Вы находитесь на странице: 1из 2

Temperature Rating of Conductor

Size 60°C 75°C 90°C 110°C


(140°F) (167°F) (194°F) (230°F)
mm2 AWG Type Types Types Type
MCM T,TW RHW, SA, AVA
THW, RHH,
THWN, THHN,
XHHW XHHW
2.0 14 15 15 25 30
3.5 12 20 20 30 35
5.5 10 30 30 40 45
8.0 8 40 45 50 60
14 6 55 65 70 80
22 4 70 85 90 105
30 3 80 100 105 120
38 2 95 115 120 135
50 1 110 130 140 160
60 0 125 150 155 190
80 00 145 175 185 215
100 000 165 200 210 245
125 0000 195 230 235 275
150 250 215 255 270 315
200 300 240 285 300 345
250 350 260 310 325 390
325 400 280 335 360 420
400 500 320 380 405 470
500 600 355 420 455 525
700 385 460 490 560
750 400 475 500 580
800 410 490 515 600
900 435 520 555

FULL LOAD CURRENT OF MOTORS


3 PHASE

F.I CURRENT (AMP)


MOTOR RATING

A. B.
220/230V 440/460
0.25HP/0.2KW 1.1 0.6
0.33HP/.25KW 1.5 0.8
.5HP/.37KW 2 1
.75HP/.56KW 2.8 1.4
1HP/.75KW 3.6 1.8
1.5HP/1.12KW 5.2 2.6
2HP/1.5KW 6.8 3.4
3HP/2.25KW 9.6 4.8
5HP/3.73KW 15.2 7.6
7.5HP/5.6KW 22 11
10HP/7.5KW 28 14
15HP/11.2KW 42 21
20HP/15KW 54 27
25HP/18.6KW 68 34
30HP/22.4KW 80 40
40HP/30KW 104 52
50HP/37.3KW 130 65
60HP/44.7KW 154 77
75HP/55.93KW 192 96
100HP/75KW 249 124
125HP/93.2KW 312 156
150HP/111.9KW 360 180
200HP/150KW 480 240
300HP/223.7KW 700 350
400HP/300KW 925 463