Calculate Air Ventilation for Transformer / D.

G- Room
Density of Air at air 1.099 kg/m3
Specific Heat of Air 0.017 kWxmin/kg x °C
Permissible temperature rise 10.8 °C

Equipment Qty Rating (KVA) Power Factor Efficiency


Transformer 1 1000 0.98 98.0%
Transformer 2 2000 0.98 98.0%

Total Heat Loss 98 Kw


Total Heat Loss 5576.2 Btu/Min
Total Heat Loss 334572 Btu/Hr
Air Quantity Required for ventilation 486 M3/Min
Air Quantity Required for ventilation 17150 CFM
Ventilation System
Fan Capacity 18000 CFM
No's of Fan 1 No's
Fan Rating 4 Kw
D.G- Room

Rating (Kw) Heat Loss (Kw)


980 19.6
1960 78.4
0
0
0
0
98