Академический Документы
Профессиональный Документы
Культура Документы
a r t i c l e i n f o a b s t r a c t
Article history: As an extensive network of resistances, capacitances, and inductances, a transformer has inherent char-
Received 22 February 2016 acteristic parameters that are functions of frequency. The form of these functions is predicated on the
Received in revised form geometric design of the transformer and materials that comprise it. Any change in the structure of a
17 September 2016
transformer will be reflected in its frequency response characteristics. Of the possible changes that can
Accepted 21 November 2016
take place in a transformer structure, an internal short circuit is one of the far-reaching incidents that
has been recently reported for many wind-farm transformers. Detecting the location of an internal short
Keywords:
circuit that has occurred in a transformer winding is therefore beneficial in the repair process and also
Sweep frequency response analysis
Internal short circuit
in improving future designs. In an effort to identify trends with inter-turn fault locations and frequency
Inter-turn fault location responses, this research investigates the effect of the location of deliberately initiated internal faults on
Transfer function parameters such as transfer voltages and input impedances by means of sweep frequency response anal-
Transformer fault diagnosis ysis (SFRA). The analysis of three different model transformers with different core and winding designs
shows several trends in frequency response patterns, depending on the location of the internal short
circuits. The paper discusses such trends as a potential use of SFRA in locating inter-turn winding failures
that may result in noticeable short circuits.
© 2016 Published by Elsevier B.V.
http://dx.doi.org/10.1016/j.epsr.2016.11.016
0378-7796/© 2016 Published by Elsevier B.V.
56 M. Khanali et al. / Electric Power Systems Research 145 (2017) 55–62
Table 1
Transformers specification.
Rated output 500 kVA, three phase 9 kVA, single phase 1 kVA, single phase
Voltage 240 V/11 kV 345 V/19.8 kV 115 V/6.6 kV
Frequency 50 Hz 60 Hz 60 Hz
Oil immersed/not immersed Not immersed Oil filled Oil filled
Number of layers for HV winding 12 37 41
Number of turns for HV winding 1334 7480 10,496
the fault develops, consumed energy increases in the early stages, Table 2
Fault numbering based on the position of short circuits according to Fig. 1.
while the opposite effect occurs during later stages of fault develop-
ment. Resonance occurred at higher frequencies as the inter-turn Fault number Location of short circuit (between
fault developed. connection leads)
Utilising FRA measurements, authors of this paper (Soloot et al.) 1 2 and 6
have previously investigated the effects of winding design on res- 2 4 and 8
onance overvoltages in transformer windings [9]. The FRA method 3 6 and 10
4 8 and 12
was adopted to measure voltage-drops between adjacent layers
5 10 and 14
and discs of transformer windings through a wide range of fre- 6 12 and 16
quency. The results showed that depending on the design of the 7 14 and 18
windings, transformers show different patterns of internal stresses. 8 16 and 20
9 18 and 23
It was concluded that disc winding has a higher internal stress
at resonance frequencies compared to that of pancake and layer
windings; layer structure showed the highest resonance voltage at
winding terminals. In another work by other authors of this paper transformers are described in Refs. [9,10,12]. The proposed scheme
(Khanali and Jayaram) [10], a comparison is made between fre- of using SFRA in identifying trends with fault locations in different
quency responses of electrostatically shielded and non-shielded layers are carried out using the model transformer I in detail while
layer type transformers with the focus being on identification the other two model transformers II and III, are used to verify the
of differences in their resonant overvoltage behaviours. Further, applicability of the SFRA approach to different designs.
it has been shown that resonances that occur with many fre- Unlike conventional FRA tests on transformers wherein the
quency components can lead to high stresses and eventually cause responses are used to detect faults such as winding deformations
layer-to-layer short circuits. Such resonance initiated high stresses or core dislocations, in this investigation, frequency responses of
particularly in transformers connected to wind-farms are also different parameters are measured against a known defect. For this
reported by Banda and Van Coller [11]. purpose, nine short circuits were created at different locations by
Through the literature, it is evident there is less focus on detec- short-circuiting a certain number of HV winding turns. Details of
tion of the position of internal short circuits using FRA method. the windings of model transformer I that is used in the analysis
Knowing the location of an internal fault can benefit operators and is given in Fig. 1. It is also presumed that access to the terminals
manufacturers by: reducing cost and time required for repair, and of each individual winding is available for measurement. It should
also providing statistical information about the areas of the wind- be noted here that although model transformer I is a three-phase
ings in which internal faults occur more often. The latter would be design, only one phase is considered in this study, while the unused
useful for more effective insulation reinforcement in future designs. phase windings are short circuited. As the effect of the core for
Greater reliability and efficiently reinforced insulation is especially magnetic coupling between windings of different legs (phases) is
valuable for transformers located in offshore wind-farms because negligible for frequencies above 10 kHz (due to the huge drop in
of higher maintenance and repair costs. In addition, due to the core permeability) [13]. Windings of different legs have insignifi-
exposure of wind turbine transformers to high dV/dt voltages from cant mutual effects on each other.
frequent switching, inter-turn and inter-layer insulation of such Transformer I is designed in a way that the number of turns
transformers is under higher stress compared to their power-grid between each two consecutive connections is 56 except for the taps
counterparts, as an internal short circuit is more likely to happen. (21–26) which have 32 turns between one another. This means that,
With an experimental approach on model transformers, the aim in terms of number of short circuited turns, all implemented faults
of the research presented is to identify the relationship between have the same number of turns (112) except the fault in the out-
locations of an internal fault and patterns of transformer fre- ermost layer, which has eight more turns. Fault numbering along
quency responses. To estimate the location of short circuits, the with short circuit locations are given in Table 2.
FRAs of faulty windings, with short circuits positioned at different Both transfer functions; HV/LV and LV/HV are measured, respec-
locations, are compared with one another and also with healthy tively, from HV and LV terminals while the other side is excited. In
winding as a reference. Comparison is based on use of statistical addition, input HV impedances with LV terminals shorted are also
parameters along with visual observations of trends in frequency utilised to correlate measured impedances with defect locations.
®
spectra. This research also compares sensitivities of different trans- An Agilent network analyser E5061B and high-frequency oscillo-
fer functions with respect to location of the fault. scope probes P2220 are used for voltage transfer measurements,
®
as well as special Ionphysics current sensors CM-100-6L-IR50 for
wide-band impedance measurements (Fig. 2).
2. Experimental
Three custom designed model transformers (Table 1) have been 3. Fault analysis
used in this study with special features to facilitate the creation of
artificial short circuits at different locations of the windings. This Variations that occur in transformer frequency responses due to
feature is made possible by inserting several connection leads along changes in the location of fault are investigated. The network anal-
the HV winding at different layers. Detailed designs of all three yser generates sinusoidal waveform with variable frequencies at
M. Khanali et al. / Electric Power Systems Research 145 (2017) 55–62 57
Fig. 1. Details for model transformer I. (a) Transformer winding with connection leads from different locations, (b) winding schematic and positions of connecting leads.
fmax
|20log10 R0 − 20log10 Rsc k |
ıASLE (Rsc k , R0 ) = (1)
N
f =fmin
Fig. 2. Test setup for FRA measurement. (a) Transfer function, (b) input HV 4. Results
impedance (1 – transformer with grounded tank and core, 2 – network analyser,
3 – high-frequency voltage probe, 4 – high-frequency current sensor).
Both transfer voltage and input impedance were measured
using procedures described in Sections 2 and 3. The results are
terminal S (Fig. 2). Connections of R and T channels are determined presented using 3D and 2D plots. In the 3D plots, X, Y, and Z axes
based on the parameter for which frequency response is mea- represent frequency, location (fault number) of the short circuit,
sured. For example, to measure LV/HV voltage transfer function, and magnitude of the parameters, respectively. For clarity, with 3D
R and T channels are connected to HV and LV terminals respec- plots, the magnitude of parameters are indicated by coloured maps
tively (Fig. 2a). On the other hand, as it is demonstrated in Fig. 2b, wherever it was helpful. Together, the 2D and 3D plots facilitate to
R and T channels are respectively connected to the current sensor identify effects of fault location on transformer frequency response
and HV terminal to measure input impedance. patterns. Sub-sections 4.1, 4.2 and 4.3 represent the results for
To analyse the FRA measurement results, both qualitative obser- model transformer I while 4.4 shows complementary results for
vations on trends, and quantitative analysis are used. Trends in model transformers II and III.
58 M. Khanali et al. / Electric Power Systems Research 145 (2017) 55–62
5. Discussion
Fig. 7. Magnitude of input impedance from HV side (LV terminal short circuit). (a) 3D view, (b) 2D plot, (c) coloured map representation.
at certain frequencies. This high amplitude can be related to the concern that saturation of the core may affect measurements. That
formation of an equipotential cylinder composed of shorted turns said, since frequencies are much higher than power frequency and
of HV winding close to the LV winding. High capacitance between excitation voltage is too low, flux density is very low and is not
this virtual cylinder and the LV winding results in high resonance significant to cause any core saturation.
for transferred voltage. From the insulation point of view, such phe- Further investigation of Fig. 7 (input impedance from HV side,
nomena can result in very high stresses inside the transformer even when LV terminal is shorted) reveals that connections of non-tested
when a very low content of the associated frequency exists in the windings are influential on the trend of frequency response changes
feeding voltage. With respect to practicality, when such high gains as a function of fault location. When impedance measurements are
in transfer voltages are observed (Figs. 3 and 5), there may be a performed with LV side short-circuited, the effect of magnetisa-
M. Khanali et al. / Electric Power Systems Research 145 (2017) 55–62 61
Fig. 8. Difference factor of input impedance from HV side (LV terminal open circuit).
6. Conclusion
tion inductance through the core and LV winding space can be Acknowledgments
neglected. This means the flux path generated by HV winding is
mainly restricted to the space out of LV winding and within the HV The authors greatly appreciate the source of funding: the
winding itself. As a result, and due to the symmetry of the HV wind- Norwegian Research Center for Offshore Wind Technology
ing, the winding with a fault just next to one end of the winding (NOWITECH) and the Natural Sciences and Engineering Research
(i.e. outermost layer fault) shows the same impedance frequency Council of Canada (NSERC). They are also thankful of Møre Trafo
response as the winding with a fault just next to the other end of Co. and Moloney Electric Inc. for their assistance in manufacturing
the winding (i.e. innermost layer fault). The same trend exists for the model transformers for the study.
other faults equally distant from the terminals.
Comparing trends in transfer ratios and input impedances, it
References
was observed that two parameters do not follow the same pattern
with respect to fault location. This observation is in compliance [1] B. Gustavsen, Study of transformer resonant over-voltages caused by
with what can be concluded from the literature stating that transfer cable-transformer high-frequency interaction, IEEE Trans. Power Deliv. 25
voltages have no direct relationship with input impedance mea- (April) (2010) 770–779.
62 M. Khanali et al. / Electric Power Systems Research 145 (2017) 55–62
[2] J. Aubin, S.A.C. Hall, Colloquium on transformer reliability and electrical [11] C.A. Banda, J.M. Van Coller, Investigation into Resonant Overvoltages in Wind
transients, Report on SC A2 Colloquium – Moscow 2005, April 2006, 18–24. Turbine Transformers due to Switching Surges, 2015 International Conference
[3] M. Nagel, T. Leibfried, Investigation on the high frequency, high voltage on Power Systems Transients (IPST), 15–18 June 2015, Paper ID 31.
insulation properties of mineral transformer-oil, in: 2006 IEEE Conference on [12] M. Khanali, S. Jayaram, J. Cheng, Effects of voltages with high-frequency
Electrical Insulation and Dielectric Phenomena, 15–18 October, 2006, pp. contents on the transformer insulation properties, in: 2013 IEEE Electrical
226–228. Insulation Conference (EIC), 2–5 June, 2013, pp. 235–238.
[4] V. Behjat, A. Vahedi, A. Setayeshmehr, H. Borsi, E. Gockenbach, Diagnosing [13] J. Merrikhi, J.S. Moghani, E. Fallah, Laminated iron core inductor model with
shorted turns on the windings of power transformers based upon online FRA flux skin effect, in: 2006 2nd International Conference on Power Electronics
using capacitive and inductive couplings, IEEE Trans. Power Deliv. 26 Systems and Applications, Hong Kong, 2006, pp. 77–78.
(October) (2011) 2123–2133. [14] J.W. Kim, B.K. Park, S.C. Jeong, S.W. Kim, P.G. Park, Fault diagnosis of a power
[5] J.R. Secue, E. Mombello, Sweep frequency response analysis (SFRA) for the transformer using an improved frequency-response analysis, IEEE Trans.
assessment of winding displacements and deformation in power Power Deliv. 20 (2005) 169–178.
transformers, Electr. Power Syst. Res. 78 (2008) 1119–1128. [15] M. Bagheri, M.S. Naderi, T. Blackburn, T. Phung, Frequency response analysis
[6] D.A.K. Pham, T.M.T. Pham, H. Borsi, E. Gockenbach, A new method for and short-circuit impedance measurement in detection of winding
purposes of failure diagnostics and FRA interpretation applicable to power deformation within power transformers, IEEE Electr. Insul. Mag. 29 (3) (2013)
transformers, IEEE Trans. Dielectr. Electr. Insul. 20 (2013) 2026–2034. 33–40.
[7] M. Florkowski, J. Furgał, Detection of winding faults in electrical machines [16] A.P. Purnomoadi, D. Fransisco, Modeling and diagnostic transformer condition
using the frequency response analysis method, Meas. Sci. Technol. 15 (2004) using sweep frequency response analysis, in: ICPADM 2009. IEEE 9th
2067–2074. International Conference on the Properties and Applications of Dielectric
[8] A. Wilk, D. Adamczyk, Investigations on sensitivity of FRA method in Materials, 19–23 July, 2009, pp. 1059–1063.
diagnosis of interturn faults in transformer winding, Proc. of IEEE [17] S.M. Islam, G. Ledwich, Locating transformer faults through sensitivity
International Symposium on Industrial Electronics (ISIE) (2011) 631–636. analysis of high frequency modeling using transfer function approach, 16–19
[9] A.H. Soloot, H.K. Hoidalen, B. Gustavsen, Influence of the winding design of June, in: Conference Record of the 1996 IEEE International Symposium on
wind turbine transformers for resonant overvoltage vulnerability, IEEE Trans. Electrical Insulation, vol. 1, 1996, pp. 38–41.
Dielectr. Electr. Insul. 22 (2015) 1250–1257. [18] J.R. Secue, E. Mombello, Sweep frequency response analysis (SFRA) for the
[10] M. Khanali, S.H. Jayaram, Effectiveness of electrostatic shielding in assessment of winding displacements and deformation in power
suppressing the impact of fast transients on transformer insulation, in: 2015 transformers, Electr. Power Syst. Res. 78 (2008) 1119–1128.
IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP),
18–21 October, 2015, pp. 652–655.