Page: 1 / 10
Eurovent classification
Cooling (EER) : A
SELECTED MOUNTING
I / S = Discharge
R = Return
E = Air extraction
N / F = Fresh air
No.
Dated: 12/13/2018
Page: 2 / 10
OPERATING CONDITIONS
SUMMER OPERATION
Outdoor Air: 35.0 0C / 40 %(RH) / 23.9 0C(WB) / 14.1 g/kg Dry air
Return air: 26.0 0C / 50 %(RH) / 18.7 0C(WB) / 10.5 g/kg Dry air
Mixed air : 28.2 0C / 48 %(RH) / 20.1 0C(WB) / 11.4 g/kg Dry air
Evaporator outlet air : 15.2 0C / 93 %(RH) / 14.6 0C(WB) / 10.1 g/kg Dry air
Supply air : 15.9 0C / 90 %(RH) / 14.8 0C(WB) / 10.1 g/kg Dry air
WINTER OPERATION
Outdoor Air: 6.00 0C / 90 %(RH) / 5.27 0C(WB) / 5.2 g/kg Dry air
Return air: 20.0 0C / 50 %(RH) / 13.8 0C(WB) / 7.3 g/kg Dry air
Mixed air : 16.4 0C / 58 %(RH) / 11.8 0C(WB) / 6.7 g/kg Dry air
Condenser outlet air : 16.4 0C / 58 %(RH) / 11.8 0C(WB) / 6.7 g/kg Dry air
Supply air : 17.0 0C / 56 %(RH) / 12.1 0C(WB) / 6.7 g/kg Dry air
COMPLETE PERFORMANCE
SUMMER OPERATION
Gross cooling capacity: 159.6 kW
Gross sensible cooling capacity: 127.7 kW
Total cooling capacity output : 152.9 kW
Sensible cooling capacity output : 121.1 kW
Compressor power input: 43.1 kW
Total input power : 60.0 kW
EER (EN 14511-2018) : 2.84
EER (EN 14511-2013) : 2.69
EXTERNAL SECTION
Number of fan(s) : 4
Air flow : 55,000 m3/h
Total motor(s) power : 3.56 kW
Error! Reference source not found. Error! Reference source not found.
No.
Dated: 12/13/2018
Page: 3 / 10
Error! Reference source not found. Error! Reference source not found.
No.
Dated: 12/13/2018
Page: 4 / 10
Dimension drawings
Chimney NOT SUPPLIED. Please, check dimensions in technical documentation.
Error! Reference source not found. Error! Reference source not found.
No.
Dated: 12/13/2018
Page: 5 / 10
Error! Reference source not found. Error! Reference source not found.
No.
Dated: 12/13/2018
Page: 6 / 10
Error! Reference source not found. Error! Reference source not found.
No.
Dated: 12/13/2018
Page: 7 / 10
Description Quantity
50EN 650V R410A MC11 1
Error! Reference source not found. Error! Reference source not found.
No.
Dated: 12/13/2018
Page: 8 / 10
TECHNICAL DESCRIPTION
ROOF TOP
Unit in accordance with the following European regulations and directives :
• Machinery Directive 2006/42/EC (MD)
• Electromagnetic Compatibility Directive 2014/30/EU (EMC)
• Low Voltage Directive 2014/35/EU (LVD)
• Pressure Equipment Directive 2014/68/EU (Categoría 2) (PED)
• RoHS Directive 2011/65/EU (RoHS)
• Harmonised Standard: EN 378-2:2012
MAIN COMPONENTS
Unit with hermetic Scroll compressor(s)
Internal protection of windings
Oil crankcase heater
Thermostatic expansion valve
Dryer
Cycle reverse valve (reversible range)
Pressure pick-ups for HP and LP manometers
Anticorrosion casing in galvanized sheet metal covered with polyester and varnish base lacquer
Removable electrical panel and filter access panels
Outdoor and indoor coil and with corrugated aluminium fins and copper tube,
Option selected: Plug fan supply air fan(s), EC motors with PID electronic control, for constant air
flow applications, with soft start. The operating point is adjusted by a rotary switch, and an air flow
rate sensor (analogue signal) adjusts the operating point to take account of filter fouling and
optimise filter service life.
Centrifugal return fan, belt driven by a motor on an adjustable base (standard).
Option selected : High performance Outdoor propeller electronic fans with EC motor, with speed managed by
the control for a better seasonal performance and with protection grilles
Automatic changing of outdoor fan speed as a function of the condensing or evaporating pressure.
Filters G4 (standard) with metal frame, M1 fire classification
Main safety switch
Protections of fans and circuits by circuit breakers
Electrical panel with wiring under channel, conforms to NF C 15-100 and EN 60204
Acoustic cover(s) on compressor( s)
Phase control relay (standard) to control phase sequence and phase loose.
CARRIERrtc REGULATION
• LCD screen (PGD1) in the electrical cabinet,
• Heating, cooling, free cooling, extraction, air quality regulation,
• Compatible with all the sizes and optional mountings,
• Anti-short cycle,
• Defrosting (reversible range): DEGIPAC (indirect detection of frosting).
• Control of ambient temperature and supply temperature,
• All seasons pressure control :
• - Cooling mode : condensation pressure control in winter,
• - Heating mode : evaporation pressure control in summer.
• Compressor discharge temperature protection,
• Anti-fire safety device.
• Air temperature sensor : outdoor, return, ambient (NTC by default, with communication RS485 as
an option for wire distances higher than 30m) and supply,
• Control with ambient temperature and anti-stratification function.
Error! Reference source not found. Error! Reference source not found.
No.
Dated: 12/13/2018
Page: 9 / 10
Control and display functions for maintenance of the standard terminal (PGD1)
• Access to parameter for commissioning,
• Different levels of parameter access (by password) : visualization and modification,
• Set point modification,
• Selection on/off, heating, cooling,
• Programming clock : it allows daily and weekly programming of the air conditioner operation.
• Display alarms with description,
• Control without PGD display : Several units may be interconnected (pLAN) with the CARRIERrtc
control. A single PGD display is sufficient in this case.
• This terminal is standard (removed by the option “Substitution TCO”), in the option “Kit remote
control PGD1” and in the option “Kit Service tool PGD1”.
EQUIPMENT CHARACTERISTICS
Error! Reference source not found. Error! Reference source not found.
No.
Dated: 12/13/2018
Page: 10 / 10
GAS BURNER
The optional gas burner uses the best in gas technology :
• High-efficiency condensing burner :
• - Efficiency of up to 105% (LHV).
• Premix (fuel and air) :
• AFR (Air-Fuel Ratio): stoichiometric air/fuel mixture over the entire operating range :
• - Perfect combustion,
• - Zero carbon monoxide,
• - Much lower NOx emission.
• Modulation range : 30-100% (On/Off below 30%) :
• - Adjustment to need,
• - High level of comfort.
• Destratification System :
• - Increased comfort,
• - Reduced heat losses through roof,
• - Reduced gas consumption
The optional smoke detector, filter restriction detection system, and fire thermostat are always
delivered with the gas option.
UNIT STRUCTURE
• Frame and casing made of panels coated with light grey (RAL 7035) polyurethane paint,
• Designed for better visual integration.
• Hinges for access panels (except for models 90 to 180)
Error! Reference source not found. Error! Reference source not found.