Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
SECTION 233413 ‐ AXIAL HVAC FANS
PART 1 GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including Conditions of
Contract and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Tubeaxial fans. Comply
2. Vaneaxial fans. Not used in the project
3. Car park jet fans. Comply
1.3 PERFORMANCE REQUIREMENTS
A. Project Altitude: Base air ratings on actual site elevations. Noted
B. Operating Limits: Classify according to AMCA 99. Comply as Noted As per EN standards.
C. Fan Unit Schedule: Performance requirements and data are described
Comply
in equipment schedule(s) on the Drawings.
D. All fan bearings, where applicable, shall be of heavy duty type suitable
Comply
for continuous operation.
1.4 SUBMITTALS
1/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
Comply Please refer section 2 of submittal
1.Certified fan performance curves with system operating conditions indicated.
2.Certified fan sound power ratings. Comply Please refer section 2 of submittal
3.Motor ratings and electrical characteristics plus motor and electrical
Comply Please refer section 2 of submittal
accessories.
4.Material gages and finishes, including color charts. Comply Hot Dipped Galvanized Steel
5.Dampers, including housings, linkages, and operators. Comply By Contractor
B. Shop Drawings from manufacturer detailing equipment assemblies and
By Contractor
indicating dimensions, weights, loadings, required clearances, method of field
assembly, components, and location and size of each field connection.
C.Coordination Drawings, including floor plans and sections drawn accurately to
scale. Submit with Shop Drawings. Show fan room layout and relationships
between components and adjacent structural and mechanical elements. Show By Contractor
support locations, type of support, and weight on each support. Indicate and
certify field measurements.
D.Wiring diagrams detailing wiring for power and control systems and
differentiating clearly between manufacturer‐installed and field‐installed By Contractor
wiring.
E.Field Test and Commissioning Reports: As specified in "Field Quality Control"
and "Commissioning" Articles in Part 3 of this Section. Indicate and interpret By Contractor
test results for compliance with performance requirements.
F.Maintenance data for fan units to include in the operation and maintenance
Comply Will be provided
1.5 QUALITY ASSURANCE
2/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
A.Electrical Component Standard: Provide components that comply with NFPA
Comply with Comments AW Fans are asper EN standard.
70 and that are listed and labeled by UL where available.
B.Listing and Labeling: Provide electrically operated fixtures specified in this
Section that are listed and labeled.
1. The Terms "Listed" and "Labeled": As defined in NFPA 70, Article 100. Comply with Comments AW Fans are asper EN standard.
C.AMCA Compliance: Provide products that meet performance requirements
Comply with Comments As per EN Standards.
and are licensed to use the AMCA Seal.
D.NEMA Compliance: Motors and electrical accessories shall comply with NEMA Motors and electrical accessories as per IEC
Noted
standards. standards
E.Local Certification: Fans should be certified by local authorities as applicable. AJR Jets are suitable for 300 deg C for 2 hours.
Compy as noted
Certiified by BSI.
1.7 PROJECT CONDITIONS
A. Field Measurements: Verify dimensions by field measurements. Verify
clearances. By Contractor
B. Do not operate fans until ductwork is clean, filters are in place, bearings are
lubricated, and fans have been commissioned. By Contractor
1.8 COORDINATION AND SCHEDULING
A.Coordinate the size and location of concrete housekeeping pads. Cast anchor‐
bolt inserts into pad. Concrete reinforcement and formwork requirements are
specified in Section "Cast‐in‐Place Concrete." By Contractor
B.Coordinate the installation of roof curbs, equipment supports, and roof
penetrations. Roof specialties are specified in Division 7 Sections. By Contractor
3/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
1.9 EXTRA MATERIALS
A. Furnish one set of belts for each belt‐driven fan that match products
installed, are packaged with protective covering for storage, and are identified Not Applicable Proposed fans are direct driven
with labels clearly describing contents.
1.10 WARRANTY
A. Manufacturer's Warranty: Provide written warranty, signed by manufacturer
agreeing to repair or replace components of the axial HVAC fans that fail in
As per the attached draft warranty
materials or workmanship within specified warranty period.
B. Provide system warranty in which Manufacturer, Installer, and Contractor
are jointly and severally liable and agree to repair or replace defective As per the attached draft warranty
components of the warranted item.
C. Warranty shall include:
As per the attached draft warranty
1. Defective materials and installation.
2. Failure to comply with requirements stated in technical specifications.
3. Structural failures including, but not limited to, excessive deflection.
4. Faulty operation of movable parts such as hardware.
5. Deterioration of metals, metal finishes, and other materials beyond
normal weathering and use.
6. Delamination of exterior or interior facing materials.
7. Making good and installation and finishing all items that are disturbed
and that may be required due to repair or replacement of defective items.
Coordinate with Employer, manufacturer, and installer of adjacent disturbed
items to ensure that their warranty is not cancelled due to the repair work.
D. Warranty Period: Two years from date of Substantial Completion.
4/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
PART 2 PRODUCTS
2.1 TUBEAXIAL FANS
A. Description: Fan wheel and housing, factory‐mounted motor with
belt or direct drive, an inlet cone section, and accessories. Comply as noted. The Proposed fans are direct driven.
B. Housings: Galvanized steel with flanged inlet and outlet connections.
Comply.
C. Wheel Assemblies: Cast aluminum, machined and fitted to shaft.
Comply.
2. Service Factor Based on Fan Motor Size: 1.2
3. Fan Shaft: Turned, ground, and polished steel designed to operate at
no more than 70 percent of first critical speed at top of fan's speed range.
4. Fan Pulleys: Cast iron with split, tapered bushing; dynamically
balanced at factory.
5. Motor Pulleys: Adjustable pitch. Select pulley so pitch adjustment is at
the middle of adjustment range at fan design conditions.
6. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for
multiple belt drives.
7. Belt Guards: Fabricate of steel for motors mounted on outside of fan
cabinet.
8. Motor Mount: Adjustable base.
9. Shaft Bearings: Radial, self‐aligning bearings.
a. Ball‐Bearing Rating Life: ABMA 9, L10 of 50,000 hours
b. Extend lubrication lines to outside of casing and terminate with grease
fittings.
E. Accessories:
5/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
1. Companion Flanges: Rolled flanges of same material as housing.
Comply
2. Inspection Door: Bolted door allowing limited access to internal parts of Provided with inspection hole. To check the
Comply as noted.
fan, of same material as housing. rotation of the baldes.
3. Propeller Access Section Door: Short duct section bolted to fan inlet
and outlet allowing access to internal parts of fan for inspection and cleaning, Noted. By contractor
of same material as housing.
4. Swingout Construction: Assembly allowing entire fan section to swing
out from duct for cleaning and servicing, of same material as housing. Noted. By contractor
5. Mounting Clips: Horizontal ceiling clips welded to fan housing, of same
Comply as noted. Provided with mounting feet.
material as housing.
6. Horizontal Support: Pair of supports bolted to fan housing, of same
Comply as noted. Provided with mounting feet.
material as housing.
7. Vertical Support: Short duct section with welded brackets bolted to fan For vertical mounting, fan can be provided with
Comply as noted.
housing, of same material as housing. mounting rings.
8. Inlet Screen: Wire‐mesh screen on fans not connected to ductwork, of
Noted. By contractor
same material as housing.
9. Outlet Screen: Wire‐mesh screen on fans not connected to ductwork,
Noted. By contractor
of same material as housing.
10. Backdraft Dampers: Butterfly style, for bolting to the discharge of fan or
Noted. By contractor
outlet cone, of same material as housing.
11. Shaft Seal: Elastomeric seal and Teflon wear plate, suitable for up to 300 Proposed fan AXC‐B is suitable for
deg F (149 deg C). 300 deg C for 2 hours.
12. Motor Cover: Cover with side vents to dissipate motor heat, of same
Proposed fans are with TEAO
material as housing. motors. These motors are cooled
by the air passing through the fan.
6/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
13. Inlet Vanes: Adjustable; with peripheral control linkage operated from
outside of airstream, bronze sleeve bearings on each end of vane support, and
Noted. By contractor
provision for manual or automatic operation of same material as housing.
14. Inlet Bell: Curved inlet for when fan is not attached to duct, of same
Noted. By contractor
material as housing.
15. Inlet Cone: Round‐to‐round transition of same material as housing.
Noted. By contractor
16. Outlet Cone: Round‐to‐round transition, of same material as housing.
Noted. By contractor
17. Stack Cap: Vertical discharge assembly with backdraft dampers, of same
Noted. By contractor
material as housing.
18. Direct‐Driven Units: Encase motor in housing outside of airstream,
factory wired to disconnect switch located on outside of fan housing. Extend The proposed fans are with motors
lubrication lines to outside of casing and terminate with grease fittings. inside the air stream.
F. Factory Finishes:
1. Sheet Metal Parts: Prime coat before final assembly.
2. Exterior Surfaces: Baked‐enamel finish coat after assembly.
3. Coatings: Hot‐dip galvanized. Comply
Variable features indicated in equipment schedule include belt driven or direct
drive as indicated, and variable or adjustable pitch.
7/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
1. Variable‐Pitch Fans: Internally mounted pneumatic actuator, externally
mounted positive positioner, and mechanical‐blade‐pitch indicator for variable‐
volume operation.
B. Housings: Galvanized steel with inlet bell and diffuser sections.
1. Inlet and Outlet Connections: Outer mounting frame and companion
flanges; inlet cone shall be welded to the fan raceway.
2. Guide Vane Section: Integral guide vanes downstream from the fan
wheel designed to straighten the airflow.
3. Sound‐Trap Housing: Housing incorporating perforated steel inner liner,
2 inch (50 mm) fiberglass duct liner sandwiched between the inner and outer
shell, and steel bands sealing the insulated cavity.
C. Wheels Assemblies: Cast‐aluminum hub assembly, machined and fitted with
threaded bearing wells to receive blade‐bearing assemblies with replaceable,
cast‐aluminum blades; factory mounted and balanced.
D. Belt Drives: Factory mounted, with final alignment and belt adjustment
made after installation.
1. Service Factor Based on Fan Motor Size: 1.2
2. Fan Shaft: Turned, ground, and polished steel designed to operate at no
more than 70 percent of first critical speed at top of fan's speed range.
3. Fan Pulleys: Cast iron with split, tapered bushing; dynamically balanced
at factory.
4. Motor Pulleys: Adjustable pitch Select pulley so pitch adjustment is at
the middle of adjustment range at fan design conditions.
5. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for
multiple belt drives.
6. Belt Guards: Fabricate of steel for motors mounted on outside of fan
cabinet.
7. Motor Mount: Adjustable base.
8/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
8. Shaft Bearings: Radial, self‐aligning bearings.
a. Ball‐Bearing Rating Life: ABMA 9, L10 of 100,000 hours.
b. Extend lubrication lines to outside of casing and terminate with grease
fittings.
E. Accessories:
1. Companion Flanges: Rolled flanges of same material as housing.
2. Inspection Door: Bolted door allowing limited access to internal parts of
fan, of same material as housing.
3. Propeller Access Section Door: Short duct section bolted to fan inlet
and outlet allowing access to internal parts of fan for inspection and cleaning,
of same material as housing.
4. Swingout Construction: Assembly allowing entire fan section to swing
out from duct for cleaning and servicing, of same material as housing.
5. Mounting Clips: Horizontal ceiling clips welded to fan housing, of same
material as housing.
6. Horizontal Support: Pair of supports bolted to fan housing, of same
material as housing.
7. Vertical Support: Short duct section with welded brackets bolted to fan
housing, of same material as housing.
8. Inlet Screen: Wire‐mesh screen on fans not connected to ductwork, of
same material as housing.
9. Outlet Screen: Wire‐mesh screen on fans not connected to ductwork,
of same material as housing.
10. Backdraft Dampers: Butterfly style, for mounting with flexible
connection to the discharge of fan or direct mounted to the discharge diffuser
section, of same material as housing.
9/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
(For parking ventilation axial fans: In case Motorized smoke damper/Motorized
damper provided as per design drawings, Backdraft damper to be cancelled)
11. Stall Alarm Probe: Sensing probe capable of detecting fan operation in
stall and signaling control devices.
12. Flow Measurement Port: Pressure measurement taps installed in the
inlet of fan to detect and signal airflow readings to temperature‐control
systems. Control devices and sequence of operation are specified in Section
230923.14 "Flow Instruments" and Section 230993.11 "Sequence of Operations
for HVAC DDC."
13. Shaft Seal: Elastomeric seal and Teflon wear plate, suitable for up to 300
deg F (148 deg C).
14. Motor Cover: Cover with side vents to dissipate motor heat, of same
material as housing.
15. Inlet Vanes: Adjustable; with peripheral control linkage operated from
outside of airstream, bronze sleeve bearings on each end of vane support, and
provision for manual or automatic operation, of same material as housing.
16. Inlet Bell: Curved inlet for when fan is not attached to duct, of same
material as housing.
17. Inlet Cone: Round‐to‐round transition, of same material as housing.
18. Outlet Cone: Round‐to‐round transition, of same material as housing.
19. Stack Cap: Vertical discharge assembly with backdraft dampers, of same
material as housing.
20. Direct‐Driven Units: Encase motor in housing outside of airstream,
factory wired to disconnect switch located on outside of fan housing. Extend
lubrication lines to outside of casing and terminate with grease fittings.
10/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
F. Factory Finishes:
1. Sheet Metal Parts: Prime coat before final assembly.
2. Exterior Surfaces: Baked‐enamel finish coat after assembly.
3. Coatings: Hot‐dip galvanized.
a. Apply to finished housings.
b. Apply to fan wheels.
B. Housing: Consist of inner and outer tube, motor flange and guide blade
assembly. Fan housing is to be manufactured from mild steel to ISO 3574, grade
Comply as Noted As per EN standards.
HR 14 or equivalent. The housing assembly is to be hot dip galvanized in
accordance with ISO 1461.
C. Performance – Independently tested and certified in accordance with EN
Comply as per EN 12101‐3, ISO AJR Jets are tested for 300 deg C for 2 hours.
12101‐3, ISO 13350, ISO 5801, fans and silencers should be rated at 300 degree
5801 Certiified by BSI.
°C for two hours.
D. Impeller: Shall be statically and dynamically balanced on a balancing
machine in accordance with the requirements of ISO 1940.The entire jet fan
assembly, when operating at full speed shall vibrate at less than 4.5 mm/s. Comply as Noted As per EN standards.
Balance class: G 2.5 measured according to ISO 1940 standard.
E. Blades and Hub: Cast from aluminum. Comply
11/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
F. Silencers: Tubular directly mounted on inlet and outlet of fan, of steel
inner casing with galvanized steel outer casing welded to hot dip galvanized
ends and bell mouths, fitted with stainless steel perforated line and galvanized
steel aerodynamic pod, and solid and galvanized steel wire mesh at inlet /
deflector vanes at outlet. Comply as Noted As per attached data sheets
Sound Pressure Level: Select to give sound levels NC 55 inside parking
measured on the A‐scale of a standard sound level meter at 3 m from the open
fan inlet. The unit shall be designed inlet and outlet attenuators which, along
with the fan unit, are encased in a Galvanized steel acoustic enclosure
G. Motor: Squirrel type reversible single speed, 50 Hz rating, pad mounted,
with self‐lubricating ball bearings of L10 life, continuously air stream rated and Comply with TEAO motors. Self lubricating ball
complying fully with IEC 60034‐1, Class F insulation. The motor shall be suitable Comply as Noted bearings of L10 ‐ 40000 hours. Class F insulation
for handling smoke laden air at 300 deg. C for 2 hours. and suitable for 300 deg C for 2 hours.
H. Suspension: Anti‐vibration compression spring type fixed to tunnel roof
by means of stainless steel studding/nut system. Studding is to be screwed into
stainless steel sockets and locked by means of heavy duty "LOCTITE" or Noted. By Contractor
approved equal. Bolts are to be painted after installation with two coats epoxy
anti‐corrosion paint.
I. Finish: The complete fan is to be painted after degreasing, with one coat of
mordant wash followed by one coat of epoxy prime and one coat of epoxy thick
Noted. By Contractor
layer and finish paint Polyurethane to give a total mean dry film thickness of 70‐
180 microns. Color to be agreed by the Engineer.
J. The contractor shall perform CFD modelling for the design based on the
actual approved equipment, layouts, and installation to confirm that the system Noted. Shall be provided on
performance meet design intent and authority have jurisdiction. request.
2.4 MOTORS
12/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
A. Refer to Section "Common Motors Requirements for HVAC Equipment" for
general requirements for factory‐installed motors.
B. Motor Construction: NEMA MG 1, general purpose, continuous duty, Design
Comply
B.
C.Enclosure Type: The following features are required as indicated:
1.Open dripproof motors where satisfactorily housed or remotely located
Not Applicable
during operation.
2.Guarded dripproof motors where exposed to contact by employees or
Not Applicable
building occupants.
2.5 FACTORY FINISHES
A.Sheet Metal Parts: Prime coat before final assembly.
B.Exterior Surfaces: Baked‐enamel finish coat after assembly.
2.6 SOURCE QUALITY CONTROL
A. Testing Requirements: The following factory tests are required as indicated:
1. Sound Power Level Ratings: Comply with AMCA 301, "Methods for
Calculating Fan Sound Ratings from Laboratory Test Data." Test fans according
Comply with Comments Systemair Labs are AMCA certified 210 & 300 .
to AMCA 300, "Reverberant Room Method for Sound Testing of Fans." Label
fans with the AMCA Seal.
2. Fan Performance Ratings: Establish flow rate, pressure, power, air density,
speed of rotation, and efficiency by factory tests and ratings according to AMCA
Comply with Comments Systemair Labs are AMCA certified 210 & 300 .
210, "Laboratory Methods of Testing Fans for Certified Aerodynamic
Performance Rating."
B. Fans used for smoke extract shall be UL listed and shall be suitable for high
Not Applicable
temperature application as per design requirements.
C. Noise level of fans shall not exceed noise level specified for location of
Comply with Comments 72/57 dB(A) at 3 Meter .
installation. The overall efficiency shall be minimum 60%.
13/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
PART 3 EXECUTION
3.1 EXAMINATION By Contractor
A. Examine areas and conditions for compliance with requirements for
installation tolerances and other conditions affecting performance of the fans.
Do not proceed with installation until unsatisfactory conditions have been
corrected.
3.2 INSTALLATION By Contractor
A.Install fans according to manufacturer's written instructions.
B.Support units using the vibration‐control devices indicated. Vibration‐control
devices are specified in Section "Vibration and Seismic Controls for HVAC Piping
and Equipment."
C.Suspend units from structure using threaded steel rods, vibration isolation
springs and seismic restraints. Vibration‐control devices are specified in Section
"Vibration and Seismic Controls for HVAC Piping and Equipment."
D.Install units with clearances for service and maintenance.
E.Label fans according to requirements specified in Section "Identification for
HVAC Piping and Equipment."
14/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
3.6 CLEANING
A.After completing installation, inspect exposed finish. Remove burrs, dirt, and
construction debris, and repair damaged finishes including chips, scratches, and
abrasions.
B.Clean fan interiors to remove foreign material and construction debris.
Vacuum clean fan wheel and cabinet.
A. Final Checks before Startup: Perform the following operations and checks
before startup, and report results in writing:
1.Verify that shipping, blocking, and bracing are removed.
2.Verify that unit is secure on mountings and supporting devices and that
connection for piping, ducts, and electrical components are complete.
Verify that proper thermal‐overload protection is installed in motors, starters,
and disconnects.
3.Perform cleaning and adjusting specified in this Section.
15/16
COMPLIANCE SHEET
Project Name Central Business District
Consultant Dar Al Handasah
S.No Specification Remarks
4.Disconnect fan drive from motor, verify proper motor rotation direction, and
verify fan wheel free rotation and smooth bearings operation. Reconnect fan
drive system, align and adjust belts, and install belt guards.
5.Verify lubrication for bearings and other moving parts.
6.Verify that manual and automatic volume control and fire and smoke
dampers in connected ductwork systems are in the fully open position.
B. Starting procedures for fans are as follows:
1.Energize motor; verify proper operation of motor, drive system, and fan
wheel. Adjust fan to indicated RPM.
2.Measure and record motor voltage and amperage.
C. Refer to Section "Testing, Adjusting, and Balancing for HVAC" for procedures
for air‐handling‐system testing, adjusting, and balancing.
D. Replace or adjust fan and motor pulleys as required to achieve design
conditions.
Fix in final position after balancing is achieved.
3.8 DEMONSTRATION By Contractor
A. Train Employer's maintenance personnel to adjust, operate, and maintain
axial fan units. Refer to Division 1.
END OF SECTION 233413