 1-N.O. M4A S1 (5.4) (6.8)
3 to 30 sec at rated volts. 230 110 M3A
FREQUENCY COMPENSATED
Frequency sensitive applications.
Otherwise same as IAV51A 115 55 140 IAV71A1A IAV71A3A
compensated 30-90 Hz.
Frequency compensated; instanta-
neous unit added, also frequency 115 55 140 IAV71B2A ➂ IAV71B3A ➂
1-N.O
compensated; for hydro-generator
applications; general duty for AC 230 110 280 B5A ➂ ----
generator overvoltage protection
and voltage regulator backup. 1 to 230 110 280 0.2/2 B6A➃ ---- S1 13 (5.9) 16 (7.3)
10 sec time delay.
Similar to IAV71A except 2 N.O.
115 55 140 IAV72A1A ----
contacts.
Similar to IAV72A except includes 115 55 140 IAV72B1A ➂ IAV72B4A ➂
2-N.O
ints. unit with 1 N.O. contact 230 110 280 ---- B3A ➂
Similar to IAV72B except includes int.
115 55 140 ---- IAV72C3A ➂
Unit with 2 N.O. contacts.
➀ IAV51D, 51K, 52D, and 52K - 10 sec rating at 360 V.
➁ Includes external capacitor.
➂ Inst. unit adjustable 120-200 V.
➃ Inst. unit adjustable 180-300 V.

4 www.GEindustrial.com/Multilin
IAV Time Delay Voltage

Selection Guide
Approx. Wt.
General Rated Tap Range Volts Target Model Numbers Case in lbs (kg)
Description VAC Seal-in Contacts Size
Min Max 60 Hz 50 Hz Net Ship
UNDERVOLTAGE (DEVICE NO. 27)
67 32 80 IAV54E14A ----
5 sec time delay at zero volts if set 115 55 140 E1A IAV54E4A
on No. 10 TD, time range 1 to 13 sec 208 110 280 E13A ----
at 80% of tap. 230 110 280 E2A E5A
460 220 560 E3A E6A
0.2/2
115 55 140 IAV54F1A ----
30 sec time delay at zero volts if set
230 110 280 1 N.C. F2A IAV54F4A
on No. 10 TD
460 220 460 F3A ----
75 sec time delay at zero volts 115 55 140 IAV54H1A ----
on No. 10 TD 12 16
460 220 560 H2A ---- S2
(5.4) (7.3)
115 55 140 IAV54J1A ----
Same as IAV54E
230 110 280 None J2A ----
except no seal-in
460 220 560 J3A IAV54J4A
115 55 140 IAV55C1A IAV55CA4
5 sec time delay same as IAV54E 5
except 2 N.C. 230 110 280 C2A C5A
460 220 560 C3A C9A
0.2/2 2 N.C.
115 55 140 IAV55F1A ----
30 sec time delay
230 110 280 F2A ----
75 sec time delay 115 55 140 IAV55H1A ----
FREQUENCY COMPENSATED
5 sec time delay at zero volts 13 17
115 55 140 0.2/2 1 N.C. IAV74A1A S2
on No. 10 TDS. Compensated 30-90 Hz (5.9) (7.7)

Order online –
save time

www.GEindustrial.com/pm

www.GEindustrial.com/Multilin 5
IAV Time Delay Voltage

Selection Guide
Approx. Wt.
General Rated Tap Range Volts Target Model Numbers Case in lbs (kg)
Description VAC Seal-in Contacts Size
Min Max 60 Hz 50 Hz Net Ship

OVER- AND UNDERVOLTAGE (DEVICE NO. 27/59)


General duty; electrically separate
contacts with target seal-in unit series 115 55 140 IAV53K1A IAV53K4A
with each contact; UV adjustable from 50 230 110 280 0.2/2 K2A K5A
to 95% of OV tap setting. Time delay 1.1 460 220 560 K3A K11A
sec at zero volts: 0.4 sec at 2 x tap. setting.
Automatic control schemes; same as 115 55 140 IAV53L1A IAV53L4A
IAV53K except target seal-in units are 230 110 280 L2A L5A
omitted. 460 220 560 L3A ----
None
Similar to IAV53K except target seal-in
115 55 140 IAV53N1A ----
units are omitted. Time delay 0.5 sec at
460 220 560 N3A ----
zero volts.
General duty; common connection
between contacts; OV setting is independ- 120 55 140 IAV69A1A IVA69A3A
1 N.C. 13 17
ent of UV adjustment; UV adjustable from 208 110 280 0.2/2 A4A ---- S2
60 to 95% of OV tap setting; target and 240 110 280 1 N.O. A2A ---- (5.9) (7.7)
seal-in units in series with each contact.
Automatic control schemes; same as
120 55 140 IAV69B1A IAV69B3A
IAV69A except target seal-in units are None
240 110 280 B2A ----
omitted.
General duty; common connection
between contacts; UV setting fixed at
95% or more of OV tap setting; target 120 55 140 IAV70A1A ----
0.2/2
seal-in unit in series with each 240 110 280 A2A ----
contact; adjustable time delay 30 sec
max. on complete loss of V.
Automatic control schemes; same as
120 55 140 IAV70B1A IAV70B3A
IAV70A except target seal-in units are None
240 110 280 B2A ----
omitted.
FREQUENCY COMPENSATED
General duty; same as IAV53K except
0.2/2 IAV73A1A ----
Frequency Compensated. 30-90 Hz
1 N.C. 13 17
Automatic control schemes; same as 115 55 140 S2 (5.9) (7.7)
1 N.O.
IAV53L except frequency compensated. None IAV73B1A ----
30-90 Hz.

6 www.GEindustrial.com/Multilin