Академический Документы
Профессиональный Документы
Культура Документы
Calculation:
Size of Anchor Fastner 10 MM
No of Anchor Fastner / Support 4 No
Basic Tensile Load / Fastner 3.5 KN
Basic Tensile Load / Fastner 357 Kg/Meter
Total Tensile Load 1428 Kg/Meter
% Spare Load Capacity 267%
Size of Anchor Fastner O.K
*Hangers shall be designed to support five times the weight of water-filled pipe plus 250 lb (115 kgs) at
support (NFPA 13 9.1.1.1.).
Water Pipe Support Jignesh.Parmar , www.electricalnotes.wordpress.com, jiguparmar@yahoo.com
MILD STEEL PIP
Nominal Bore Outside Diameter
INCH MM INCH MM
103.5 1/8" 3 mm 0.406 10.32
di = do - 2 t 1/4" 6 mm 0.532 13.49
3/8" 10 mm 0.872 17.1
1/2" 15 mm 0.844 21.43
3/4" 20 mm 1.094 27.2
wp= (π / 4) ρm (do2 - di2) 1" 25 mm 1.312 33.8
w= (π / 4) [ρm (do2 - di2) + ρl di2] 1.1/4" 32 mm 1.656 42.9
1.1/2" 40 mm 1.906 48.4
2" 50 mm 2.375 60.3
2.1/2" 65 mm 3.004 76.2
3" 80 mm 3.5 88.9
4" 100 mm 4.5 114.3
5" 125 mm 5.5 139.7
6" 150 mm 6.5 165.1