Structural Calculation

Report

TITLE : Bagging Electrical Room Rev[B]

Contents

1. Introduction................................................................................................................................................ 3
2. Design criteria............................................................................................................................................ 3
2.1 Materials.................................................................................................................................................... 3
2.2 Design Loads............................................................................................................................................. 4
2.2.1 Dead Loads............................................................................................................................................... 4
2.2.2 Superimposed Dead Load (SIDL).............................................................................................................. 4
2.2.3 Live Loads ( LL )........................................................................................................................................ 4
2.2.4 Seismic Load............................................................................................................................................. 4
2.2.5 Wind Load.................................................................................................................................................. 6
2.3 Method of analysis and design for structure.............................................................................................. 6
2.3.1 Codes and Standards................................................................................................................................ 6
2.3.2 Load Combination...................................................................................................................................... 6
2.3.3 Design of Structural Members................................................................................................................... 7
2.3.3.1 Factor of Safety......................................................................................................................................... 7
2.4 Drift and Deflection Limits.......................................................................................................................... 8
2.4.1.1 Drift Limits.................................................................................................................................................. 8
2.4.1.2 Deflection Limits........................................................................................................................................ 8
2.5 Geotechnical Design Parameters.............................................................................................................. 8
3. General Sketch.......................................................................................................................................... 9
4. Analysis and Design.................................................................................................................................. 9
4.1 Structural Modelling................................................................................................................................... 9
4.2 Section Properties.................................................................................................................................... 10
4.3 Load Application...................................................................................................................................... 12
4.3.1 Dead Loads............................................................................................................................................. 12
4.3.2 Roof Live Load......................................................................................................................................... 14
4.3.3 Wind Loads.............................................................................................................................................. 15
4.3.4 SeismicLoads.......................................................................................................................................... 24
4.4 Load Combinations.................................................................................................................................. 26
4.5 Analysis Output........................................................................................................................................ 28
4.5.1 Shear Y Diagram..................................................................................................................................... 28
4.5.2 Shear Z Diagram..................................................................................................................................... 28
4.5.3 Moment Y Diagram.................................................................................................................................. 29
4.5.4 Moment Z Diagram.................................................................................................................................. 29
4.6 Serviceability Check................................................................................................................................. 30
4.6.1 Drift Check............................................................................................................................................... 30
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.6.2 Deflection Check...................................................................................................................................... 31


4.7 Concrete Design...................................................................................................................................... 32
4.7.1 Concrete Columns................................................................................................................................... 32
4.7.2 Concrete Tie Beams................................................................................................................................ 50
4.7.3 Concrete Ground Beams......................................................................................................................... 63
4.7.4 Concrete Deck Beams............................................................................................................................. 76
4.7.5 Concrete Two way Slab......................................................................................................................... 111
4.7.6 Concrete Slab on Grade........................................................................................................................ 117
4.8 Foundation Design................................................................................................................................. 119
4.8.1 Foundation Layout................................................................................................................................. 119
4.8.2 Foundation Design................................................................................................................................. 119
4.8.3 Foundation Schedule............................................................................................................................. 126
4.8.4 Transformer Equipment......................................................................................................................... 126
4.8.4.1 Base Pressure Check............................................................................................................................ 126
4.8.4.2 Concrete Design.................................................................................................................................... 127

Appendix A. STAAD INPUT/OUTPUT


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

1. Introduction
This calculation is for the structural analysis and design of Bagging Electrical Room for Cemex Cement Plant.

2. Design criteria
The following cover the design criteria used for the analysis and design of the Bagging Electrical Room. The
criteria used are in accordance with Owner Specification as well as the accepted Codes and Standard practises
in Philippines.

2.1 Materials

Reinforced Concrete (Modulus of elasticity, E = 15,100 √f’c)

Material Type Material Description Material Strength

Concrete Buildings Compressive Strength, f’c = 250 kg/cm2 (3.5 ksi)


Basis for Equipment Compressive Strength, f’c = 250 kg/cm2 (3.5 ksi)
Foundations Compressive Strength, f’c = 250 kg/cm2 (3.5 ksi)
Tie columns and beams Compressive Strength, f’c = 200 kg/cm2 (3.5 ksi)

Steel Reinforcement 16mm diameter and above Yield Strength, fy = 4200 kg/cm2 (60 ksi) Yield
12mm diameter and below Strength, fy = 2800 kg/cm2 (40 ksi)

Concrete Cover to Reinforcement

Unless indicated, otherwise, the minimum cover for reinforced concrete structures shall be:

Concrete deposited against earth 75mm


Concrete surface (formed) exposed to earth or water
20 to 36 mm bars 50mm
16mm bars and smaller 40mm
Concrete not exposed to earth or water or in contact with ground:
Structural slabs and walls, joists:
36mm and smaller 20mm
Beams and columns:
Primary reinforcement, ties, stirrups, spirals 40mm

In no case shall the clear distance be less than 25 mm or less than 1 1/3 times the maximum size of aggregate,
whichever is greater.
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

2.2 Design Loads


2.2.1 Dead Loads

Dead loads are the weights of the structures and any permanent equipment and appurtenant
structures that do not change with the mode of operation. Dead loads shall include the following:
1. Self-weight of the structure.
2. Weight of permanent machineries and equipment’s shall be based on the vendor’s drawing
and load data.

The density of the common materials is as follows;


 Reinforced Concrete : 2400 kg/m3 (4042 lb/yd3)
 Structural steel : 7800 kg/m3 (13136 lb/yd3)
 Load of dust on metal roof : 45 kg/m2 (4.6 psf)
2.2.2 Superimposed Dead Load (SIDL)

Superimposed dead loads (SIDL) are the weight of all permanently materials such as cladding,
roofing, etc.
2.2.3 Live Loads ( LL )

The live loads on the limestone crusher shall be based on the following
 Live load on concrete deck : 100 kg/m2
 Live load in steel roof (slope > 5%) : 60 kg/m2
 Live load in floor slab : 500 kg/m2
 Live load in stairways : 250 kg/m2
2.2.4 Seismic Load

Inertia force by seismic shall be designed according to the Static Lateral Force procedure in NSCP 2015 Vo. 1

Parameter Formula/Value Reference

Earthquake Load, E E = ρ Eh + Ev NSCP 2010 Vol.1 Eq. 208-18

Base Shear, V V = Cv I W NSCP 2010 Vol. 1 Eq. 208-8


RT
Where:
V < 2.5Ca I W NSCP 2010 Vol. 1 Eq. 208-9
R
V > 0.11Ca I W NSCP 2010 Vol. 1 Eq. 208-10
V > 0.8Z Nv I W (for Zone 4) NSCP 2010 Vol. 1 Eq. 208-11
R

Structure Period, T T = Ct (hn)3/4 NSCP 2010 Vol. 1 Eq. 208-12

Horizontal Earthquake Load, Eh Eh = V NSCP 2010 Vol. 1 Section 208.6.1

Vertical Earthquake Load, Ev Ev = 0.5Ca I D = 0.22D NSCP 2010 Vol. 1 Section 208.6.1

Reliability/Redundancy Factor, ρ ρ = 1.0 NSCP 2010 Vol. 1 Section 208.6.1

Seismic Zone Factor, Z Z = 0.4 ( Zone 4) NSCP 2010 Vol. 1 Table 208-3

Soil Profile Type SD (Stiff Soil) NSCP 2010 Vol. 1 Table 208-2
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Parameter Formula/Value Reference

Importance Factor, I I = 1 (Standard Occupancy) NSCP 2010 Vol. 1 Table 208-1

Seismic Over-strength Coefficient, R R = 8.5 (SMRF) NSCP 2010 Vol. 1 Table 208-11A

Seismic Coefficient, Ca Ca = 0.44 (for Na = 1.0, source w/in 10km) NSCP 2010 Vol. 1 Table 208-7

Seismic Coefficient, Cv Cv = 0.768 (for Nv = 1.2, source w/in 10km) NSCP 2010 Vol. 1 Table 208-8

Near-Source Factor, Na Na = 1.0 (source w/in 10km, Source Type A) NSCP 2010 Vol. 1 Table 208-5

Near-Source Factor, Nv Nv = 1.2 (source w/in 10km, Source Type A) NSCP 2010 Vol. 1 Table 208-6

Seismic Source Type A (faults capable of Magnitude M ≥ 7.0) NSCP 2010 Vol. 1 Table 208-4

Numerical Coefficient, Ct Ct = 0.0488 NSCP 2010 Vol. 1 Section 208.5.2.2

Structure Period, T as per staad calculation:


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

2.2.5 Wind Load

Wind load shall be designed according to the Directional Procedure for Main Wind-Force Resisting Systems
(MWFRS), as stated in NSCP 2015 Vol. 1 Section 207B.

Parameter Formula/Value Reference

Velocity Pressure, qz qz = 0.613 Kz Kzt Kd V2 NSCP 2015 Vol. 1 Eq. 207B.3-1

Basic Wind Speed, V V = 260 kph = 72.22 m/s NSCP 2015 Vol. 1 Section 207A.5

Exposure Coefficient, Kz Varies depending on height NSCP 2015 Vol. 1 Table 207B.3-1

Topographic Factor, Kzt Kzt = 1.0 (No hills, ridges, trenches, etc.) NSCP 2015 Vol. 1 Section 207A.8.2

Wind Directionality Factor, Kd Kd = 0.85 NSCP 2015 Vol. 1 Table 207A.6-1


2.3 Method of analysis and design for structure

The analysis of the structure shall be carried out in Staad with an idealised 3D model. The design shall
be as per NSCP 2015 Vol. 1.
2.3.1 Codes and Standards

For the design and the execution of the works as well as for the quality of the selected materials in the
performance of the works, applicable codes and standards shall be followed.
1. Philippines local code (National Structural Code of the Philippines) NSCP 2015
2. Reinforced concrete and commentary (latest edition) ACI-318
3. American Institute of Steel Construction (latest edition) AISC
4. American Society of Testing Materials (latest edition) ASTM
5. International Building Code (latest edition) IBC
6. American Society of Civil Engineers (latest edition) ASCE
2.3.2 Load Combination

Load Combinations using Strength Design or Load and Resistance Factor Design:

Where load and resistance factor design is used, structures and all portions thereof shall resist the
most critical effects from the following combinations of factored loads:
 1.4(D + F)
 1.2(D+ F+T)+1.6(L+H)+0.5(Lr or R)
 1.2D+1.6(Lr or R)+( f1L or 0.5W)
 1.2D+1.0W+f1L+0.5(Lr or R)
 1.2D+1.0E+f1L
 0.9D+1.0 W+1.6H
 0.9D+1.0 E+1.6H

f1 = 1.0 for floors in places of public assembly, for live loads in excess of 4.8 kPa, and for garage live
load = 0.5 for other live loads

Load Combinations Using Allowable Stress Design


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Where allowable stress design (working stress design) is used, structures and all portions thereof shall
resist the most critical effects resulting from the following combinations of loads:
 D+F
 D+H+F+L+T
 D+H+F+(Lr or R)
 D+H+F+0.75[L+T+(Lr or R)]
 D+H+F+(0.6W or E/1.4)

Alternate Load Combinations

In lieu of the basic load combinations, structures and portions thereof shall resist the most critical
effects from the following combinations of loads:
 D+H+F+0.75[L+Lr+(0.6W or E/1.4)]
 0.6D+0.6W+H
 0.6D+E/1.4+H
 D+L+(Lr or R)
 D+L+0.6W
 D+L+E/1.4

Note: One-third increase in allowable stresses for all combinations including wind or seismic is
permitted.

Special Seismic Load Combinations

For both allowable stress design and strength design, the following special load combinations for
seismic design shall be used:
 1.2D+f1L+1.0Em
 0.9D±1.0Em

where:
f1 = 1.0 for floors in places of public assembly, for live loads in excess of 4.8 kPa, and for garage live
load = 0.5 for other live loads
Em = The maximum effect of horizontal and vertical forces
2.3.3 Design of Structural Members

Design of structural member will be carried out in Ultimate Limit State and Serviceability Limit State,
with the help of Excel spread sheets in tabular form with proper validation of the design.
2.3.3.1 Factor of Safety

All structures which are subjected to overturning and sliding shall be designed based on the following
requirements:
Overturning Safety Factor = 1.5
Sliding Safety Factor = 1.5
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

2.4 Drift and Deflection Limits


2.4.1.1 Drift Limits

Calculated storey drift using ΔM due to seismic effect shall not exceed as follows (NSCP section
208.6.5)
 0.025 times the storey height - for structures having a fundamental period less than 0.7 sec.
 0.020 times the storey height - for structures having a fundamental period of 0.7 sec. or more

Drift limits from the wind load effect for building design shall be 1/600 to 1/400 of the building height or
storey height (ASCE 7-16 Appendix CC.2.2).
2.4.1.2 Deflection Limits

The below table are the deflection limits as per IBC section 1604.3.1

CONSTRUCTION L S or W D+L

Roof members
Supporting plaster ceiling l/360 l/360 l/240
Supporting nonplaster ceiling l/240 l/240 l/180
Not supporting ceiling l/180 l/180 l/120

Floor members l/360 - l/240

Exterior walls and interior partitions:


With brittle finishes - l/240 -
With flexible finishes - l/120 -

Farm buildings - - l/18

Greenhouses - - l/120

2.5 Geotechnical Design Parameters

The following are the geotechnical design parameters obtained from Soil Investigation Report (Ref.No. GII-
32582-65501-17):

Allowable Allowable Bearing Subgrade


Area Borehole Bearing Capacity Capacity (Total Modulus φ c Es
(DL + LL), kPa loads incl seismic (kN/m3)
(kPa) (kPa)
or wind), kPa

216 300 400 95000 40o 2138 32500


Electrical Rooms
o
252 300 400 95000 40 2264 32500

Note: Water table not encountered

3. General Sketch
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4. Analysis and Design


4.1 Structural Modelling

Figure below shows the visual representation of the model developed in StaadPro.
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.2 Section Properties


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.3 Load Application


4.3.1 Dead Loads

M etal roof and purlins = 0.50 kPa


Wall metal c ladding and girts = 0.50 kPa
Weight of the c onc rete hollow bloc k = 2.45 kPa 250 kg/ m2
Height
4.10 m = 10.06 kN/ m
3.50 m = 8.58 kN/ m
2.00 m = 4.91 kN/ m

Load of dust on c onc rete roofs = 1.77 kPa 180 kg/ m2


Load of dust on metal roofs = 0.44 kPa 45 kg/ m2
Roof c onc rete w eight = 3.53 kPa 0.15 m
c antilever: 1.7m = 6.00 kN/ m 1.7 m
M ec hanic al/ Elec tric al = 1.28 kPa 130 kg/ m2

Platform:
Gratings/ C hec kered plate = 0.36 kPa
Elec tric al trays and piping ` 0.97 kPa 130 kg/ m
Total = 1.33 kPa
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Railings = 0.17 kN/m

Stairs (gratings &railings) = 0.33 kN/m

Equipment Load
Weight of elec tric al equipment = 4.91 kPa 500 kg/ m2
Weight of c able rac k on roof (limestone transport) = 1.96 kN/ m 200 kg/ m
1.63 m = 3.19 kN
Weight of c ondensing units on roof = 5.89 kN 600 kg
Weight of indoor unit hang on c onc rete c eiling = 3.43 kN 350 kg
Weight of transformer = 41.20 kN 4200 kg
Load per node (4 support points) = 10.30 kN

4.3.2 Roof Live Load

Conc rete Dec k = 0.98 kPa 100 kg/ m2


Cable gallery = 0.59 kPa 60 kg/ m2
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.3.3 Wind Loads

reference: 1) DESIGN PARAMETERS


NSCP 2015/ 1.1) Wind Parameters
ASCE Zone = II
Occupancy Category = IV
Exposure Category = C
Enclosure Classification(normal to ridge), EC @x = Partially Enclosed
Enclosure Classification(parallel to ridge), EC @Y = Partially Enclosed
Wind Directionality Factor, Kd = 0.85
Topographic Factor, Kzt = 1

1.2) Structure Configuration


Building Width, B = 9.5 m
Building Length, L = 15 m
Ridge height, Hr = 8.6 m
Height above ground level, z = 8.6 m
Approx. Area = 142.5 m2
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

2) ANALYSIS
2.1) Geometrical results
Mean roof height, h = 8.6 m
slope, q = 0.00 degrees
2.2) Wind Parameters and Coeffecients
Wind Velocity, V = 260 kph
Importance factor, Iw = 1
Gust effect factor, G = 0.85

Wall Pressure Coeffi cients, Cp


Surface L/B Cp
Windward All Values 0.8
Leeward 1.578947368 -0.50 (normal)
Sidewall All Values -0.7

Roof Pressure Coeffi cients, Cp


Normal to Ridge
Surface 1st Value, Cp1 1st Value, Cp2
Wind ward -1.013 -0.180
Leeward -0.662

Parallel to Ridge
windward Leeward
1st Value, Cp1 1st Value, Cp2 L/B Cp
0 to h/2 -0.921 -0.180 1.579 -0.384
h/2 to h -0.921 -0.180
h to 2h -0.529 -0.180
>2h -0.359 -0.180

Internal Pressure Coeffi cient


along x-dir along y-dir
+Gcpi 0.55 0.55
-Gcpi -0.55 -0.55

z (m) kz qz(kpa)
5.1 0.868 2.360
8.6 0.969 2.634

h (m) kz qh(kpa)
8.6 0.969 2.634
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

NORMAL TO RIDGE
Design Pressure on Wall, P = qzGCp-qhGCpi
Windward Leeward
Case 1 Case 2 Case 1 Case 2
z(m) qzGCp-qh(+GCpi) qzGCp-qh(-GCpi) qhGCp-qh(+GCpi) qhGCp-qh(-GCpi)
5.1 0.156 3.053 -2.568 0.329
8.6 0.342 3.240

Design Pressure on Side Wall, P = qzGCp-qhGCpi


Case 1 Case 2
h(m) qzGCp-qh(+GCpi) qzGCp-qh(-GCpi)
8.6 -3.016 -0.119

Design Pressure on Roof, P = qhGCp -qiGCpi (Windward)


Case 1 Case 2 Case 3 Case 4
qhGCp 1 -qh(+GCpi) qhGCp 2 -qh(+GCpi) qhGCp 1 -qh(-GCpi) qhGCp 2 -qh(-GCpi)
-3.718 -1.852 -0.820 1.046

Design Pressure on Roof, P = qhGCp -qiGCpi (Leeward)


Case 1 Case 2
qzGCp 1 -qh(+GCpi) qzGCp 1 -qh(-GCpi) ***Might also get the average of qz and qh
-2.931 -0.034 **Not applicable for Flat roof or Monoslope

PARALLEL TO RIDGE
Design Pressure on Wall, P = qzGCp-qhGCpi
Windward Leeward
Case 1 Case 2 Case 1 Case 2
z(m) qzGCp-qh(+GCpi) qzGCp-qh(-GCpi) qhGCp-qh(+GCpi) qhGCp-qh(-GCpi)
5.1 0.156 3.053 -2.309 0.588
8.6 0.342 3.240

*if considering up to h 0.342 3.240

Design Pressure on Side Wall, P = qzGCp-qhGCpi


Case 1 Case 2
h(m) qzGCp-qh(+GCpi) qzGCp-qh(-GCpi)
8.6 -3.016 -0.119

Design Pressure on Roof, P = qhGCp -qiGCpi


Case 1 Case 2 Case 3 Case 4
qhGCp 1 -qh(+GCpi) qhGCp 2 -qh(+GCpi) qhGCp 1 -qh(-GCpi) qhGCp 2 -qh(-GCpi)
0 to h/2 -3.510 -1.852 -0.612 1.046
h/2 to h -3.510 -1.852 -0.612 1.046
h to 2h -2.634 -1.852 0.264 1.046
>2h -2.252 -1.852 0.646 1.046
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

3) SUMMARY
NORMAL TO RIDGE: W1 Rw1 Rl1 L1
-3.016
CASE1:
-3.718 -2.931

0.342 -2.568

0.156

-3.016
W1 Rw2 Rl1 L1
CASE2:
-3.016
-1.852 -2.931

0.342 -2.568

0.156

-3.016
CASE3: W2 Rw3 Rl2 L2
-0.820 -0.034 -0.119

3.240 0.329

3.053

-0.119
CASE4: W2 Rw4 Rl2 L2 -0.119
1.046 -0.034

3.240 0.329

3.053

-0.119
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

PARALLEL TO RIDGE:

CASE 5: 0 to h/2 h/2 to h h to 2h h to 2h


-3.510 -3.510 -2.634 -2.252 -3.016

-2.309
0.342

0.156
-3.016

CASE 6: 0 to h/2 h/2 to h h to 2h h to 2h

-1.852 -1.852 -1.852 -1.852 -3.016

-2.309
0.342

0.156
-3.016

CASE 7: 0 to h/2 h/2 to h h to 2h h to 2h

-0.612 -0.612 0.264 0.646 -0.119

0.588
3.240

3.053
-0.119

CASE 8: 0 to h/2 h/2 to h h to 2h h to 2h


1.046 1.046 1.046 1.046 -0.119

0.588
3.240

3.053
-0.119
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Wind Load Positive Direction X – Case 1

Wind Load Positive Direction X – Case 2


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Wind Load Negative Direction X – Case 1

Wind Load Negative Direction X – Case 2


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Wind Load Positive Direction Z – Case 1

Wind Load Positive Direction Z – Case 2

Wind Load Negative Direction Z – Case 1


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Wind Load Negative Direction Z – Case 2

4.3.4 SeismicLoads

Seismic Load Positive Direction X


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Seismic Load Negative Direction X

Seismic Load Positive Direction Z


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Seismic Load Negative Direction Z


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.4 Load Combinations


COMBINATIO
SLS LOAD COMBINATION
N
COMB 101 1 DL
COMB 102 1 DL + 1 LL
COMB 103 1 DL + 1 LR
COMB 104 1 DL + 0.75 LL + 0.75 LR
COMB 105 1 DL + 0.6 WD+X1
COMB 106 1 DL + 0.6 WD+X2
COMB 107 1 DL + 0.6 WD-X1
COMB 108 1 DL + 0.6 WD-X2
COMB 109 1 DL + 0.6 WD+Z1
COMB 110 1 DL + 0.6 WD+Z2
COMB 111 1 DL + 0.6 WD-Z1
COMB 112 1 DL + 0.6 WD-Z2
COMB 113 0.714 EQ X+ + 1 DL
COMB 114 0.714 EQ X- + 1 DL
COMB 115 0.714 EQ Z+ + 1 DL
COMB 116 0.714 EQ Z- + 1 DL

COMBINATIO
ULS LOAD COMBINATION
N
COMB 201 1.4 DL
COMB 202 1.2 DL + 1.6 LL + 0.5 LR
COMB 203 1.2 DL + 0.5 LL + 1.6 LR
COMB 204 1.2 DL + 1.6 LR + 0.5 WD+X1
COMB 205 1.2 DL + 1.6 LR + 0.5 WD-X1
COMB 206 1.2 DL + 1.6 LR + 0.5 WD+Z1
COMB 207 1.2 DL + 1.6 LR + 0.5 WD-Z1
COMB 208 1.2 DL + 0.5 LL + 0.5 LR + 1 WD+X1
COMB 209 1.2 DL + 0.5 LL + 0.5 LR + 1 WD+X2
COMB 210 1.2 DL + 0.5 LL + 0.5 LR + 1 WD-X1
COMB 211 1.2 DL + 0.5 LL + 0.5 LR + 1 WD-X2
COMB 212 1.2 DL + 0.5 LL + 0.5 LR + 1 WD+Z1
COMB 213 1.2 DL + 0.5 LL + 0.5 LR + 1 WD+Z2
COMB 214 1.2 DL + 0.5 LL + 0.5 LR + 1 WD-Z1
COMB 215 1.2 DL + 0.5 LL + 0.5 LR + 1 WD-Z2
COMB 216 1 EQ X+ + 1.42 DL + 0.5 LL
COMB 217 1 EQ X- + 1.42 DL + 0.5 LL
COMB 218 1 EQ Z+ + 1.42 DL + 0.5 LL
COMB 219 1 EQ Z- + 1.42 DL + 0.5 LL
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

COMBINATIO
ULS LOAD COMBINATION
N
COMB 220 0.9 DL + 1 WD+X1
COMB 221 0.9 DL + 1 WD+X2
COMB 222 0.9 DL + 1 WD-X1
COMB 223 0.9 DL + 1 WD-X2
COMB 224 0.9 DL + 1 WD+Z1
COMB 225 0.9 DL + 1 WD+Z2
COMB 226 0.9 DL + 1 WD-Z1
COMB 227 0.9 DL + 1 WD-Z2
COMB 228 1 EQ X+ + 1.12 DL
COMB 229 1 EQ X- + 1.12 DL
COMB 230 1 EQ Z+ + 1.12 DL
COMB 231 1 EQ Z- + 1.12 DL
COMB 232 1 EQ X+ + 0.68 DL
COMB 233 1 EQ X- + 0.68 DL
COMB 234 1 EQ Z+ + 0.68 DL
COMB 235 1 EQ Z- + 0.68 DL

Note: The effect of Ev is considered by modifying the dead load factor on the load combination.

Ev = 0.5*Ca*I*DL = 0.22DL; 1.2DL + Ev = 1.2DL + 0.22DL = 1.42DL;

0.9DL + Ev = 0.9DL + 0.22DL = 1.12DL; 0.9DL - Ev = 0.9DL - 0.22DL = 0.68DL

where: (Primary Load Cases)

DL - Dead Load WD+Z2 - Wind Load Z Dir Pos Case 2


LL - Live Load WD-Z1 - Wind Load Z Dir Neg Case 1
LR - Roof Live Load WD-Z2 - Wind Load Z Dir Neg Case 2
WD+X1 - Wind Load X Dir Pos Case 1 EQ X+ - Seismic X Dir Pos
WD+X2 - Wind Load X Dir Pos Case 2 EQ X- - Seismic X Dir Neg
WD-X1 - Wind Load X Dir Neg Case 1 EQ Z+ - Seismic Z Dir Pos
WD-X2 - Wind Load X Dir Neg Case 2 EQ Z- - Seismic Z Dir Neg
WD+Z1 - Wind Load Z Dir Pos Case 1
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.5 Analysis Output


4.5.1 Shear Y Diagram

4.5.2 Shear Z Diagram


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.5.3 Moment Y Diagram

4.5.4 Moment Z Diagram


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.6 Serviceability Check


4.6.1 Drift Check

Wind Load - Drift Check


Node Height Joint Max Drift - X Joint Max Drift - Z
Load Case (SLS) Load Case (SLS) Allow Drift (H/400) Remarks
Direction Direction
3518 6.600 106 2.862 110 3.897 16.500 OK
3585 6.600 106 3.185 110 3.853 16.500 OK
3577 6.600 108 -3.164 110 5.009 16.500 OK
3519 6.600 106 2.842 110 5.088 16.500 OK
3520 6.600 106 2.827 110 5.394 16.500 OK
3524 6.600 108 -3.192 110 5.328 16.500 OK
3521 6.600 108 -2.835 110 4.391 16.500 OK
3522 6.600 108 -3.229 110 4.339 16.500 OK
3525 6.600 108 -2.487 110 5.310 16.500 OK
3523 6.600 108 -2.503 110 4.325 16.500 OK
3578 6.600 108 -2.475 110 4.994 16.500 OK
3586 6.600 108 -2.465 110 3.839 16.500 OK

Seismic Load - Drift Check


Node Height Joint Max Drift - X Max Drift X-Dir Joint Max Drift - Z Max Drift Z-Dir
Load Case (ULS) Load Case (ULS) Allow Drift (0.02H) Remarks
Direction Δm = 0.7 R Δs Direction Δm = 0.7 R Δs
3518 6.600 233 -12.178 -24.721 218 13.110 26.613 132.000 OK
3585 6.600 216 13.507 27.419 218 13.067 26.526 132.000 OK
3577 6.600 216 13.501 27.407 218 16.291 33.071 132.000 OK
3519 6.600 233 -12.190 -24.746 218 16.364 33.219 132.000 OK
3520 6.600 233 -12.196 -24.758 218 17.198 34.912 132.000 OK
3524 6.600 216 13.514 27.433 218 17.156 34.827 132.000 OK
3521 6.600 233 -12.199 -24.764 218 14.659 29.758 132.000 OK
3522 6.600 216 13.507 27.419 218 14.602 29.642 132.000 OK
3525 6.600 232 11.074 22.480 218 17.134 34.782 132.000 OK
3523 6.600 232 11.064 22.460 218 14.579 29.595 132.000 OK
3578 6.600 216 11.083 22.498 218 16.273 33.034 132.000 OK
3586 6.600 216 11.090 22.513 218 13.046 26.483 132.000 OK
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.6.2 Deflection Check

Allowable deflection due to LIVELOAD = L / 360; L= 4500mm; 4500/360 = 12.50mm

Allowable deflection due to DEAD + LIVELOAD = L / 240; L= 4500mm; 4500/240 = 18.75mm

4.7 Concrete Design


4.7.1 Concrete Columns
General Data
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Column No. : C1,C2,C3,C4,C5,C6,C8,C9,C10,C11,C12


Level : 0m To 0.5m
Design Code = ACI 318M - 2011
Grade Of Concrete = C25 N/sqmm
Grade Of Steel = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover = 50 mm
Clear Floor Height @ lux = 100 mm
Clear Floor Height @ luy = 100 mm
No Of Floors = 1
No Of Columns In Group = 11

Load Data

Analysis Reference No. = 9242

Critical Analysis Load Combination : 219

[35] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD)


Load Combination =
+(LOAD 4: EQ Z-)
Critical Location = Bottom Joint
Put = 359.12 kN
Muxt = 0.03 kNm
Muyt = -72.53 kNm
Vuxt = -20.52 kN
Vuyt = -0.95 kN
Pub = 361.8 kN
Muxb = 0.5 kNm
Muyb = -82.79 kNm
Vuxb = -20.52 kN
Vuyb = -0.95 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness Beta
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 426.667 No Beam No Beam - - 1
Top 426.667 4500 x 250 x 400 4500 x 250 x 400 29.63 29.63 9.001

Sway Condition (as per Stability Index) = Non Sway


Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness Beta
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Depth) Depth)
N-M mm mm N-M N-M
Bottom 426.667 No Beam No Beam - - 1
Top 426.667 6500 x 250 x 400 No Beam 20.513 - 26.016

Sway Condition (as per Stability Index) = Non Sway


Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
       Q = 0.002
0.002< 0.05, Column shall be designed as non-sway frame (Braced)
       
Along B
       Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 0.75
M1 = 0.03 kNm
M2 = 0.5 kNm
34 - 12 x (M1/M2) = 33.3
0.75 < 33.3, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 0.75
M1 = -72.53 kNm
M2 = -82.79 kNm
34 - 12 x (M1/M2) = 23.49
0.75 < 23.49, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 0.03 - 0.03
Major Axis Mux (bottom) 0.5 - 0.5
Minor Axis Muy (top) -72.53 - -72.53
Minor Axis Muy (bottom) -82.79 - -82.79

Where

A = Moments from analysis


B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
 

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 361.8 kN
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Mux = 0.5 kNm


Muy = -82.79 kNm

Moment Capacity Check


Pt Calculated = 1.43
Reinforcement Provided = 8-#19
Load Angle = Tan-1(Muy/Mux)
= 89.65 deg
MRes = 82.79 kNm
MCap = 201.2 kNm
Capacity Ratio = MRes/ MCap
= 0.411 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 221
[37] : 0.9 (LOAD 5: DEAD LOADS) +(LOAD 9:
Critical Load Combination = kN
WIND X+ CASE2)
Nu = 196.52 kN
Muy = 42.6 kNm
Vuy = 38.3431 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 11.66 kNm
Vcy Permissible = 114.04 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
 
Design for shear along B
Critical Analysis Load Combination : 234
[50] : 0.68 (LOAD 5: DEAD LOADS) +(LOAD
Critical Load Combination = kN
3: EQ Z+)
Nu = 157.33 kN
Mux = 26.66 kNm
Vux = 43.5194 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 1.88 kNm
Vcx Permissible = 118.18 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

  > Max. longitudinal bar dia / 4


  = 4.75 mm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Criterion for spacing of normal links


Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 3
S1 = 100 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshD = 321.43 sqmm
Along B
No of bars along B = 3
S1 = 100 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshB = 321.43 sqmm
Provided Links = 2#10@100 c/c
 
Table For Links
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 2-#10 10 2-#10
Spacing 200 --- 100 200 100

 
General Data
Column No. : C1,C2,C3,C4,C5,C6,C8,C9,C10,C11,C12
Level : 0.5m To 2.5m
Design Code = ACI 318M - 2011
Grade Of Concrete = C25 N/sqmm
Grade Of Steel = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover = 50 mm
Clear Floor Height @ lux = 2000 mm
Clear Floor Height @ luy = 1600 mm
No Of Floors = 1
No Of Columns In Group = 11

Load Data

Analysis Reference No. = 994

Critical Analysis Load Combination : 219

[35] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD)


Load Combination =
+(LOAD 4: EQ Z-)
Critical Location = Bottom Joint
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Put = 285.13 kN
Muxt = -0.24 kNm
Muyt = -23.41 kNm
Vuxt = 40.87 kN
Vuyt = -0.19 kN
Pub = 295.84 kN
Muxb = -0.62 kNm
Muyb = -105.13 kNm
Vuxb = 40.87 kN
Vuyb = -0.19 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness Beta
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 106.667 4500 x 250 x 400 4500 x 250 x 400 29.63 29.63 9.001
Top 106.667 4500 x 250 x 400 4500 x 250 x 400 29.63 29.63 2.678

Sway Condition (as per Stability Index) = Non Sway


Effective Length Factor along Major Axis = 1

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness Beta
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 106.667 6500 x 250 x 400 No Beam 20.513 - 26.016
Top 106.667 No Beam No Beam - - 1

User Defined Effective Length Factor = 1

Check For Stability Index


Along D
       Q = 0.009
0.009< 0.05, Column shall be designed as non-sway frame (Braced)
       
Along B
       Q = 0.011
0.011< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 13.86
M1 = -0.24 kNm
M2 = -0.62 kNm
34 - 12 x (M1/M2) = 29.38
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

13.86 < 29.38, Column not slender along D


Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 17.32
M1 = -23.41 kNm
M2 = -105.13 kNm
34 - 12 x (M1/M2) = 31.33
17.32 < 31.33, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.24 - -0.24
Major Axis Mux (bottom) -0.62 - -0.62
Minor Axis Muy (top) -23.41 - -23.41
Minor Axis Muy (bottom) -105.13 - -105.13

Where

A = Moments from analysis


B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
 

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 295.84 kN
Mux = -0.62 kNm
Muy = -105.13 kNm

Moment Capacity Check


Pt Calculated = 1.43
Reinforcement Provided = 8-#19
Load Angle = Tan-1(Muy/Mux)
= 89.66 deg
MRes = 105.13 kNm
MCap = 195.95 kNm
Capacity Ratio = MRes/ MCap
= 0.537 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 217
[33] : 1.42 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = kN
(LOAD 6: LIVELOAD) +(LOAD 2: EQ X-)
Nu = 334.39 kN
Muy = 74.23 kNm
Vuy = -52.5637 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 21.58 kNm
Vcy Permissible = 112.96 kN
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Vuy < Vcy Permissible


Link For Shear Design Along D are not required
 
Design for shear along B
Critical Analysis Load Combination : 219
[35] : 1.42 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = kN
(LOAD 6: LIVELOAD) +(LOAD 4: EQ Z-)
Nu = 285.62 kN
Mux = 61.36 kNm
Vux = -44.5616 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 16.4 kNm
Vcx Permissible = 113.06 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

  > Max. longitudinal bar dia / 4


  = 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 3
S1 = 100 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshD = 321.43 sqmm
Along B
No of bars along B = 3
S1 = 100 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshB = 321.43 sqmm
Provided Links = 2#10@100 c/c
 
Table For Links
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 2-#10 10 2-#10
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Spacing 200 --- 100 200 100

 
General Data
Column No. : C1,C2,C3,C4,C5,C6,C8,C9,C10,C11,C12
Level : 2.5m To 6.6m
Design Code = ACI 318M - 2011
Grade Of Concrete = C25 N/sqmm
Grade Of Steel = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover = 50 mm
Clear Floor Height @ lux = 3650 mm
Clear Floor Height @ luy = 3650 mm
No Of Floors = 1
No Of Columns In Group = 11

Load Data

Analysis Reference No. = 9292

Critical Analysis Load Combination : 218

[34] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD)


Load Combination =
+(LOAD 3: EQ Z+)
Critical Location = Top Joint
Put = 331.19 kN
Muxt = -9.1 kNm
Muyt = -148.96 kNm
Vuxt = -58.45 kN
Vuyt = 5.3 kN
Pub = 353.15 kN
Muxb = 12.63 kNm
Muyb = 90.61 kNm
Vuxb = -58.45 kN
Vuyb = 5.3 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness Beta
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 52.032 No Beam 4500 x 250 x 400 - 29.63 5.334
Top 52.032 4500 x 250 x 450 4500 x 250 x 450 42.188 42.188 0.616

User Defined Effective Length Factor = 1


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness Beta
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 52.032 No Beam 6500 x 250 x 400 - 20.513 7.741
Top 52.032 4500 x 300 x 450 6500 x 300 x 450 50.625 35.048 0.607

User Defined Effective Length Factor = 1

Check For Stability Index


Along D
       Q = 0.014
0.014< 0.05, Column shall be designed as non-sway frame (Braced)
       
Along B
       Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 31.61
M1 = -9.1 kNm
M2 = 12.63 kNm
34 - 12 x (M1/M2) = 42.64
31.61 < 42.64, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 1
r = 115.47 mm
Klux /r = 31.61
M1 = 90.61 kNm
M2 = -148.96 kNm
34 - 12 x (M1/M2) = 41.3
31.61 < 41.3, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -9.1 - -9.1
Major Axis Mux (bottom) 12.63 - 12.63
Minor Axis Muy (top) -148.96 - -148.96
Minor Axis Muy (bottom) 90.61 - 90.61

Where

A = Moments from analysis


B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
 
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 331.19 kN
Mux = -9.1 kNm
Muy = -148.96 kNm

Moment Capacity Check


Pt Calculated = 1.43
Reinforcement Provided = 8-#19
Load Angle = Tan-1(Muy/Mux)
= 86.5 deg
MRes = 149.24 kNm
MCap = 195.38 kNm
Capacity Ratio = MRes/ MCap
= 0.764 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 210
[26] : 1.2 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = (LOAD 6: LIVELOAD) +(LOAD 10: WIND X- kN
CASE1) +0.5 (LOAD 7: ROOF LIVE LOAD)
Nu = 163.18 kN
Muy = 35.79 kNm
Vuy = -38.4791 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 10.1 kNm
Vcy Permissible = 115.03 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
 
Design for shear along B
Critical Analysis Load Combination : 222
[38] : 0.9 (LOAD 5: DEAD LOADS) +(LOAD
Critical Load Combination = kN
10: WIND X- CASE1)
Nu = 118.57 kN
Mux = 28.5 kNm
Vux = 41.5019 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 9.83 kNm
Vcx Permissible = 117.18 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Diameter of link = 10 mm

  > Max. longitudinal bar dia / 4


  = 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 3
S1 = 100 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshD = 321.43 sqmm
Along B
No of bars along B = 3
S1 = 100 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshB = 321.43 sqmm
Provided Links = 2#10@100 c/c
 
Table For Links
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 2-#10 10 2-#10
Spacing 200 --- 100 200 100

 
General Data
Column No. : C7
Level : 0m To 0.5m
Design Code = ACI 318M - 2011
Grade Of Concrete = C25 N/sqmm
Grade Of Steel = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover = 50 mm
Clear Floor Height @ lux = 100 mm
Clear Floor Height @ luy = 100 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Analysis Reference No. = 989


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Critical Analysis Load Combination : 234

Load Combination = [50] : 0.68 (LOAD 5: DEAD LOADS) +(LOAD 3: EQ Z+)


Critical Location = Bottom Joint
Put = 181.92 kN
Muxt = -0.9 kNm
Muyt = 53.73 kNm
Vuxt = -30.37 kN
Vuyt = 2.18 kN
Pub = 183.2 kN
Muxb = 0.2 kNm
Muyb = 68.91 kNm
Vuxb = -30.37 kN
Vuyb = 2.18 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness Beta
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 426.667 No Beam No Beam - - 1
Top 426.667 4500 x 250 x 400 4500 x 250 x 400 29.63 29.63 8.079

Sway Condition (as per Stability Index) = Non Sway


Effective Length Factor along Major Axis = 0.87

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness Beta
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 426.667 No Beam No Beam - - 1
Top 426.667 4500 x 250 x 400 6500 x 250 x 400 29.63 20.513 9.526

Sway Condition (as per Stability Index) = Non Sway


Effective Length Factor along Minor axis = 0.87

Check For Stability Index


Along D
       Q = 0.002
0.002< 0.05, Column shall be designed as non-sway frame (Braced)
       
Along B
       Q = 0.003
0.003< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

r = 115.47 mm
Kluy /r = 0.75
M1 = 0.2 kNm
M2 = -0.9 kNm
34 - 12 x (M1/M2) = 36.62
0.75 < 36.62, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.87
r = 115.47 mm
Klux /r = 0.75
M1 = 53.73 kNm
M2 = 68.91 kNm
34 - 12 x (M1/M2) = 24.64
0.75 < 24.64, Column not slender along B

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) -0.9 - -0.9
Major Axis Mux (bottom) 0.2 - 0.2
Minor Axis Muy (top) 53.73 - 53.73
Minor Axis Muy (bottom) 68.91 - 68.91

Where

A = Moments from analysis


B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
 

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 183.2 kN
Mux = 0.2 kNm
Muy = 68.91 kNm

Moment Capacity Check


Pt Calculated = 1.43
Reinforcement Provided = 8-#19
Load Angle = Tan-1(Muy/Mux)
= 89.84 deg
MRes = 68.91 kNm
MCap = 186.63 kNm
Capacity Ratio = MRes/ MCap
= 0.369 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 219
[35] : 1.42 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = kN
(LOAD 6: LIVELOAD) +(LOAD 4: EQ Z-)
Nu = 429.94 kN
Muy = 0.48 kNm
Vuy = 4.8067 kN
λ = 1
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 67.21 kNm
Vcy Permissible = 263.43 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
 
Design for shear along B
Critical Analysis Load Combination : 235
[51] : 0.68 (LOAD 5: DEAD LOADS) +(LOAD
Critical Load Combination = kN
4: EQ Z-)
Nu = 212.59 kN
Mux = 44.28 kNm
Vux = 37.4128 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 10.81 kNm
Vcx Permissible = 113.73 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

  > Max. longitudinal bar dia / 4


  = 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 3
S1 = 100 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshD = 321.43 sqmm
Along B
No of bars along B = 3
S1 = 100 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshB = 321.43 sqmm
Provided Links = 2#10@100 c/c
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

 
Table For Links
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 2-#10 10 2-#10
Spacing 200 --- 100 200 100

 
General Data
Column No. : C7
Level : 2.5m To 6.6m
Design Code = ACI 318M - 2011
Grade Of Concrete = C25 N/sqmm
Grade Of Steel = Fy420 N/sqmm
Consider Ductile = Yes
Type of Frame = Special
Column B = 400 mm
Column D = 400 mm
Clear Cover = 50 mm
Clear Floor Height @ lux = 5650 mm
Clear Floor Height @ luy = 5650 mm
No Of Floors = 1
No Of Columns In Group = 1

Load Data

Analysis Reference No. = 9269

Critical Analysis Load Combination : 218

[34] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD)


Load Combination =
+(LOAD 3: EQ Z+)
Critical Location = Top Joint
Put = 337.81 kN
Muxt = 3.47 kNm
Muyt = -126.66 kNm
Vuxt = -38.79 kN
Vuyt = -0.81 kN
Pub = 370.48 kN
Muxb = -1.47 kNm
Muyb = 109.91 kNm
Vuxb = -38.79 kN
Vuyb = -0.81 kN

Effective Length Calculation


Calculation Along Major Axis Of Column
Joint Column Stiffness Beam Sizes Beam Stiffness Beta
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 52.032 No Beam No Beam - - 8.079
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Top 52.032 4500 x 250 x 450 4500 x 250 x 450 42.188 42.188 0.616

Sway Condition (as per Stability Index) = Non Sway


Effective Length Factor along Major Axis = 0.83

Calculation Along Minor Axis Of Column


Joint Column Stiffness Beam Sizes Beam Stiffness Beta
Beam 1 Beam 2 Beam 1 Beam 2
(Length x Width x (Length x Width x
Depth) Depth)
N-M mm mm N-M N-M
Bottom 52.032 No Beam No Beam - - 9.526
Top 52.032 4500 x 300 x 450 6500 x 300 x 450 50.625 35.048 0.607

Sway Condition (as per Stability Index) = Non Sway


Effective Length Factor along Minor axis = 0.83

Check For Stability Index


Along D
       Q = 0.014
0.014< 0.05, Column shall be designed as non-sway frame (Braced)
       
Along B
       Q = 0.016
0.016< 0.05, Column shall be designed as non-sway frame (Braced)

Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.83
r = 115.47 mm
Kluy /r = 40.61
M1 = -1.47 kNm
M2 = 3.47 kNm
34 - 12 x (M1/M2) = 39.07
40.61 > 39.07,Column slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.83
r = 115.47 mm
Klux /r = 40.61
M1 = 109.91 kNm
M2 = -126.66 kNm
34 - 12 x (M1/M2) = 44.41
40.61 < 44.41, Column not slender along B
Moment Magnification:
For Non-sway frame:
Along D
βdns = 0.6
Ec = 23500 N/sqmm
Ig ( x 10 9) = 2.133 mm^4
EI ( x 10 6) = 14472240 >N-sqmm
M2min = 10 kNm
Cm = 1
Pc = 6495.05 kN
δns = 1.08
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Mc1 = -10.83 kN
Mc2 = 10.83 kN

Calculation of Design Moment


Direction Manalysis Msldr or Mc Mdesign-final
A B C
Major Axis Mux (top) 3.47 10.83 10.83
Major Axis Mux (bottom) -1.47 -10.83 -10.83
Minor Axis Muy (top) -126.66 - -126.66
Minor Axis Muy (bottom) 109.91 - 109.91

Where

A = Moments from analysis


B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
 

Final Critical Design Forces


Critical Case - Axial Load & BiAxial Bending
Pu = 337.81 kN
Mux = 10.83 kNm
Muy = -126.66 kNm

Moment Capacity Check


Pt Calculated = 1.43
Reinforcement Provided = 8-#19
Load Angle = Tan-1(Muy/Mux)
= 85.11 deg
MRes = 127.12 kNm
MCap = 192.77 kNm
Capacity Ratio = MRes/ MCap
= 0.659 < 1

Design Of Shear
Design for shear along D
Critical Analysis Load Combination : 219
[35] : 1.42 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = kN
(LOAD 6: LIVELOAD) +(LOAD 4: EQ Z-)
Nu = 390.35 kN
Muy = 1.52 kNm
Vuy = -0.8332 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 59.93 kNm
Vcy Permissible = 258.06 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
 
Design for shear along B
Critical Analysis Load Combination : 218
[34] : 1.42 (LOAD 5: DEAD LOADS) +0.5
Critical Load Combination = kN
(LOAD 6: LIVELOAD) +(LOAD 3: EQ Z+)
Nu = 370.48 kN
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Mux = 109.91 kNm


Vux = -38.7935 kN
λ = 1
φ = 0.65
deff = 340.5 mm
ρw = 0.007
mm = 51.59 kNm
Vcx Permissible = 110.95 kN
Vux < Vcx Permissible
Link For Shear Design Along B are not required

Design Of Links

Links in the zone where special confining links are not required

Normal Links

Diameter of link = 10 mm

  > Max. longitudinal bar dia / 4


  = 4.75 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 304 mm
48 x diameter of links = 480 mm
Provided spacing = 200 mm

Special confining reinforcement as per ACI


Along D
No of bars along D = 3
S1 = 100 mm
Ag = 160000 sqmm
dc2 = 320 mm
Ach = 102400 sqmm
AshD = 321.43 sqmm
Along B
No of bars along B = 3
S1 = 100 mm
Ag = 160000 sqmm
bc2 = 320 mm
Ach = 102400 sqmm
AshB = 321.43 sqmm
Provided Links = 2#10@100 c/c
 
Table For Links
Required Provided
Normal Design Shear Design Ductile Design Normal Zone Ductile Zone
Link Dia. 10 --- 2-#10 10 2-#10
Spacing 200 --- 100 200 100

4.7.2 Concrete Tie Beams


Group : G1
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Beam No : B1,B4,B7

0.5m : 9093,9098,9271

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 232 232 229 217 232 216
Critical L/C - RCDC 48 48 45 33 48 32
Mu (kNm) 10.131 10.131 9.98 34.001 8.779 34.522
As (flex) (sqmm) (C) 82.03 82.03 80.79 282.11 70.99 286.59
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.236 0.236 0.47 0.587 0.15 0.524
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 275 275 275 366.74 275 372.57
AstPrv (sqmm) 397.12 397.12 397.12 397.12 397.12 397.12
Reinforcement 2-#16 2-#16 2-#16 2-#16 2-#16 2-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
Total area of longitudinal reinforcement calculated at a given
C = As (flex) =
section
Distributed longitudinal torsional reinforcement at section
D = Al (Dist) =
considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.481 0.481 0.481
Vu (kN) 22.63 11.72 23.17
Mu-Sect (kNm) - 2.11 -
Vc (kN) 72.75 72.75 72.75
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Vs (kN) - - -
VD+L (kN) 16.38 16.34
Mh (kNm) 64.71 64.71
Ms (kNm) 64.71 64.71
Sway-Right (kN) 15.18 47.91
Sway-Left (kN) 47.95 15.22
Vu-Sway (kN) 47.95 47.91
Vud (kN) 47.95 47.91
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.54 0.54 0.54
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Depth = 400 <= 1000
  

Group : G1
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Beam No : B2,B5,B8

0.5m : 9094,9099,9272

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 228 228 217 217 232 216
Critical L/C - RCDC 44 44 33 33 48 32
Mu (kNm) 9.902 10.032 9.97 33.672 8.885 33.839
As (flex) (sqmm) (C) 80.15 81.22 80.7 279.28 71.85 280.72
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.263 0.263 0.22 0.387 0.134 0.34
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 275 275 275 363.07 275 364.93
AstPrv (sqmm) 397.12 397.12 397.12 397.12 397.12 397.12
Reinforcement 2-#16 2-#16 2-#16 2-#16 2-#16 2-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.481 0.481 0.481
Vu (kN) 22.84 11.51 22.96
Mu-Sect (kNm) - 2.07 -
Vc (kN) 72.75 72.75 72.75
Vs (kN) - - -
VD+L (kN) 16.37 16.37
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Mh (kNm) 64.71 64.71


Ms (kNm) 64.71 64.71
Sway-Right (kN) 15.19 47.94
Sway-Left (kN) 47.94 15.2
Vu-Sway (kN) 47.94 47.94
Vud (kN) 47.94 47.94
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.36 0.36 0.36
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Depth = 400 <= 1000
  

Group : G1

Beam No : B3,B6,B9
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

0.5m : 9095,9100,9273

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 228 233 229 217 233 216
Critical L/C - RCDC 44 49 45 33 49 32
Mu (kNm) 10.044 10.181 9.97 34.647 9.099 33.827
As (flex) (sqmm) (C) 81.31 82.44 80.73 287.66 73.6 280.61
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.225 0.312 0.53 0.684 0.174 0.737
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 275 275 275 373.96 275 364.8
AstPrv (sqmm) 397.12 397.12 397.12 397.12 397.12 397.12
Reinforcement 2-#16 2-#16 2-#16 2-#16 2-#16 2-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.481 0.481 0.481
Vu (kN) 23.17 11.72 22.62
Mu-Sect (kNm) - 2.11 -
Vc (kN) 72.75 72.75 72.75
Vs (kN) - - -
VD+L (kN) 16.34 16.38
Mh (kNm) 64.71 64.71
Ms (kNm) 64.71 64.71
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Sway-Right (kN) 15.23 47.94


Sway-Left (kN) 47.9 15.19
Vu-Sway (kN) 47.9 47.94
Vud (kN) 47.9 47.94
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.7 0.7 0.7
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Depth = 400 <= 1000
  

Group : G4

Beam No : B10,B16

0.5m : 9092,9097

Beam Length : 4499.99 mm


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Breadth (B) : 250 mm


Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 231 235 234 218 234 219
Critical L/C - RCDC 47 51 50 34 50 35
Mu (kNm) 10.147 10.034 7.4 36.449 8.857 37.817
As (flex) (sqmm) (C) 82.16 81.23 59.72 303.21 71.62 315.05
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.151 0.097 0.06 0.234 0.124 0.197
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 275 275 297.84 394.18 275 409.57
AstPrv (sqmm) 397.12 397.12 397.12 595.68 595.68 595.68
Reinforcement 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.722 0.481 0.722
Vu (kN) 21.81 12.54 23.99
Mu-Sect (kNm) - 0.46 -
Vc (kN) 76.13 72.75 76.13
Vs (kN) - - -
VD+L (kN) 15.37 17.81
Mh (kNm) 94 94
Ms (kNm) 64.71 64.71
Sway-Right (kN) 54.08 20.9
Sway-Left (kN) 23.34 56.52
Vu-Sway (kN) 54.08 56.52
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Vud (kN) 54.08 56.52


Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.17 0.17 0.17
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Depth = 400 <= 1000
  

Group : G4

Beam No : B11,B17

0.5m : 9091,9096

Beam Length : 6499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Design Code : ACI 318M - 2011


Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 165 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis - 227 - 218 235 219
Critical L/C - RCDC - 43 - 34 51 35
Mu (kNm) - 10.144 - 50.537 4.578 49.065
As (flex) (sqmm) (C) - 82.13 - 426.98 36.87 413.85
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) - 0.313 - 0.127 0.081 0.158
Tcr/4 (kNm) - 2.39 - 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 297.84 275 297.84 555.07 275 538.01
AstPrv (sqmm) 397.12 397.12 397.12 595.68 595.68 595.68
Reinforcement 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.722 0.722 0.722
Vu (kN) 33.36 22.34 32.78
Mu-Sect (kNm) - 5.32 -
Vc (kN) 76.13 76.13 76.13
Vs (kN) - - -
VD+L (kN) 24.05 23.2
Mh (kNm) 94 94
Ms (kNm) 64.71 64.71
Sway-Right (kN) 50.07 2.82
Sway-Left (kN) 1.97 49.22
Vu-Sway (kN) 50.07 49.22
Vud (kN) 50.07 49.22
Av (sqmm) 208.33 208.33 208.33
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Tu (kNm) 0.12 0.12 0.12


Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Depth = 400 <= 1000
  

Group : G5

Beam No : B12,B14

0.5m : 9275,9277

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Grade Of Steel : Fy420 N/sqmm


Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 226 230 212 218 219 219
Critical L/C - RCDC 42 46 28 34 35 35
Mu (kNm) 6.166 10.171 10.17 33.004 10.133 27.15
As (flex) (sqmm) (C) 49.73 82.35 82.34 273.54 82.04 223.64
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.295 0.003 0.02 0.002 0.021 0.021
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 275 275 275 355.61 275 290.73
AstPrv (sqmm) 397.12 397.12 397.12 397.12 397.12 397.12
Reinforcement 2-#16 2-#16 2-#16 2-#16 2-#16 2-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.481 0.481 0.481
Vu (kN) 8.09 4.38 6.76
Mu-Sect (kNm) - 0.56 -
Vc (kN) 72.75 72.75 72.75
Vs (kN) - - -
VD+L (kN) 7 4.12
Mh (kNm) 64.71 64.71
Ms (kNm) 64.71 64.71
Sway-Right (kN) 38.57 27.44
Sway-Left (kN) 24.57 35.69
Vu-Sway (kN) 38.57 35.69
Vud (kN) 38.57 35.69
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.03 0.03 0.03
Ao= Φ*Aoh - - -
At (sqmm) - - -
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Depth = 400 <= 1000
  

Group : G5

Beam No : B13,B15

0.5m : 9274,9276

Beam Length : 6499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Mubal : 172.5 kNm


As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 235 230 230 218 219 219
Critical L/C - RCDC 51 46 46 34 35 35
Mu (kNm) 10.039 10.054 10.13 28.717 8.977 31.327
As (flex) (sqmm) (C) 81.27 81.39 82.01 236.94 72.6 259.19
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) - 0.001 - 0.035 0.009 0.009
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 275 275 275 308.02 275 336.94
AstPrv (sqmm) 397.12 397.12 397.12 397.12 397.12 397.12
Reinforcement 2-#16 2-#16 2-#16 2-#16 2-#16 2-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.481 0.481 0.481
Vu (kN) 10.58 7.3 10.87
Mu-Sect (kNm) - 2.34 -
Vc (kN) 72.75 72.75 72.75
Vs (kN) - - -
VD+L (kN) 7.31 8.14
Mh (kNm) 64.71 64.71
Ms (kNm) 64.71 64.71
Sway-Right (kN) 28.52 13.07
Sway-Left (kN) 13.91 29.36
Vu-Sway (kN) 28.52 29.36
Vud (kN) 28.52 29.36
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.02 0.02 0.02
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Av Total Reqd (sqmm) 208.33 208.33 208.33


Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Depth = 400 <= 1000
  

4.7.3 Concrete Ground Beams


Group : G1

Beam No : B1,B5

2.5m : 363,371

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 209 221 233 217 233 216
Critical L/C - RCDC 25 37 49 33 49 32
Mu (kNm) 9.402 10.173 9.45 52.95 10.168 53.986
As (flex) (sqmm) (C) 76.07 82.37 76.46 448.58 82.32 457.91
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.569 0.996 0.25 0.614 0.251 0.761
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 275 275 496.4 583.16 275 595.28
AstPrv (sqmm) 397.12 397.12 595.68 774.16 397.12 774.16
Reinforcement 2-#16 2-#16 3-#16 2-#22 2-#16 2-#22
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
Total area of longitudinal reinforcement calculated at a given
C = As (flex) =
section
Distributed longitudinal torsional reinforcement at section
D = Al (Dist) =
considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.938 0.481 0.938
Vu (kN) 38.75 19.94 39.5
Mu-Sect (kNm) - 3.61 -
Vc (kN) 79.16 72.75 79.16
Vs (kN) - - -
VD+L (kN) 28.02 27.97
Mh (kNm) 118.58 118.58
Ms (kNm) 64.71 94
Sway-Right (kN) 16.68 72.67
Sway-Left (kN) 79.87 23.88
Vu-Sway (kN) 79.87 72.67
Vud (kN) 79.87 72.67
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.69 0.69 0.69
Ao= Φ*Aoh - - -
At (sqmm) - - -
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Torsion = 0.69 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 0 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 242.31 sqmm
SR provided = 1-#13EF
Asr provided = 253.35 sqmm
Provided Spacing = 140.95 mm
  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
  

Group : G1
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Beam No : B2,B6

2.5m : 364,368

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 232 217 233 217 233 216
Critical L/C - RCDC 48 33 49 33 49 32
Mu (kNm) 10.096 17.72 9.2 53.087 9.936 53.261
As (flex) (sqmm) (C) 81.73 144.56 74.42 449.82 80.43 451.38
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.088 2.509 1.26 2.509 1.259 2.307
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - 393.75 - 393.75 - -
Al (sqmm) (Tor.) (E) - 80.47 - 80.47 - -
Al (Dist) (sqmm) (D) - 75.72 - 75.72 - -
Ast (sqmm) 275 286.36 496.4 683.2 275 586.8
AstPrv (sqmm) 397.12 397.12 595.68 774.16 397.12 774.16
Reinforcement 2-#16 2-#16 3-#16 2-#22 2-#16 2-#22
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.938 0.481 0.938
Vu (kN) 39.05 19.64 39.21
Mu-Sect (kNm) - 3.6 -
Vc (kN) 79.16 72.75 79.16
Vs (kN) - - -
VD+L (kN) 27.98 27.97
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Mh (kNm) 118.58 118.58


Ms (kNm) 64.71 94
Sway-Right (kN) 16.73 72.67
Sway-Left (kN) 79.82 23.88
Vu-Sway (kN) 79.82 72.67
Vud (kN) 79.82 72.67
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 2.37 2.37 2.37
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Torsion = 2.37 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 393.75 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 242.31 sqmm
SR provided = 1-#13EF
Asr provided = 253.35 sqmm
Provided Spacing = 140.95 mm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
  

Group : G1

Beam No : B3,B7

2.5m : 365,369

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 232 217 233 217 232 216
Critical L/C - RCDC 48 33 49 33 48 32
Mu (kNm) 9.278 18.925 8.62 54.267 10.159 52.88
As (flex) (sqmm) (C) 75.06 154.57 69.65 460.44 82.25 447.96
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 1.498 2.868 0.76 2.868 1.498 3.044
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - 393.75 - 393.75 - 393.75
Al (sqmm) (Tor.) (E) - 91.97 - 91.97 - 97.63
Al (Dist) (sqmm) (D) - 75.72 - 75.72 - 75.72
Ast (sqmm) 496.4 299.38 496.4 697.01 275 680.79
AstPrv (sqmm) 595.68 397.12 595.68 774.16 397.12 774.16
Reinforcement 3-#16 2-#16 3-#16 2-#22 2-#16 2-#22
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 35 35 35
PtPrv (%) 0.938 0.481 0.938
Vu (kN) 40.2 20.36 39.17
Mu-Sect (kNm) - 3.48 -
Vc (kN) 79.16 72.75 79.16
Vs (kN) - - -
VD+L (kN) 27.95 28
Mh (kNm) 118.58 118.58
Ms (kNm) 94 94
Sway-Right (kN) 23.9 79.85
Sway-Left (kN) 79.8 23.85
Vu-Sway (kN) 79.8 79.85
Vud (kN) 79.8 79.85
Av (sqmm) 301.82 301.82 301.82
Tu (kNm) 4.8 4.8 4.8
Ao= Φ*Aoh 44550 44550 44550
At (sqmm) 301.82 301.82 301.82
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 301.821 301.821 301.821
Av Total Reqd (sqmm) 301.82 301.82 301.82
Asv Reqd (sqmm) 301.821 301.821 301.821
SCalc (mm) 100 125 100
SPrv (mm) 100 125 100
Av Total Prv (sqmm) 1417.6 1134.08 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
       For Torsion                                 
                (X1 = 180, Y1 = 330)
                Spc3 = X1 = 180 mm
                Spc4=(X1+Y1)/4 = 125 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc6 = d / 4 = 82 mm
              Spc7 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Torsion = 4.8 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 393.75 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 242.31 sqmm
SR provided = 1-#13EF
Asr provided = 253.35 sqmm
Provided Spacing = 140.95 mm
  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
  

Group : G2

Beam No : B4,B10

2.5m : 9293,367

Beam Length : 6499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 232 217 233 217 232 216
Critical L/C - RCDC 48 33 49 33 48 32
Mu (kNm) 51.142 42.293 56.65 95.727 31.584 93.519
As (flex) (sqmm) (C) 432.38 354.07 481.97 854.97 261.38 832.78
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.651 1.604 0.82 1.604 0.651 1.44
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Ast (sqmm) 595.68 460.29 626.57 1111.46 339.8 1082.62


AstPrv (sqmm) 595.68 595.68 992.8 1161.24 595.68 1161.24
3-#16 3-#16 3-#16 3-#22 3-#16 3-#22
Reinforcement
2-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 35 35 35
PtPrv (%) 1.408 1.408 1.408
Vu (kN) 40.86 25.28 65.15
Mu-Sect (kNm) - 0.98 -
Vc (kN) 85.74 85.74 85.74
Vs (kN) - - -
VD+L (kN) 39.94 40.8
Mh (kNm) 166.2 166.2
Ms (kNm) 94 146.43
Sway-Right (kN) 103.41 22.67
Sway-Left (kN) 36.31 117.05
Vu-Sway (kN) 103.41 117.05
Vud (kN) 103.41 117.05
Av (sqmm) 289.37 289.37 208.33
Tu (kNm) 4.6 4.6 0.37
Ao= Φ*Aoh 44550 44550 -
At (sqmm) 289.37 289.37 -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 289.369 289.369 289.369
Av Total Reqd (sqmm) 289.37 289.37 208.33
Asv Reqd (sqmm) 376.14 289.369 507.383
SCalc (mm) 100 125 100
SPrv (mm) 100 125 100
Av Total Prv (sqmm) 1417.6 1134.08 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
       For Torsion                                 
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

                (X1 = 180, Y1 = 330)


                Spc3 = X1 = 180 mm
                Spc4=(X1+Y1)/4 = 125 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc6 = d / 4 = 82 mm
              Spc7 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Torsion = 4.6 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 0 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 242.31 sqmm
SR provided = 1-#13EF
Asr provided = 253.35 sqmm
Provided Spacing = 124.67 mm
  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
  

Group : G4

Beam No : B8,B11

2.5m : 366,372

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 227 206 234 218 218 219
Critical L/C - RCDC 43 22 50 34 34 35
Mu (kNm) 10.061 10.093 9.44 57.074 10.036 57.784
As (flex) (sqmm) (C) 81.45 81.71 76.35 485.81 81.24 492.26
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 2.277 1.859 0.04 1.245 1.245 1.103
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 275 275 496.4 631.56 275 639.94
AstPrv (sqmm) 397.12 397.12 595.68 859.56 595.68 1161.24
Reinforcement 2-#16 2-#16 3-#16 3-#19 3-#16 3-#22
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 1.042 0.481 1.408
Vu (kN) 38.84 19.85 39.41
Mu-Sect (kNm) - 3.35 -
Vc (kN) 80.61 72.75 85.74
Vs (kN) - - -
VD+L (kN) 28.46 28.15
Mh (kNm) 129.75 166.2
Ms (kNm) 64.71 94
Sway-Right (kN) 84.78 28.17
Sway-Left (kN) 26.12 82.72
Vu-Sway (kN) 84.78 82.72
Vud (kN) 84.78 82.72
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 1.14 1.14 1.14
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 233.921 208.333 208.333
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

SCalc (mm) 100 150 100


SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Torsion = 1.14 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 0 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 242.31 sqmm
SR provided = 1-#13EF
Asr provided = 253.35 sqmm
Provided Spacing = 140.95 mm
  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
  

Group : G4

Beam No : B9,B12

2.5m : 370,9299

Beam Length : 6499.99 mm


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Breadth (B) : 250 mm


Depth (D) : 400 mm
Effective Depth (d) : 330 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 172.5 kNm
As,min (flex) (sqmm) (B) : 275 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 235 218 234 218 212 219
Critical L/C - RCDC 51 34 50 34 28 35
Mu (kNm) 35.064 32.745 37.01 81.998 9.667 79.74
As (flex) (sqmm) (C) 291.26 271.32 308.05 719.33 78.23 697.53
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.004 0.695 0.11 0.695 0.422 0.806
Tcr/4 (kNm) 2.39 2.39 2.39 2.39 2.39 2.39
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 496.4 352.72 496.4 935.13 275 906.79
AstPrv (sqmm) 595.68 397.12 595.68 1161.24 595.68 1161.24
Reinforcement 3-#16 2-#16 3-#16 3-#22 3-#16 3-#22
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 1.408 1.408 1.408
Vu (kN) 56.89 38.05 56.14
Mu-Sect (kNm) - 10.37 -
Vc (kN) 85.74 85.74 85.74
Vs (kN) - - -
VD+L (kN) 40.92 39.81
Mh (kNm) 166.2 166.2
Ms (kNm) 94 94
Sway-Right (kN) 83.58 2.84
Sway-Left (kN) 1.73 82.47
Vu-Sway (kN) 83.58 82.47
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Vud (kN) 83.58 82.47


Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.76 0.76 0.76
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 165 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 82 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 165 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 400 mm
Depth = 400 <= 1000

  

4.7.4 Concrete Deck Beams


Group : G1

Beam No : B1

Analysis Reference (Member) 6.6m : 373

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Depth (D) : 450 mm


Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 216 216 229 217 232 216
Critical L/C - RCDC 32 32 45 33 48 32
Mu (kNm) 36.609 37.187 9.91 55.366 13.061 65.288
As (flex) (sqmm) (C) 262.01 266.27 69.49 402.28 91.81 478.32
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 4.009 4.009 2.73 3.527 2.04 4.009
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) 439.92 439.92 - 445.83 - 439.92
Al (sqmm) (Tor.) (E) 122.58 122.58 - 107.86 - 122.58
Al (Dist) (sqmm) (D) 78.56 78.56 - 79.61 - 78.56
Ast (sqmm) 442.74 448.27 496.4 626.46 316.67 723.94
AstPrv (sqmm) 595.68 595.68 595.68 774.16 397.12 774.16
Reinforcement 3-#16 3-#16 3-#16 2-#22 2-#16 2-#22
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
Total area of longitudinal reinforcement calculated at a given
C = As (flex) =
section
Distributed longitudinal torsional reinforcement at section
D = Al (Dist) =
considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 20 20 20
PtPrv (%) 0.815 0.627 0.815
Vu (kN) 22.97 25.66 36.5
Mu-Sect (kNm) - 1.35 -
Vc (kN) 89.16 86.13 89.16
Vs (kN) - - -
VD+L (kN) 22.02 21.43
Mh (kNm) 138.9 138.9
Ms (kNm) 109.63 109.63
Sway-Right (kN) 38.6 82.05
Sway-Left (kN) 82.64 39.19
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Vu-Sway (kN) 82.64 82.05


Vud (kN) 82.64 82.05
Av (sqmm) 231.19 231.19 231.19
Tu (kNm) 4.23 4.23 4.23
Ao= Φ*Aoh 51300 51300 51300
At (sqmm) 231.19 231.19 231.19
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 231.188 231.188 231.188
Av Total Reqd (sqmm) 231.19 231.19 231.19
Asv Reqd (sqmm) 231.188 231.188 231.188
SCalc (mm) 100 175 100
SPrv (mm) 100 175 100
Av Total Prv (sqmm) 1417.6 810.06 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
       For Torsion                                 
                (X1 = 180, Y1 = 380)
                Spc3 = X1 = 180 mm
                Spc4=(X1+Y1)/4 = 125 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc6 = d / 4 = 95 mm
              Spc7 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Torsion = 4.23 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 445.83 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 286.61 sqmm
SR provided = 1-#16EF
Asr provided = 397.11 sqmm
Provided Spacing = 165.95 mm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
  

Group : G1

Beam No : B2

Analysis Reference (Member) 6.6m : 374

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 232 203 233 217 232 216
Critical L/C - RCDC 48 19 49 33 48 32
Mu (kNm) 13.276 13.364 12.81 54.095 12.495 55.279
As (flex) (sqmm) (C) 93.33 93.96 90.02 392.64 87.79 401.62
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.623 1.194 0.57 1.229 0.623 1.281
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 496.4 316.67 316.67 510.43 316.67 522.11
AstPrv (sqmm) 595.68 397.12 397.12 774.16 397.12 774.16
Reinforcement 3-#16 2-#16 2-#16 2-#22 2-#16 2-#22
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.815 0.418 0.815
Vu (kN) 30.11 19.44 30.73
Mu-Sect (kNm) - 1.46 -
Vc (kN) 89.16 82.75 89.16
Vs (kN) - - -
VD+L (kN) 21.75 21.7
Mh (kNm) 138.9 138.9
Ms (kNm) 109.63 75.13
Sway-Right (kN) 38.87 82.32
Sway-Left (kN) 73.95 30.5
Vu-Sway (kN) 73.95 82.32
Vud (kN) 73.95 82.32
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 1.24 1.24 1.24
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 175 100
SPrv (mm) 100 175 100
Av Total Prv (sqmm) 1417.6 810.06 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 95 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement

  
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Beam Width = 250 mm


Beam Depth = 450 mm
Depth = 450 <= 1000
  

Group : G1

Beam No : B3

Analysis Reference (Member) 6.6m : 375

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 216 217 229 217 233 216
Critical L/C - RCDC 32 33 45 33 49 32
Mu (kNm) 2.375 37.522 34.44 66.038 13.296 54.276
As (flex) (sqmm) (C) 16.56 268.73 246.03 484.13 93.47 394.01
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 5.118 5.517 4.4 5.517 2.751 5.118
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) 406.01 393.81 428.1 393.81 - 406.01
Al (sqmm) (Tor.) (E) 156.49 168.69 134.4 168.69 - 156.49
Al (Dist) (sqmm) (D) 72.5 70.32 76.45 70.32 - 72.5
Ast (sqmm) 496.4 440.77 496.4 720.79 316.67 606.46
AstPrv (sqmm) 595.68 595.68 595.68 774.16 397.12 774.16
Reinforcement 3-#16 3-#16 3-#16 2-#22 2-#16 2-#22
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Critical L/C - RCDC 26 26 26


PtPrv (%) 0.815 0.418 0.815
Vu (kN) 36.17 26.13 18.26
Mu-Sect (kNm) - 1.31 -
Vc (kN) 89.16 82.75 89.16
Vs (kN) - - -
VD+L (kN) 21.42 22.04
Mh (kNm) 138.9 138.9
Ms (kNm) 109.63 109.63
Sway-Right (kN) 39.2 82.65
Sway-Left (kN) 82.03 38.58
Vu-Sway (kN) 82.03 82.65
Vud (kN) 82.03 82.65
Av (sqmm) 331.27 331.27 331.27
Tu (kNm) 6.07 6.07 6.07
Ao= Φ*Aoh 51300 51300 51300
At (sqmm) 331.27 331.27 331.27
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 331.268 331.268 331.268
Av Total Reqd (sqmm) 331.27 331.27 331.27
Asv Reqd (sqmm) 331.268 331.268 331.268
SCalc (mm) 100 125 100
SPrv (mm) 100 125 100
Av Total Prv (sqmm) 1417.6 1134.08 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
       For Torsion                                 
                (X1 = 180, Y1 = 380)
                Spc3 = X1 = 180 mm
                Spc4=(X1+Y1)/4 = 125 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc6 = d / 4 = 95 mm
              Spc7 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

  

Beam Width = 250 mm


Beam Depth = 450 mm
Torsion = 6.07 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 428.1 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 286.61 sqmm
SR provided = 1-#16EF
Asr provided = 397.11 sqmm
Provided Spacing = 165.95 mm
  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
  

Group : G2

Beam No : B4

Analysis Reference (Member) 6.6m : 422

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 225 216 233 205 - 216
Critical L/C - RCDC 41 32 49 21 - 32
Mu (kNm) 13.418 47.205 0.77 13.017 - 48.22
As (flex) (sqmm) (C) 94.34 340.71 5.34 91.49 - 348.32
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.332 0.695 0.29 0.779 - 0.695
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 - 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 316.67 442.92 316.67 316.67 190 452.81
AstPrv (sqmm) 397.12 595.68 397.12 595.68 595.68 595.68
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Reinforcement 2-#16 3-#16 2-#16 3-#16 3-#16 3-#16


 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.627 0.627 0.627
Vu (kN) 44.41 34.2 58.4
Mu-Sect (kNm) - 29.23 -
Vc (kN) 86.13 80.5 86.13
Vs (kN) - - -
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.66 0.66 0.66
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 200 200 200
SPrv (mm) 200 200 200
Av Total Prv (sqmm) 708.8 708.8 708.8

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Depth = 450 <= 1000
  
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Group : G2

Beam No : B5

Analysis Reference (Member) 6.6m : 424

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 190 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis - 233 - 217 - 216
Critical L/C - RCDC - 49 - 33 - 32
Mu (kNm) - 13.341 - 51.114 - 45.414
As (flex) (sqmm) (C) - 93.79 - 370.1 - 327.31
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) - 0.027 - 0.085 - 0.133
Tcr/4 (kNm) - 2.81 - 2.81 - 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 190 316.67 190 481.13 190 425.5
AstPrv (sqmm) 397.12 397.12 397.12 595.68 595.68 595.68
Reinforcement 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.627 0.418 0.627
Vu (kN) 52.55 28.35 50.27
Mu-Sect (kNm) - 17.73 -
Vc (kN) 86.13 80.1 86.13
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Vs (kN) - - -
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.11 0.11 0.11
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 125 200 200
SPrv (mm) 125 200 200
Av Total Prv (sqmm) 1134.08 708.8 708.8

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Depth = 450 <= 1000
  

Group : G2

Beam No : B6

Analysis Reference (Member) 6.6m : 426

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Critical L/C - Analysis 208 217 222 217 - 219


Critical L/C - RCDC 24 33 38 33 - 35
Mu (kNm) 3.382 48.677 13.11 42.787 - 13.508
As (flex) (sqmm) (C) 23.6 351.75 92.15 307.73 - 94.98
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.956 0.839 0.81 0.839 - 0.721
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 - 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 316.67 457.28 316.67 400.04 190 316.67
AstPrv (sqmm) 397.12 595.68 397.12 595.68 595.68 595.68
Reinforcement 2-#16 3-#16 2-#16 3-#16 3-#16 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.627 0.627 0.627
Vu (kN) 57.18 32.98 45.64
Mu-Sect (kNm) - 32.13 -
Vc (kN) 86.13 79.95 86.13
Vs (kN) - - -
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.76 0.76 0.76
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 125 200 200
SPrv (mm) 125 200 200
Av Total Prv (sqmm) 1134.08 708.8 708.8

Maximum Spacing Criteria

    

       Basic                               
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

                Spc1 =d/2 = 190 mm


                Spc2 = 300 mm
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Depth = 450 <= 1000
  

Group : G3

Beam No : B7

Analysis Reference (Member) 6.6m : 376

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 216 216 229 217 229 216
Critical L/C - RCDC 32 32 45 33 45 32
Mu (kNm) 44.931 47.882 4.49 68.037 9.804 95.216
As (flex) (sqmm) (C) 323.7 345.78 31.35 499.63 68.75 716.24
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.477 0.477 0.44 0.549 0.441 0.477
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 420.82 449.52 496.4 649.52 316.67 931.12
AstPrv (sqmm) 595.68 595.68 595.68 859.56 595.68 1161.24
Reinforcement 3-#16 3-#16 3-#16 3-#19 3-#16 3-#22
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

B = As,min (flex) = Min area of flexural reinforcement


C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.905 0.627 1.222
Vu (kN) 40.15 37.75 54.6
Mu-Sect (kNm) - 4.73 -
Vc (kN) 90.61 86.13 95.74
Vs (kN) - - -
VD+L (kN) 34.34 33.34
Mh (kNm) 152.32 196.69
Ms (kNm) 109.63 109.63
Sway-Right (kN) 40.37 108.05
Sway-Left (kN) 98.23 30.55
Vu-Sway (kN) 98.23 108.05
Vud (kN) 98.23 108.05
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.5 0.5 0.5
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 252.901 208.333 302.791
SCalc (mm) 100 175 100
SPrv (mm) 100 175 100
Av Total Prv (sqmm) 1417.6 810.06 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 95 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Depth = 450 <= 1000
  

Group : G3

Beam No : B8

Analysis Reference (Member) 6.6m : 377

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 228 212 233 217 216 216
Critical L/C - RCDC 44 28 49 33 32 32
Mu (kNm) 4.101 13.394 10.51 78.207 13.355 79.291
As (flex) (sqmm) (C) 28.64 94.17 73.72 579.39 93.89 587.97
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.609 0.758 0.4 0.817 0.777 0.777
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 496.4 316.67 496.4 753.2 316.67 764.37
AstPrv (sqmm) 595.68 397.12 595.68 1161.24 595.68 859.56
Reinforcement 3-#16 2-#16 3-#16 3-#22 3-#16 3-#19
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))


 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 1.222 0.627 0.905
Vu (kN) 46.27 31.63 48.49
Mu-Sect (kNm) - 2.01 -
Vc (kN) 95.74 86.13 90.61
Vs (kN) - - -
VD+L (kN) 33.92 33.76
Mh (kNm) 196.69 152.32
Ms (kNm) 109.63 109.63
Sway-Right (kN) 29.97 97.65
Sway-Left (kN) 108.63 40.95
Vu-Sway (kN) 108.63 97.65
Vud (kN) 108.63 97.65
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.78 0.78 0.78
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 307.63 208.333 248.064
SCalc (mm) 100 175 100
SPrv (mm) 100 175 100
Av Total Prv (sqmm) 1417.6 810.06 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 95 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

  

Beam Width = 250 mm


Beam Depth = 450 mm
Depth = 450 <= 1000
  

Group : G3

Beam No : B9

Analysis Reference (Member) 6.6m : 378

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 232 217 217 217 233 216
Critical L/C - RCDC 48 33 33 33 49 32
Mu (kNm) 9.814 47.084 42.1 85.446 12.872 54.569
As (flex) (sqmm) (C) 68.81 339.8 302.63 637.08 90.47 396.23
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.754 1.438 1.44 1.438 0.663 1.529
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 496.4 441.74 393.42 828.21 316.67 515.1
AstPrv (sqmm) 595.68 595.68 397.12 859.56 595.68 595.68
Reinforcement 3-#16 3-#16 2-#16 3-#19 3-#16 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

For Transverse Reinf


Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.905 0.627 0.627
Vu (kN) 55.59 38.73 39.16
Mu-Sect (kNm) - 5.42 -
Vc (kN) 90.61 86.13 86.13
Vs (kN) - - -
VD+L (kN) 33.27 34.41
Mh (kNm) 152.32 109.63
Ms (kNm) 109.63 75.13
Sway-Right (kN) 20.21 87.89
Sway-Left (kN) 88.74 21.07
Vu-Sway (kN) 88.74 87.89
Vud (kN) 88.74 87.89
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 1.47 1.47 1.47
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 175 100
SPrv (mm) 100 175 100
Av Total Prv (sqmm) 1417.6 810.06 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 95 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Beam Depth = 450 mm


Depth = 450 <= 1000
  

Group : G4

Beam No : B10

Analysis Reference (Member) 6.6m : 428

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 231 216 233 233 - 216
Critical L/C - RCDC 47 32 49 49 - 32
Mu (kNm) 13.465 37.512 0.81 12.953 - 46.661
As (flex) (sqmm) (C) 94.68 268.66 5.68 91.04 - 336.64
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.329 0.298 0.21 0.212 - 0.298
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 - 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 316.67 349.26 316.67 316.67 190 437.63
AstPrv (sqmm) 397.12 397.12 397.12 595.68 595.68 595.68
Reinforcement 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

PtPrv (%) 0.627 0.627 0.627


Vu (kN) 36.18 25.5 50.51
Mu-Sect (kNm) - 20.92 -
Vc (kN) 86.13 80.69 86.13
Vs (kN) - - -
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.34 0.34 0.34
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 200 200 200
SPrv (mm) 200 200 200
Av Total Prv (sqmm) 708.8 708.8 708.8

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Depth = 450 <= 1000
  

Group : G4

Beam No : B11

Analysis Reference (Member) 6.6m : 430

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 190 sqmm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis - 229 - 217 232 216
Critical L/C - RCDC - 45 - 33 48 32
Mu (kNm) - 13.503 - 43.585 1.379 46.502
As (flex) (sqmm) (C) - 94.94 - 313.66 9.61 335.44
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) - 0.148 - 0.184 0.071 0.159
Tcr/4 (kNm) - 2.81 - 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 190 316.67 190 407.76 316.67 436.08
AstPrv (sqmm) 397.12 397.12 397.12 595.68 595.68 595.68
Reinforcement 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.627 0.627 0.627
Vu (kN) 42.58 19.1 44.11
Mu-Sect (kNm) - 9.79 -
Vc (kN) 86.13 83.5 86.13
Vs (kN) - - -
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.17 0.17 0.17
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 200 200 200
SPrv (mm) 200 200 200
Av Total Prv (sqmm) 708.8 708.8 708.8

Maximum Spacing Criteria


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Depth = 450 <= 1000
  

Group : G4

Beam No : B12

Analysis Reference (Member) 6.6m : 432

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Regular Beam
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 190 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis - 217 225 217 - 232
Critical L/C - RCDC - 33 41 33 - 48
Mu (kNm) - 37.171 13.37 48.113 - 11.511
As (flex) (sqmm) (C) - 266.15 93.99 347.52 - 80.82
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) - 0.549 0.27 0.549 - 0.265
Tcr/4 (kNm) - 2.81 2.81 2.81 - 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 190 345.99 316.67 451.77 190 316.67
AstPrv (sqmm) 397.12 397.12 397.12 595.68 595.68 595.68
Reinforcement 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16
 

Note: Calculation of Ast


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.627 0.418 0.627
Vu (kN) 51.33 26.32 35.36
Mu-Sect (kNm) - 19.75 -
Vc (kN) 86.13 79.42 86.13
Vs (kN) - - -
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.55 0.55 0.55
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 125 200 200
SPrv (mm) 125 200 200
Av Total Prv (sqmm) 1134.08 708.8 708.8

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Depth = 450 <= 1000
  

Group : G5

Beam No : B13
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Analysis Reference (Member) 6.6m : 379

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 220 214 229 217 229 216
Critical L/C - RCDC 36 30 45 33 45 32
Mu (kNm) 12.96 13.508 13.2 48.895 12.449 56.318
As (flex) (sqmm) (C) 91.09 94.98 92.8 353.39 87.46 409.53
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 2.551 1.825 1.56 1.987 1.557 2.1
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 316.67 316.67 316.67 459.41 316.67 532.38
AstPrv (sqmm) 397.12 397.12 397.12 595.68 595.68 595.68
Reinforcement 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.627 0.627 0.627
Vu (kN) 23.06 19.43 29.7
Mu-Sect (kNm) - 3.52 -
Vc (kN) 86.13 86.13 86.13
Vs (kN) - - -
VD+L (kN) 19.08 18.62
Mh (kNm) 109.63 109.63
Ms (kNm) 75.13 75.13
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Sway-Right (kN) 25.99 63.68


Sway-Left (kN) 64.14 26.45
Vu-Sway (kN) 64.14 63.68
Vud (kN) 64.14 63.68
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 2.01 2.01 2.01
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 175 100
SPrv (mm) 100 175 100
Av Total Prv (sqmm) 1417.6 810.06 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 95 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Torsion = 2.01 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 0 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 286.61 sqmm
SR provided = 1-#16EF
Asr provided = 397.11 sqmm
Provided Spacing = 169.1 mm
  
Spacing Criteria
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

           
Maximum Spacing = 280 mm
        
  
  

Group : G5

Beam No : B14

Analysis Reference (Member) 6.6m : 380

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 216 216 217 217 232 216
Critical L/C - RCDC 32 32 33 33 48 32
Mu (kNm) 13.24 13.477 13.12 47.678 11.245 47.787
As (flex) (sqmm) (C) 93.07 94.76 92.23 344.26 78.93 345.08
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.352 0.352 0.12 0.125 0.225 0.352
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 316.67 316.67 316.67 447.53 316.67 448.6
AstPrv (sqmm) 397.12 397.12 397.12 595.68 595.68 595.68
Reinforcement 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Left Mid Right


Critical L/C - RCDC 17 17 17
PtPrv (%) 0.627 0.418 0.627
Vu (kN) 26.4 16.12 26.37
Mu-Sect (kNm) - 1.29 -
Vc (kN) 86.13 82.75 86.13
Vs (kN) - - -
VD+L (kN) 18.85 18.85
Mh (kNm) 109.63 109.63
Ms (kNm) 75.13 75.13
Sway-Right (kN) 26.22 63.91
Sway-Left (kN) 63.91 26.22
Vu-Sway (kN) 63.91 63.91
Vud (kN) 63.91 63.91
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 0.24 0.24 0.24
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 175 100
SPrv (mm) 100 175 100
Av Total Prv (sqmm) 1417.6 810.06 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 95 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Depth = 450 <= 1000


  

Group : G5

Beam No : B15

Analysis Reference (Member) 6.6m : 381

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 228 205 212 217 228 216
Critical L/C - RCDC 44 21 28 33 44 32
Mu (kNm) 13.209 13.489 12.81 55.971 12.507 48.976
As (flex) (sqmm) (C) 92.85 94.85 90.03 406.89 87.87 354
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 1.418 2.355 2.6 1.803 1.418 1.801
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) - - - - - -
Al (sqmm) (Tor.) (E) - - - - - -
Al (Dist) (sqmm) (D) - - - - - -
Ast (sqmm) 316.67 316.67 316.67 528.95 316.67 460.2
AstPrv (sqmm) 397.12 397.12 397.12 595.68 595.68 595.68
Reinforcement 2-#16 2-#16 2-#16 3-#16 3-#16 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 17 17
PtPrv (%) 0.627 0.418 0.627
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Vu (kN) 29.73 19.45 23.04


Mu-Sect (kNm) - 3.45 -
Vc (kN) 86.13 82.75 86.13
Vs (kN) - - -
VD+L (kN) 18.61 19.08
Mh (kNm) 109.63 109.63
Ms (kNm) 75.13 75.13
Sway-Right (kN) 26.45 64.14
Sway-Left (kN) 63.68 25.99
Vu-Sway (kN) 63.68 64.14
Vud (kN) 63.68 64.14
Av (sqmm) 208.33 208.33 208.33
Tu (kNm) 1.78 1.78 1.78
Ao= Φ*Aoh - - -
At (sqmm) - - -
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 0 0
Av Total Reqd (sqmm) 208.33 208.33 208.33
Asv Reqd (sqmm) 208.333 208.333 208.333
SCalc (mm) 100 175 100
SPrv (mm) 100 175 100
Av Total Prv (sqmm) 1417.6 810.06 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc3 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc4 = d / 4 = 95 mm
              Spc5 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Torsion = 1.78 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Al Tor. (max) = 0 sqmm


Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 286.61 sqmm
SR provided = 1-#16EF
Asr provided = 397.11 sqmm
Provided Spacing = 169.1 mm
  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
  

Group : G6

Beam No : B16,B22

6.6m : ((418,386),431,389)

Beam Length : 4499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 316.67 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 231 219 234 218 226 219
Critical L/C - RCDC 47 35 50 34 42 35
Mu (kNm) 37.425 38.625 10.79 67.985 13.259 100.6
As (flex) (sqmm) (C) 268.02 276.88 75.74 499.22 93.21 760.53
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 4.059 5.159 0.99 5.211 1.738 2.724
Tcr/4 (kNm) 2.81 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) 438.39 404.75 - 403.16 - -
Al (sqmm) (Tor.) (E) 124.11 157.75 - 159.34 - -
Al (Dist) (sqmm) (D) 78.28 72.28 - 71.99 - -
Ast (sqmm) 450.2 453.9 673.6 742.58 316.67 988.69
AstPrv (sqmm) 595.68 595.68 992.8 774.16 397.12 1347.2
3-#16 3-#16 3-#16 2-#22 2-#16 2-#22
Reinforcement
2-#16 2-#19
 

Note: Calculation of Ast

  
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 33 33 33
PtPrv (%) 0.815 0.627 1.418
Vu (kN) 31.09 20.67 50.54
Mu-Sect (kNm) - 10.86 -
Vc (kN) 89.16 83.32 98.9
Vs (kN) - - -
VD+L (kN) 12.97 42.53
Mh (kNm) 138.9 221.68
Ms (kNm) 109.63 172.49
Sway-Right (kN) 93.78 38.28
Sway-Left (kN) 62.98 118.48
Vu-Sway (kN) 93.78 118.48
Vud (kN) 93.78 118.48
Av (sqmm) 509.44 509.44 435.09
Tu (kNm) 9.33 9.33 7.97
Ao= Φ*Aoh 51300 51300 51300
At (sqmm) 509.44 509.44 435.09
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 509.436 509.436 435.092
Av Total Reqd (sqmm) 509.44 509.44 435.09
Asv Reqd (sqmm) 509.436 509.436 435.092
SCalc (mm) 100 125 100
SPrv (mm) 100 125 100
Av Total Prv (sqmm) 1417.6 1134.08 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
       For Torsion                                 
                (X1 = 180, Y1 = 380)
                Spc3 = X1 = 180 mm
                Spc4=(X1+Y1)/4 = 125 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc6 = d / 4 = 95 mm
              Spc7 = 150 mm
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

             Provided Spacing = 100 mm


    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Torsion = 9.33 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 438.39 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 286.61 sqmm
SR provided = 1-#16EF
Asr provided = 397.11 sqmm
Provided Spacing = 127.47 mm
  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
  

Group : G6

Beam No : B17,B23

6.6m : ((417,382),425,385)

Beam Length : 6499.99 mm


Breadth (B) : 250 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 228.73 kNm
As,min (flex) (sqmm) (B) : 190 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis - 218 234 218 234 219
Critical L/C - RCDC - 34 50 34 50 35
Mu (kNm) - 75.895 21.05 117.593 7.873 87.046
As (flex) (sqmm) (C) - 561.12 148.85 903.6 55.13 649.94
Asc (flex) (sqmm) (A) - - - - - -
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Tu (kNm) - 5.655 3.1 5.655 2.659 7.677


Tcr/4 (kNm) - 2.81 2.81 2.81 2.81 2.81
Al, min(sqmm)(Tor.) (D) - 389.59 445.83 389.59 - 327.75
Al (sqmm) (Tor.) (E) - 172.91 94.85 172.91 - 234.75
Al (Dist) (sqmm) (D) - 69.57 79.61 69.57 - 58.53
Ast (sqmm) 673.6 819.9 485.08 1265.13 316.67 921.01
AstPrv (sqmm) 992.8 992.8 595.68 1347.2 397.12 970.16
3-#16 3-#16 3-#16 2-#22 2-#16 2-#19
Reinforcement
2-#16 2-#16 2-#19 2-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 33 33 33
PtPrv (%) 1.418 1.045 1.021
Vu (kN) 68.25 39.68 54.56
Mu-Sect (kNm) - 23.81 -
Vc (kN) 98.9 86.69 92.49
Vs (kN) - - -
VD+L (kN) 51.97 33.74
Mh (kNm) 221.68 169.13
Ms (kNm) 172.49 109.63
Sway-Right (kN) 107.97 22.27
Sway-Left (kN) 2.35 88.05
Vu-Sway (kN) 107.97 88.05
Vud (kN) 107.97 88.05
Av (sqmm) 505.81 558 558
Tu (kNm) 9.26 10.22 10.22
Ao= Φ*Aoh 51300 51300 51300
At (sqmm) 505.81 558 558
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 505.808 558.002 558.002
Av Total Reqd (sqmm) 505.81 558 558
Asv Reqd (sqmm) 557.386 558.002 558.002
SCalc (mm) 100 125 100
SPrv (mm) 100 125 100
Av Total Prv (sqmm) 1417.6 1134.08 1417.6

Maximum Spacing Criteria


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
       For Torsion                                 
                (X1 = 180, Y1 = 380)
                Spc3 = X1 = 180 mm
                Spc4=(X1+Y1)/4 = 125 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc6 = d / 4 = 95 mm
              Spc7 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement

  

Beam Width = 250 mm


Beam Depth = 450 mm
Torsion = 10.22 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 445.83 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 286.61 sqmm
SR provided = 1-#16EF
Asr provided = 397.11 sqmm
Provided Spacing = 127.47 mm
  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
  

Group : G7

Beam No : B18,B20

6.6m : ((427,387),429,388)

Beam Length : 4499.99 mm


Breadth (B) : 300 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Grade Of Concrete (Fck) : C25 N/sqmm


Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 274.48 kNm
As,min (flex) (sqmm) (B) : 380 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis 219 216 - 218 219 219
Critical L/C - RCDC 35 32 - 34 35 35
Mu (kNm) 54.752 67.424 - 84.431 48.231 188.982
As (flex) (sqmm) (C) 394.68 490.23 - 621.25 346.17 1514.5
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) 0.805 4.399 - 0.586 0.405 0.405
Tcr/4 (kNm) 3.78 3.78 - 3.78 3.78 3.78
Al, min(sqmm)(Tor.) (D) - 522.5 - - - -
Al (sqmm) (Tor.) (E) - 114.66 - - - -
Al (Dist) (sqmm) (D) - 104.5 - - - -
Ast (sqmm) 513.08 773.15 1340.68 807.63 450.02 1968.85
AstPrv (sqmm) 794.24 794.24 1588.48 859.56 595.68 2681.37
4-#16 4-#16 4-#16 3-#19 3-#16 3-#25
Reinforcement
4-#16 3-#22
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 17 32 32
PtPrv (%) 0.754 0.697 2.352
Vu (kN) 57.76 81.12 106.93
Mu-Sect (kNm) - 6.55 -
Vc (kN) 105.81 104.7 136.78
Vs (kN) - - -
VD+L (kN) 21.97 95.12
Mh (kNm) 155.51 379.51
Ms (kNm) 144.81 262.35
Sway-Right (kN) 149.85 32.76
Sway-Left (kN) 79.95 197.04
Vu-Sway (kN) 149.85 197.04
Vud (kN) 149.85 197.04
Av (sqmm) 250 250 250
Tu (kNm) 0.83 4.54 4.54
Ao= Φ*Aoh - 65550 65550
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

At (sqmm) - 194.06 194.06


Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 0 327.981 327.981
Av Total Reqd (sqmm) 250 250 250
Asv Reqd (sqmm) 588.927 370.761 789.056
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
       For Torsion                                 
                (X1 = 230, Y1 = 380)
                Spc3 = X1 = 230 mm
                Spc4=(X1+Y1)/4 = 150 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc5 = 6 x Small Longitudinal Dia = 95.4 mm
              Spc6 = d / 4 = 95 mm
              Spc7 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement

  

Beam Width = 300 mm


Beam Depth = 450 mm
Torsion = 4.54 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 522.5 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 313.5 sqmm
SR provided = 1-#16EF
Asr provided = 397.11 sqmm
Provided Spacing = 122.67 mm
  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

  

Group : G7

Beam No : B19,B21

6.6m : ((421,383),423,384)

Beam Length : 6499.99 mm


Breadth (B) : 300 mm
Depth (D) : 450 mm
Effective Depth (d) : 380 mm
Design Code : ACI 318M - 2011
Beam Type : Ductile Beam (Special Frame)
Grade Of Concrete (Fck) : C25 N/sqmm
Grade Of Steel : Fy420 N/sqmm
Clear Cover (Cmin) : 40 mm
Es : 2x10^5 N/sqmm
Mubal : 274.48 kNm
As,min (flex) (sqmm) (B) : 228 sqmm
 
For Longitudinal Reinf
Beam Bottom Beam Top
Left Mid Right Left Mid Right
Critical L/C - Analysis - 216 234 218 235 219
Critical L/C - RCDC - 32 50 34 51 35
Mu (kNm) - 153.82 15.06 224.955 10.808 138.034
As (flex) (sqmm) (C) - 1194.58 105.81 1868.88 75.74 1058
Asc (flex) (sqmm) (A) - - - - - -
Tu (kNm) - 4.714 0.42 1.298 0.769 1.502
Tcr/4 (kNm) - 3.78 3.78 3.78 3.78 3.78
Al, min(sqmm)(Tor.) (D) - 522.5 - - - -
Al (sqmm) (Tor.) (E) - 122.88 - - - -
Al (Dist) (sqmm) (D) - 104.5 - - - -
Ast (sqmm) 1340.68 1688.8 727.62 2429.54 380 1375.4
AstPrv (sqmm) 1432.6 1719.12 859.56 2681.37 595.68 1455.24
3-#19 3-#19 3-#19 3-#25 3-#16 3-#19
Reinforcement
2-#19 3-#19 3-#22 3-#16
 

Note: Calculation of Ast

  

Ast = Max {B, C+D, A+D}


Where,
A = Asc (flex) = Compression reinforcement required for bending moment
B = As,min (flex) = Min area of flexural reinforcement
C = As (flex) = Total area of longitudinal reinforcement calculated at a given section
D = Al (Dist) = Distributed longitudinal torsional reinforcement at section considered
Ast (Dist) (sqmm) = Max(Al,min (Tor), Al (Tor)) x ((2B) / (2B + 2D))
 
For Transverse Reinf
Left Mid Right
Critical L/C - RCDC 33 33 33
PtPrv (%) 2.352 1.508 1.277
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Vu (kN) 134.87 102.84 105.01


Mu-Sect (kNm) - 16.94 -
Vc (kN) 136.78 120.43 115.94
Vs (kN) - - -
VD+L (kN) 106.26 63.21
Mh (kNm) 379.51 244.54
Ms (kNm) 241.44 155.51
Sway-Right (kN) 185.92 16.46
Sway-Left (kN) 18.55 150.92
Vu-Sway (kN) 185.92 150.92
Vud (kN) 185.92 150.92
Av (sqmm) 525.74 360.69 334.92
Tu (kNm) 5.99 5.99 4.31
Ao= Φ*Aoh 65550 65550 65550
At (sqmm) 256.05 256.05 184.05
Legs 2 2 2
Stirrup Rebar 10 10 10
Asv Torsion (sqmm) 256.052 256.052 184.046
Av Total Reqd (sqmm) 525.74 360.69 334.92
Asv Reqd (sqmm) 731.293 480.355 534.35
SCalc (mm) 100 150 100
SPrv (mm) 100 150 100
Av Total Prv (sqmm) 1417.6 945.07 1417.6

Maximum Spacing Criteria

    

       Basic                               
                Spc1 =d/2 = 190 mm
                Spc2 = 300 mm
       For Torsion                                 
                (X1 = 230, Y1 = 380)
                Spc3 = X1 = 230 mm
                Spc4=(X1+Y1)/4 = 150 mm
  
 
     For Ductility (Special Frames)                  
       Left Section,  Right Section
              Spc5 = 6 x Small Longitudinal Dia = 114.6 mm
              Spc6 = d / 4 = 95 mm
              Spc7 = 150 mm
             Provided Spacing = 100 mm
    
       Mid Section
              Provided Spacing = 190 mm
    
 

Skin reinforcement

  

Beam Width = 300 mm


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Beam Depth = 450 mm


Torsion = 5.99 > 0 kNm
Beam Depth >1000 Or Torsion > 0,
Hence SFR Provided
Al Tor. (max) = 522.5 sqmm
Asr = Max(Al(min)(Tor.), Al(Tor.)) x (2D / (2B+2D))
= 313.5 sqmm
SR provided = 1-#16EF
Asr provided = 397.11 sqmm
Provided Spacing = 118.25 mm
  
Spacing Criteria
           
Maximum Spacing = 280 mm
        
  

  

4.7.5 Concrete Two way Slab

lx x
½ Column strip
Middle strip
ly

½ Column strip

124 mm

½ Column strip Middle strip ½ Column strip


150 mm

TWO-WAY SLAB PANEL

300 mm
Section at middle strip along
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

lx x

½ Column strip
A'sy_col
Asx_col A'sx_col

Asy_mid

Middle strip
ly

Asx_mid A'sx_mid
Asy_col

½ Column strip
A'sy_mid

½ Column strip Middle strip ½ Column strip

TWO-WAY SLAB PANEL Legend -


Top reinf.
(Reinforcement layout)
Bottom reinf.

4.7.6 Concrete Slab on Grade

#4@6" each way


6 in

Slab foundation-refer to Sec


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

P
p/2
PpP
p/2 P
100 in pPp

50 in

;
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.8 Foundation Design


4.8.1 Foundation Layout

4.8.2 Foundation Design


Design Code : ACI 318M - 2011

Footing No : FC1  

Column No : C1,C2,C3,C4,C5,C6,C7,C8,C9,C10,C11,C12 ( 400mm X 400mm)

Analysis No : 9244,9243,9242,9241,9247,1007,989,9240,9246,9245,9238,9239  

       
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Concrete Grade : C20  

Steel Grade : Fy420  

Clear Cover : 75 mm  

Dfd : 1.8 M  

Dw : 15 M  

Density of Soil = 18 KN/cuM

Soil Bearing Capacity = 300 kN/sqm

Gross Bearing Capacity = 332.4 kN/sqm

Permissible SBC Increase for =0 %


EQ
Permissible SBC Increase for =0 %
Wind
Live Load Reduction =0 %

Permissible area of loss of = 50 %


contact

Design cross section by : Average pressure


Consider overburden pressure
Consider overburden pressure
 

Footing Type : Pad  

Footing Size (L x B x D) : 1400mm X 1400mm X 300mm

Soil Wt. + Footing Wt. = 63.30 KN   

Offset Along L (Loff) = 500 mm   

Offset Along B (Boff) = 500 mm   

          
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Check For Maximum Soil Pressure:       

Critical Column No = C6    

Critical Analysis Load Combination = 113

Critical Load Combination = [13] : (LOAD 5: DEAD LOADS) +0.714 (LOAD 1: EQ X+)    

Pcomb = 381.69 kN      

P
= Pcomb + Effective Self Weight

P = 444.99 kN      
Mx = 39.68 kNm      
My = 1.2 kNm      
P/A = 227.04 kN/sqm
Mx/Zx = 86.77 kN/sqm
My/Zy = 2.62 kN/sqm
Maximum Soil Pressure = 316.44 kN/sqm
Allowable Soil Pressure = 1 X 332.4 kN/sqm
= 332.4 kN/sqm
 
Check For Minimum Soil Pressure:
Footing designed with loss of contact      
Critical Column No = C1
Critical Analysis Load Combination = 115
Critical Load Combination = [15] : (LOAD 5: DEAD LOADS) +0.714 (LOAD 3: EQ Z+)
Pcomb = 135.34 kN        
P = Pcomb + Soil Wt. + Footing Wt.           
P = 198.64 kN          
Mx = -1.23 kNm          
My = 47.26 kNm          
P/A = 101.35 kN/sqm          
Mx/Zx = -2.7 kN/sqm          
My/Zy = 103.35 kN/sqm          
Minimum Soil Pressure = -4.7 kN/sqm  
< 0    
Uplift condition = Corner uplift          
Area of loss of contact = 0.01995 sqm          
= 1.018 %          
< 50 %          
Corner pressure P1 = 202 kN/sqm          
Corner pressure P2 = 207.449 kN/sqm          
Corner pressure P3 = 0.66 kN/sqm          
Corner pressure P4 = -4.79 kN/sqm          
Point of zero pressure Distance measured from uplift corner         
Along long edge = 0.03 m          
Along short edge = 1.23 m          
           
P = 198.64 kN          
Mx = -1.23 kNm          
My = 47.26 kNm          
P/A = 101.35 kN/sqm          
Mx/Zx = -2.7 kN/sqm          
My/Zy = 103.35 kN/sqm          
Minimum Soil Pressure = -4.7 kN/sqm  
> 0    
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Check For Sliding:


Critical Column No = C1   
Critical Analysis Load Combination = 116
Critical Load Combination = [16] : (LOAD 5: DEAD LOADS) +0.714 (LOAD 4: EQ Z-)
P = 176.67 kN      
Coefficient Of Friction = 0.4    
Factor of safety = 1.5    
Shear Vx = 33.40 kN  
shear Vy = 9.43 kN  
Resultant sliding force = 34.71 kN  
Downward force = 239.97 kN  
Upward water pressure = 0.00 kN  
Net downward force = 239.97 kN  
Force resisting sliding = Friction Coeff X Net Downward Force  
= 95.99 kN  
Factor of safety available = Resisting Force / Sliding Force  
= 2.77  
> 1.5  
 
Check For Overturning:
Along Width:
Critical Analysis Load Combination = 113
Critical Load Combination = (LOAD 5: DEAD LOADS) +0.714 (LOAD 1: EQ X+)   
Factor of safety = 1.50    
VEd = 130.53 kN  
Stabilizing Moment for V = 91.37 kNm  
Stabilizing Moment for Pslfwt,fdn = 10.29 kNm  
Stabilizing Moment for soil = 34.02 kNm  
Total Stabilizing Moment = 135.68 kNm  
DeStabilizing Moment = 35.98 kNm  
Overturning Factor of safety = 3.77    
Safe in Overturning > 1.50    
 
Along Length:
Critical Analysis Load Combination = 115
Critical Load Combination = (LOAD 5: DEAD LOADS) +0.714 (LOAD 3: EQ Z+)   
Factor of safety = 1.50    
VEd = 135.34 kN  
Stabilizing Moment for V = 94.74 kNm  
Stabilizing Moment for Pslfwt,fdn = 10.29 kNm  
Stabilizing Moment for soil = 34.02 kNm  
Total Stabilizing Moment = 139.05 kNm  
DeStabilizing Moment = 47.26 kNm  
Overturning Factor of safety = 2.94    
Safe in Overturning > 1.50    
 
Design For Bending:
Bottom Reinforcement Along L:
Critical Column No = C6
Critical Analysis Load Combination = 216
Critical Load Combination = [83] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD) +(LOAD 1:
EQ X+)
Pu = 541.48 kN          
Mux = 55.6 kNm          
Muy = 1.71 kNm          
P/A = 276.27 kN/sqm          
Mx/Zx = 121.57 kN/sqm          
My/Zy = 3.73 kN/sqm          
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

 
Deff = 217 mm         
Beff = 1400 mm         
SPu = 397.83 kN/sqm         
Mu = SPu X B X Loff X Loff / 2      
= 69.62 kNm         
Ast Rqd (BM) = 880 sqmm         
Ast Prv = 8 - #16 @ 200          
  = 1588 sqmm  
Distributed Across Total Width     
 
Top Steel Along L:
Percentage loss of contact (LOC) = 1.018 %          
Weight of footing per unit area (W1) = D X Concrete Density          
= 7.5 kN/sqm          
Weight of soil over footing (W2) = (Df - D) X SoilDen          
= 27 kN/sqm          
Total downward weigth per unit area (W) = W1 + W2          
= 34.5 kN/sqm          
Component of footing length subjected to LOC
= (LOC / 100) X L      
(LOCL)
= 14.252 mm          
Moment along L = W X (LOCL^2) X B / 2          
= 0.005 kNm          
Effective width = B          
= 1400 mm          
Pt = 0.18 %          
Ast Calculated = 547 sqmm          
Ast Provided = #16 @ 200 c/c          
= 1588 sqmm          
 
Bottom Reinforcement Along B:
Critical Column No = C6
Critical Analysis Load Combination = 218
Critical Load Combination = [85] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD) +(LOAD 3:   
EQ Z+)
Pu = 497.19 kN          
Mux = 1.05 kNm          
Muy = 66.07 kNm          
P/A = 253.67 kN/sqm          
Mx/Zx = 2.31 kN/sqm          
My/Zy = 144.46 kN/sqm          
 
Deff = 201 mm          
Leff = 1400 mm          
SPu = 398.13 kN/sqm          
Mu = SPu X L X Boff X Boff / 2          
= 69.67 kNm          
Ast Rqd (BM) = 957 sqmm          
Ast Prv = 8 - #16 @ 200          
  = 1588 sqmm    
Distributed Across Total Length      
 
 
Top Steel Along B:
Percentage loss of contact (LOC) = 1.018 %          
Weight of footing per unit area (W1) = D X ConDen          
= 7.5 kN/sqm          
Weight of soil over footing (W2) = (Df - D) X SoilDen          
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

= 27 kN/sqm      
Total downward weigth per unit area (W) = W1 + W2      
= 34.5 kN/sqm      
Component of footing breadth subjected to
= (LOC / 100) X B      
LOC (LOCB)
= 14.252 mm          
Moment along B = W X (LOCB^2) X L / 2          
= 0.005 kNm          
Effective width = L          
= 1400 mm          
Pt = 0.19 %          
Ast Calculated = 546 sqmm          
Ast Provided = 8 - #16 @ 200 c/c          
= 1588 sqmm          
Design For Shear:
One Way Shear Along L:
Critical Section @ d from Column Face  
  = 217 mm  
Critical Column No = C6
Critical Analysis Load Combination = 216
Critical Load Combination = [83] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD) +(LOAD 1:   
EQ X+)
Pu = 541.48 kN          
Mux = 55.6 kNm          
Muy = 1.71 kNm          
P/A = 276.27 kN/sqm          
Mx/Zx = 121.57 kN/sqm          
My/Zy = 3.73 kN/sqm          
 
Deff = 217 mm          
Beff = 1400 mm          
SPu = 397.83 kN/sqm          
Vu = SPu X (Loff - d) X B          
  = 157.62 kN          
Vc = 244.39 kN           
Vu < Vc            
 
One Way Shear Along B:
Critical Section @ d from Column Face
 
  = 201 mm  
Critical Column No = C6
Critical Analysis Load Combination = 218
Critical Load Combination = [85] : 1.42 (LOAD 5: DEAD LOADS)    
+0.5 (LOAD 6: LIVELOAD) +(LOAD 3:
EQ Z+)
Pu = 497.19 kN          
Mux = 1.05 kNm        
Muy = 66.07 kNm          
P/A = 253.67 kN/sqm          
Mx/Zx = 2.31 kN/sqm          
My/Zy = 144.46 kN/sqm          
 
Deff = 201 mm          
Leff = 1400 mm          
SPu = 398.13 kN/sqm          
Vu = SPu X (Boff - d) X L          
  = 166.66 kN          
Vc = 228.36 kN           
Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

Vu < Vc        
 
Design For Punching Shear:
Critical Section @ d/2 from Column Face
  = 104 mm
   
Critical Column No = C6
Critical Analysis Load Combination = 216
Critical Load Combination = [83] : 1.42 (LOAD 5: DEAD LOADS) +0.5 (LOAD 6: LIVELOAD) +(LOAD 1:   
EQ X+)
Pu = 541.48 kN          
Mux = 55.6 kNm          
Muy = 1.71 kNm          
P/A = 276.27 kN/sqm          
Mx/Zx = 121.57 kN/sqm          
My/Zy = 3.73 kN/sqm          
 
Deff = 209 mm          
Leff = 609 mm          
Beff = 609 mm          
SPu = Average Pressure           
  = 276.27 kN/sqm          
Vud = { N - Pcr(axial)[ (Cx + d) X (Cy + d)]}            
= 439.02 kN          
Vn = 1138.436 kN           
Vc = 751.368 kN           
Vud < Vc No Shear Reinforcement Required          
 
Load Transfer Check For Load Transfer From Column To Footing
Critical Column No = C6
Critical Analysis Load Combination = 216
Critical Load Combination = [83] : 1.42 (LOAD 5: DEAD LOADS)
+0.5 (LOAD 6: LIVELOAD) +(LOAD 1:
EQ X+)
Pu = 541.48 kN
A2 = 0.16 sqm
A1 = 2.56 sqm
Base Area = 1.96 sqm
A1 > Base Area
Thus, A1 = 1.96
Modification Factor = SquareRoot(A1/A2)  < = 2
SquareRoot(A1/A2) = 3.5
Thus, Modification Factor = 2
ΦPnb = 0.85 X 0.75 X Fck X Modication Factor X Column Area
= 4080 kN
ΦPnb > Pu, Hence Safe.  

4.8.3 Foundation Schedule


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]

4.8.4 Transformer Equipment


4.8.4.1 Base Pressure Check

4.8.4.2 Concrete Design


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]


Structural Calculation
Report

TITLE : Bagging Electrical Room Rev[B]