Академический Документы
Профессиональный Документы
Культура Документы
mm
Indian Standard
ROOM AIR CONDITIONERS - SPECIFICATION
PART 2 SPLIT AIR CONDITIONERS
( Second Revision )
UDC 697’94
0 BIS 1992
FOREWORD
This Indian Standard ( Second Revision ) was adopted by the Bureau of Indian Standards, after the
draft finalized by the Refrigeration and Air Conditioning Sectional Committee had been approved
by the Heavy Mechanical Engineering Division Council.
This Indian Standard was first published in 1960 and revised in 1971. The committee responsible
to formulate this standard decided to cover the requirements of split air conditioners also in the
standard. Accordingly, this standard has been splitted up in following two parts:
IS 1391 ( Part 1 ) : 1992 Room air conditioners - Specification : Part 1 Unitary air conditioners
IS 1391 ( Part 2 ) : 1992 Room air conditioners - Specification : Part 2 Split air conditioners
In the preparation of this standard assistance has been derived from ISO/DIS 5151 ‘Room air
conditioners and heat pumps - Testing and rating’, issued by the International Organization for
Standardization.
In this standard split air conditioners from 3 000 kcal/h to 9 000 kcal/h capacities have been covered.
While formulating this standard due importance has been given to energy conservation, noise
pollution and safety.
The basic units of measurement together with their symbols for the various quantities used in the
text have been listed in Annex A.
For the purpose of deciding whether a particular requiremen? of this standard is complied with, the
final value, observed or calculated, expressing the result of a test or analysis, shall be rounded off
in accordance with IS 2 : 1960 ‘Rules for rounding off numerical values ( revised 1’. The number
of significant places retained in the rounded off value should be the same as that of the specified
value in this standard.
IS 1391( Part 2 ) : 1992
Indian Standard
ROOM AIR CONDITIONERS - SPECIFICATION
PART 2 SPUT A\R COND\T\QNERS
( Second Revision )
1 SCOPE compressor, heat exchangers, fan motors and air
handling system installed in two separate cabinets.
1.1 This standard prescribes the constructional and
performance requirements of split air conditioners. It is designed primarily to provide conditioned air
to an enclosed space, room or zone (conditioned
1.2 This standard also prescribes the test conditions space). It includes a prime source of refrigeration
and the corresponding test procedures for determining for cooling and dehumidification and means for the
various performance characteristics of split air circulation and filtering of air.
conditioners which operate non-frosting when cooling
and dehumidifying at standard rating conditions. 3.1.2 Standard Barometric Pressure
Barometric pressure of 1.013 25 bar (760 mm Hg).
1.3 This standard specifies split air conditioners
which may also serve as heaters by heat pump/electric 3.1.3 Wet-Bulb Temperature
heater application.
Temperature indicated when the temperature sensing
2 REFERENCES element and wetted wick have reached a state of
constant temperature (evaporative equilibrium)
The Indian Standards given in Annex B are necessary (see 11.15).
adjuncts to this standard.
3.1.4 Room Discharge Air Flow of a Unit
3 TERMINOLOGY Bate of flow of air from the room side outlet of
the unit. *
3.1 For the purpose of this standard, the following
definitions shall apply. Definitions relating to air 3.1.5 Room Intake Air Flow of a Unit
flow (3.1.4 to 3.15) are illustrated in Fig. 1. Exhaust
air or fresh air in room side may be indicated in Rate of flow of air into the unit from the conditioned
Fig. 1, if provided. space.
3.1.1 Split Air Conditioner 3.1.6 Net Total Room Cooling Effect of a Unit
It comprises of Indoor unit and Outdoor unit. The Total available capacity of the unit for removing
Indoor unit may be mounted on floor or wall or sensible and latent heat from the space to be
ceiling. The Indoor and Outdoor units consist of conditioned.
ROOM SIDE
n OUT DOOR SIDE
ROOM DISCHARGE
INDOOR Ur;rll
DOOR UNIT
FIG. 1 DEFINITIONS
RJLATINGTO AIR FLOW
1
IS 1391( Part 2 ) : 1992
3.1.7 Net Room Dehumidifying Effect (Latent Cooling 4.4 Recommended classification of nominal cooling
Effect) capacities of the split air conditioners shall be as
under:
Total available capacity of the unit for removing
latent heat from the space to be conditioned. 3 000, 4500, 6 000, 7 500 and 9 000 k&/h.
3.1.10 Room Calorimeter 51.2 There shall be no sharp edges or comers liable
to cause injury under normal conditions of use and
It is a test facility consisting of two contiguous all moving parts which constitute accident hazards
calorimeters with a common partition. One is shall be effectively guarded.
designated as the room side compartment, and the
other as the outdoor compartment. Each side is 51.3 Parts which require periodic servicing shall
equipped with instrumented reconditioning be readily accessible.
equipment whose output may be measured and
controlled to counter balance the room side 5.2 Material
dehumidifying and cooling effect and the outdoor
side humidifying and heating effect of the split air 5.2.1 Materials used in the construction of cabinet,
conditioner under test. front panel, etc, shall comply with the corresponding
Indian Standards wherever applicable except where
3.1.11 Rated Voltage such requirements are modified by this standard.
Voltage shown on the nameplate of the unit. 5.2.2 The material shall be free from defects which
are liable to cause undue deterioration or failure.
3.1.12 Rated Frequency c
5.2.3 Under normal conditions of use and
Frequency shown on the nameplate of the unit. maintenance, the materials used shall not shrink,
deteriorate, warp or cause mould or odours and shall
4 CLASSIFICATION be resistant to attack of vermin and destructive pests.
According to function and nominal cooling capacity, 5.2.4 Sealing and insulating materials shall not lose
split air conditioners shall be classified as follows. their essential properties such as adhesion, moisture
and heat resistance.
4.1 Classification by Function
5.2.5 Internal and external finishes shall be capable
4.1.1 Cooling and Dehumidification
of being cleaned effectively without undue deterioration
and shall be such as to afford protection against climatic
4.1.2 Cooling and Heating by Heat Pump action in all seasons under normal use. All metal
parts which are exposed to moisture or ambient
4.1.3 Cooling and Heating by Electric Heater conditions shall be corrosion resistant or adequately
protected against corrosion.
4.2 Unit Type
5.3 Electrically Charged Parts
4.2.1 Single Split having Single Indoor and Outdoor
5.3.1 The electricallylive parts shall be protected
Unit
from accidental contact of the user.
4.2.2 Multi Split having Multble Indoor and Single
5.3.2 Electric conductors shall be of electrically,
Outdoor Unit \ thermally and mechanically stable and anti-corrosive
materials such as copper and copper alloy.
4.3 Unit Mounting Arrangement
5.3.3 Switches and the like shall work smoothly and
4.3.1 Floor Type keep good electrical contact.
4.3.2 Ceiling Type 5.3.4 Make and break operation or status of a manual
switch shall be marked on prominent place by letters,
4.3.3 Wall Type symbols or colours.
2
IS 1391( Part 2 ) : 1992
5.3.5 Electrical cables used shall conform to 5.8 Thermostat
IS 694 : 1977.
5.8.1 The thermostat shall conform to IS 11338 :
5.4 Refrigerant Circuit 1985. Alternatively electronic thermostat may also
be used.
5.4.1 The refrigerant pipes and fittings shall be of
approved quality and shall withstand normal working 5.9 Hermetic Compressors
pressures of air conditioners and should conform to
Hermetically sealed compressors shall conform to
IS 10773 : 1983 or equivalent national standard/
IS 10617 (Part 1) : 1983.
international standard.
5.10 Motors
5.4.2 The refrigerant used shall be chemically pure,
free from moisture or any other chemical Fan/blower motor shall conform to IS 996 : 1979.
contamination.
6 RATING REQUIREMENTS
5.5 Eiectrical Heater
6.1 The declared ratings of the air conditioner shall
5.5.1 The heating element and fittings shall be firmly be based on conditions specified in 6.1.1 to 6.1.8.
installed. Also, the heating element shall be so built
that its broken end has no possibility to make contact 6.1.1 Run-in Period
with non-live metallic parts.
Before testing to determine ratings, the unit shall
5.5.2 Air conditioners which have electric heaters be run-in continuously for a period of about 15 hours.
for heating shall be so constructed that electric heater
circuit will not be completed when the recirculating 6.1.2 Cooling Capacity Ratings
air handling system remains switched off. Alternatively
switches of air handling motor and electric heater 6.1.2.1 Domestic market
shall work together simultaneously. Cooling capacity ratings shall be based on tests
conducted under conditions specified in 8.1 and with
5.5.3 With electric heater which has the possibility apparatus described in 12. Ratings shall include the
of causing hazard by temperature rise, temperature- total cooling capacity and the latent cooling capacity
rise preventive device (inclusive of thermal fuse) shall stated in kilocalories per hour.
be installed. In addition heating thermostat shall be t
used to control temperature. 6.1.2.2 Export market
5.5.4 The heat insulators shall be made of non- Air conditioners manufactured for export shall be
flammable material and shall withstand normal working rated on the conditions given in Annex C or as specified
temperature. by the purchaser.
3
IS 1391( Part 2 ) : 1992
capacity ratings determined by measurement of the 8 BATING AND TEST CONDITIONS
total electrical power consumed by the heating element
or elements. 8.1 Capacity Rating Test Conditions
6.1.7 Electrical Ratings The split air conditioner shall have nameplate rating
determined by tests conducted at the standard rating
Ratings in watts for split air conditioner shall be conditions specified below:
based, on standard voltage which shall be 230 volts,
single phase, 50 c/s, the units, however, shall be Room air temperature:
capable of working at any voltage within 210 percent a) Dry bulb 27OC
of the standard voltage. In case of three phase power
supply the ratings in watts shall be based on standard b) Wet bulb 19%
400 volts, 50 c/s, the units, however, shall be capable
of working at any voltage within 25 percent of the Outside air temperature:
standard voltage. a) Dry bulb 35oc
b) Wet bulb 3ooc
In the case of dc machines, the standard voltage
shall be 220 volts and the units shall be capable Test voltage Rated voltage
of working within a voltage variation of 25 percent
of the standard dc voltage. Test frequency Rated frequency
4
IS 1391( Part 2 ) : 1992
8.4 Enclosure Sweat Test Conditions b) +O.S°C for the specified temperatures.
The enclosure sweat test shall be conducted under 9.2 Safety
the conditions given below:
Split air conditioners shall meet as far as applicable
Rated air temperature: the requirements of IS 660 : 1963.
a) Dry bulb 27OC
9.3 Power Factor Test
b) Wet bulb 24OC
When operating under normal load under the conditions
Outside air temperature: specified in 8.1 with controls set for maximum cooling
the split air conditioner shall have overall power
a) Dry bulb 27OC factor, measured at 230 volts, 50 c/s, not less than
b) Wet bulb 24OC 0.85.
Test voltage 90 percent and 110 percent 9.4.5.1 During one entire test, the split air conditioner
of nameplate rating should operate without visible or audible indication
Test frequency Rated frequency of damage.
5
IS 1391( Part 2 ) : 1992
9.4.5.4 For those models so designed that resumption 9.6.2 Test Conditions
of operation does not occur after initial trip within An enclosure sweat test shall be conducted under
the first 5 minutes, the unit may remain out of operation the conditions specified in 8.4. The unit controls,
for not longer than 60 minutes. It should then operate fans, dampers, and grilles shall be set to produce
continuously for 1 hour.
the maximum tendency to sweat provided such settings
are not contrary to manufacturers’ operating
9.5 Freeze-Up Tests
instructions.
9.5.1 Purpose
9.6.3 Procedure
The air blockage test and the drip test shall be After establishment of the specified temperature
conducted to determine the ability of the air conditioner conditions, the unit shall be operated continuously
to operate satisfactorily under conditions with the for a period of 4 hours.
maximum tendency to frost or ice the evaporator.
9.6.4 Requirements
9.5.2 Test Conditions
During the test, no condensed water shall drip, run
or blow off the unit.
Freeze-up test shall be conducted under the conditions
given in 8.3. Temperature control and fan speed at
9.7 Power Consumption Test for Cooling
the lowest and all dampers closed to produce the
maximum tendency to frost or ice the evaporator,
9.7.1 Purpose
provided such settings are not contrary to the
manufacturers operating instructions. The purpose of the power consumption test is to
determine the power in watts.
9.5.3 Air Blockage Test
9.7.2 Test Condition
9.5.3.1 Procedure
The power measurement shall be determined during
The test should be continuous, with the unit on the the capacity rating test under the conditions given
cooling cycle for 12 hours after establishment of in 8.1.
the specified temperature conditions.
9.7.3 Procedure
9.5.3.2 Requirement
The power measurement shall be the average power
At the end of 12 hours the accumulation of ice or measurement in watts measured during the capacity
frost on the evaporator shall not obstruct the air passing rating test (see 9.9 and Annex D).
through the evaporator coil.
9.7.4 Requirements
9.5.4 Drip Test The power consumption for air conditions tested under
the conditions laid in 8.1 shall not exceed the values
9.5.4.1 Procedure as given in Table 1.
The unit should be operated for 6 hours with the Table 1 Power Consumption Rating
room-side air inlet covered to completely block the
passage of air so as to attempt to achieve complete Rated Cooling Capacity Maxtmum Power Consumption
blockage of the evaporator coil by frost. (kcalh) (kW
3m 1.7
9.5.4.2 After the 6 hours operating period, the unit
4 500 2.6
should be stopped and the air inlet covering removed
until the accumulation of ice or frost has melted. 6000 3.4
The unit should then be turned on again, with the 7 500 4.5
fans operating at the highest speed, for 5 minutes. 9ooo 5.4
The purpose of this test is to determine the resistance The power measurement shall be determined during
to sweating of the air conditioner when operating the heat pump rating test under the condition given
under conditions of high humidity. in 8.5.
6
IS 1391( Part 2 ) : 1992
9.8.3 Procedure capacity on the room side and the other shall determine
the capacity on the outdoor side.
The power measurement shall be the average power
measurement in watts measured during the heating
(These two simultaneous determinations shall agree
pump rating test (see 9.11 and Annex D).
within 4 percent of the value obtained on the room
side for the test to be valid.)
9.8.4 Requirements
The rate of energy consumption for air conditioners 9.9.4.1 Test conditions shall be maintained until
tested under the conditions laid in 8.!l shall not exceed equilibrium has been reached, and maintained for
115 percent of the rated energy for heating by heat not less than 1 hour before recording data for the
pump. capacity test. The test shall then be run for 1 hour
recording data every 10 minutes, giving 7 sets of
9.9 Capacity Rating Test readings.
9.9.1 Purpose 9.9.4.2 The data to be recorded for this test are given
in Annex D. This Annex shows general information
The purpose of the capacity rating test is to determine required, but is not intended to limit the data to
the magnitude of the following functions: be obtained.
a) Net total cooling effect,
As an interim measure till the date by which the
b) Net dehumidifying effect, testing facilities as per calorimeter are available in
c) Net sensible cooling effect, and the country, the capacity rating test shall be conducted
d) Net total air capacity for cooling. adopting the psychrometric method on the evaporator
side as described in 4.1(a) and calculations as given
in 5.1.1 of IS 8148 : 1976 employing nozzle method
9.9.2 Test Conditions
of measuring velocity. This method shall, however,
Capacity rating test shall be conducted under the be followed without having any ducting arrangement
conditions specified in 8.1 and within the allowable shown in Fig. 1 of IS 8148 : 1976, during temperature
variation given in Table 2. The air conditioner shall measurements. The room discharge air flow shall
be in the condition as normally intended for use. be measured separately in accordance with 13 of
Filters and grilles where supplied shall be in position. IS 1391 (Part 2) : 1992.
The measured heating capacity shall not be less than 4to = q. - K, m. - KIE + (hw3 - hw,) W,
90 percent of the rated heat pump capacity. . ...(2)
+ 41, + 41,
10 CALCULATIONS
where
10.1 CapacityRating net total room cooling effect as determined
%0 =
on outdoor side;
10.1.1Net Total Cooling Eflect on Room Side heat removed by cooling coil in outdoor
4, =
side compartment;
The net total cooling effect on the room side, as K, = 1 (= 0.860 kcal/Wh);
tested in either the calibrated or balanced ambient
room type calorimeter (Fig. 2A and 2B) is calculated
m0 = sum of all power input to any equipment,
as follows: such as heaters, circulating fans, etc, in
outdoor side compartment;
h02 = enthalpy of condensed moisture leaving
the room side compartment, as defined
where in 10.1.1;
E = total power input to air conditioner,
% = net total room cooling effect as determined h w3 = enthalpy of condensate removed by air-
on room side compartment (kcal/h); treating coil in outdoor side compartment
1 (= 0.860 kcal/Wh); reconditioning equipment taken at the
&* 1 sum of all power input to room side temperature at which the condensate leaves
compartment; the compartment;
h Wl = enthalpy of water of steam supplied to w, = water vapour condensed by air conditioner,
maintain humidity. If no water is as defined in 10.1.1;
introduced during the test, hw, is taken 4 1P = heat leakage out of outdoor side
at the temperature of the water in the compartment through separating partition
humidifier tank of reconditioning between room side and outdoor side
equipment; compartments, as determined from
h 02 = enthalpy of condensed moisture leaving calibrating test (or may be based on
the room side compartment. Since transfer f calculation in case of balanced ambient
of condensed moisture from room side room type calorimeter). This quantity will
to outdoor side compartment usually takes be numerically equal to ql, used in
place within the air conditioner, with equation (1) (see 10.1.1) only if the area
consequent difficulty in measuring its of separating partition exposed to outdoor
temperature, the temperature of the side is equal to the area exposed to the
condensate may be assumed to be at the room side compartment; and
measured or estimated, wet bulb 4 lo =
heat leakage out of outdoor side (but not
temperature of the air leaving the air including the separating partition), as
conditioner; determined from the calibrating test.
w, = water vapour (rate) condensed by air
conditioner. This is measured by Net Room DehumidijjGng Effect
10.1.3
reconditioning equipment as the amount
of water evaporated into room side The net dehumidifying,effect is calculated as follows:
compartment to maintain required
humidity; qd = K2 Wr . ...(3)
4 lp =
heat leakage rate into room side
compartment through separating partition where
between room side and outdoor side = net room dehumidifying effect;
qd
compartments, as determined from
K2
= 2 460 Id/kg (= 588 kcal/kg); and
calibrating test (or may be based on
,calculation in case of balanced ambient Y = water vapour condensed by air conditioner
room type calorimeter); and as defined in 10.1.1.
4 lr =
heat leakage rate into room side
compartment through wall, floor and Net Room Sensible Cooling Effect
10.1.4
ceiling (but not including the separating The net room sensible cooling effect is calculated
partition) as determined from calibrating as follows:
test.
4, = %, - qd . ...(4)
Net Total Cooling Effect on Outdoor Side
10.1.2
where
The net total room cooling effect on the outdoor
side, as tested in either the calibrated or balanced 4, = net room sensible cooling effect,
8
IS 1391( Part 2 ) : 1992
PRESSURE
EQUALIZING
DEVICE
7
IUINT 1
II xxxxw-
I II N
L!-
AIR SAMPLING TUBE
FIG. 2A CALIBRATED
ROOMTYPECALORIME~R
CONTROLLED PRESSURE
EQUALIZING
DEVICE
7
HEATER
-
HUMIDIFIER
FAN
-
FIG.2B BALANCED
AMBIENTRook WE CALORIMETER
9
IS 1391( Part 2 ) : 1992
10.2 Calculation of Heating Capacity by Heat 11 INSTRUMENTS
Pump
11.1 Temperature Measuring Instruments
10.2.1 The Heating Capacity by Heat Pump on Room
Side 11.1.1 Temperature measurements shall be made with
one 01 more of the following instruments:
The net heating effect on the room side as tested
in either the calibrated or balanced ambient room Mercury-in-glass thermometers,
4
type calorimeter is calculated as follows:
b) Thermocouples,
4hr = 4 - 860 =hr - (hw4 - h,JY + 41, + 41, 4 Electric resistance thermometers, and
. ...(6) 4 Electronic temperature indicator.
qh, = 860 ZEho t 860 E (hw, - h,)Wr t ql, t q1 11.1.6 Whenever possible, temperature measuring
....(7) instruments used to measure the change in temperature
should be arranged so that they can be readily
where interchanged between inlet and outlet positions to
net heating capacity calculated on the improve accuracy.
qh, =
outdoor side of the calorimeter (k&/h);
CEho = total input to the outdoor side of the 11.1.7 Temperature of fluids within conduits should
calorimeter; be measured by inserting temperature instruments
E = total power input to air conditioner; directly within the fluid or within a well inserted
hw, = enthalpy of water or vapour flowing into into the fluid. If a glass thermometer is to be inserted
the outdoor side of the calorimeter (kcal/ directly into the fluid, it shall be calibrated for the
effect of pressure.
kg);
h, = enthaply of condensed water flowing out
of the outdoor side of the calorimeter (kcal/ 11.1.8 Temperature measuring instruments should be
adequately shielded from radiation from any adjacent
kg);
wr = quantity of water condensed at the heat sources.
conditioner (kg/h);
heat leakage through the partition between 11.2 Pressure Measuring Instruments
4 lp =
room side and outdoor side (kcal/h); and
heat leakage through the floor, the wall 11.2.1 Accuracy of pressure measuring instruments,
41 =
(exclusive of the partition) and the ceiling not including barometers should permit measurements
(kcal/h). within +l N/m* (0.01 m bar) (0.1 mm IzQ).
10
IS 1391( Part 2 ) : 1992
11.2.2 In no case the smallest scale division of the effect by balancing the heat and water rejection on
pressure measuring instrument shall exceed the the condenser side with a measured amount of cooling
specified accuracy. medium.
12.2.2 The two calorimeters compartments, room
11.2.3 Barometric pressure shall be measured by a
side and outdoor side, are separated by an insulated
barometer having scale markings permitting readings
partition having an opening into which the split air
with an accuracy within 20.1 percent.
conditioner is mounted. The air conditioner shall be
installed using supporting members and filler pieces
11.3 Electrical Instruments
in a manner similar to a normal installation. No effort
shall be made to seal the internal construction of
11.3.1 Electrical measurements shall be made with
the air conditioner to prevent air leakage from the
either indicating type or integrating type of instruments.
condenser side to the evaporator side or vice versa.
No connections or alterations shall be made to the
11.3.2 Instruments used for measuring all electrical
air conditioner which might in any way alter its normal
inputs to the calorimeter compartments shall be
operation.
accurate to +O.S percent of the quantity measured.
12.2.3 A pressure equalizing device shall be
11.4 Water Flow Measuring Instruments provided in the partition wall between the room side
and the outdoor side compartments to maintain a
11.4.1 Volume measurements shall be made with balanced pressure between these compartments and
either of the following instruments having an accuracy also to permit measurement of leakage, exhaust and
of 51.0 percent of the quantity measured: ventilation air. This device consists of one or more
nozzles of the type shown in Fig. 3, a discharge
a) Liquid-quantity meter, measuring either mass
chamber equipped with an exhaust fan and manometers
or volume; and
for measuring compartment and air flow pressures.
b) Liquid flow rate meter. A suggested arrangement of components is shown
in Fig. 4. Since the air flow from one compartment
11.4.2 Liquid quantity meter shall employ a tank to the other may be in either direction, two such
having sufficient capacity to accumulate the flow devices mounted in opposite direction, or a reversing
for at least two minutes. device shall be used.
11.5 Noise Measuring Instrument The manometer pressure pick-up tubes shall be so
located as te be affected by air discharged from the
Noise measurement shall be made with a sound level air conditioner on test or by the exhaust from the
meter whose accuracy is 21.0 percent of the quantity pressure equalizing device. The fan or blower which
measured. The instrument shall be able to measure exhaust air from the discharge chamber shall permit
a weighted sound pressure level. variation of its air flow by suitable means, such as
a variable speed drive, or a damper as shown in
11.6 Other Instruments Fig. 4. The exhaust from this fan or blower shall
be such that it will not effect the inlet air to the
11.6.1 Time interval measurements should be made air conditioner on test.
with instruments whose accuracy is 20.2 percent of
the quantity measured. The equalizing device shall be adjusted during
calorimeter tests or air flow measurements, so that
11.6.2 Mass measurements should be made with
apparatus whose accuracy is 21.0 percent of the
quantity measured.
12 CALORIMETERS
the room side and the outdoor side. The room side
capacity determination is made by balancing the APPROACH
cooling and dehumidifying effects with measured heat
and water inputs. The outdoor side capacity provides
a conforming test of the cooling and dehumidifying FIG. 3 AIR FLOW ~~EASUREMENT
NOZZLE
IS 1391( Part 2 ) : 1992
e- ffl ,,
NOZZLE
DISCHARGE CHAMBER
FIG.4 PRESSURE
EQUAIDJNG NOZZLE
the static pressure difference between the roomside 12.23 Each compartment shall be provided with
and outdoor side compartments is not greater than reconditioning equipment to maintain specified air
1.5 N/m2 or 0.015 mbar or 0.153 mm HrO. The flow and prescribed conditions. Reconditioning
construction details and calculations are specified equipment for the mom side compartment shall consist
in 13. of heaters to supply sensible heat and a humidifier
to supply moisture. The energy supply may be electric,
12.2.4 The size of the calorimeter shall be sufficient steam or any other source that can be controlled
to avoid any restriction to intake or discharge openings and measured. Reconditioning equipment for the
of the air conditioner. Perforated plates or other outdoor side compartment shall provide cooling and
suitable grilles shall be provided at the discharge dehumidification. A cooling coil equipped with by-
opening from the reconditioning equipment to avoid pass dampers to control the dry bulb temperature
face velocities exceeding 0.5 m/s. Sufficient space and supplied with a variable temperature water or
shall be allowed in front of any inlet or discharge variable water quantity to control the wet bulb
grilles of the air conditioner to avoid interference temperature may be used. If desired, dehumidifying
with air flow. Minimum distance from the air apparatus or reheating apparatus or both may be used
conditioner to side walls or ceiling of the compartments in combination with the cooling coil. Reconditioning
should be 1 m except for the back of a console equipment for both compartments shall be provided
type room air conditioner which should be in normal with fans of sufficient capacity to overcome the
relation to the wall. The suggested dimensions for resistance of the reconditioning equipment and
the calorimeter are given below: circulate not less than two times the quantity of air
12
IS 1391( Part 2 ) : 1992
b) At the point of measurement, the temperature 12.3.4 For the outdoor side compartment equipped
of air shall not be a,ffected by air discharged with means for cooling, an alternate means of
from the test unit. This makes it mandatory calibration may be to cool the compartment to
that the temperatures are measured upstream temperature at least ll°C below the ambient
of any recirculation produced by the test temperature (on six sides) and carry out a similar
unit. analysis.
13
IS 1391( Part 2 ) : 1992
12.4 Balanced Ambient Room Type Calorimeter the air within the surrounding space to prevent
stratification.
12.4.1 The balanced ambient room type calorimeter
12.4.3 Heat leakage through the separating partition
similar to that shown in Fig. 3B is based on the
shall be introduced into the heat balance calculation
principle of maintaining the dry bulb temperatures
and may be calibrated in accordance with 12.3 or
surrounding the particular compartment equal to the
may be calculated.
dry-bulb temperatures maintained within that
compartment. 12.4.4 It is recommended that the floor, ceiling and
walls of the calorimeter compartments be insulated
If the ambient wet bulb temperature is also maintained so as to limit heat leakage (including radiation) to
equal to that within the compartment, the vapour- not more than 10 percent of the air conditioner
proofing provisions of 12.2.8 are not required. capacity, with a ll°C temperature difference or 300
W (250 kcal/h) for the same temperature difference,
12.4.2 The floor, ceiling and walls of the calorimeter whichever is greater, as tested using the procedure
compartments shall be spaced at a sufficient distance given in 12.3.2.
away from the floor, ceiling and walls of the controlled
areas in which the compartments are located in order 13 AIR FLOW MEASUREMENT
to provide uniform air temperature in the intervening
13.1 Air Flow Determination
space. It is recommended that this distance be at
least 300 mm. Means shall be provided to circulate 13.1.1 The following air quantities may be measured
Cd
O-
10 -
‘w-.
30-
40-
50 -
60 -
“C
0.5
cm H20
DISCHARGE
I Dl::ETEf?
SCALE
DRY-BULB
TEMPERATURE
COEFFICIENT
VELOCITY
PRESSURE
VDU
c, = f (IL) : Rc = -
P
where
c, = discharge coefficient,
Rc = Reynolds number,
V = $ (9
D = nozle diameter,
” = velocity,
t = dry bulb temperature,
= density,
; = velocity pressure, and
P = viscosity.
Enter graph using diameter and temperature scales to obtain point on index(X) scale. Use index and pressure scale to obtain Reynolds number
and discharge coefficient.
14
IS 1391( Part 2 ) : 1992
using the apparatus described in 13.2 and 13.3 and chamber, and should be of such a size that the throat
testing procedure specified in 13.4 and 13.5: velocity is not less than 15 m/s. Centre distance
between nozzles in use should not be less than three
a) Room discharge air flow;
throat diameters, and the distance from the centre
b) Exhaust air flow; and of any nozzle to any of the four adjacent side walls
c) Fresh air flow, if room air conditioner is should be not less than 1.5 throat diameters. If the
equipped to provide same. nozzles are of different diameters, the distance between
axes shall be based upon the average diameter. Size
13.1.2 Air flow quantities are determined as mass and arrangement of the receiving chamber shall be
flow rate. If air flow quantities are to be expressed sufficient to provide uniform approach velocity to
for rating purposes in volume flow rates, such ratings the nozzle(s) or have suitable diffusion baffle to
should state the conditions (pressure, temperature accomplish this purpose. Nozzles so installed may
and humidity) at which the specific volume is be considered to have a negligible correction for
determined. approach velocity.
DAMPER
CHAMBER
15
IS 1391( Part 2 ) : 1992
one or more static pressure connections in the wall vn = specific volume of humid air at dry bulb
of the discharge chamber. Static pressure connections and wet bulb temperature conditions
should be located so as not to be affected by air existing at nozzle inlet but at standard
flow. barometric pressure.
NOTE! - Where the barometric pressure deviates from the
If desired, the velocity head of the air stream leaving standard barometric pressure by not more than 0.03 bar (22.5
the nozzle(s) may be measured by a pitot tube, but, mm Hg), V,’ may, for simplicity, be considered equal to V..
when more than one nozzle(s) are in use, the pitot
13.4.6 Air flow through multiple nozzle shall be
tube reading shall be determined for each nozzle.
calculated in accordance with 13.4.5 except the total
Temperature readings at the nozzle(s) should be used
flow rate will be the sum of the Q, for each nozzle
only for determining air density.
used.
13.4 Room Discharge Air Flow Measurement
13.5 Ventilation, Exhaust and Leakage Air Flow
Measurements
13.4.1 Room discharge air flow shall be measured
with apparatus similar to that illustrated in Fig. 6. 13.5.1 Ventilation, exhaust and leakage air flow shall
be measured by apparatus similar to that illustrated
13.4.2 The outlet or outlets of the mom air conditioner in Fig. 4 with the cooling means and the heating
shall be connected to the receiving chamber by adapter means, if any, inoperative.
ducting of negligible air resistance.
13.5.2 With the equalizing device adjusted for a
13.4.3 The exhaust fan shall be adjusted to give zero maximum static pressure differential between room
static pressure at the discharge of the unitary air side and outdoor side compartment of 1 N/m2 ; 0.01
conditioner in the receiving chamber. m bar (0.1 mm H,O) the following readings should
be taken:
13.4.4 The following readings shall be taken:
a) Barometric pressure,
a) Barometric pressure,
b) Nozzle dry bulb and wet bulb temperatures,
b) Nozzle dry bulb and wet bulb temperatures, and
and
c) Nozzle velocity pressure.
c) Nozzle velocity pressure.
135.3 Air flow values shall be calculated in
13.4.5 Air mass flow rate and air volume flow rate accord&e with 13.45.
through a single nozzle shall be determined as follows:
14 NOISE TEST
Q, = K3 C, A
J& ”
... ...(8)
14.1 Noise Measuring Room
Q, = K3CdA dhp
v’. The noise measuring room shall be anechoic room
complying with the following:
v’. =
PO 4 Background noise should be less than the
P measured value by at least 11 dBA.
K = c) Acceptance tests.
specific humidity at nozzle inlet; and
16
IS 1391( Part 2 ) : 1992
MICROPHONE
tm
-_--
J
1 =
0.3m I fs5-d 0.3m
1 I
NOTES
1 For noise. test room, the figure indicates for floor model split air conditioners.
2 For other split airconditioner models like ceiling, wall or ceiling concealed mounted types, the microphone of the noise level
measuring instrument should be kept at one meter distance from the supply air grill while taking readings.
15.3.6 Leakage Current Test b) Type or model number and serial number
of the unit;
The leakage current shall not exceed 3.5 mA when
tested as per IS 302-l(1979). 4 Name and quantity of refrigerant charge;
Besides all the production routine tests outlined 17.2 Standard Marking
in 15.3, the type tests shall comprise the
following: Details available with the Bureau of Indian Standards.
18
IS 1391( Part 2 ) : 1992
ANNEX A
( Foreword )
BASIC UNITS OF MEASUREMENT AND THEIR SYMBOLS
$1
UO.
Quantity
I International System
(SI) Units
Metric Units
1 Air mass flow rate kilogram per second kg/s kilogram per hour kg/h
Air volume flow rate cubic metre per second m3/s cubic metre per hour m3/h
2 Air specific humidity kilogram per kilogram kg/kg kilogram per kilogram k@g
3 Air specific volume cubic metre per m3/kg cubic metre per m3/kg
kilogram kilogram
Air static pressure newton per square metre N/m2 millimetre of water
or dynamic pressure ;:
Air velocity metre per second m/S metre per second m/S
.5 Rotating speed radian per second radls turn per second tr/s
turn per minute trlmin
10 Water mass flow rate kilogram per second kilogram per hour kg/h
!l Acceleration metre per square second metre per square second m/s2
19
IS 1391( Part 2 ) : 1992
ANNEX B
( Clause 2 )
196 : 1966 Atmospheric conditions for 996 : 1979 Single-phase small ac and
testing universal electric motors (second
302-l(1979) Safety of household and similar revision)
electrical appliances : Part 1 8148 : 1976 Packaged air conditioners
General requirements cfifth 10617 (Part 1) : Hermetic compressors : Part 1
revision) 1983 High temperature application
660 : 1963 Safety code for mechanical group
10773 : 1983 Copper tubes for refrigeration
refrigeration
purposes
694 : 1977 PVC insulated cables for 11338 : 1985 Thermostats for use in
working voltages up to and refrigerators, air conditioners,
including 1 100 volts (second water coolers and beverage
.. \ *
remion) coolers
ANNEX C
( Clause 6.1.2.2 )
C-l COOLING CAPACITY EATING TEST C-2.1 The maximum operating test conditions shall
CONDITIONS be as follows:
Test Condition
C.l.l The tesl conditions for the cooling capacity c h -.
shall be as follows: A B
2. Wet bulb 24OC 24OC d) Test voltage 1. 90 percent and 110 percent
for units with single name-
c) Test frequency Rated frequency* plate rating
d) Test voltage Rated voltage+ 2. 95 percent of minimum
voltage and 110 percent of
C-2 MAXIMUM OPERATING CONDITIONS voltage for units with dual
nameplate
Wnits having dual rated voltages should be tested at the higher voltage.
20
IS 1391( Part 2 ) : 1992
ANNEX D
( Clauses 9.7.3,9.8.3 and 9.9.4.2 )
D-l The following data shall be recorded for cooling 11. Total power input to room side and outdoor
capacity tests: side compartments;
1. Date; 12. Water quantity evaporated in humidifier;
2. Observers;
13. Temperature of humidifier water entering
3. Barometric pressure; room side compartment or in humidifier tank,
4. Applied voltage for each test unit motor;
14. Cooling water-flow rate through outdoor side
5. Frequency of applied voltage for each test compartment heat rejection coil;
unit motor;
15. Temperature of cooling water entering outdoor
6. Total power input to unit, except if more side compartment for heat rejection coil;
than one external power connection is provided
on unit, record input to each connection 16. Temperature of cooling water leaving outdoor
separately; side compartment from heat rejection coil;
7. Total current input to unit;
17. Water condensed in outdoor side compartment;
8. Control dry bulb and wet bulb temperatures
of air (room side calorimeter compartment) 18. Temperature of condensed water leaving
(see 12.2.7); outdoor side compartment;
9. Control dry bulb and wet bulb temperatures
19. Volume of air flow through measuring nozzle
of air (outdoor side calorimeter compartment)
of separating partition flow meter; and
(see 12.2.7);
10. Average air temperature outside the calori- 20. Static air pressure difference across separating
meter (calibrated room type) (see Fig. 2A); pa&ion calorimeter compartments.
21
Standard Mark
The use of the Standard Mark is governed by the provisions of the Bureau of Indian
Standards Act, 1986 and the Rules and Regulations made thereunder. The Standard Mark on
products covered by an Indian Standard conveys the assurance that they have been produced
to comply with the requirements of that standard under a well defined system of inspection,
testing and quality control which is ‘devised and supervised by BIS and operated by the
producer. Standard marked products are also continuously checked by BIS for conformity
to that standard as a further safeguard. Details of conditions under which a licence for the
use of the Standard Mark may be granted to manufacturers or producers may be obtained
from the Bureau of Indian Standards.
Bureau of ludiau Standards
BIS is a statutory institution established under the Bureau of Indian Standards Acf, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.
Copyright
BIS has the copyright of all its pubhcations. No part of these publications may be reproduced in
any form without the. prior permission in writing of BIS. This does not preclude the free use, in the
course of implementing the standard, of necessary details, such as symbols and sizes, type or grade
designations. Enquiries relating to copyright be addressed to the Director ( Publications ). BIS.
Indian Standards are reviewed periodically and’ revised, when necessary and amendments, if any, are
issued from time to time. Users of Indian Standards should ascertain that they are in possession of
the latest amendments or edition. Comments on this Indian Standard may be sent to BIS giving the
following reference :
t
BUREAU OF INDIAN STANDARDS
Headquarters:
Eastern “i l/l4 c:-I. ~.“-&_%t&~ ii1.i M, $.‘I. P. Road, Maniktola 37 8499, 378561
CALCUTTA 700054
I 37 86 26, 37 86 62
( Page 3, clause 5.3.5, second line) — Substitute ‘1S 694 :1990’ for
‘IS 694:1977’.
( Page 3, C1(IUSC5.4.1, fourth line) — Substitute ‘IS 10773 :1995’ for
‘IS 10773 :1983’.
(Page 6, clause 9.5.3.1, second line) — Substitute ‘4 hours’ for ’12 houm’.
(Page 6, clause 9.5.3.2, first line) — Substitute ‘4 houm’ for ’12 hours’.
( Page 18, clause 15.3.7) – Insert the following Note at the end of the
clause:
‘NOTE — The tests at 15.3.1 and 15.3,5 may he carried out separately on each indoor and
condensing units without inter-connecting. These tests on the inter-cmttteeted units maybe
carried out as per sampling plan agreed between manufacturer and purchaser.’
3cm 1.65
4500 2.3
61XKI 3.1
7500 3.6
9(XKI 4.4
1
Amend No. 1 to IS 1391 ( Part 2 ) :1992
( P~/ge 20, Amex B ) — Substitute the following IS No. and title for
existing:
IS No. Tide
694:1990 PVC insulated cables for working
voltages up to and including 1 100 volts
( dlird revision )
(ME3)