Академический Документы
Профессиональный Документы
Культура Документы
Wall-frame Buildings
1
Associate Professor, Department of Architectural Engineering, Kangwon National University, Korea
2
Graduate Student, Department of Architectural Engineering, Kangwon National University, Korea
Abstract
Korean seismic design practice for ordinary reinforced concrete wall-frame buildings is similar to but a
little different from the equivalent lateral force design procedure per ASCE 7. The specific feature of the
Korean practice is not to separate the walls and frames into an independent structural system, but to analyze
and design them simultaneously, while they are separated and then analyzed and designed individually if
following ASCE 7. Therefore, the Korean practice is assessed by using the performance evaluation procedure
presented in FEMA P695. The results showed that the Korean design practice is not always applicable to
all RC wall-frame buildings with ordinary shear walls. This negative result is due to a significant reduction
in the design moment of the walls. The reduced moment makes the thickness and vertical reinforcement of
walls designed by the Korean practice significantly smaller than those by ASCE 7, while the frame member
sizes are similar. If structural engineers want to keep using the same design practice, appropriate methods to
offset the significant reduction in the design moment should be incorporated such as reducing the R-factor or
limiting reduction in the design moment.
Keywords: wall-frame building; RC shear wall; seismic design; low-rise RC building; seismic performance
(4)
Fig.8. Example of Incremental Dynamic Analysis for KDP-4m
evaluation has been conducted by checking only the By substituting the variables in Eq. (4) for the values
R-factor used for the design of the buildings even described above, βTOT values for the BFS and KDP are
though the procedure in FEMA P695 may also evaluate 0.612 and 0.726, respectively; these values are used to
the overstrength factor and deflection amplification estimate the acceptable values of the ACMR.
factor. 6.2 Evaluation of R
6.1 Evaluation of Total System Collapse Uncertainty Performance evaluation results for the example
When determining collapse capacity, there inherently buildings are presented in Table 4. As described in
exist various sources of uncertainty contributing to Chapter 3, the appropriateness of the R-factor is
its variability. The larger the variability, the larger the determined by checking the ACMR and ACMR10%.
collapse margin ratio. Therefore, it is significant to The ACMR10% is determined to be 2.20 and 2.53 for
consider all likely sources of uncertainty in determining the BFS and KDP, respectively, based on Table 7-3 in
the collapse. FEMA P695 presents four different FEMA P695. As they depend on the βTOT, the value of
sources of uncertainties: Record-to-record uncertainty acceptable collapse probability for the KDP is larger
(RTR), Design requirement uncertainty (DR), Test data than that for the BFS. That is to say, the ACMR for the
uncertainty (TD), and Modeling uncertainty (MDL). KDP needs to be larger than that for the BFS to achieve
RTR is attributed to variability in the response of acceptable performance.
buildings to different ground motion records. FEMA As presented in Table 4., KDP-4m only fails to
P695 suggests a fixed value of RTR, βRTR = 0.40, which satisfy the criterion because the ACMR is relatively
is assumed for systems with the period-based ductility, low while ACMR10% is relatively high. As can be seen
μT ≥3. For systems with μT <3, values of RTR can be in Table 2. and Table 3., the thickness and vertical
reduced based on the following equation: reinforcement of walls in KDP-4m are significantly
smaller than those in BFS-4m, while frame member
(3) sizes are similar, which is the main cause for the failure
where βRTR must be greater than or equal to 0.20. The of KDP-4m. This result indicates that the Korean
period-based ductility for the KDP is over 3.0, so βRTR design practice, which analyzes and designs the walls
of 0.40 is used, while that for the BFS is around 2.0, so and frames simultaneously but uses the seismic design
βRTR of 0.30 is calculated using Eq. (3). parameters corresponding to the BFS in ASCE 7, is not
DR is related to the completeness and robustness of always applicable to every wall-frame building with
the design requirements. For the two design options, ordinary RC shear walls.
different levels of rating are assumed, which are "good"
and "fair" for the BFS and KDP, respectively. The KDP 7. Conclusion
is relatively low complete, robust, and confident as The Korean design practice for ordinary RC wall-
compared to the BFS. The resulting βDR values are 0.20 frame buildings is assessed by using the performance
and 0.35 for the BFS and KDP, respectively. evaluation procedure presented in FEMA P695. The
Table 4. Results of Performance Assessment of the Example Buildings per FEMA P695
Type SMT (g) ŜCT (g) CMR μT SSF ACMR ACMR10% Decision
BFS-4m 0.75 1.80 2.40 2.2 1.06 2.54 2.20 Pass
KDP-4m 0.75 1.60 2.13 4.2 1.09 2.33 2.53 Fail
BFS-6m 0.75 1.73 2.40 2.1 1.06 2.44 2.20 Pass
KDP-6m 0.75 2.00 2.67 4.1 1.09 2.91 2.53 Pass
References
1) AIK (Architectural Institute of Korea). (2016) Korean building
code – Structural. Seoul: AIK.
2) ASCE 41. (2013) Seismic retrofit of existing buildings. Reston,
Virginia: American Society of Civil Engineers.
3) ASCE 7. (2010) Minimum design loads for buildings and other
structure. Reston, Virginia: American Society of Civil Engineers.
4) Atalay, M.B., Penzien, J. (1975). The seismic behavior of critical
regions of reinforced concrete components as influenced by
moment, shear and axial force. Report No. EERC 75-19. Berkeley:
University of California.
5) Dazio, A., Beyer, K., and Bachmann, H. (2009) Quasi-static cyclic
tests and plastic hinge analysis of RC structural walls. Engineering
Structures, 31 (7), pp.1556-1571.
6) F E M A P695. (2009) Q u a n t i f i c a t i o n o f b u i l d i n g s e i s m i c
performance factors. Washington D. C.: Federal Emergency
Management Agency.
7) Lynn, A. (1999) Seismic evaluation of existing reinforced concrete
building columns. Ph.D. Thesis. Berkley, California: University of
California at Berkeley.
8) Massone, L.M., Bonelli, P., Lagos, R., Lüders, C., Moehle, J.,
Wallace, J.W. (2012) Seismic design and construction practices for
RC structural wall buildings. Earthquake Spectra, 28 (S1), S245–
S256.
9) Nosho, K., Stanton, J., MacRae, G. (1996) Retrofit of rectangular
reinforced concrete columns using tonen forca tow sheet carbon
fiber wrapping. Report No. SGEM 96-2. Seattle, Washington:
Department of Civil Engineering, University of Washington.
10) Oesterle, R.G., Fiorato, A.E., Johal, L.S., Carpenter, J.E., Russell,
H.G., Corley, W.G. (1976) Earthquake resistant structural walls
– tests of isolated walls. Report to National Science Foundation.
Skokie, Illinois: PCA Construction Technology Laboratories.