Generalities
A
E
Language interface
F
Diagnostic
At a Glance :
Analog modules are standard format modules, this offer is made up of
two Input modules :
4 channels for the BMX AMI 0410 module
The BMX AMI 0410 module offers the following range for each
input :
1. +/-10 V
2
2. 0 10 V
0..10
3. 0..5 V / 0..20 mA
4. 1..5 V / 4..20 mA
5. +/- 5 V +/- 20 mA
At a Glance :
Analog modules are standard format modules, this offer is made up of
two Input modules :
4 channels for the BMX ART 0414 module
At a Glance :
Analog modules are standard format modules, this offer is made up of
one output Input module :
2 channels for the BMX AMO 0210 module
BMX ART 0414 module is a multi-range acquisition device with four inputs
isolated from each other.
other This module offers the following ranges for each
input,according to the selection made at configuration:
Analog modules are standard format modules, this offer is made up of one
output Input module :
2 Analog Output and 4 Analog Input for the BMX AMM 0600 module
-2a analog
a og output notot isolated
so ated from
o oone
e ot
other.
e Itt o
offers
e s tthe
e following
o o g
ranges for each output:
Voltage +/-10 V
BMX AMM 0600 Current 0..20 mA and 4..20 mA
- 4 analog input offers the following range for each input:
+/-10 V,0..10 V,
0..5 V / 0..20 mA,
1..5 V / 4..20 mA,
+/- 5 V +/- 20 mA
20-pin connector
2 -BMX AMI 0410
-BMX AMO 0210
40-pin connector
3 - BMX ART 0414
Operationnal mode OK
Module out of service
Channel not configured S
Internal fault
BMX AMO 0210
1 only => Not calibrated
Communication fault with S
CPU
Module not configured S
BMX ART 0414 only => Fault over range S S S S
Sensor fault F F F F
5V or 1000°c
Module type BMX AMI 0410 4 Analog isolated input high level
Input Voltage and current input ( Internal resistor protected
until +/- 30Vdc)
Channel number 4
periodic acquisition for the declared channels used 1 ms + 1 ms for each channel used
R
Resolution
l ti 16 bits
Max Current + / - 30 mA
Measurement range +/-10 V, 0..10 V, 0..5 V / 1..5 V, 0..20 mA, 4..20 mA, +/- 20 mA
+/- 5 V
Max value + / - 11,4V + / - 30 mA
Resolution ( 16 bits ) 0,35 mV 0,92 AA
Internal resistor - 250 Ohms
Resistor occurancy - 0.1% - ( 25 ppm/°C)
Measurement error:
1. at 25°C 0,05 % de Full Scale 0,15 % de Full Scale
2. Maximum in the range (0..60°C) 0,1 % de Full Scale 0,3 % de Full Scale
NC 6 5 NC
COM 1 8 7 IN_Voltage
Channel 1
NC 10 9 IN_Current
channel 1
COM 2 12 11 IN_Voltage
Channel 2
NC 14 13 IN_Current
Channel 2
NC 16 15 NC
COM 3 18 17 IN_Voltage
Channel 1
NC 20 19 IN_Current
Channel 1
NC 6 5 NC
COM 1 8 7 IN_V Ch 1
NC 10 9 IN_I Ch 1
COM 2 12 11 IN V Ch 2
IN_V +
NC 14 13 IN_I Ch 2
-
NC 16 15 NC
COM 3 18 17 IN_V Ch 1
At a Glance :
ABE7CPA410
ABE7CPA410
The cycle time values are based on the channel used according with the configuration done ( by
default all the channel are used )
Module cycle is not synchronized with the PLC cycle. at the beginning of each PLC cycle,
each channel value is taken into account.
If the MAST/FAST task cycle time is less than the module's, some values will not have changed.
System
IN Ch0 Example :
1 If xxx
Then..
e
Ch1
In our application the scan time of
… Ch2
the CPU is 4 ms and we use 4
CPU Scan OUT Ch3
Channels on the BMX AMI 0410.
time : IN system
= 4ms 2 If xxx
Then..
Ch0
… Ch1
1 In the first scan time we obtain the value
OUT Ch2 read in one scan time of the module.
IN Ch3
3 If xxx
System 2 Like the cycles are not synchronized, not
Then..
…
Ch0 all channel information will be read in the
OUT
Ch1 scan
Ch2
IN PLC scan time should be long enough to
read all the channels used.
Stategy and communication 21
BMX AMI 0410: Software
Scale for 0 to
100%
left
Symbol
used for
the channel
Forced or
The value The filter The value of
Unforced a
read used the offset
value
Measurement range +/- 40mV, +/- 80mV, +/- 160mV, 400 Ohms ( 2 or 3 wires )
+/- 320mV, +/- 640mV, +/- 1280mV, 3850 Ohms ( 2 or 3 wires )
Measurement range B E J K L
-130 -270 -200 +760°C -270 + -200 + 900°C
+1820°C +1000°C 1370°C
Measurement range N R S T U
-270 -50 +1665°C -50 + 1665°C -270 + 400°C -200 + 600°C
+1300°C
+1300 C
Resolution 0.1 °C
Detection type Open circuit
Measurement error:
1. at 25°C +/-3 °c ( J,K,E,T,U) +/-5°c ( S,R,B,N,L )
2. Maximum in the range (0..60°C) +/-5 °c ( J,K,E,T,U) +/-8°c ( S,R,B,N,L )
This error is given with the TELEFAST Cold junction compensation
Eg : If we use the PT100 input on the channel 0 the error will be divise by 2
18 38
using
CJ0 CJ-
37
TELEFAST
17 MS- MS+
16 EX- EX+ 36
15 NC NC 35
14 NC NC 34
9 NC NC 29
8 NC NC 28
7 MS- MS+ 27
6 EX- EX+ 26
5 NC NC 25
4 NC NC 24
3 NC NC 23
2 MS- MS+ 22
1 EX- EX+ 21
13 NC NC 33
12 MS- MS+ 32
RTD 2 Wires
11 EX- EX+ 31
10 NC NC 30
9 NC NC 29
8 NC NC 28
5 NC NC 25
4 NC NC 24
3 NC NC 23
Thermocouple
Channel 0
RTD ( 2 wires )
9 NC NC 29
0°c. But in our case the cold
8 NC NC 28
junction is never egal to 0°C so
7 MS- MS+ 27
we must measure and apply a
correction called : 6 EX- EX+ 26
5 NC NC 25
cold junction compensationThis 4 24
NC NC
compensation is applied
3 NC NC 23
according with the formula :
2 MS- MS+ 22
19 DTC CJ+ 39
- 2 wires / 3 wires / 4 wires 38
18 CJ0 CJ-
RTD ?
17 MS- MS+ 37
16 EX- EX+ 36
15 NC NC 35
14 NC NC 34
4
3 wires :: In
2 wires In this
this case
case the current
we use the 13 NC NC 33
i
generator
same wireand for :the measure are 12 32
MS- MS+
separate - one wire is used for RTD 2 Wires
current g the current
generator andgenerator
for the measure 11 EX- t EX+ 31 i
The measure is given without error. 10 NC NC 30
andit’s mandatory to use
For this wiring 9 NC NC 29
exactly thethesame resistor for the three
measure 8 NC NC 28 i
wires. 27
7 MS- MS+ RTD 3 Wires
so the measure is given with an error
The
due module provideofathe
to the resistor specific
wire used to
6 EX- t EX+ 26 i
algorithmic to calculate
provide the current. the resistor of 5 NC NC 25
i
Stategy and communication 36
BMX ART 0414: Software
Configuration
Type of
measure
This function
Selecting is dedicated
where to eliminate
the cold junction is a perturbation coming from
the power supply .
realized
Rule :
If the electrical supply network = 60hz =>selecting 60 hz (Ex: US)
If the electrical supply network = 50hz =>selecting 50 hz (Ex: Fr)
We use or not the channel .
Remenber : 1 channel RTD used Scantime 400ms
Only thermocouples used Scantime 200ms
Overflow automatically
Scale
calculed
asked according with the
Scale
Overflow automatically
calculated according to the
scaling values
Symbol
used for
the channel
Foreced or
The value The filter The value of
Unforced a
read used the offset
value
Module type BMX AMI 0210 2 Analog isolated output high level
output Voltage and current output
Channel number 2
Overflow control
ERR ERR
NC 1 1 NC
NC 12 11 NC
2 1
NC 1 1 NC
NC 14 13 NC
4 3
NC 1 1 NC
NC 16 15 NC
6 5
+ -
COM 1 1 1 OUT ch 1
COM 1 18 U_I17 OUT channel 1
The TERMINAL block is 8 7 Voltage _Current
provided with accessories NC NC
for keying NC 2 1 20 19 NC
0 9
left
Symbol
used for
the
channel Forced
or
Unforced The value Fallback The value for the
a value Write value used alignement
on fault
% I, Q, X, W, D r m c i j
M, K F
left
IfIfthe
thefault
faultisisaaover
over
range
rangethese
theselamps
lamps
provide
provide ififthe
thevalue
value In this example the
is
isover
over or
orunder
underthethe fault is due to a
limit
limit overflow
left