Вы находитесь на странице: 1из 45

Full Scale Testing on

Indonesian Reinforced Masonry


House

RIHS Research Team


Friday, November 12, 2010

M I N I S T RY OF P U B L I C W
KS
AGENCY FOR RESEARCH A
DEVELOPMENT
RESEARCH INSTITUTE FOR 1 HUM
SETTLEMENTS
BACKGROUND
• Indonesia is an earthquake prone area
• Many public houses that were damaged by
earthquake
• Technical guidelines for earthquake
resistant houses that circulate in the
community has not been tested in
laboratory

2
OBJECTIVE
• Knowing the reliability of earthquake-
resistant houses under the technical
guidance that circulate in the community
• Provide recommendations on earthquake-
resistant brick house that has been tested
to the community

3
Scope of Research
Start

Evaluation of existing
earthquake-resistant housing
design
Preparation of
specimen

Testing of
specimen
Material Full Scale House

Analysis &
Evaluation
Recommendation

4
Evaluation of existing earthquake-
resistant housing design
• Design reference:
Buku Saku Persyaratan Pokok Rumah
yang Lebih Aman, 2009.
(Hand Book of Principal Requirement for
Safer Houses) published by Ministry of
Public Works, JICA and Provincial
Government of West Sumatera)
• 36 m2 Reinforced masonry house

5
Specification
• Concrete : 1 PC : 2 Sand : 3 Gravel +0.5
Water
• Mortar : 1 PC : 4 Sand
• Reinforcing Steel, round bar, fy = 240 MPa
• Brick : Compressive Strength = 5 MPa

6
Layout

7
Section 1-1

8
Section 1-1

9
Section B-B

10
Section B-B

11
Tie Beam
Dimension : 15 cm x 20
cm
Main reinforcing : 4 φ 10 mm
Stirrup : φ 8 mm -150
Concrete cover : 15 mm

Column
Dimension : 15 cm x 15 cm
Main reinforcing : 4 φ 10 mm
Stirrup : φ 8 mm -150
Concrete Cover : 15 mm
12
Ring Beam
Dimension : 12 cm x 15
cm
Main Reinforcing : 4 φ 10 mm
Stirrup : φ 8 mm - 150
Concrete Cover : 10 mm

column

Tie beam

Column to tie beam Column to ring beam connection


13
connection in corner
Detailing

14
Preparation of specimens

15
Preparation of specimens

16
Preparation of specimens

17
Preparation of specimens

18
Anchorage every 6 layer
Preparation of specimens

19
SCOPE OF TESTING
• Material Testing
– Brick testing
– Reinforcing steel testing
– Concrete testing
– Mortar testing
• Full Scale Testing
– Reinforced masonry house

20
Brick Testing
• Compressive strength of brick
– Based on SII 0021-78
– 16 samples
• Horizontal shear strength of brick
– Based on SNI 03-4164-1996
– 3 samples with plaster
– 3 samples without plaster
• Diagonal shear strength of brick
– Based on SNI 03-4164-1996
– 3 samples with plaster
– 3 samples without plaster

21
Compressive strength of brick

Rapid testing of
compressive strength of
brick 22
Compressive strength of brick

Failure pattern
Set Up

Failure pattern Failure pattern 23


Horizontal Shear Strength Test

24
Horizontal Shear Strength Test

With plaster Without plaster

Failure pattern Failure pattern


25
Diagonal Shear Strength Test

No. Shear Area P max Shear Strength Shear Modulus


Strain
Sample mm2 N MPa MPa
With Plaster
1 90805 203500 2.24 0.0184 122
2 90480 168000 1.86 0.0166 111.75
3 89440 139100 1.56 0.0177 87.87
average 1.88 107.21
Without Plaster
1 64090 27200 0.42 0.0077 54.95
2 64090 23900 0.37 0.0081 46.08
3 64090 25300 0.39 0.0059 66.91
average 0.40 55.98

26
Diagonal Shear Strength Test

With plaster Without plaster

Failure pattern Failure pattern


27
Reinforcing Bar Testing

• Tensile strength test


– Based on SNI 07-2529-1991 tentang Metode
Pengujian Kuat Tarik Baja Beton

28
Yield and Ultimate Strength
Load Strength
Kode
ø As
Yield Ultimate Yield Ultimate
(mm) (mm2) (N) (N) (MPa) (MPa)
BU-1 7.60 45.365 15500 23800 341.68 524.64
BU-2 7.60 45.365 15200 23500 335.06 518.03
BU-3 7.60 45.365 15300 23600 337.27 520.23
BU-4 7.60 45.365 15000 23600 330.65 520.23
BU-5 7.60 45.365 15200 23600 335.06 520.23
Average 335.94 520.67

Load Strength
Kode
ø As
Yield Ultimate Yield Ultimate
(mm) (mm2) (N) (N) (MPa) (MPa) Average yield
BU-1 9.80 75.430 26500 28800 351.32 381.81 strength of φ8 and
BU-2 9.80 75.430 27300 42000 361.93 556.81 φ10 reinforcing bar
BU-3 9.80 75.430 27200 42200 360.60 559.46
BU-4 9.80 75.430 27200 42600 360.60 564.76 = 335.94 MPa &
BU-5 9.80 75.430 25900 38800 343.37 514.39 355.56 MPa higher
Average 355.56 515.45 than spec, fy 240
MPa
29
Concrete Test

• Compressive Test
– Based on SNI 03-1974-1990 tentang ”Metoda
Pengujian Kuat Tekan Beton”

Slump
30
test
Compressive Test
Foundation Data

Tie Beam

31
Compressive Test
Ring Beam Data

Column

32
Mortar Test

• Compressive Test
– Based on SNI 03-1974-1990 tentang ”Metoda
Pengujian Kuat Tekan Beton”

33
Mortar for Wall

34
Mortar for Plastering

35
Full Scale Reinforced Masonry
Testing
• Set up

36
Preparation of specimens

37
Loading Pattern

Based on FEMA 450, target drift is


38
1.191 %
Hystertic Loop Lateral Load vs Lateral Deformation North Side Wall

60

40

20
Lateral Load (tf)

-20

-40

-60
-150 -100 -50 0 50 100 150
Lateral Deformation (mm)

39
Hystertic Loop Lateral Load vs Lateral Deformation Middle Side Wall

60

40

20
Lateral Load (tf)

-20

-40

-60
-150 -100 -50 0 50 100 150
Lateral Deformation (mm)

40
Hystertic Loop Lateral Load vs Lateral Deformation South Side Wall (CH - 4)

60

40

20
Lateral Load (tf)

-20

-40

-60
-150 -100 -50 0 50 100 150
Lateral Deformation (mm)

41
Hystertic Loop Lateral Load vs Lateral Deformation South Side Wall (CH - 6)

60

40

20
Lateral Load (tf)

-20

-40

-60
-150 -100 -50 0 50 100 150
Lateral Deformation (mm)

42
43
Conclusion

To be discussed…..

44
THANK YOU

45