MEASUREMENT BOOK
C.M.B.NO. /FWRCT/MCED-III/2017-18
Name of work: Construction of Institute and hostel building
(New Institutional complex) of Family Welfare Training and Research Center (FWTRC), At
New Panvel, Navi-Mumbai including internal water supply, sanitary installation, drainage,
development work, Internal electrical installation,Automatic fire alarm system,Down comer
system,SITC of VRF Type Air conditioning, D.G. set, Sub station, pump set, street light, Passenger
Lift & Solar water heating system etc. (BALANCE WORK)
Review Notes
By officer of Department
1.By Superior Officer of the Department
Fan Points
Ground Floor
Room No. 1 (Room + Toilet) 3 1 1 5 Nos.
Room No. 2 (Room + Toilet) 3 1 1 5 Nos.
Room No. 3 (Room + Toilet) 3 1 1 5 Nos.
Room No. 4 (Room + Toilet) 3 1 1 5 Nos.
Room No. 5 (Room + Toilet) 3 1 1 5 Nos.
Room No. 6 (Room + Toilet) 3 1 1 5 Nos.
Room No. 7 (Room + Toilet) 3 1 1 5 Nos.
Room No. 8 (Room + Toilet) 3 1 1 5 Nos.
Room No. 9 (Room + Toilet) 3 1 1 5 Nos.
Room No. 10 (Room + Toilet) 3 1 1 5 Nos.
Room No. 11 (Room + Toilet) 3 1 1 5 Nos.
Watchman Room (Room + Toilet) 3 1 1 1 6 Nos.
Warden Room (Room + Toilet) 3 1 1 1 6 Nos.
Passage and Corridors 4 1 5 Nos.
Sub-Total (Ground Floor) 72 Nos.
First Floor
Room No. 1 (Room + Toilet) 3 1 1 5 Nos.
Room No. 2 (Room + Toilet) 3 1 1 5 Nos.
Room No. 3 (Room + Toilet) 3 1 1 5 Nos.
Room No. 4 (Room + Toilet) 3 1 1 5 Nos.
Room No. 5 (Room + Toilet) 3 1 1 5 Nos.
Room No. 6 (Room + Toilet) 3 1 1 5 Nos.
Room No. 7 (Room + Toilet) 3 1 1 5 Nos.
Room No. 8 (Room + Toilet) 3 1 1 5 Nos.
Room No. 9 (Room + Toilet) 3 1 1 5 Nos.
Room No. 10 (Room + Toilet) 3 1 1 5 Nos.
Room No. 11 (Room + Toilet) 3 1 1 5 Nos.
Room No. 12 (Room + Toilet) 3 1 1 5 Nos.
Room No. 13 (Room + Toilet) 3 1 1 5 Nos.
Room No. 14 (Room + Toilet) 3 1 1 5 Nos.
Passage and Corridors 4 1 5 Nos.
Sub-Total (First Floor) 75 Nos.
Total (Ground Floor + First Floor) 147 Nos.
4) Wiring for circuit/ sub main wiring along with earth wire with the following
sizes of FRLS PVC insulated copper conductor, single core cable in surface/
recessed medium class PVC conduit as required.
b) 6 x 1.5 sq. mm
Hostel Bldg. (Ground Floor)
Room No. 4 and Watchman Room
LDB-1 to SB in Room No. 4 8.80 mtr
Room No 2 and Room No 3
LDB-1 to SB in Room No. 3 11.80 mtr
Room No 7 and Room No 8
LDB-1 to SB 11.80 mtr
Room No. 9 and Room No. 10
LDB-2 to SB 10.70 mtr
Sub-Total (Ground Floor) 43.10 mtr
Hostel Bldg. (First Floor)
Room No 2 and Room No 3
LDB-4 to SB 8.20 mtr
Room No. 4 and Room No. 5
LDB-3 to SB 7.20 mtr
Room No. 8 and Room No. 9
LDB-3 to SB 8.30 mtr
Room No. 10 and Room No. 11
LDB-4 to SB 11.80 mtr
Room No. 12 and Room No. 13
LDB-4 to SB 14.20 mtr
Sub-Total (First Floor) 49.70 mtr
Total (Ground Floor + First Floor) 92.80 mtr
Notes:-
LDB-1;
Light Ckt - Distribution Box for Ground Floor
LBD-2
LDB-3;
Light Ckt - Distribution Box for First Floor
LBD-4
SB Switch Board for Room
TSB Switch Board for Toilet
R/M Rising Main
PDB-3,
Power Ckt - Distribution Box at First Floor
PDB-4
SB Switch Board for Room
TSB Switch Board for Toilet
R/M Rising Main
Sub work:-I
Sub Head : SITC of passenger lift.
Sub work:- E
SH:- Supplying, Installation, testing, commissioning of 11 KV substation equipments.
PR 1247521.00 1,247,521.00
Item No. Description of Item Qty Unit Rate Up to date
FR 1559401.00
SUB-HEAD II : MV EQUIPMENT
Main Board
1 (L.T. panels)
Supplying of Indoor floor mounted modular type,
sectionalized, compartmentalized, extendable type
MV cubical panel having 35 MVA breaking
capacity of suitable size fabricated from CRCA
sheet steel of 2.5 mm thick for frame work, 2 mm
thick for enclosure, 1.6 mm thick for doors, top
covers and partitions with stiffeners wherever
required, having vibration free structure chemically
treated with seven tank process before painting for
surface treatment, epoxy powder coated, with
suitable electrolytic grade high conductivity copper
bus bar extensible type, suitable for operation on 3
phase 415 V 50 HZ AC supply i/c providing and
fixing the following switchgear mounted thereon
complete with gaskets and interconnections as per
specifications complete as required. ( The board
shall be dust & vermin proof with degree of
protection of IP 52 as per IS : 2147, free standing
type, mounted on base channel of ISMC - 75)
4) Busbar Ratings
a) Section - I : 630 Amps tinned Copper Busbar (50
kA) (100% Neutral)
b) Section - II : 630 Amps tinned Copper Busbar (50
kA) (100% Neutral) 1 set
PR 1384650.00 1,384,650.00
FR 1730813.00
B/F CMB 196/Page No.
B) Essential Panel
1) Incoming :
a) 400A FP 36KA MCCB MOCROPROCESSOR
BASED RELEASE O/L & S/C PROTECTION
WITH SPREADER LINK, ROHM & MECHANICAL
KEY INTERLOCK - 2 Nos
b) ON/OFF INDICATION LAMP 230 V AC -2 Nos
c) DIGITAL AMMETER WITH INBUILT SELECTOR
SWITCH - 2 Nos
d) 400/5A CT's CL 1.0 15VA - 6 Nos
e) (0/500V ) DIGITAL VOLTMETER WITH INBUILT
SELECTOR SWITCH - 2 Nos
f) 2A HRC CONTROL FUSE - 14 Nos
g) R/Y/B PHASE INDICATION LAMP 230V AC - 2
Nos
2) OUTGOING
a) 200A FP 36KA MCCB THERMAL MAGNETIC
BASED RELEASE O/L & S/C PROTECTION
WITH SPREADER LINK & ROHM - 1 No
b) 125A FP 36KA MCCB THERMAL MAGNETIC
BASED RELEASE O/L & S/C PROTECTION
WITH SPREADER LINK & ROHM - 2 Nos
c) 63A FP 36KA MCCB THERMAL MAGNETIC
BASED RELEASE O/L & S/C PROTECTION
WITH SPREADER LINK & ROHM- 5 Nos
3) Busbar Ratings
Item No. Description of Item Qty Unit Rate Up to date
400 Amps tinned Copper Busbar (100% Neutral)
1 Set
PR 352862.00 352,862.00
FR 441078.00
B/F CMB 196/Page No.
2 APFC PANELS
a) Supplying of factory built floor mounted auto-
manual power factor correction system of
75KVAR capacity having 3 phase APP Type
heavy duty capacitors self fusing ,self healing resin
bonded terminal in Six steps
{(2+3+5+10+15+20+20)} as per ISI 13585
mounted on suitable arrangement and provided
with Power Contactor. The system shall have
micro processor based power factor controller
provided in the command module having set
points for target P. F setting and digital P. F.
display .The system shall be provided with
required capacity master MCCB, to check its main
operating parameters such as over loads, short
circuit, etc.
Sub work:-G
SH :- Providing Drinking water pump set .
9) Pump Panel.
Item No. Description of Item Qty Unit Rate Up to date
Supplying of suitable size indoor type wall
mounted dust and vermin proof totally enclosed
compartmentalized cubical panel board made out
of 2.0 mm CRCA sheet with stiffeners wherever
required, chemically treated with seven tank
process before painting for surface treatment and
powder coated alongwith Electrolytic grade high
conductivity copper bus bar, detachable gland
plate for top/bottom cable entry, cable alley &
suitable for operation on 3 phase 415 Volts 50
HZ AC supply including providing and fixing the
following switch gears and accessories complete
with all incoming and out going connections,
interconnections with suitable copper wire,
copper lugs and thimbles, earthing the body etc
as required.(Depth 30 cm)
Incoming
a) 63A FP 25KA MCCB THERMAL MAGNETIC BASED
RELEASE O/L & S/C PROTECTION WITH
SPREADER LINK & ROHM - 1 No
b) ON/OFF INDICATION LAMO 230V AC - 1 No
DIGITAL AMMETER WITH INBUILT SELECTOR
c)
SWITCH - 1 No
d) 100/5A CT's CL 1.0 5VA - 3 Nos
(0-500V) DIGITAL VOLTMETER WITH INBUILT
e)
SELECTOR SWITCH - 1 No
f) 2A HRC CONTROL FUSE -7 Nos
Sub work:-C
SH:- Providing Down comer system
Item No. Description of Item Qty Unit Rate Up to date
2 Fabrication, Supply of wall mounted compartmentalized
with hinged lockable doors cubical electrical control
panel of suitable size fabricated from CRCA sheet of 2
mm thick, dust and vermin proof, powder coated of
approved shade after chemically treated with seven tank
process , cable alley, suitable for operation on 3 phase
415 volt 50 Hz AC supply i/c providing and fixing
following switch gear to be mounted on complete with
gaskets, interconnections and earthing etc. as required.
The enclosure protection class shall be of IP 54. Make :
ABAK
Sub work:-I
Sub Head : SITC of passenger lift.
Rs. 12,710,995.00
Rs. 12,710,995.00
Less paid in Last - 2nd RA Bill vide
CMB /FWRCT/MCED-III/2017-18 CV __ pg._ Rs. 9,185,519.00
Net value of work done since previous Rs. 3,525,476.00
Less 8.13% Rs. 286,621.00
Rs. 3,238,855.00
Certified that:
1). The work has been carried out as per CPWD Specifications.
2). No T&P is issued to the contractor.
3). No Labour complaint is recevied so far.
4) The Engineer has been engaged by the contractor as per clause 36.
5) F.N.L.R. has been received from the contractor.
Chargeble to :
2nd RA Bill of M/s. HILLTOP REFRIGERATION
Agreement No.:- 09/CE/WZ- III//EE/MCD VI/CPWD/17-18
Less recoveries
a 5% SD
b 2% Income tax
c 2% WC tax
d 1% Labour cess
Total Recoveries
Net Payable
(Rupees only)
3rd Running Account Bill
(Referred to in paragraph 10-2-10 and 10-2-12)
(Final payments must invariably to be made on forms printed on yellow paper which should not be used for intermediate payments)
(For Contractors – This Form provides for (1) Advance payments and (2) Payments for Measured Works, form of Account Secured advances, which
has been printed separately should be attached should be attached where necessary.)
No. and date of the previous Bill for this work:- 2nd RA Bill
Agreement No.:- 09/CE/WZ- III//EE/MCD VI/CPWD/17-18
Date of Start:- / /2017
11463474
9185519
3525476
Less 8.13% 286621
9185519
2043465
7142054
Less 8.13% 580649
3,238,855 00 3,238,855 00
Figure (F) in words Rs. Twenty Lakh Ninety Two Thousand Seven Hundred Fifty Seven only.
N.B. When there are two or more entries in column 6 relating to each sub-head of estimate they should in the case of works the
accounts of which are kept by sub-heads, be totaled and the total recorded in column 7 for posting the Works Abstract.
1 The measurements on which are based on the entries in columns 1 to 6 of Account 1, were made by
1. Total value of work actually measured, as per Acct. 1 col.5 entry [A] Rs. P
2. Total `up to date’ advance payments for work not yet measured, as details
given below
Rs. P
a) Total as per previous Bill _____ (B)
b) Since previous Bill ___________ as per page of M.B. No.
3. Total `up to date’ secured advances on security of materials, as per Annexure
(Form 26 – A) Col. Entry (C)
4. Total (items 1+2+3+)
5. Deduct amount withheld Rs. P
Figures for
Works abstract 5
Rs. P a) From previous bill as per last Running Account Bill
b) From this Bill
6. Balance i.e “up to date” payments (items 4-5) K
7.Total amount of payments already made as per Entry (K) of last running
(G)
c) By Cheque
Pay: ___________________________ ý 8
_____________________________________(by Chque)
Dated initials of Disbursing Officer
Received Rs. ( )
as per above memorandum, on account of the work.
[amount in vernacular]
. This figures should be tested to see that it agrees with the total of items 7 and 8
If the net amount to be paid is less than Rs. 10 and it cannot be included in a cheque, the payment should be made
. in cash, this entry being altered suitable and the alteration attested by dated initials.
. Here specify the net amount payable vide item 8 (c)
. The payee’s acknowledgement should be or the gross amount paid as per items 8 (i.e.a.b.c.)
Payment should be attestyed by some known person when the payee's acknowledgement given by a mark seal or
. thumb imprression.
IV – REMARKS
This space is reserved for any remarks which the disbursing Officer or the Divisional Officer may wish
to record of the execution of work, check of measurement or the state of contractor’s amount.
Checked
Checked
Reviewed
Sub work:-D
SH : SITC of VRF type Air Conditioning.
1 Supply, Insttaltion, Testing & Commissioning of
VRF outdoor units equipped with highly efficient
100% inverter scroll compressor(s) working on
R-410 A refrigerant. The system shall be suitable
to operate on 3 phase, 380-415 V, 50 Hz AC
supply. The unit shall be compatible with all type
of indoor units like cassettee units, False ceiling
mounted Ductable units & Hiwall Split unit etc.
The unit shall be complete with full charge of
Refrigerant Gas and Oil, MS stand duly painted
Freight & Insurance. The unit should be
capacable to work upto 53 Degree C ambient
temprature. The Unit should have COP value of
3.7 at 100% load and COP Value 5.5 at 50 %
load at ARI Condition.
Sub work:- E
SH:- Supplying, Installation, testing,
commissioning of 11 KV substation equipments.
Main Board
1 (L.T. panels)
Supplying of Indoor floor mounted modular type,
sectionalized, compartmentalized, extendable type
MV cubical panel having 35 MVA breaking
capacity of suitable size fabricated from CRCA
sheet steel of 2.5 mm thick for frame work, 2 mm
thick for enclosure, 1.6 mm thick for doors, top
covers and partitions with stiffeners wherever
required, having vibration free structure chemically
treated with seven tank process before painting for
surface treatment, epoxy powder coated, with
suitable electrolytic grade high conductivity copper
bus bar extensible type, suitable for operation on 3
phase 415 V 50 HZ AC supply i/c providing and
fixing the following switchgear mounted thereon
complete with gaskets and interconnections as per
specifications complete as required. ( The board
shall be dust & vermin proof with degree of
protection of IP 52 as per IS : 2147, free standing
type, mounted on base channel of ISMC - 75)
4) Busbar Ratings
a) Section - I : 630 Amps tinned Copper Busbar (50
kA) (100% Neutral)
b) Section - II : 630 Amps tinned Copper Busbar (50
1 set
kA) (100% Neutral) PR 1,557,732 173,082.00 1,384,650.00
FR 1,730,813
B/F CMB 196/Page No.
B) Essential Panel
1) Incoming :
a) 400A FP 36KA MCCB MOCROPROCESSOR
BASED RELEASE O/L & S/C PROTECTION
WITH SPREADER LINK, ROHM & MECHANICAL
KEY INTERLOCK - 2 Nos
b) ON/OFF INDICATION LAMP 230 V AC -2 Nos
c) DIGITAL AMMETER WITH INBUILT SELECTOR
SWITCH - 2 Nos
d) 400/5A CT's CL 1.0 15VA - 6 Nos
e) (0/500V ) DIGITAL VOLTMETER WITH INBUILT
SELECTOR SWITCH - 2 Nos
f) 2A HRC CONTROL FUSE - 14 Nos
g) R/Y/B PHASE INDICATION LAMP 230V AC - 2
Nos
2) OUTGOING
a) 200A FP 36KA MCCB THERMAL MAGNETIC
BASED RELEASE O/L & S/C PROTECTION
WITH SPREADER LINK & ROHM - 1 No
b) 125A FP 36KA MCCB THERMAL MAGNETIC
BASED RELEASE O/L & S/C PROTECTION
WITH SPREADER LINK & ROHM - 2 Nos
c) 63A FP 36KA MCCB THERMAL MAGNETIC
BASED RELEASE O/L & S/C PROTECTION
WITH SPREADER LINK & ROHM- 5 Nos
3) Busbar Ratings
400 Amps tinned Copper Busbar (100% Neutral)
1 Set PR 396,970 44,108.00 352,862.00
FR 441,078
B/F CMB 196/Page No.
2 APFC PANELS
a) Supplying of factory built floor mounted auto-
manual power factor correction system of
75KVAR capacity having 3 phase APP Type
heavy duty capacitors self fusing ,self healing resin
bonded terminal in Six steps
{(2+3+5+10+15+20+20)} as per ISI 13585
mounted on suitable arrangement and provided
with Power Contactor. The system shall have
micro processor based power factor controller
provided in the command module having set
points for target P. F setting and digital P. F.
display .The system shall be provided with
required capacity master MCCB, to check its main
operating parameters such as over loads, short
circuit, etc.
Sub work:-G
SH :- Providing Drinking water pump set .
9) Pump Panel.
Supplying of suitable size indoor type wall
mounted dust and vermin proof totally enclosed
compartmentalized cubical panel board made out
of 2.0 mm CRCA sheet with stiffeners wherever
required, chemically treated with seven tank
process before painting for surface treatment and
powder coated alongwith Electrolytic grade high
conductivity copper bus bar, detachable gland
plate for top/bottom cable entry, cable alley &
suitable for operation on 3 phase 415 Volts 50
HZ AC supply including providing and fixing the
following switch gears and accessories complete
with all incoming and out going connections,
interconnections with suitable copper wire,
copper lugs and thimbles, earthing the body etc
as required.(Depth 30 cm)
Incoming
a) 63A FP 25KA MCCB THERMAL MAGNETIC BASED
RELEASE O/L & S/C PROTECTION WITH
SPREADER LINK & ROHM - 1 No
b) ON/OFF INDICATION LAMO 230V AC - 1 No
DIGITAL AMMETER WITH INBUILT SELECTOR
c)
SWITCH - 1 No
d) 100/5A CT's CL 1.0 5VA - 3 Nos
(0-500V) DIGITAL VOLTMETER WITH INBUILT
e)
SELECTOR SWITCH - 1 No
f) 2A HRC CONTROL FUSE -7 Nos
Sub work:-C
SH:- Providing Down comer system
2 Fabrication, Supply of wall mounted compartmentalized
with hinged lockable doors cubical electrical control
panel of suitable size fabricated from CRCA sheet of 2
mm thick, dust and vermin proof, powder coated of
approved shade after chemically treated with seven tank
process , cable alley, suitable for operation on 3 phase
415 volt 50 Hz AC supply i/c providing and fixing
following switch gear to be mounted on complete with
gaskets, interconnections and earthing etc. as required.
The enclosure protection class shall be of IP 54.
Sub work:-I
Sub Head : SITC of passenger lift.
Supplying, installation, testing & commissioning
of 8 passenger ( 544 Kg) elevator having
contract speed of 1.0 mps gearless machine
room less serving different floors in the lift
shaft as per details below and CPWD General
specification for electrical works ( Lifts &
Escalators ) Part - III 2003 etc. as required.
Type of doors :
Car :- Power operated Centre opening horizontal
sliding stainless steel scratch resistant ( honey
comb finish ) doors.
Landing Doors : Power operated centre opening
horizontal sliding stainless steel scratch resistant
(honey comb finish )
Voice announcement system
Intercom ( in car, machine room &
at reception)
digital position Indicators ( in car and at all
landings)
Battery operated emergency light and
alarm bell.
Full length infrared door curtain.
4,216,986.00
342,840.96
3,874,145.04
1,247,521.00
1403461.00
(155,940.00)
9185536
746784
8438752
1877331
6561421
-
PART RATE STATEMENT 3rd RA Bill
(The panel shall be complete with test terminal 1247521.00 1559401.00 Set
blocks, fuses, circuit labels, illuminating lamps of
9 W CFL in each panel, indicating lamps etc.,
wiring for interconnection with suitable size
copper cable, suitable cable end box with cable
entry from top for incoming and outgoing
cables, HV Danger Notice board, Earth bus bars,
foundation bolts and nuts etc. as required )
SUB-HEAD II : MV EQUIPMENT
Main Board
1 (L.T. panels)
Supplying of Indoor floor mounted modular type,
sectionalized, compartmentalized, extendable type
MV cubical panel having 35 MVA breaking
capacity of suitable size fabricated from CRCA
sheet steel of 2.5 mm thick for frame work, 2 mm
thick for enclosure, 1.6 mm thick for doors, top
covers and partitions with stiffeners wherever
required, having vibration free structure chemically
treated with seven tank process before painting
for surface treatment, epoxy powder coated, with
suitable electrolytic grade high conductivity copper
bus bar extensible type, suitable for operation on
3 phase 415 V 50 HZ AC supply i/c providing and
fixing the following switchgear mounted thereon
complete with gaskets and interconnections as per
specifications complete as required. ( The board
shall be dust & vermin proof with degree of
protection of IP 52 as per IS : 2147, free standing
type, mounted on base channel of ISMC - 75)
4) Busbar Ratings
a) Section - I : 630 Amps tinned Copper Busbar (50
kA) (100% Neutral)
b) Section - II : 630 Amps tinned Copper Busbar (50
kA) (100% Neutral)
Incoming
a) 63A FP 25KA MCCB THERMAL MAGNETIC BASED
RELEASE O/L & S/C PROTECTION WITH
SPREADER LINK & ROHM - 1 No
b) ON/OFF INDICATION LAMO 230V AC - 1 No
DIGITAL AMMETER WITH INBUILT SELECTOR
c)
SWITCH - 1 No
d) 100/5A CT's CL 1.0 5VA - 3 Nos
(0-500V) DIGITAL VOLTMETER WITH INBUILT
e)
SELECTOR SWITCH - 1 No
f) 2A HRC CONTROL FUSE -7 Nos
Sub work:-C
SH:- Providing Down comer system
2 Fabrication, Supply of wall mounted compartmentalized
with hinged lockable doors cubical electrical control
panel of suitable size fabricated from CRCA sheet of 2
mm thick, dust and vermin proof, powder coated of
approved shade after chemically treated with seven tank
process , cable alley, suitable for operation on 3 phase
415 volt 50 Hz AC supply i/c providing and fixing
following switch gear to be mounted on complete with
gaskets, interconnections and earthing etc. as required.
The enclosure protection class shall be of IP 54.
4 Fabrication, Supply of wall mounted compartmentalized
with hinged lockable doors cubical electrical control
panel of suitable size fabricated from CRCA sheet of 2
mm thick, dust and vermin proof, powder coated of
approved shade after chemically treated with seven tank
process , cable alley, suitable for operation on 3 phase
415 volt 50 Hz AC supply i/c providing and fixing
following switch gear to be mounted on complete with
gaskets, interconnections and earthing etc. as required.
The enclosure protection class shall be of IP 54.
J.E.(ELECT.) A.E.(Elect.)
CESD-III, CPWD, CESD-III, CPWD,
Navi Mumbai Navi Mumbai
J.E.(ELECT.) A.E.(Elect.)
CESD-III, CPWD, CESD-III, CPWD,
Navi Mumbai Navi Mumbai
Remark
Supplied only
Supplied only
Supplied only
Supplied only
Supplied only
Supplied only
UN-STAMPED RECEIPT
b
c a 6.4 mm dia with 13mm thick nitrile rubber insulation 200 Mt 386
d b 9.52 mm dia with 13mm thick nitrile rubber insulation 180 Mt 718
e c 12.7 mm dia with 13mm thick nitrile rubber insulation 180 Mt 828
f d 15.88 mm dia with 13mm thick nitrile rubber insulation 125 Mt 1012
g e 19.05 mm dia with 13mm thick nitrile rubber insulation 172 Mt 1242
h f 22.2 mm dia with 19mm thick nitrile rubber insulation 150 Mt 1343
i g 28.58 mm dia with 19mm thick nitrile rubber insulation 100 Mt 1601
h 34.92 mm dia with 19mm thick nitrile rubber insulation 90 Mt 1877
7 i 41.1 mm dia with 19mm thick nitrile rubber insulation 80 Mt 2429
2198800
1420664
49864
459540
190440
49588
687700
660192
286120
662400
168912
276000
77200
129240
149040
126500
213624
201450
160100
168930
194320
13510
33120
84160
10313182