GUARANTEED TECHNICAL PARTICULAR FOR 145 KV TRANSFORMER CT

Sr. Particular Requirement


No.
1 Application 1) Applicable standard shallOutdoor
be mentioned in the
Type Oil GTP.Live Tank
Cooled,
2. Type of Mounting 2) Vendor to comply local utility requirement
Pedestal Type if any.
3. Design 3) CT & PT shall be suitableOilfor hotline
Filled Livewashing.
Tank
4) All ferrous part exposed to atmosphere shall be hot dip galvanized.
4. Nominal System Voltage 132 KV
5) CT & PT burdon shall be considered as per approved CT PT sizing
5. Highest System Voltage calculation. 145 KV
6. Rated System Frequency / Phases 6) Add the following in accessories
50 Hz / fitting details for CT & PT:
7. Type of Earthing a) Rating and diagram plateEffectively earthed
8. No. of phase for CT’s b) Two earth pads Single Phase
9. No. of Secondary windings c) Lifting lugs Five
10. Core Detail 7) Oil shall be of Apar/SavitaCore
make.1 Core 2 Core 3 Core 4 Core 5
8) CT shall have the provision for the tan delta measurement .
CT Ratio 200/1A 200/1A 200/1A 200/1A 200/1A
11. Rated Secondary Current 1A 1A 1A 1A 1A
12. Class of accuracy of each secondary winding PS 0.2S PS PS PS
13. Rated Burden of each secondary winding NA 20 NA NA NA
14. Accuracy Limit Factor (ALF/ISF) NA <5 NA NA NA
15. Min. Knee Point Voltage ≥500V NA ≥500V ≥500V ≥500V
16. Max Exciting Current at Vk/4 30mA NA 30mA 30mA 30mA
17. Resistance 2.5 Ω NA 2.5 Ω 2.5 Ω 2.5 Ω
15. Maximum Current ratio error Within limits as per IS 2705/1992 (Latest Amendment)
16. Maximum phase angle displacement error Within limits as per IS 2705/1992 (Latest Amendment)
17. Rated Continuous thermal current 120% of highest current rating
18. Rated short time thermal current of primary for 1 sec. 31.5 KA rms
19. Rated Dynamic withstand current of primary (KA peak) 78.75 KA peak
20. Temperature category 50OC Max
21. Maximum temperature rise at rated continuous thermal Within limits as per IS 2705/1992 (Latest Amendment)
current at rated frequency and with rated burden over
maximum ambient temperature of 50 deg C
22. Insulation Class A Class
23. Rated insulation level for primary winding
i. 1.2/50 µS impulse withstand voltage 650 KV peak
ii. One minute power frequency withstand voltage 275 KV rms
24. One minute power frequency withstand voltage test for
secondary winding
i. Each secondary winding to earth 3 KV rms
ii. Between secondary winding 3 KV rms
25. Acceptable partial discharge level 1.1 times the rated Less than 10 pico coulombs
voltage
26. Tangent of loss angle at rated frequency and rated voltage Not more than 0.005
27. Minimum creepage distance of porcelain housing 3625 mm
28. Tank Light Grey Paint
29. Safety devices / accessories / fittings to be provided a. Pressure Relief Cum Oil Filling Device
b. Oil level indicator
c. Nitrogen blanket for hermetical sealing
d. Weather proof secondary terminal box with
sealing arrangement
30. Insulating Oil used EHV grade oil and as per IS 335
GUARANTEED TECHNICAL PARTICULAR FOR 145 KV LINE CT
Sr. Particular Requirement
No.
1 Application Outdoor Type Oil Cooled, Live Tank
2. Type of Mounting Pedestal Type
3. Design Oil Filled Live Tank
4. Nominal System Voltage 132 KV
5. Highest System Voltage 145 KV
6. Rated System Frequency / Phases 50 Hz
7. Type of Earthing Effectively earthed
8. No. of phase for CT’s Single Phase
9. No. of Secondary windings Five
10. Core Detail Core 1 Core 2 Core 3 Core 4 Core 5
CT Ratio 200-400 200-400 200-400 200-400 200-400
11. Rated Secondary Current 1A 1A 1A 1A 1A
12. Class of accuracy of each secondary winding PS 0.2S PS PS PS
13. Rated Burden of each secondary winding NA 20 NA NA NA
14. Accuracy Limit Factor (ALF/ISF) NA <5 NA NA NA
15. Min. Knee Point Voltage ≥500V NA ≥500V ≥500V ≥500V
16. Max Exciting Current at Vk/4 30mA NA 30mA 30mA 30mA
17. Resistance 2.5 Ω NA 2.5 Ω 2.5 Ω 2.5 Ω
15. Maximum Current ratio error Within limits as per IS 2705/1992 (Latest Amendment)
16. Maximum phase angle displacement error Within limits as per IS 2705/1992 (Latest Amendment)
17. Rated Continuous thermal current 120% of highest current rating
18. Rated short time thermal current of primary for 1 sec. 31.5 KA rms
19. Rated Dynamic withstand current of primary (KA peak) 78.75 KA peak
20. Temperature category 50OC Max
21. Maximum temperature rise at rated continuous thermal Within limits as per IS 2705/1992 (Latest Amendment)
current at rated frequency and with rated burden over
maximum ambient temperature of 50 deg C
22. Insulation Class A Class
23. Rated insulation level for primary winding
i. 1.2/50 µS impulse withstand voltage 650 KV peak
ii. One minute power frequency withstand voltage 275 KV rms
24. One minute power frequency withstand voltage test for
secondary winding
i. Each secondary winding to earth 3 KV rms
ii. Between secondary winding 3 KV rms
25. Acceptable partial discharge level 1.1 times the rated Less than 10 pico coulombs
voltage
26. Tangent of loss angle at rated frequency and rated voltage Not more than 0.005
27. Minimum creepage distance of porcelain housing 3625 mm
28. Tank Light Grey Paint
29. Safety devices / accessories / fittings to be provided a. Pressure Relief Cum Oil Filling Device
b. Oil level indicator
c. Nitrogen blanket for hermetical sealing
d. Weather proof secondary terminal box with
sealing arrangement
30. Insulating Oil used EHV grade oil and as per IS 335
GUARANTEED TECHNICAL PARTICULAR FOR 145 KV METER CT
Sr. Particular Requirement
No.
1 Application Outdoor Type Oil Cooled, Live Tank
2. Type of Mounting Pedestal Type
3. Design Oil Filled Live Tank
4. Nominal System Voltage 132 KV
5. Highest System Voltage 145 KV
6. Rated System Frequency / Phases 50 Hz
7. Type of Earthing Effectively earthed
8. No. of phase for CT’s Single Phase
9. No. of Secondary windings Two
10. Core Detail Core 1 Core 2
CT Ratio 200-400/1A 200-400/1A
11. Rated Secondary Current 1A 1A
12. Class of accuracy of each secondary winding 0.2S 0.2S
13. Rated Burden of each secondary winding 20 20
14. Instrument Security Factor (ISF) <5 <5
15. Min. Knee Point Voltage NA NA
16. Max Exciting Current at Vk/4 NA NA
17. Resistance NA NA
15. Maximum Current ratio error Within limits as per IS 2705/1992 (Latest
Amendment)
16. Maximum phase angle displacement error Within limits as per IS 2705/1992 (Latest
Amendment)
17. Rated Continuous thermal current 120% of highest current rating
18. Rated short time thermal current of primary for 1 sec. 31.5 KA rms
19. Rated Dynamic withstand current of primary (KA peak) 78.75 KA peak
20. Temperature category 50OC Max
21. Maximum temperature rise at rated continuous thermal Within limits as per IS 2705/1992 (Latest
current at rated frequency and with rated burden over Amendment)
maximum ambient temperature of 50 deg C
22. Insulation Class A Class
23. Rated insulation level for primary winding
i. 1.2/50 µS impulse withstand voltage 650 KV peak
ii. One minute power frequency withstand voltage 275 KV rms
24. One minute power frequency withstand voltage test for
secondary winding
i. Each secondary winding to earth 3 KV rms
ii. Between secondary winding 3 KV rms
25. Acceptable partial discharge level 1.1 times the rated Less than 10 pico coulombs
voltage
26. Tangent of loss angle at rated frequency and rated voltage Not more than 0.005
27. Minimum creepage distance of porcelain housing 3625 mm
28. Tank Light Grey Paint
29. Safety devices / accessories / fittings to be provided a. Pressure Relief Cum Oil Filling Device
b. Oil level indicator
c. Nitrogen blanket for hermetical sealing
d. Weather proof secondary terminal box with
sealing arrangement
30. Insulating Oil used EHV grade oil and as per IS 335
GUARANTEED TECHNICAL PARTICULAR FOR 145 KV BUS PT
Sr. No. Particular Requirement
1 Application Outdoor Type Oil Cooled
2. Type of Mounting Pedestal Type
3. Nominal System Voltage 132 KV
4. Highest System Voltage 145 KV
5. Rated System Frequency / Phases 50 Hz
6. Type of Earthing Effectively earthed
7. No. of phase for PT’s Single Phase
8. No. of Secondary windings Three
9. Transformation Ratio
i. Winding I, II & III 132KV/√3/110V/√3-110V/√3-110V/√3
10. Rated Secondary Voltage
i. Winding I, II & III 110/√3 V
11. Class of accuracy of each secondary winding
i. Winding I, II & III 3P-3P-0.2
12. Rated Burden of each secondary winding
i. Winding I, II & III 30 VA
13. Maximum Voltage ratio error Within limits as per IS 3156/1992
14. Maximum phase angle displacement error Within limits as per IS 3156/1992
15. Voltage Factor 1.2 continuous 1.5 for 30 seconds
16. Temperature category 50OC Max
17. Maximum temperature rise (Limits of Within limits as per IS 3156/1992
temperature rise of winding)
18. Rated insulation level
i. 1.2/50 µS impulse withstand voltage 650 KV peak
ii. Induced Over voltage withstand test 275 KV rms
19. One minute power frequency test
i. withstand voltage between low 3 KV rms
voltage terminal & earth terminal
ii. withstand voltage for secondary 3 KV rms
winding
20. Minimum creepage distance of porcelain 3625 mm (min)
housing
21. Tank Light Grey Paint
22. Safety devices / accessories / fittings to be a. Pressure Relief Cum Oil Filling Device
provided b. Oil level indicator
c. Nitrogen blanket for hermetical sealing
d. Weather proof secondary terminal box with
sealing arrangement
23. Insulating Oil used EHV grade oil and as per IS 335
24. Insulation Class A Class
GUARANTEED TECHNICAL PARTICULAR FOR 145 KV METER PT
Sr. No. Particular Requirement
1 Application Outdoor Type Oil Cooled
2. Type of Mounting Pedestal Type
3. Nominal System Voltage 132 KV
4. Highest System Voltage 145 KV
5. Rated System Frequency / Phases 50 Hz
6. Type of Earthing Effectively earthed
7. No. of phase for PT’s Single Phase
8. No. of Secondary windings Two
9. Transformation Ratio
i. Winding I & II 132KV/√3/110V/√3-110V/√3
10. Rated Secondary Voltage
i. Winding I & II 110/√3 V
11. Class of accuracy of each secondary winding
i. Winding I & II 0.2- 0.2
12. Rated Burden of each secondary winding
i. Winding I & II 10 VA
13. Maximum Voltage ratio error Within limits as per IS 3156/1992
14. Maximum phase angle displacement error Within limits as per IS 3156/1992
15. Voltage Factor 1.2 continuous 1.5 for 30 seconds
16. Temperature category 50OC Max
17. Maximum temperature rise (Limits of Within limits as per IS 3156/1992
temperature rise of winding)
18. Rated insulation level
i. 1.2/50 µS impulse withstand voltage 650 KV peak
ii. Induced Over voltage withstand test 275 KV rms
19. One minute power frequency test
i. withstand voltage between low 3 KV rms
voltage terminal & earth terminal
ii. withstand voltage for secondary 3 KV rms
winding
20. Minimum creepage distance of porcelain 3625 mm (min)
housing
21. Tank Light Grey Paint
22. Safety devices / accessories / fittings to be a. Pressure Relief Cum Oil Filling Device
provided b. Oil level indicator
c. Nitrogen blanket for hermetical sealing
d. Weather proof secondary terminal box with
sealing arrangement
23. Insulating Oil used EHV grade oil and as per IS 335
24. Insulation Class A Class