Вы находитесь на странице: 1из 1

#REF!

AHU Ventilation Calculations


Design case
Zone Identification Standard Case: ASHRAE 62.1-2004 Ventilation Rate Procedure (Multiple Zone Recirculating Systems

Breathing
Outdoor Air Outdoor Air Table 6-2 Zone Table 6-3
Table 6-1 Zone Floor Rate Rate Required Zone Zone Zone Air Outdoor System Outdoor 30 ‰ percentage
Area Population Outdoor Air Intake supply Voz/30‰ of Maixmum Required
Zone Occupancy Required Per Unit Area Distribution Airflow Ventilation of supply Fraction
(Az) (Pz) Airflow Flow air supply air fraction out door air
Category Per Person (Ra) Effectiveness (Voz) Efficicncy air
(Vbz) (Vot)
(Rp) (Ez) (Ev)

(m^2) (l/s/person) (l/s/m^2) (people) (l/s) (l/s) (l/s) (l/s) (l/s) (l/s)
spacc 1(office) office 30 2.5 0.3 5 21.5 0.7 30.71 0.8 38.39 300 90 0.30 0.13 0.27 81
spacc 2(workstation work station 50 2.5 0.3 8 35 0.7 50.00 0.8 62.50 200 60 0.30 0.31 0.27 54
spacc 3(meeting room) meeting room 70 2.5 0.3 7 38.5 0.7 55.00 0.8 68.75 400 120 0.30 0.17 0.27 108

150 95 135.71 169.64 900 243

maximum fraction 0.27

Вам также может понравиться