Академический Документы
Профессиональный Документы
Культура Документы
BNI CCL-202-100-Z001
BNI CCL-302-100-Z001
BNI CCL-305-100-Z001
User Manual
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
2 Safety
2.1 Intended Use 3
2.2 General Safety Notes 3
2.3 Meaning of the warnings 3
3 Getting Started
3.1 Connection overview 4
3.2 Mechanical connection 5
3.3 Supply voltage connection 5
3.4 CC-Link connection 6
3.5 Connecting sensors / actuators 6
4 Technical data
4.1 Dimensions 7
4.2 Mechanical Data 7
4.3 Operating conditions 7
4.4 Electrical Data 7
4.5 CC-Link Port 8
4.6 Function Indicators 8
5 Remote signals
5.1 Port overview 9
5.2 Remote I/O / Data mapping 9
5.2.1 BNI CCL-104-100-Z001 9
5.2.2 BNI CCL-202-100-Z001 10
5.2.3 BNI CCL-302-100-Z001 11
5.2.4 BNI CCL-305-100-Z001 12
5.3 Remote register allocation 12
5.4 Error Code register 12
5.5 Port sensor diagnostic register 13
5.6 Channel actuator diagnostic register 13
5.7 Port direction register 13
5.8 Display register 13
5.9 Port direction settings 13
6 Display
6.1 General 14
6.2 Default address 14
6.3 Display information 14
6.4 Menu structure 14
6.5 Edit mode 15
7 Included Material
7.1 Included Material 15
Appendix
Ordercode / order informations 15
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
1.1 About this guide This guide describes the Balluff CC-Link Field bus Module BNI CCL-… which enables
expanded communication down to the lowest level so as to provide improved process
optimizing and preventive maintenance. This module is IP67 protected and features a
rugged metal IP67 housing. The device is ideal for use in harsh industrial environments.
1.2 Structure of the guide The Guide is organized so that the sections build on one another.
Section 2. Basic safety informations.
Section 3: The main steps for installing the device.
Section 4: T echnical data for the device.
…
1.3 Typographical The following typographical conventions are used in this guide.
Conventions
Syntax Numbers:
− Decimal numbers are shown without additional indicators (e.g. 123),
− Hexadecimal numbers are shown with additional indicator hex (e.g. 00hex)
Cross-references Cross-references indicate where further information on the topic can be found ("see
Section 4 “).
Attention!
This symbol in connection with the word "Attention" warns of a possible hazardous
situation for the health of persons or for equipment damage. Disregard of these
warning notes may result in injury or damage to equipment.
Always observe the described measures for preventing this danger.
www.balluff.com 2
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
2 Safety
2.1 Intended Use The BNI CCL-… serves as a decentral input/output module for connecting to a CC-Link
network.
www.balluff.com 3
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
3 Getting Started
16 2
15
3
14 4
13
12 5
11 6
10 7
9 8
Connection overview for the module type BNI CCL-305-100-Z001. Different overviews are
related to different modules. The port interfaces are shown in the following chapters.
www.balluff.com 4
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
3 Getting Started
− 24 V DC.
− Provide sensor/bus power and actuator power from separate power sources if possible.
− T otal current <9A. The total current of all modules may not exceed 9A even when daisy
chaining the actuator supply.
Function ground
Note!
The FE connection from the housing to the machine must be low-impedance and
kept as short as possible.
www.balluff.com 5
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
3 Getting Started
3.4 CC-Link Connection The CC-Link connection is made using the M12 sockets Bus In and Bus Out (A-coded).
3.5 Connecting sensors / 8 I/O ports are provided for connecting actuators and sensors
actuators
Note!
Unused I/O port sockets must be fitted with cover caps to ensure IP67
protection rating.
www.balluff.com 6
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
4 Technical Data
4.1 Dimensions
4.2 Mechanical data Housing material Die-case zinc, matte nickel plated
Enclosure rating per IEC 60529 IP 67 (only when plugged-in and threaded-in)
Supply voltage 7/8” 5-pin male and female
Input ports / Output ports M12, A coded (8 x female)
Dimensions (W x H x D in mm) 68 x 224 x 30.9
Mounting type 2-hole screw mount
Ground strap attachment M4
Weight Approx. 580gr.
www.balluff.com 7
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
4 Technical Data
LED indicators Each M12 Port (digital input/output) is assigned two 2-color LEDs which indicate the
input ports configuration or operating states.
LED Function LED Pin 2 / Pin 4
Off Input signal = 0
Yellow Input signal = 1
Red Input signal = SC Short circuit*
LED indicators
output ports
LED Function LED Pin 2 / Pin 4
Off Output signal = 0
Yellow Output signal = 1
Red Output signal = Error, I max.
*SC=Short circuit detection on Pin 1. In this case both LEDs are red.
www.balluff.com 8
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
Port 0 Port 4
Port 1 Port 5
Port 2 Port 6
Port 3 Port 7
www.balluff.com 9
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
www.balluff.com 10
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
www.balluff.com 11
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
www.balluff.com 12
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
Pn
- Port n Pin m
Pm
Pn 0 - Input
- Port n Pin m
Pm 1 - Output
www.balluff.com 13
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
6 Display
6.1 General The BNI CCL-… serves as a decentralised input module for connecting to a CC-Link
network. With the implemented display, the address and the communication speed is set
directly on the BNI CCL… devices.
www.balluff.com 14
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
6 Display
The BNI CCL-… serves as a decentralised input module for connecting to a CC-Link
network. With the implemented display, the address and the communication speed is set
directly on the BNI CCL… devices.
Additional features:
- “Lock function” by PLC, edit mode is not accessible
- “Free controllable” LEDs by PLC
www.balluff.com 15
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
7 Included Material
7.1 Included Material The BNI CCL consists of the following components:
• IO-block
• 4 blind plugs M12
• Ground strap
• Screw M4x6
• 20 labels
• Short guide
www.balluff.com 16
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
Appendix
CC-Link interface
Functions
104 = IP 67 Input module, 16 Inputs
202 = IP 67 Input module, 8 Outputs
302 = IP 67 Input module, max. 16 Inputs/Outputs
305 = IP 67 Input module, 8 Inputs + 8 Outputs
Variant
100 = Display version
Mechanical version
Z001 = Die-cast zinc housing
Material: 1. Balluff housing version
Bus In: 1 x M12x1 internal thread
Bus Out: 1 x M12x1 internal thread
Power: 7/8“ external thread
I/O Ports: 8 x M12x1 internal thread
www.balluff.com 17
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
www.balluff.com 18
Balluff Network Interface / CC-Link BNI-CCL-104/202/302/305-100-Z001
www.balluff.com
Balluff GmbH
Schurwaldstrasse 9
73765 Neuhausen a.d.F .
Germany
T el. +49 7158 173-0
Fax +49 7158 5010
balluff@balluff.de
n www.balluff.com