Report
Contents
1. Introduction................................................................................................................................................ 3
2. Design criteria............................................................................................................................................ 3
2.1 Materials.................................................................................................................................................... 3
2.2 Design Loads............................................................................................................................................. 4
2.2.1 Dead Loads............................................................................................................................................... 4
2.2.2 Superimposed Dead Load (SIDL).............................................................................................................. 4
2.2.3 Live Loads ( LL )........................................................................................................................................ 4
2.2.4 Seismic Load............................................................................................................................................. 4
2.2.5 Wind Load.................................................................................................................................................. 6
2.3 Method of analysis and design for structure.............................................................................................. 6
2.3.1 Codes and Standards................................................................................................................................ 6
2.3.2 Load Combination...................................................................................................................................... 6
2.3.3 Design of Structural Members................................................................................................................... 7
2.3.3.1 Factor of Safety......................................................................................................................................... 7
2.4 Drift and Deflection Limits.......................................................................................................................... 8
2.4.1.1 Drift Limits.................................................................................................................................................. 8
2.4.1.2 Deflection Limits........................................................................................................................................ 8
2.5 Geotechnical Design Parameters.............................................................................................................. 8
3. General Sketch.......................................................................................................................................... 9
4. Analysis and Design.................................................................................................................................. 9
4.1 Structural Modelling................................................................................................................................... 9
4.2 Section Properties.................................................................................................................................... 10
4.3 Load Application...................................................................................................................................... 12
4.3.1 Dead Loads............................................................................................................................................. 12
4.3.2 Roof Live Load......................................................................................................................................... 14
4.3.3 Wind Loads.............................................................................................................................................. 15
4.3.4 SeismicLoads.......................................................................................................................................... 24
4.4 Load Combinations.................................................................................................................................. 26
4.5 Analysis Output........................................................................................................................................ 28
4.5.1 Shear Y Diagram..................................................................................................................................... 28
4.5.2 Shear Z Diagram..................................................................................................................................... 28
4.5.3 Moment Y Diagram.................................................................................................................................. 29
4.5.4 Moment Z Diagram.................................................................................................................................. 29
4.6 Serviceability Check................................................................................................................................. 30
4.6.1 Drift Check............................................................................................................................................... 30
Structural Calculation
Report
1. Introduction
This calculation is for the structural analysis and design of Bagging Electrical Room for Cemex Cement Plant.
2. Design criteria
The following cover the design criteria used for the analysis and design of the Bagging Electrical Room. The
criteria used are in accordance with Owner Specification as well as the accepted Codes and Standard practises
in Philippines.
2.1 Materials
Steel Reinforcement 16mm diameter and above Yield Strength, fy = 4200 kg/cm2 (60 ksi) Yield
12mm diameter and below Strength, fy = 2800 kg/cm2 (40 ksi)
Unless indicated, otherwise, the minimum cover for reinforced concrete structures shall be:
In no case shall the clear distance be less than 25 mm or less than 1 1/3 times the maximum size of aggregate,
whichever is greater.
Structural Calculation
Report
Dead loads are the weights of the structures and any permanent equipment and appurtenant
structures that do not change with the mode of operation. Dead loads shall include the following:
1. Self-weight of the structure.
2. Weight of permanent machineries and equipment’s shall be based on the vendor’s drawing
and load data.
Superimposed dead loads (SIDL) are the weight of all permanently materials such as cladding,
roofing, etc.
2.2.3 Live Loads ( LL )
The live loads on the limestone crusher shall be based on the following
Live load on concrete deck : 100 kg/m2
Live load in steel roof (slope > 5%) : 60 kg/m2
Live load in floor slab : 500 kg/m2
Live load in stairways : 250 kg/m2
2.2.4 Seismic Load
Inertia force by seismic shall be designed according to the Static Lateral Force procedure in NSCP 2015 Vo. 1
Vertical Earthquake Load, Ev Ev = 0.5Ca I D = 0.22D NSCP 2010 Vol. 1 Section 208.6.1
Seismic Zone Factor, Z Z = 0.4 ( Zone 4) NSCP 2010 Vol. 1 Table 208-3
Soil Profile Type SD (Stiff Soil) NSCP 2010 Vol. 1 Table 208-2
Structural Calculation
Report
Seismic Over-strength Coefficient, R R = 8.5 (SMRF) NSCP 2010 Vol. 1 Table 208-11A
Seismic Coefficient, Ca Ca = 0.44 (for Na = 1.0, source w/in 10km) NSCP 2010 Vol. 1 Table 208-7
Seismic Coefficient, Cv Cv = 0.768 (for Nv = 1.2, source w/in 10km) NSCP 2010 Vol. 1 Table 208-8
Near-Source Factor, Na Na = 1.0 (source w/in 10km, Source Type A) NSCP 2010 Vol. 1 Table 208-5
Near-Source Factor, Nv Nv = 1.2 (source w/in 10km, Source Type A) NSCP 2010 Vol. 1 Table 208-6
Seismic Source Type A (faults capable of Magnitude M ≥ 7.0) NSCP 2010 Vol. 1 Table 208-4
Wind load shall be designed according to the Directional Procedure for Main Wind-Force Resisting Systems
(MWFRS), as stated in NSCP 2015 Vol. 1 Section 207B.
Basic Wind Speed, V V = 260 kph = 72.22 m/s NSCP 2015 Vol. 1 Section 207A.5
Exposure Coefficient, Kz Varies depending on height NSCP 2015 Vol. 1 Table 207B.3-1
Topographic Factor, Kzt Kzt = 1.0 (No hills, ridges, trenches, etc.) NSCP 2015 Vol. 1 Section 207A.8.2
The analysis of the structure shall be carried out in Staad with an idealised 3D model. The design shall
be as per NSCP 2015 Vol. 1.
2.3.1 Codes and Standards
For the design and the execution of the works as well as for the quality of the selected materials in the
performance of the works, applicable codes and standards shall be followed.
1. Philippines local code (National Structural Code of the Philippines) NSCP 2015
2. Reinforced concrete and commentary (latest edition) ACI-318
3. American Institute of Steel Construction (latest edition) AISC
4. American Society of Testing Materials (latest edition) ASTM
5. International Building Code (latest edition) IBC
6. American Society of Civil Engineers (latest edition) ASCE
2.3.2 Load Combination
Load Combinations using Strength Design or Load and Resistance Factor Design:
Where load and resistance factor design is used, structures and all portions thereof shall resist the
most critical effects from the following combinations of factored loads:
1.4(D + F)
1.2(D+ F+T)+1.6(L+H)+0.5(Lr or R)
1.2D+1.6(Lr or R)+( f1L or 0.5W)
1.2D+1.0W+f1L+0.5(Lr or R)
1.2D+1.0E+f1L
0.9D+1.0 W+1.6H
0.9D+1.0 E+1.6H
f1 = 1.0 for floors in places of public assembly, for live loads in excess of 4.8 kPa, and for garage live
load = 0.5 for other live loads
Where allowable stress design (working stress design) is used, structures and all portions thereof shall
resist the most critical effects resulting from the following combinations of loads:
D+F
D+H+F+L+T
D+H+F+(Lr or R)
D+H+F+0.75[L+T+(Lr or R)]
D+H+F+(0.6W or E/1.4)
In lieu of the basic load combinations, structures and portions thereof shall resist the most critical
effects from the following combinations of loads:
D+H+F+0.75[L+Lr+(0.6W or E/1.4)]
0.6D+0.6W+H
0.6D+E/1.4+H
D+L+(Lr or R)
D+L+0.6W
D+L+E/1.4
Note: One-third increase in allowable stresses for all combinations including wind or seismic is
permitted.
For both allowable stress design and strength design, the following special load combinations for
seismic design shall be used:
1.2D+f1L+1.0Em
0.9D±1.0Em
where:
f1 = 1.0 for floors in places of public assembly, for live loads in excess of 4.8 kPa, and for garage live
load = 0.5 for other live loads
Em = The maximum effect of horizontal and vertical forces
2.3.3 Design of Structural Members
Design of structural member will be carried out in Ultimate Limit State and Serviceability Limit State,
with the help of Excel spread sheets in tabular form with proper validation of the design.
2.3.3.1 Factor of Safety
All structures which are subjected to overturning and sliding shall be designed based on the following
requirements:
Overturning Safety Factor = 1.5
Sliding Safety Factor = 1.5
Structural Calculation
Report
Calculated storey drift using ΔM due to seismic effect shall not exceed as follows (NSCP section
208.6.5)
0.025 times the storey height - for structures having a fundamental period less than 0.7 sec.
0.020 times the storey height - for structures having a fundamental period of 0.7 sec. or more
Drift limits from the wind load effect for building design shall be 1/600 to 1/400 of the building height or
storey height (ASCE 7-16 Appendix CC.2.2).
2.4.1.2 Deflection Limits
The below table are the deflection limits as per IBC section 1604.3.1
CONSTRUCTION L S or W D+L
Roof members
Supporting plaster ceiling l/360 l/360 l/240
Supporting nonplaster ceiling l/240 l/240 l/180
Not supporting ceiling l/180 l/180 l/120
Greenhouses - - l/120
The following are the geotechnical design parameters obtained from Soil Investigation Report (Ref.No. GII-
32582-65501-17):
3. General Sketch
Structural Calculation
Report
Figure below shows the visual representation of the model developed in StaadPro.
Structural Calculation
Report
Platform:
Gratings/ C hec kered plate = 0.36 kPa
Elec tric al trays and piping ` 0.97 kPa 130 kg/ m
Total = 1.33 kPa
Structural Calculation
Report
Equipment Load
Weight of elec tric al equipment = 4.91 kPa 500 kg/ m2
Weight of c able rac k on roof (limestone transport) = 1.96 kN/ m 200 kg/ m
1.63 m = 3.19 kN
Weight of c ondensing units on roof = 5.89 kN 600 kg
Weight of indoor unit hang on c onc rete c eiling = 3.43 kN 350 kg
Weight of transformer = 41.20 kN 4200 kg
Load per node (4 support points) = 10.30 kN
2) ANALYSIS
2.1) Geometrical results
Mean roof height, h = 8.6 m
slope, q = 0.00 degrees
2.2) Wind Parameters and Coeffecients
Wind Velocity, V = 260 kph
Importance factor, Iw = 1
Gust effect factor, G = 0.85
Parallel to Ridge
windward Leeward
1st Value, Cp1 1st Value, Cp2 L/B Cp
0 to h/2 -0.921 -0.180 1.579 -0.384
h/2 to h -0.921 -0.180
h to 2h -0.529 -0.180
>2h -0.359 -0.180
z (m) kz qz(kpa)
5.1 0.868 2.360
8.6 0.969 2.634
h (m) kz qh(kpa)
8.6 0.969 2.634
Structural Calculation
Report
NORMAL TO RIDGE
Design Pressure on Wall, P = qzGCp-qhGCpi
Windward Leeward
Case 1 Case 2 Case 1 Case 2
z(m) qzGCp-qh(+GCpi) qzGCp-qh(-GCpi) qhGCp-qh(+GCpi) qhGCp-qh(-GCpi)
5.1 0.156 3.053 -2.568 0.329
8.6 0.342 3.240
PARALLEL TO RIDGE
Design Pressure on Wall, P = qzGCp-qhGCpi
Windward Leeward
Case 1 Case 2 Case 1 Case 2
z(m) qzGCp-qh(+GCpi) qzGCp-qh(-GCpi) qhGCp-qh(+GCpi) qhGCp-qh(-GCpi)
5.1 0.156 3.053 -2.309 0.588
8.6 0.342 3.240
3) SUMMARY
NORMAL TO RIDGE: W1 Rw1 Rl1 L1
-3.016
CASE1:
-3.718 -2.931
0.342 -2.568
0.156
-3.016
W1 Rw2 Rl1 L1
CASE2:
-3.016
-1.852 -2.931
0.342 -2.568
0.156
-3.016
CASE3: W2 Rw3 Rl2 L2
-0.820 -0.034 -0.119
3.240 0.329
3.053
-0.119
CASE4: W2 Rw4 Rl2 L2 -0.119
1.046 -0.034
3.240 0.329
3.053
-0.119
Structural Calculation
Report
PARALLEL TO RIDGE:
-2.309
0.342
0.156
-3.016
-2.309
0.342
0.156
-3.016
0.588
3.240
3.053
-0.119
0.588
3.240
3.053
-0.119
Structural Calculation
Report
4.3.4 SeismicLoads
COMBINATIO
ULS LOAD COMBINATION
N
COMB 201 1.4 DL
COMB 202 1.2 DL + 1.6 LL + 0.5 LR
COMB 203 1.2 DL + 0.5 LL + 1.6 LR
COMB 204 1.2 DL + 1.6 LR + 0.5 WD+X1
COMB 205 1.2 DL + 1.6 LR + 0.5 WD-X1
COMB 206 1.2 DL + 1.6 LR + 0.5 WD+Z1
COMB 207 1.2 DL + 1.6 LR + 0.5 WD-Z1
COMB 208 1.2 DL + 0.5 LL + 0.5 LR + 1 WD+X1
COMB 209 1.2 DL + 0.5 LL + 0.5 LR + 1 WD+X2
COMB 210 1.2 DL + 0.5 LL + 0.5 LR + 1 WD-X1
COMB 211 1.2 DL + 0.5 LL + 0.5 LR + 1 WD-X2
COMB 212 1.2 DL + 0.5 LL + 0.5 LR + 1 WD+Z1
COMB 213 1.2 DL + 0.5 LL + 0.5 LR + 1 WD+Z2
COMB 214 1.2 DL + 0.5 LL + 0.5 LR + 1 WD-Z1
COMB 215 1.2 DL + 0.5 LL + 0.5 LR + 1 WD-Z2
COMB 216 1 EQ X+ + 1.42 DL + 0.5 LL
COMB 217 1 EQ X- + 1.42 DL + 0.5 LL
COMB 218 1 EQ Z+ + 1.42 DL + 0.5 LL
COMB 219 1 EQ Z- + 1.42 DL + 0.5 LL
Structural Calculation
Report
COMBINATIO
ULS LOAD COMBINATION
N
COMB 220 0.9 DL + 1 WD+X1
COMB 221 0.9 DL + 1 WD+X2
COMB 222 0.9 DL + 1 WD-X1
COMB 223 0.9 DL + 1 WD-X2
COMB 224 0.9 DL + 1 WD+Z1
COMB 225 0.9 DL + 1 WD+Z2
COMB 226 0.9 DL + 1 WD-Z1
COMB 227 0.9 DL + 1 WD-Z2
COMB 228 1 EQ X+ + 1.12 DL
COMB 229 1 EQ X- + 1.12 DL
COMB 230 1 EQ Z+ + 1.12 DL
COMB 231 1 EQ Z- + 1.12 DL
COMB 232 1 EQ X+ + 0.68 DL
COMB 233 1 EQ X- + 0.68 DL
COMB 234 1 EQ Z+ + 0.68 DL
COMB 235 1 EQ Z- + 0.68 DL
Note: The effect of Ev is considered by modifying the dead load factor on the load combination.
Load Data
Depth) Depth)
N-M mm mm N-M N-M
Bottom 426.667 No Beam No Beam - - 1
Top 426.667 6500 x 250 x 400 No Beam 20.513 - 26.016
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 0.75
M1 = 0.03 kNm
M2 = 0.5 kNm
34 - 12 x (M1/M2) = 33.3
0.75 < 33.3, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 0.75
M1 = -72.53 kNm
M2 = -82.79 kNm
34 - 12 x (M1/M2) = 23.49
0.75 < 23.49, Column not slender along B
Where
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 221
[37] : 0.9 (LOAD 5: DEAD LOADS) +(LOAD 9:
Critical Load Combination = kN
WIND X+ CASE2)
Nu = 196.52 kN
Muy = 42.6 kNm
Vuy = 38.3431 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 11.66 kNm
Vcy Permissible = 114.04 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design for shear along B
Critical Analysis Load Combination : 234
[50] : 0.68 (LOAD 5: DEAD LOADS) +(LOAD
Critical Load Combination = kN
3: EQ Z+)
Nu = 157.33 kN
Mux = 26.66 kNm
Vux = 43.5194 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 1.88 kNm
Vcx Permissible = 118.18 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
General Data
Column No. : C1,C2,C3,C4,C5,C6,C8,C9,C10,C11,C12
Level : 0.5m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete = C25 N/sqmm
Grade Of Steel = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover = 50 mm
Clear Floor Height @ lux = 2000 mm
Clear Floor Height @ luy = 1600 mm
No Of Floors = 1
No Of Columns In Group = 11
Load Data
Put = 285.13 kN
Muxt = -0.24 kNm
Muyt = -23.41 kNm
Vuxt = 40.87 kN
Vuyt = -0.19 kN
Pub = 295.84 kN
Muxb = -0.62 kNm
Muyb = -105.13 kNm
Vuxb = 40.87 kN
Vuyb = -0.19 kN
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 13.86
M1 = -0.24 kNm
M2 = -0.62 kNm
34 - 12 x (M1/M2) = 29.38
Structural Calculation
Report
Where
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 217
[33] : 1.42 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = kN
(LOAD 6: LIVELOAD) +(LOAD 2: EQ X-)
Nu = 334.39 kN
Muy = 74.23 kNm
Vuy = -52.5637 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 21.58 kNm
Vcy Permissible = 112.96 kN
Structural Calculation
Report
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
General Data
Column No. : C1,C2,C3,C4,C5,C6,C8,C9,C10,C11,C12
Level : 2.5m To 6.6m
Design Code = ACI 318M - 2011
Grade Of Concrete = C25 N/sqmm
Grade Of Steel = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 11
Load Data
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 31.61
M1 = -9.1 kNm
M2 = 12.63 kNm
34 - 12 x (M1/M2) = 42.64
31.61 < 42.64, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 31.61
M1 = 90.61 kNm
M2 = -148.96 kNm
34 - 12 x (M1/M2) = 41.3
31.61 < 41.3, Column not slender along B
Where
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 210
[26] : 1.2 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = (LOAD 6: LIVELOAD) +(LOAD 10: WIND X- kN
CASE1) +0.5 (LOAD 7: ROOF LIVE LOAD)
Nu = 163.18 kN
Muy = 35.79 kNm
Vuy = -38.4791 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 10.1 kNm
Vcy Permissible = 115.03 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design for shear along B
Critical Analysis Load Combination : 222
[38] : 0.9 (LOAD 5: DEAD LOADS) +(LOAD
Critical Load Combination = kN
10: WIND X- CASE1)
Nu = 118.57 kN
Mux = 28.5 kNm
Vux = 41.5019 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 9.83 kNm
Vcx Permissible = 117.18 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Structural Calculation
Report
Diameter of link = 10 mm
General Data
Column No. : C7
Level : 0m To 0.5m
Design Code = ACI 318M - 2011
Grade Of Concrete = C25 N/sqmm
Grade Of Steel = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover = 50 mm
Clear Floor Height @ lux = 100 mm
Clear Floor Height @ luy = 100 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
Structural Calculation
Report
r = 115.47 mm
Kluy /r = 0.75
M1 = 0.2 kNm
M2 = -0.9 kNm
34 - 12 x (M1/M2) = 36.62
0.75 < 36.62, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 0.75
M1 = 53.73 kNm
M2 = 68.91 kNm
34 - 12 x (M1/M2) = 24.64
0.75 < 24.64, Column not slender along B
Where
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 219
[35] : 1.42 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = kN
(LOAD 6: LIVELOAD) +(LOAD 4: EQ Z-)
Nu = 429.94 kN
Muy = 0.48 kNm
Vuy = 4.8067 kN
λ = 1
Structural Calculation
Report
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 67.21 kNm
Vcy Permissible = 263.43 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design for shear along B
Critical Analysis Load Combination : 235
[51] : 0.68 (LOAD 5: DEAD LOADS) +(LOAD
Critical Load Combination = kN
4: EQ Z-)
Nu = 212.59 kN
Mux = 44.28 kNm
Vux = 37.4128 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 10.81 kNm
Vcx Permissible = 113.73 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
Table For Links
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 2-#10 10 2-#10
Spacing 200 --- 100 200 100
General Data
Column No. : C7
Level : 2.5m To 6.6m
Design Code = ACI 318M - 2011
Grade Of Concrete = C25 N/sqmm
Grade Of Steel = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover = 50 mm
Clear Floor Height @ lux = 5650 mm
Clear Floor Height @ luy = 5650 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Top 52.032 4500 x 250 x 450 4500 x 250 x 450 42.188 42.188 0.616
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.83
r = 115.47 mm
Kluy /r = 40.61
M1 = -1.47 kNm
M2 = 3.47 kNm
34 - 12 x (M1/M2) = 39.07
40.61 > 39.07,Column slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.83
r = 115.47 mm
Klux /r = 40.61
M1 = 109.91 kNm
M2 = -126.66 kNm
34 - 12 x (M1/M2) = 44.41
40.61 < 44.41, Column not slender along B
Moment Magnification:
For Non-sway frame:
Along D
βdns = 0.6
Ec = 23500 N/sqmm
Ig ( x 10 9) = 2.133 mm^4
EI ( x 10 6) = 14472240 >N-sqmm
M2min = 10 kNm
Cm = 1
Pc = 6495.05 kN
δns = 1.08
Structural Calculation
Report
Mc1 = -10.83 kN
Mc2 = 10.83 kN
Where
Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 219
[35] : 1.42 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = kN
(LOAD 6: LIVELOAD) +(LOAD 4: EQ Z-)
Nu = 390.35 kN
Muy = 1.52 kNm
Vuy = -0.8332 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 59.93 kNm
Vcy Permissible = 258.06 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
Design for shear along B
Critical Analysis Load Combination : 218
[34] : 1.42 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = kN
(LOAD 6: LIVELOAD) +(LOAD 3: EQ Z+)
Nu = 370.48 kN
Structural Calculation
Report
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
Beam No : B1,B4,B7
0.5m : 9093,9098,9271
Vs (kN) - - -
VD+L (kN) 16.38 16.34
Mh (kNm) 64.71 64.71
Ms (kNm) 64.71 64.71
Sway-Right (kN) 15.18 47.91
Sway-Left (kN) 47.95 15.22
Vu-Sway (kN) 47.95 47.91
Vud (kN) 47.95 47.91
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.54 0.54 0.54
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Group : G1
Structural Calculation
Report
Beam No : B2,B5,B8
0.5m : 9094,9099,9272
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Group : G1
Beam No : B3,B6,B9
Structural Calculation
Report
0.5m : 9095,9100,9273
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Group : G4
Beam No : B10,B16
0.5m : 9092,9097
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Group : G4
Beam No : B11,B17
0.5m : 9091,9096
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Group : G5
Beam No : B12,B14
0.5m : 9275,9277
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Group : G5
Beam No : B13,B15
0.5m : 9274,9276
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Beam No : B1,B5
2.5m : 363,371
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 209 221 233 217 233 216
Critical L/C - RCDC 25 37 49 33 49 32
Mu (kNm) 9.402 10.173 9.45 52.95 10.168 53.986
As (flex) (sqmm) (C) 76.07 82.37 76.46 448.58 82.32 457.91
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.569 0.996 0.25 0.614 0.251 0.761
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 275 275 496.4 583.16 275 595.28
AstPrv (sqmm) 397.12 397.12 595.68 774.16 397.12 774.16
Reinforcement 2-#16 2-#16 3-#16 2-#22 2-#16 2-#22
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Group : G1
Structural Calculation
Report
Beam No : B2,B6
2.5m : 364,368
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Spacing Criteria
Maximum Spacing = 280 mm
Group : G1
Beam No : B3,B7
2.5m : 365,369
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 35 35 35
PtPrv (%) 0.938 0.481 0.938
Vu (kN) 40.2 20.36 39.17
Mu-Sect (kNm) - 3.48 -
Vc (kN) 79.16 72.75 79.16
Vs (kN) - - -
VD+L (kN) 27.95 28
Mh (kNm) 118.58 118.58
Ms (kNm) 94 94
Sway-Right (kN) 23.9 79.85
Sway-Left (kN) 79.8 23.85
Vu-Sway (kN) 79.8 79.85
Vud (kN) 79.8 79.85
Av (sqmm) 301.82 301.82 301.82
Tu (kNm) 4.8 4.8 4.8
Ao= Φ*Aoh 44550 44550 44550
At (sqmm) 301.82 301.82 301.82
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 301.821 301.821 301.821
Av Total Reqd (sqmm) 301.82 301.82 301.82
Asv Reqd (sqmm) 301.821 301.821 301.821
SCalc (mm) 100 125 100
SPrv (mm) 100 125 100
Av Total Prv (sqmm) 1417.6 1134.08 1417.6
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Torsion
(X1 = 180, Y1 = 330)
Spc3 = X1 = 180 mm
Spc4=(X1+Y1)/4 = 125 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
Spc6 = d / 4 = 82 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Structural Calculation
Report
Skin reinforcement
Group : G2
Beam No : B4,B10
2.5m : 9293,367
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Torsion
Structural Calculation
Report
Skin reinforcement
Group : G4
Beam No : B8,B11
2.5m : 366,372
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 227 206 234 218 218 219
Critical L/C - RCDC 43 22 50 34 34 35
Mu (kNm) 10.061 10.093 9.44 57.074 10.036 57.784
As (flex) (sqmm) (C) 81.45 81.71 76.35 485.81 81.24 492.26
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 2.277 1.859 0.04 1.245 1.245 1.103
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 275 275 496.4 631.56 275 639.94
AstPrv (sqmm) 397.12 397.12 595.68 859.56 595.68 1161.24
Reinforcement 2-#16 2-#16 3-#16 3-#19 3-#16 3-#22
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Group : G4
Beam No : B9,B12
2.5m : 370,9299
Basic
Spc1 =d/2 = 165 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 82 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 165 mm
Skin reinforcement
Beam No : B1
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Torsion
(X1 = 180, Y1 = 380)
Spc3 = X1 = 180 mm
Spc4=(X1+Y1)/4 = 125 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
Spc6 = d / 4 = 95 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
Spacing Criteria
Maximum Spacing = 280 mm
Group : G1
Beam No : B2
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.815 0.418 0.815
Vu (kN) 30.11 19.44 30.73
Mu-Sect (kNm) - 1.46 -
Vc (kN) 89.16 82.75 89.16
Vs (kN) - - -
VD+L (kN) 21.75 21.7
Mh (kNm) 138.9 138.9
Ms (kNm) 109.63 75.13
Sway-Right (kN) 38.87 82.32
Sway-Left (kN) 73.95 30.5
Vu-Sway (kN) 73.95 82.32
Vud (kN) 73.95 82.32
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 1.24 1.24 1.24
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 175 100
SPrv (mm) 100 175 100
Av Total Prv (sqmm) 1417.6 810.06 1417.6
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 95 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
Structural Calculation
Report
Group : G1
Beam No : B3
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Torsion
(X1 = 180, Y1 = 380)
Spc3 = X1 = 180 mm
Spc4=(X1+Y1)/4 = 125 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
Spc6 = d / 4 = 95 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
Structural Calculation
Report
Group : G2
Beam No : B4
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
Skin reinforcement
Group : G2
Beam No : B5
Vs (kN) - - -
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.11 0.11 0.11
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 125 200 200
SPrv (mm) 125 200 200
Av Total Prv (sqmm) 1134.08 708.8 708.8
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
Skin reinforcement
Group : G2
Beam No : B6
Basic
Structural Calculation
Report
Skin reinforcement
Group : G3
Beam No : B7
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 95 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Structural Calculation
Report
Skin reinforcement
Group : G3
Beam No : B8
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 95 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
Structural Calculation
Report
Group : G3
Beam No : B9
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 95 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
Group : G4
Beam No : B10
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
Skin reinforcement
Group : G4
Beam No : B11
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis - 229 - 217 232 216
Critical L/C - RCDC - 45 - 33 48 32
Mu (kNm) - 13.503 - 43.585 1.379 46.502
As (flex) (sqmm) (C) - 94.94 - 313.66 9.61 335.44
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) - 0.148 - 0.184 0.071 0.159
Tcr/4 (kNm) - 2.81 - 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 190 316.67 190 407.76 316.67 436.08
AstPrv (sqmm) 397.12 397.12 397.12 595.68 595.68 595.68
Reinforcement 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
Skin reinforcement
Group : G4
Beam No : B12
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
Skin reinforcement
Group : G5
Beam No : B13
Structural Calculation
Report
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 95 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
Maximum Spacing = 280 mm
Group : G5
Beam No : B14
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 95 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
Group : G5
Beam No : B15
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
Spc4 = d / 4 = 95 mm
Spc5 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
Group : G6
Beam No : B16,B22
6.6m : ((418,386),431,389)
Structural Calculation
Report
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Torsion
(X1 = 180, Y1 = 380)
Spc3 = X1 = 180 mm
Spc4=(X1+Y1)/4 = 125 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
Spc6 = d / 4 = 95 mm
Spc7 = 150 mm
Structural Calculation
Report
Skin reinforcement
Group : G6
Beam No : B17,B23
6.6m : ((417,382),425,385)
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Torsion
(X1 = 180, Y1 = 380)
Spc3 = X1 = 180 mm
Spc4=(X1+Y1)/4 = 125 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
Spc6 = d / 4 = 95 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
Group : G7
Beam No : B18,B20
6.6m : ((427,387),429,388)
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Torsion
(X1 = 230, Y1 = 380)
Spc3 = X1 = 230 mm
Spc4=(X1+Y1)/4 = 150 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
Spc6 = d / 4 = 95 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
Group : G7
Beam No : B19,B21
6.6m : ((421,383),423,384)
Basic
Spc1 =d/2 = 190 mm
Spc2 = 300 mm
For Torsion
(X1 = 230, Y1 = 380)
Spc3 = X1 = 230 mm
Spc4=(X1+Y1)/4 = 150 mm
For Ductility (Special Frames)
Left Section, Right Section
Spc5 = 6 x Small Longitudinal Dia = 114.6 mm
Spc6 = d / 4 = 95 mm
Spc7 = 150 mm
Provided Spacing = 100 mm
Mid Section
Provided Spacing = 190 mm
Skin reinforcement
lx x
½ Column strip
Middle strip
ly
½ Column strip
124 mm
300 mm
Section at middle strip along
Structural Calculation
Report
lx x
½ Column strip
A'sy_col
Asx_col A'sx_col
Asy_mid
Middle strip
ly
Asx_mid A'sx_mid
Asy_col
½ Column strip
A'sy_mid
P
p/2
PpP
p/2 P
100 in pPp
50 in
;
Structural Calculation
Report
Footing No : FC1
Analysis No : 9244,9243,9242,9241,9247,1007,989,9240,9246,9245,9238,9239
Structural Calculation
Report
Clear Cover : 75 mm
Dfd : 1.8 M
Dw : 15 M
Structural Calculation
Report
Critical Load Combination = [13] : (LOAD 5: DEAD LOADS) +0.714 (LOAD 1: EQ X+)
P
= Pcomb + Effective Self Weight
P = 444.99 kN
Mx = 39.68 kNm
My = 1.2 kNm
P/A = 227.04 kN/sqm
Mx/Zx = 86.77 kN/sqm
My/Zy = 2.62 kN/sqm
Maximum Soil Pressure = 316.44 kN/sqm
Allowable Soil Pressure = 1 X 332.4 kN/sqm
= 332.4 kN/sqm
Check For Minimum Soil Pressure:
Footing designed with loss of contact
Critical Column No = C1
Critical Analysis Load Combination = 115
Critical Load Combination = [15] : (LOAD 5: DEAD LOADS) +0.714 (LOAD 3: EQ Z+)
Pcomb = 135.34 kN
P = Pcomb + Soil Wt. + Footing Wt.
P = 198.64 kN
Mx = -1.23 kNm
My = 47.26 kNm
P/A = 101.35 kN/sqm
Mx/Zx = -2.7 kN/sqm
My/Zy = 103.35 kN/sqm
Minimum Soil Pressure = -4.7 kN/sqm
< 0
Uplift condition = Corner uplift
Area of loss of contact = 0.01995 sqm
= 1.018 %
< 50 %
Corner pressure P1 = 202 kN/sqm
Corner pressure P2 = 207.449 kN/sqm
Corner pressure P3 = 0.66 kN/sqm
Corner pressure P4 = -4.79 kN/sqm
Point of zero pressure Distance measured from uplift corner
Along long edge = 0.03 m
Along short edge = 1.23 m
P = 198.64 kN
Mx = -1.23 kNm
My = 47.26 kNm
P/A = 101.35 kN/sqm
Mx/Zx = -2.7 kN/sqm
My/Zy = 103.35 kN/sqm
Minimum Soil Pressure = -4.7 kN/sqm
> 0
Structural Calculation
Report
Deff = 217 mm
Beff = 1400 mm
SPu = 397.83 kN/sqm
Mu = SPu X B X Loff X Loff / 2
= 69.62 kNm
Ast Rqd (BM) = 880 sqmm
Ast Prv = 8 - #16 @ 200
= 1588 sqmm
Distributed Across Total Width
Top Steel Along L:
Percentage loss of contact (LOC) = 1.018 %
Weight of footing per unit area (W1) = D X Concrete Density
= 7.5 kN/sqm
Weight of soil over footing (W2) = (Df - D) X SoilDen
= 27 kN/sqm
Total downward weigth per unit area (W) = W1 + W2
= 34.5 kN/sqm
Component of footing length subjected to LOC
= (LOC / 100) X L
(LOCL)
= 14.252 mm
Moment along L = W X (LOCL^2) X B / 2
= 0.005 kNm
Effective width = B
= 1400 mm
Pt = 0.18 %
Ast Calculated = 547 sqmm
Ast Provided = #16 @ 200 c/c
= 1588 sqmm
Bottom Reinforcement Along B:
Critical Column No = C6
Critical Analysis Load Combination = 218
Critical Load Combination = [85] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD) +(LOAD 3:
EQ Z+)
Pu = 497.19 kN
Mux = 1.05 kNm
Muy = 66.07 kNm
P/A = 253.67 kN/sqm
Mx/Zx = 2.31 kN/sqm
My/Zy = 144.46 kN/sqm
Deff = 201 mm
Leff = 1400 mm
SPu = 398.13 kN/sqm
Mu = SPu X L X Boff X Boff / 2
= 69.67 kNm
Ast Rqd (BM) = 957 sqmm
Ast Prv = 8 - #16 @ 200
= 1588 sqmm
Distributed Across Total Length
Top Steel Along B:
Percentage loss of contact (LOC) = 1.018 %
Weight of footing per unit area (W1) = D X ConDen
= 7.5 kN/sqm
Weight of soil over footing (W2) = (Df - D) X SoilDen
Structural Calculation
Report
= 27 kN/sqm
Total downward weigth per unit area (W) = W1 + W2
= 34.5 kN/sqm
Component of footing breadth subjected to
= (LOC / 100) X B
LOC (LOCB)
= 14.252 mm
Moment along B = W X (LOCB^2) X L / 2
= 0.005 kNm
Effective width = L
= 1400 mm
Pt = 0.19 %
Ast Calculated = 546 sqmm
Ast Provided = 8 - #16 @ 200 c/c
= 1588 sqmm
Design For Shear:
One Way Shear Along L:
Critical Section @ d from Column Face
= 217 mm
Critical Column No = C6
Critical Analysis Load Combination = 216
Critical Load Combination = [83] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD) +(LOAD 1:
EQ X+)
Pu = 541.48 kN
Mux = 55.6 kNm
Muy = 1.71 kNm
P/A = 276.27 kN/sqm
Mx/Zx = 121.57 kN/sqm
My/Zy = 3.73 kN/sqm
Deff = 217 mm
Beff = 1400 mm
SPu = 397.83 kN/sqm
Vu = SPu X (Loff - d) X B
= 157.62 kN
Vc = 244.39 kN
Vu < Vc
One Way Shear Along B:
Critical Section @ d from Column Face
= 201 mm
Critical Column No = C6
Critical Analysis Load Combination = 218
Critical Load Combination = [85] : 1.42 (LOAD 5: DEAD LOADS)
+0.5 (LOAD 6: LIVELOAD) +(LOAD 3:
EQ Z+)
Pu = 497.19 kN
Mux = 1.05 kNm
Muy = 66.07 kNm
P/A = 253.67 kN/sqm
Mx/Zx = 2.31 kN/sqm
My/Zy = 144.46 kN/sqm
Deff = 201 mm
Leff = 1400 mm
SPu = 398.13 kN/sqm
Vu = SPu X (Boff - d) X L
= 166.66 kN
Vc = 228.36 kN
Structural Calculation
Report
Vu < Vc
Design For Punching Shear:
Critical Section @ d/2 from Column Face
= 104 mm
Critical Column No = C6
Critical Analysis Load Combination = 216
Critical Load Combination = [83] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD) +(LOAD 1:
EQ X+)
Pu = 541.48 kN
Mux = 55.6 kNm
Muy = 1.71 kNm
P/A = 276.27 kN/sqm
Mx/Zx = 121.57 kN/sqm
My/Zy = 3.73 kN/sqm
Deff = 209 mm
Leff = 609 mm
Beff = 609 mm
SPu = Average Pressure
= 276.27 kN/sqm
Vud = { N - Pcr(axial)[ (Cx + d) X (Cy + d)]}
= 439.02 kN
Vn = 1138.436 kN
Vc = 751.368 kN
Vud < Vc No Shear Reinforcement Required
Load Transfer Check For Load Transfer From Column To Footing
Critical Column No = C6
Critical Analysis Load Combination = 216
Critical Load Combination = [83] : 1.42 (LOAD 5: DEAD LOADS)
+0.5 (LOAD 6: LIVELOAD) +(LOAD 1:
EQ X+)
Pu = 541.48 kN
A2 = 0.16 sqm
A1 = 2.56 sqm
Base Area = 1.96 sqm
A1 > Base Area
Thus, A1 = 1.96
Modification Factor = SquareRoot(A1/A2) < = 2
SquareRoot(A1/A2) = 3.5
Thus, Modification Factor = 2
ΦPnb = 0.85 X 0.75 X Fck X Modication Factor X Column Area
= 4080 kN
ΦPnb > Pu, Hence Safe.