IMDSI1M
®
WARNING
INSTRUCTION MANUALS
DO NOT INSTALL, MAINTAIN, OR OPERATE THIS EQUIPMENT WITHOUT READING, UNDERSTANDING,
AND FOLLOWING THE PROPER Bailey Controls INSTRUCTIONS AND MANUALS; OTHERWISE, INJURY
OR DAMAGE MAY RESULT.
AVERTISSEMENT
MANUELS D’OPÉRATION
NE PAS METTRE EN PLACE, RÉPARER OU FAIRE FONCTIONNER L’ÉQUIPEMENT SANS AVOIR LU, COM-
PRIS ET SUIVI LES INSTRUCTIONS RÉGLEMENTAIRES DE Bailey Controls TOUTE NÉGLIGENCE À CET
ÉGARD POURRAIT ÊTRE UNE CAUSE D’ACCIDENT OU DE DÉFAILLANCE DU MATÉRIEL.
PERTURBATIONS DU PROCÉDÉ
L’ENTRETIEN DOIT ÊTRE ASSURÉ PAR UNE PERSONNE QUALIFIÉE EN CONSIDÉRANT L’ASPECT SÉCU-
RITAIRE DES ÉQUIPEMENTS CONTRÔLÉS PAR CE PRODUIT. L’AJUSTEMENT ET/OU L’EXTRACTION DE
CE PRODUIT PEUT OCCASIONNER DES À-COUPS AU PROCÉDÉ CONTRÔLE LORSQU’IL EST INSÉRÉ
DANS UNE SYSTÈME ACTIF. CES À-COUPS PEUVENT ÉGALEMENT OCCASIONNER DES BLESSURES
OU DES DOMMAGES MATÉREILS.
NOTICE
WBPEEUI240752A0
®
Preface Original
List of Effective Pages Original
iii through vii Original
1-1 through 1-8 Original
2-1 through 2-4 Original
3-1 through 3-8 Original
4-1 Original
5-1 through 5-3 Original
6-1 through 6-4 Original
7-1 Original
8-1 Original
A-1 through A-3 Original
B-1 Original
C-1 through C-3 Original
Index-1 through Index-2 Original
When an update is received, insert the latest changed pages and dispose of the super-
seded pages.
NOTE: On an update page, the changed text or table is indicated by a vertical bar in the outer mar-
gin of the page adjacent to the changed area. A changed figure is indicated by a vertical bar in the
outer margin next to the figure caption. The date the update was prepared will appear beside the
page number.
WBPEEUI240752A0
Table of Contents
Page
SECTION 1 - INTRODUCTION ....................................................................................................1-1
OVERVIEW ..................................................................................................................1-1
INTENDED USER .........................................................................................................1-1
MODULE DESCRIPTION ..............................................................................................1-2
INSTRUCTION CONTENT .............................................................................................1-3
HOW TO USE THIS MANUAL ........................................................................................1-3
DOCUMENT CONVENTIONS ........................................................................................1-4
GLOSSARY OF TERMS AND ABBREVIATIONS .............................................................1-4
REFERENCE DOCUMENTS..........................................................................................1-4
NOMENCLATURE ........................................................................................................1-5
RELATED HARDWARE.................................................................................................1-5
SPECIFICATIONS .........................................................................................................1-6
WBPEEUI240752A0 iii
®
iv WBPEEUI240752A0
List of Figures
No. Title Page
List of Tables
WBPEEUI240752A0 v
®
Safety Summary
vi WBPEEUI240752A0
Trademarks and Registrations
WBPEEUI240752A0 vii
SECTION 1 - INTRODUCTION
OVERVIEW
INTENDED USER
OVERVIEW
WBPEEUI240752A0 1-1
INTRODUCTION ®
COMMUNICATION
MODULES
CONTROLWAY
MFP
OTHER MODULES
OTHER I/O
MODULES
T00083A
MODULE DESCRIPTION
The digital input module has three card edge connectors for
external signals and power (P1, P2 and P3). P1 connects to
common (ground) and +5 VDC power. P2 connects the module
to the I/O expander bus to communicate with a control mod-
ule. P3 inputs the digital signals using a cable connected to a
termination unit (TU) or termination module (TM). The termi-
nal blocks (physical connection points) for field wiring are on
the TU/ TM.
MODULE DESCRIPTION
1-2 WBPEEUI240752A0
INTRODUCTION
INSTRUCTION CONTENT
Description and Uses block diagrams and schematics to explain module opera-
Operation tion and input circuitry.
Installation Covers the preliminary steps to install the module and prepare
for operation. It covers dipswitch and jumper settings, mount-
ing, wiring connections, cabling and preoperational checks.
Repair and Replacement Contains procedures that explain how to replace the module.
Procedures
Support Services Explains the services and training that Elsag Bailey makes
available to their customers.
INSTRUCTION CONTENT
WBPEEUI240752A0 1-3
INTRODUCTION ®
DOCUMENT CONVENTIONS
Term Definition
EWS Engineering work station.
Function Code (FC) An algorithm which manipulates specific functions.
These functions are linked together to form the con-
trol strategy.
I/O Expander Bus Parallel communication bus between the control and
I/O modules.
MFP Multi-function processor module. A multiple loop con-
troller with data acquisition and information process-
ing capabilities.
MMU Module mounting unit. A card cage that provides
electrical and communication support for INFI 90
OPEN/Network 90 modules.
OIS Operator interface station. Integrated operator con-
sole with data acquisition and reporting capabilities.
It provides a digital access into the process for flexi-
ble control and monitoring.
TM Termination module. Provides input/output direct
connection between plant equipment and the INFI 90
OPEN/Network 90 modules.
TU Termination unit. Provides input/output direct con-
nection between plant equipment and the INFI 90
OPEN/Network 90 modules.
REFERENCE DOCUMENTS
DOCUMENT CONVENTIONS
1-4 WBPEEUI240752A0
INTRODUCTION
Number Document
I-E92-501-2 Configuration and Tuning Terminal (CTT)
I-E96-192-1 Operation, Operator Interface Station (40 Series)
IIOIS42
I-E96-200 Function Code Application Manual
I-E96-201 Multi-Function Processor (IMMFP01)
I-E96-202 Multi-Function Processor (IMMFP02)
I-E96-203 Multi-Function Processor (IMMFP03/IMMFP03B)
I-E96-209 Logic Master Module (IMLMM02)
I-E96-211 IMMFC03 Multi-Function Controller
I-E96-212 IMMFC04 Multi-Function Controller
I-E96-213 IMMFC05 Multi-Function Controller
I-E96-424 Termination Unit (NTDI01)
I-E96-410 Termination Module (NIDI01)
WBPEEUI200501A0 Module Mounting Unit (IEMMU11/12/21/22)
WBPEEUI220756A0 Operation, Operator Interface Station (40 Series)
IIOIS43
NOMENCLATURE
Nomenclature Description
IMDSI12 Digital input module (24 VDC, 48 VDC, 125 VDC or
120 VAC input)
IMDSI13 Digital input module (24 VDC input)
IMDSI14 Digital input module (48 VDC input)
IMDSI15 Digital input module (125 VDC or 120 VAC input)
RELATED HARDWARE
Nomenclature Description
IEMMU11/12/21/22 Module mounting unit
NIDI01 Termination module, digital input
NKTM01/02 Cable, termination module (PVC)
NKTU01 Cable, termination unit (PVC)
NKTU02 Cable, termination module (PVC)
NOMENCLATURE
WBPEEUI240752A0 1-5
INTRODUCTION ®
Nomenclature Description
NKTU11 Cable, termination unit (non PVC)
NKTU12 Cable, termination module (non PVC)
NTDI01 Termination unit, digital input
SPECIFICATIONS
Property Characteristic/Value
Power consumption 95 mA at 5 VDC (typical), 115 mA maximum
Overvoltage category on inputs II, per IEC 1010-1
Digital inputs 16 channels
IMDSI12
IMDSI13 IMDSI14 IMDSI15
Turn-on voltage (min) 16.8 VDC 20.1 VDC 69.3 VDC 54 VAC
Off-leakage current (max) 7 µA (at Vin 10 µA (at Vin 10 µA (at Vin 10 µA (at Vin
≤12 VDC) ≤12 VDC) ≤60 VDC) ≤60 VAC)
Communication interface Passive contact input interface read by the MFP or logic master mod-
ule (LMM) via the I/O expander bus
Mounting Occupies one slot in a standard INFI 90 OPEN module mounting unit
(IEMMU)
Environmental
Ambient temperature Temperature rating within the cabinet or enclosure applies. INFI 90
(per IEC 68-2-1, 2,14) OPEN internal cabinet rating: 0° to 70° C (32° to 158° F)
Relative humidity 5% to 95% up to 55° C (131° F), noncondensing
(per IEC 68-2-3) 5% to 45% at 70° C (158° F), noncondensing
Pollution degree: 1 (no condensation)
Atmospheric pressure Sea level to 3 Km (1.86 miles)
Air quality (per ISA S71.04, Noncorrosive
Class LA, LB, LC - level 1)
SPECIFICATIONS
1-6 WBPEEUI240752A0
INTRODUCTION
Property Characteristic/Value
Isolation
Normal
(IEC 1010-1, IEC 255, IEC 60) Test Common Mode
Mode
IMDSI12/15
Channel to channel and channel to Insulation resistance 100 MΩ N/A
logic (100/500 VDC)
Dielectric VAC (45 - 65 Hz) or 1.4 kV rms/1min. or N/A
VDC 1.95 kV DC/1min.
Impulse voltage (1.2/50 µS) ±2.55 kVp ±1 kVp
IMDSI13/14
Insulation resistance 100 MΩ N/A
(100/500 VDC)
Dielectric VAC (45 - 65 Hz) or 1 kV rms/1min. or N/A
VDC 1.5 kV DC/1min.
Impulse voltage (1.2/50 µS) ±2 kVp ±1 kVp
Electromagnetic compatibility
Normal
Test Common Mode
Mode
SPECIFICATIONS
WBPEEUI240752A0 1-7
INTRODUCTION ®
Property Characteristic/Value
Magnetic and electromagnetic
fields (continued)
Radio-frequency common mode, Unmodulated rms: 10 V/m
amplitude modulated, 0.15 MHz Amplitude modulated: 80% AM (1 kHz)
to 80 MHz Source impedance: 150 Ω
(ENV 50141)
Emission test Class A
RF radiated fields, 30 MHz to 1000
MHz (ENV 55011)
CE Mark Declaration This product, when installed in an INFI 90 OPEN cabinet, complies
with the following directives/standards requested for CE marking:
EMC 89/336/EEC EN50081-2 Generic Emission Standard - Part 2: Industrial
Environment
EN50082-2 Generic Immunity Standard - Part 2: Industrial
Environment
Low Voltage Directive 73/23/EEC EN 61010 Safety Requirements for Electrical Equipment for
Measurement, Control and Laboratory Use - Part 1: General
Requirements
Certifications
CSA (Canadian Standards Associ- Certified for use as process control equipment in an ordinary
ation) (non-hazardous) location per CSA C22.2 No. 1010.1-92
SPECIFICATIONS
1-8 WBPEEUI240752A0
SECTION 2 - DESCRIPTION
INTRODUCTION
INPUTS
The IMDSI13 (+24 VDC) module and the IMDSI14 (+48 VDC)
module have a fixed configuration and do not require any
jumper selections. The IMDSI15 (+125 VDC/120 VAC) module
has jumpers to select DC or AC mode. The IMDSI12 (+24, +48,
+125 VDC or 120 VAC) module has jumpers to select the DC
or AC mode and jumpers to select the working voltage. Refer to
the Installation section for an explanation of the jumper con-
nections.
Input Circuits
INTRODUCTION
WBPEEUI240752A0 2-1
DESCRIPTION ®
ADDRESS
SWITCH
P1
LOGIC
1 8 POWER
S1
GROUP A OPEN
LEDs
TP65206B
The control logic block consists of buffers that hold the input
and status byte values. The I/O expander bus interface allows
the control module to read these bytes.
NOTE: The components inside the dashed boxes in Figure 2-2 are
mounted only on the module versions stated in the note.
INPUTS
2-2 WBPEEUI240752A0
DESCRIPTION
A +5 VDC
1 B
+5 VDC
VREF
C + LED
JUMPER
JUMPER B RESISTORS
1 – DIGITAL
DI– INPUT
+5 VDC
NOTE:
A = MOUNTED ON IMDSI12 A,D
B = MOUNTED ON IMDSI14 VREF
C = MOUNTED ON IMDSI13
D = MOUNTED ON IMDSI15 JUMPER
ISOLATION
T00103A
The contact input signals connect to the 30-pin card edge con-
nector (P3), shown in Figure 2-1, using a termination cable
from a termination unit or termination module.
CONTROL LOGIC
Status Byte
CONTROL LOGIC
WBPEEUI240752A0 2-3
DESCRIPTION ®
LOGIC POWER
The DSI uses a custom gate array to perform the I/O expander
bus interface function. All the control logic and communica-
tion protocol are built into an integrated circuit (IC). This IC
provides the following functions:
LOGIC POWER
2-4 WBPEEUI240752A0
SECTION 3 - INSTALLATION
INTRODUCTION
SPECIAL HANDLING
NOTE: Always use the Elsag Bailey field static kit (part number
19483851, consisting of two wrist straps, ground cord assembly,
alligator clip, and static dissipating work surface when working with
static sensitive devices. The kit is designed to connect the techni-
cian and the static dissipating work surface to the same ground
point to prevent damage to the static sensitive devices by electro-
static discharge.
INTRODUCTION
WBPEEUI240752A0 3-1
INSTALLATION ®
SETUP/PHYSICAL INSTALLATION
1 2 3 4 5 6 7 8
OPEN
MSB LSB
MUST I/O
REMAIN ADDRESS
CLOSED
NOTE: OPEN POSITION = LOGIC 1 TP65205B
SETUP/PHYSICAL INSTALLATION
WBPEEUI240752A0 3-3
INSTALLATION ®
IMDSI12 module To set the jumpers for the IMDSI12 module, refer to following
procedures.
1. Refer to Table 3-2 and start with input A1, jumper J1.
Move to the right and locate the desired working voltage. Note
the jumper/pin position. Position the J1 jumper strap in that
position.
2. Refer to Table 3-3 and start with input A1, jumper J2.
Move to the right and locate the correct digital input mode (AC
or DC) and note the jumper/pin position. Position the J2
jumper strap in that position.
3. Repeat steps 1 and 2 until the jumpers are set for group A
and group B inputs.
IMDSI15 module To set the jumpers for the IMDSI15 module, refer to following
procedures.
1. Refer to Table 3-3 and start with input A1, jumper J2.
Move to the right and locate the correct digital input mode (AC
or DC) and note the jumper/pin position. Position the J2
jumper strap in that position.
SETUP/PHYSICAL INSTALLATION
3-4 WBPEEUI240752A0
INSTALLATION
2. Repeat step 1 until the jumpers are set for group A and
group B inputs.
125 VDC/
Input Jumper +24 VDC +48 VDC
120 VAC
A1 J1 2-3 1-2 3-4
A2 J3 2-3 1-2 3-4
A3 J5 2-3 1-2 3-4
A4 J7 2-3 1-2 3-4
A5 J9 2-3 1-2 3-4
A6 J11 2-3 1-2 3-4
A7 J13 2-3 1-2 3-4
A8 J15 2-3 1-2 2-3
B1 J17 2-3 1-2 3-4
B2 J19 2-3 1-2 3-4
B3 J21 2-3 1-2 3-4
B4 J23 2-3 1-2 3-4
B5 J25 2-3 1-2 3-4
B6 J27 2-3 1-2 3-4
B7 J29 2-3 1-2 3-4
B8 J31 2-3 1-2 3-4
SETUP/PHYSICAL INSTALLATION
WBPEEUI240752A0 3-5
INSTALLATION ®
Termination Configuration
Physical Installation
4. Align the digital input module with the guide rails in the
MMU; gently slide the module in until the front panel is flush
with the top and bottom of the MMU frame and the module is
seated in the cable to the termination device.
SETUP/PHYSICAL INSTALLATION
3-6 WBPEEUI240752A0
INSTALLATION
The DSI has three card edge connectors to supply logic power,
establish I/O expander bus communication and provide digital
inputs (P1, P2, P3 respectively).
Wiring
Cable Connections
P1
NKTM01/02
IMDSI1
OR 16 DIGITAL FIELD INPUTS
P3
NKTU02/12
P1 NIDI01 (24/48/125 VDC OR 120 VAC)
P2
P1
IMDSI1
NKTU01/11 16 DIGITAL FIELD INPUTS
P3 P1 NTDI01
(24/48/125 VDC OR 120 VAC)
P2
T00105A
FUSING
The IMDSI1 digital input module does not have any on board
fusing requirements.
PREOPERATING ADJUSTMENTS
PREOPERATING ADJUSTMENTS
3-8 WBPEEUI240752A0
SECTION 4 - OPERATING PROCEDURES
INTRODUCTION
INDICATORS
The DSI module has point (input) status LED indicators on the
front panel to aid in system test and diagnosis. There are 16
LEDs divided into two groups of eight (group A and group B).
The location of the LEDs is shown in Figure 4-1. Each indicator
represents a digital input. A red LED indicates an energized
input. A blank LED indicates a non-energized input.
START-UP PROCEDURES
CAPTIVE RETAINING
SCREW IN LOCKED
POSITION
IMDSI12
1
2
3
4 A
5
6
7
8
INPUT STATUS
1
2
3
4 B
5
6
7
8
CAPTIVE RETAINING
SCREW IN LOCKED
POSITION
T00106A
INTRODUCTION
WBPEEUI240752A0 4-1
SECTION 5 - TROUBLESHOOTING
INTRODUCTION
You can obtain the status of the DSI by checking the control
module for good quality on its input blocks. Use any INFI 90
OPEN operator interface (e.g., Operator Interface Station,
Engineering Work Station, Configuration and Tuning Termi-
nal) to do this.
NOTE: If you look at the DSI front panel input status LED indicators
and there are no LEDs lit, this may indicate a faulty DSI (an input
must be energized to light an LED). Check the control module for
bad quality on its input blocks.
- or -
INTRODUCTION
WBPEEUI240752A0 5-1
TROUBLESHOOTING ®
digital input module and the control module. Verify the bus
connection on the MMU back plane.
The digital input module has three connection points for exter-
nal signals and power (P1, P2 and P3). Tables 5-1, 5-2 and 5-3
show the pin connections.
Group A Group B
Digital Digital
Pin (+) Pin (-) Pin (+) Pin (-)
Input Input
1 A 1 1 K 9
2 B 2 2 L 10
3 C 3 3 M 11
4 D 4 4 N 12
5 E 5 5 P 13
6 F 6 6 R 14
7 H1 7 7 S1 15
8 H J 8 S 8
NOTE:
1. Shared pin (inputs 7 and 8)
INTRODUCTION
• Antistatic vacuum.
• Screwdriver (medium length).
• Isopryl alcohol (99.5 percent electronic grade).
• Distilled water.
• Compressed air.
• Foam tipped swabs.
• Lint free cloths.
INTRODUCTION
WBPEEUI240752A0 6-1
MAINTENANCE ®
Task Frequency
Check cabinet, module mounting unit backplane assem- Every six
bly, digital input module and termination device for dust. months or dur-
Clean as necessary using an antistatic vacuum. If circuit ing plant shut-
board cleaning is necessary, refer to procedure. down,
Check all signal, power and ground connections that are whichever
associated with the digital input module. Verify that they occurs first.
are secure. Refer to procedure.
This section covers tasks from Table 6-1 that require specific
instructions or further explanation.
3. Work the cloth back and forth parallel to the edge connec-
tor contacts.
Checking Connections
NOTE: Power to the cabinet should be off while performing this pre-
ventive maintenance task.
INTRODUCTION
MODULE REPAIR/REPLACEMENT
1. Push and turn the two front panel captive retaining screws
one half turn to unlatch the module. It is unlatched when the
slots on the screws are vertical and the open end of the slots
face away from the module.
INTRODUCTION
WBPEEUI240752A0 7-1
SECTION 8 - SUPPORT SERVICES
INTRODUCTION
TRAINING
TECHNICAL DOCUMENTATION
INTRODUCTION
WBPEEUI240752A0 8-1
APPENDIX A - TERMINATION UNIT (NTDI01)
CONFIGURATION
INTRODUCTION
+5 VDC
E1 E2 ECO M
1
2
3
+ +
4 FIELD
P3 P1 CONTACT
5
– –
6
7 TERMINAL
8 BLOCKS
TB1-TB4
E1 E CO M
DIPSHUNTS
XU1-XU16
INTRODUCTION
WBPEEUI240752A0 A-1
TERMINATION UNIT (NTDI01) CONFIGURATION ®
XU17
1 2 3 4 5 6 7 8
120 VAC
XU17
1 2 3 4 5 6 7 8
XU17
1 2 3 4 5 6 7 8
TP27114A
INTRODUCTION
A-2 WBPEEUI240752A0
TERMINATION UNIT (NTDI01) CONFIGURATION
1 + + + +
A1 XU13 A5 XU9 B5 XU5 B1 XU1
2 – – – –
3 + + + +
A2 XU14 A6 XU10 B6 XU6 B2 XU2
4 – – – –
TERMINAL
NUMBER
5 + + + +
A3 XU15 A7 XU11 B7 XU7 B3 XU3
6 – – – –
7 + + + +
A4 XU16 A8 XU12 B8 XU8 B4 XU4
8 – – – –
TP27163A
INTRODUCTION
WBPEEUI240752A0 A-3
APPENDIX B - TERMINATION MODULE (NIDI01)
CONFIGURATION
INTRODUCTION
The IMDSI1 digital input module can use a NIDI01 for termi-
nation. Jumpers on the NIDI01 Termination Module configure
the digital inputs. The digital input module accepts inputs of
24 VDC, 48 VDC, 125 VDC and 120 VAC, depending on the
module selected. Refer to Table 1-3 for the variations available.
Application/Signal
Jumper Configuration
Type
24 VDC, 48 VDC, J1-J10
125 VDC, 120 VAC 1 2 3 4 5 6 7 8 9 10
TP27115A
TERMINAL NUMBER
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
NOT
USED 8B 7B 7B 6B 5B 4B 3B 2B 1B 8A 7A 7A 6A 5A 4A 3A 2A 1A
8B 8A
TP27159A
INTRODUCTION
WBPEEUI240752A0 B-1
APPENDIX C - QUICK REFERENCE INFORMATION
INTRODUCTION
1 2 3 4 5 6 7 8
OPEN
MSB LSB
MUST I/O
REMAIN ADDRESS
CLOSED
NOTE: OPEN POSITION = LOGIC 1 TP65205B
INTRODUCTION
WBPEEUI240752A0 C-1
QUICK REFERENCE INFORMATION ®
INTRODUCTION
C-2 WBPEEUI240752A0
QUICK REFERENCE INFORMATION
125 VDC/
Input Jumper +24 VDC +48 VDC
120 VAC
A1 J1 2-3 1-2 3-4
A2 J3 2-3 1-2 3-4
A3 J5 2-3 1-2 3-4
A4 J7 2-3 1-2 3-4
A5 J9 2-3 1-2 3-4
A6 J11 2-3 1-2 3-4
A7 J13 2-3 1-2 3-4
A8 J15 2-3 1-2 2-3
B1 J17 2-3 1-2 3-4
B2 J19 2-3 1-2 3-4
B3 J21 2-3 1-2 3-4
B4 J23 2-3 1-2 3-4
B5 J25 2-3 1-2 3-4
B6 J27 2-3 1-2 3-4
B7 J29 2-3 1-2 3-4
B8 J31 2-3 1-2 3-4
INTRODUCTION
WBPEEUI240752A0 C-3
Index
C J
Cable connections ...................................................... 3-7
Jumper settings...........................................................3-2
Certifications............................................................... 1-7
Checking connections ................................................ 6-4
Cleaning L
Edge connectors................................................... 6-3 Logic master module...................................................1-5
Printed circuit boards ............................................ 6-2 Logic power..........................................................2-1, 2-4
Communication levels ................................................ 1-1
Configuration and Tuning Terminal (CTT).................. 1-5
M
Control logic ........................................................ 2-1, 2-3
Conventions, document.............................................. 1-4 Maintenance ...............................................................6-1
Schedule ...............................................................6-1
D Tools required .......................................................6-1
Module description......................................................1-2
DC/AC mode jumper settings ..................................... 3-2 Module mounting unit..................................................1-4
Digital inputs ........................................................ 1-6, 2-1 Module replacement ...................................................7-1
Dipshunt ..............................................................3-6, A-1 Multi-function processor module ..........................1-4, 1-5
E N
Electromagnetic compatibility ..................................... 1-7 NIDI01 termination module .........................................3-7
Errors Nomenclature..............................................................1-5
Control module ..................................................... 5-1 NTDI01 termination unit ...................................... 3-7, A-1
Indications............................................................. 5-1
MISSING SLAVE MODULE.................................. 5-1
O
EWS ........................................................................... 1-4
Operator interface station ...........................................1-4
F Overview .....................................................................1-1
WBPEEUI240752A0 Index - 1
®
Index (continued)
R T
Reference documents .................................................1-4 Technical documentation............................................ 8-1
Related hardware........................................................1-5 Termination configuration
Relative humidity.........................................................1-7 Termination module (TM) ..................................... 3-6
Replacement parts ......................................................8-1 Termination unit (TU) ............................................ 3-6
Replacement, module .................................................7-1 Termination module (TM) ........................................... 1-4
Termination unit (TU)................................... 1-4, 1-5, A-1
S Training....................................................................... 8-1