Вы находитесь на странице: 1из 1

Client: CLIENT NAME Sheet: _____ of _____

Project: PROJECT NAME Date: 09/Mar/2020


Description: SEISMIC ANALYSIS - HYDRODYNAMIC FORCES Job No: 184031010
Design Task: RRP Sludge mixing tank By: AS Chkd By: MJ

Calculate Weights of Stored Liquid, Tank Walls, and Tank Roof Reference

WL = Weight of stored liquid


π 2
WL :=  D  HL  γL WL = 3956  kip
4
WW = Weight of all tank walls

Ww := π  ( D + t w)  Hw  tw  γc Ww = 742  kip

Wroof = Weight of roof slab


π
 ( D + 2  t w)  t r  γc
2
Wroof := Wroof = 0  kip
4

Ws = Weight of earth cover


π
 (D + 2  tw)  ts  γs
2
Wsoil := Wsoil = 0  kip
4

Calculate Equivalent Weights of Accelerated Liquids ACI 350.3-06


Section 9.3.1
Wi = Equivalent weight of the impulsive component of the stored liquid

tanh 0.866  
D

Wi :=
 HL 
 WL Wi = 1460  kip (Eqn. 9-15)
D
0.866 
HL

Wc = Equivalent weight of the convective component of the stored liquid

 D  HL  
Wc :=  0.230   tanh 3.68     WL Wc = 2340  kip (Eqn. 9-16)
 HL  D 

Calculate Effective Mass Coefficient, e ACI 350.3-06


Section 9.6.2
  - 0.1908  D + 1.021
2
ε := min1 , 0.0151  
D
 ε = 0.575 (Eqn. 9-45)
  HL  HL 

Calculations 04. 2016 CBC - Hydrodynamic Loading - circular tank_non-flexible base.xmcd


Page 2 of 10 PF - #.#.#