PROJECT TITLE
VIETNAM OIL AND GAS GROUP (PVN) FICHTNER GmbH & Co. KG PV ENGINEERING
PJT_345 RELAY
PROTECTION CALCULATION
2019.09
Calculation Cover Sheet
Method of Checking
Rev No.
Description
Checking
Result
Remarks
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
Table of Contents
1. INTRODUCTION ………………………………………………………………………………… 3
2. REFERENCES ……………………………………………………………………………………… 3
2 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
1. INTRODUCTION
The purpose of this calculation is to determine the relay settings for the protective relays associated with excitation
transformer of the Vietnal Songhau.
2. REFERENCES
2.1 IEEE Std. 242-2001 : IEEE Recommended Practice for Protection and Coordination of Industrial and
Commercial Power Systems
2.2 Single Line Diagram for Transformer Protection System
2.3 Schematic Diagram for Transformer Protection System
GE digital protection relay SR345 provide excitation transformer protecion. The SR345 has one diff-
erential(87T/87I) element, one instantaneous overcurrent (50) element as backup protection for primary winding
phase fault, two time overcurrent (51) element as backup protection for the transforemer.
The 87T should protect transformer internal fault when fault current is bigger than minimum differential pickup
current. The setting of minimum differential pickup (87T) should be considered CT mismatch, relay error(5%),
safety margin (5%) and NLTC tolerance(5%). The instantaneous differential (87I) does not have to operate during
transformer inrush condition and external fault current. The pickup of 87I could be set to 150% of the Inrush current
of the transformer to prevent misoperation.
The Phase IOC (50) does not have to operate during transformer inrush condition and external fault current which
is three phase fault current of transformer secondary. The IOC would detect minimum phase fault current of excitation
primary winding.
The Phase TOC (51) must protect phase fault and overload of excitation transforemr. The pickup is set to 150% of the
rated current of excitation transformer. This will provide overload and short circuit protection for the transformer.
3 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
4. INPUT DATA
The protective relays to be applied are as follows.
4 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
5. Protection Calculation
5 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
6 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
Item Setting
Transformer Rated Load 6.50MVA
Transformer Type Y/d330°
Phase Compensation Internel (Software)
Winding 1 Nominal Voltage 22.00kV
Winding 1 Grounding Not Within zone
Winding 2 Nominal Voltage 0.950kV
Winding 2 Grounding Not Within zone
4) Calculation of the Reference Winding
This is based on the reference of pick up current for percent differencial.
7 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
8 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
9 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
10 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
11 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
𝐾 I I
T TDM if, 20, 20
I I I
1
I
K = 13.50 , E = 1, T = 0.10sec
TDM = 0.07
F) Phase TOC1 Reset : Instantaneous
G) Phase TOC1 Relays : Relay 3
12 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
𝐾 I I
T TDM if, 20, 20
I I I
1
I
K = 13.50 , E = 1, T = 0.10sec
TDM = 0.07
F) Phase TOC2 Reset : Instantaneous
G) Phase TOC2 Relays : Relay 4
13 of 14
PROTECTION CALCULATIONS AND SETTINGS Rev No : 0
D. Coordination Curve
1) OCR
14 of 14