Вы находитесь на странице: 1из 1

SAUDI ARAMCO ID/PIEU -3- July-2018 - REV. 2018.04.00 (Standards Cutoff -April 30, 2018) Rev. 2018.04.

00 30-Apr-18
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Receiving Inspection of Power Piping & Auxillaries SAIC-F-2022 3-Jul-18 MECH-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME

SAUDI ARAMCO USE ONLY


SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

A General:

Damage was avoided during shipment, to all instruments and valves, 32-SAMSS-021,
A1
including auxiliary systems. Para. 25.1.5

All exposed finished and machined surfaces, including bolts, are coated 32-SAMSS-021,
A2
with a rust-inhibiting compound. Para. 25.1.6

Bearings and seal assemblies are fully protected against the entry of 32-SAMSS-021,
A3
moisture and dirt. Para. 25.1.7

Flanged connections and all other machined surfaces are protected by a 32-SAMSS-021,
A4
coating, such as MIL-C-16173 Grade IV. Para. 25.1.8

Flanges are fitted with a steel or wood cover, 3 mm thick and neoprene 32-SAMSS-021,
A5
gaskets. Para. 25.1.8

32-SAMSS-021,
A6 Threaded connections are protected with threaded plugs.
Para. 25.1.12

SAEP-385 Table
Pipe shall not be stored directly on the ground, Pipe shall be placed on
A7 2001 General
mounds or sleepers (SAES-L-350, Section 7)
Requirements 13

SAEP-385 Table
End protectors on pipes, flanges, weld bevels, threads, and socket ends
A8 2001 General
shall be firmly attached (SAES-L-350, paragraph 7.4)
Requirements 14

Bare and coated stainless steel pipe material shall be protected against SAEP-385 Table
A9 exposure to seawater splash during shipment and storage (SAES-L-350, 2001 General
paragraph 7.5) Requirements 15

C. Packing:

02-SAMSS-005,
C1 All fittings must be protected from mechanical damage.
Para. 10.5

Welding ends must be protected with suitable wood, plastic, or metal 02-SAMSS-005,
C2
covers. Para. 10.5

Fittings must be packaged in steel-banded wooden crates or secured to 02-SAMSS-005,


C3
skids. Para. 10.5

Saudi Aramco: Company General Use