BOILER STEAM & WATER SYSTEM

Nama Set Point Unit Remark


HHH 250 Trip (2 out of 3)
HH 125 Alarm
H 50 Alarm
Drum Level mmH2O
L -50 Alarm
LL -200 Alarm
LLL -350 Trip (2 Out of 3)
Interlock Open ERV
H 18.2
No.1
SH Outlet Steam Pressure No.1 MPa
Interlock Close ERV
L 17.9
No.1
Interlock Open ERV
H 18.5
No.2
SH Outlet Steam Pressure No.2 MPa
Interlock Close ERV
L 18.2
No.2
Interlock Open ERV
H 18.5
No.3
SH Outlet Steam Pressure No.3 MPa
Interlock Close ERV
L 18.2
No.3

AIR & GAS SYSTEM


Nama Set Point Unit Remark
HH 3240 Trip (2 Out of 3)
H 996 Alarm
Furnace Pressure No.1,2,3,4 Pa
L -996 Alarm
LL -2490 Trip (2 Out of 3)
Interlock Start Oil
H 60
0 Pump
APH Guide Bearing Temp. C
Interlock Stop Oil
L 50
Pump
Interlock Start Oil
H 50
0 Pump
APH Pedestal/Support Bearing Temp. C
Interlock Stop Oil
L 45
Pump
Interlock Start
Seal Air Fan Outlet & PA. Header DP L 4 kPa
Standby Fan
Furnace/Winbox DP (L/R) H 2.3 kPa Alarm
PA/Furnace DP NO.1 & No.2 LL 5 kPa Alarm
Interlock Start
L 3.5 kPa
Flam Cooling Fan Outlet Header Standby Fan
H 3.5 kPa Alarm
Flam Cooling Fan Outlet Header No.1,2,3 LL 2.8 kPa Trip (2 Out of 3)
Flam Cooling Fan Inlet Filter H 0.75 kPa Alarm
FD FAN

Nama Set Point Unit Remark


H 70 0 Alarm
FD Fan Bearing Temp. C
HH 80 Trip
H 80 0 Alarm
FD Fan Motor Bearing Temp. C
HH 95 Trip
H 110 0 Alarm
FD Fan Motor Stator Winding Temp. C
HH 120 Trip
H 4.5 Alarm
FD Fan Bearing Vibration mm/s
HH 6.3 Trip
Interlock Start FD
N 2.5
Fan
Lube Oil Press MPa
Interlock Start
L 0.8
Standby Pump
Lube Oil Flow L 3 L/min Alarm
Lube Oil Filter DP H 0.35 MPa Alarm
Lube Oil Tank Level L Alarm
Interlock Start
L 20
0 Heater
Lube Oil Tank Temp. C
Interlock Stop
H 35
Heater
DP Alarm to Proteck H 5 kPa Alarm

ID FAN

Nama Set Point Unit Remark


H 70 0 Alarm
ID Fan Bearing Temp. C
HH 80 Trip
H 80 0 Alarm
ID Fan Motor Bearing Temp. C
HH 95 Trip
H 110 0 Alarm
ID Fan Motor Stator Winding Temp. C
HH 120 Trip
H 4.5 Alarm
ID Fan Bearing Vibration mm/s
HH 6.3 Trip
Interlock Start FD
N 0.3
Fan
Lube Oil Press MPa
Interlock Start
L 0.2
Standby Pump
Lube Oil Flow L 3 L/min Alarm
Lube Oil Filter DP H 0.1 MPa Alarm
Lube Oil Tank Level L Alarm
Interlock Start
L 25
0 Heater
Lube Oil Tank Temp. C
Interlock Stop
H 35
Heater
DP Alarm to Proteck H 5 kPa Alarm

PA FAN
Nama Set Point Unit Remark
H 90 0 Alarm
PA Fan Bearing Temp. C
HH 100 Trip
H 80 0 Alarm
PA Fan Motor Bearing Temp. C
HH 90 Trip
H 110 0 Alarm
PA Fan Motor Stator Winding Temp. C
HH 130 Trip
H 5.6 Alarm
PA Fan Bearing Vibration mm/s
HH 7.1 Trip
H 0.4 Alarm
Lube Oil Press MPa
L 0.1 Alarm
Lube Oil Filter DP H 0.1 MPa Alarm
Lube Oil Tank Level L Alarm
Interlock Start
L 25
0 Heater
Lube Oil Tank Temp. C
Interlock Stop
H 35
Heater

MILL

Nama Set Point Unit Remark


H 85 0 Alarm
Mill Motor Bearing Temp. C
HH 95 Trip
H 135 0 Alarm
Mill Motor Stator Winding Temp. C
HH 145 Trip
H 71 0 Alarm
Mill Outlet Temp. C
HH 93 Trip
Mill Grinding Bowl Upper & Lower DP H 3.25 MPa Alarm
Mill Seal Air & Inlet PA DP L 3 kPa Alarm
Lube Oil Flow L 121 L/min Alarm
L 0.09 Alarm
Lube Oil Filter Outlet Pressure MPa
LL 0.07 Trip Mill
Lube Oil Filter DP H 0.2 MPa Alarm
Lube Oil Tank Level L 200 mm Alarm
Interlock Start
L 25
0 Heater
Lube Oil Tank Temp. C
Interlock Stop
H 49
Heater
L 30 0 No Allowed Start
Mill Reduce Box Inlet Oil Temp C
HH 65 Alarm
H 75 0 Alarm
Mill Gear Box Bearing Temp C
HH 80 Trip
H 85 0 Alarm
Mill Gear Box Drive Shaft Bearing Temp. C
HH 90 Trip

OIL SYSTEM
Nama Set Point Unit Remark
H 1.8 Alarm
Fuel Oil Pressure L 0.4 MPa Alarm
LL 0.3 Trip (2 Out Of 3)
N 1.9 Fuel Oil Leak Test
Fuel Oil Leak Test Pressure MPa
L 1.85 Alarm
Fuel Oil Adequate Pressure N 1 MPa Allow Fuel Oil
0
Fuel Oil Header Temp OK 10 C Allow Fuel Oil
L 0.5 Alarm
Atomazing Air Header Pressure MPa
LL 0.4 Not Allow

Generator Transformator

Nama Set Point Unit Remark


0
HHH 97 C Trip
0
HH 85 C Trip
GT Oil Temp. 0
H 60 C Start Cooling Fan
0
L 55 C Stop Cooling Fan
0
HHH 120 C Trip
0
HH 110 C Alarm
GT Winding Temp. 0
HH 90 C Start Cooling Fan
0
L 85 C Stop Cooling Fan

CWP

Nama Set Point Unit Remark


H 80 0 Alarm
CWP Motor Upper Guide Bearing Temp. C
HH 90 Trip
H 80 0 Alarm
CWP Motor Upper Thrust Bearing Temp. C
HH 85 Trip
H 115 0 Alarm
CWP Motor Stator Winding Temp. C
HH 120 Trip
H 80 0 Alarm
CWP Motor Bottom Bearing Temp C
HH 90 Trip
Cooling Water Flow L 46 M3/h Alarm
Electrick Filter DP A,B,C H 3 kPa Start Washing
Interlock Start
Secondary Filter DP Side A & B H 6 kPa
Discharging
Interlock Start
CW A & B Strainer Screen DP H 10 kPa
Washing
Interlock Start
LFO Supply Pump Pressure L 1.5 MPa
Standby Pump
Interlock Start
SAC & IAC Outlet Pressure L 0.5 MPa
Standby
AUX BOILER

Nama Set Point Unit Remark


Drum Pressure H 1.1 MPa Alarm
Main Steam Pressure H 1.1 MPa Alarm
Water Pressure H 1 MPa Alarm
Oil Pressure H 2.3 MPa Alarm
Furnace Pressure H 3 kPa Alarm

STEAM BY PASS SYSTEM

Nama Set Point Unit Remark


HP Exhaust Pressure H 4.82 MPa Trip
0
HP Exhaust Temp. HH 428 C Trip (ETS)
0
H 404 C Alarm
HP By Pass Desuperheater Water Spray L 6 MPa Fast Close HP By Pass
LP By Pass Desuperheater Water Spray L 1 MPa Fast Close LP By Pass
Main Steam Pressure H 17.5 MPa Fast Open HP By Pass
LP By Pass Inlet Pressure H 3.8 MPa Fast Open LP By Pass

TURBIN & GENERATOR PROPER (DEH)

Nama Set Point Unit Remark


HH 254 um Trip (ETS)
Turbin Rotor Vibration
H 125 um Alarm
HH -1 -- 1 um Trip (ETS)
Turbin Shaft Position
H -0.9 -- 0.9 um Alarm
Turbin LP Casing Diff Expansion HH 15.92 mm Trip (ETS)
H 15.17 mm Alarm
Turbin Eccentricity H 76 um Alarm
L 1.834 Trip (ETS)
Ratio HP Cylinder Exhaust Steam Press.
LL 1.734 Alarm
0
Bearing 1,2,3,4 Metal Temp. H 107 C Alarm
0
Bearing 5,6,7 Metal Temp. H 99 C Alarm
0
Thtust Bearing metal Temp. H 98 C Alarm
Auto Stop Latched 1,2,3 (Reset) H 6.89 MPa Turbin Latched
HH 3330 rpm Trip
H 1000 rpm Interlock Stop JOP
Turbin Speed L 1000 rpm Interlock Start JOP
200 rpm Interlock Stop Gear
1 rpm Interlock Start Gear
HP & LP HEATER

Nama Set Point Unit Remark


Heater Trip (Close
HHH 238 mm extraction & Open
By Pass Heater)
HP Heater 1,2,3 Interlock Open
HH 188 mm
EMG Drain
H 138 mm Alarm
L 62 mm Alarm
HHH 2650 mm Alarm (Switch)
Interlock Open
HH 2600 mm
EMG Drain
Interlock Open
H 2500 mm
Overflow
Dearator Interlock Close
L 24 mm
EMG Drain
Interlock Close
LL 2200 mm
Overflow
Feedwater Pump
LL 1150 mm
Trip (Switch)
Heater Trip (Close
HH 188 mm extraction & Open
By Pass Heater)
LP Heater 4,6,7,8
Interlock Open
H 138 mm
EMG Drain
L 62 mm Alarm

CONDENSATE SYSTEM

Nama Set Point Unit Remark


HH 80 0 Trip
CEP Thrust Bearing Temp. C
H 75 Alarm
HH 80 0 Trip
CEP Motor Upper Bearing Temp. C
H 70 Alarm
HH 140 0 Trip
CEP Motor Stator Coil Temp. C
H 130 Alarm
Interlock Start
CEP Outlet Pressure L 1.8 MPa
Standby Pump
HH 1800 mm Alarm
Hot Well Level
LL 3000 mm Alarm
Interlock Close
Make Up Water Tank Level H 5000 mm
Make Up Valve
Interlock Open
L 3000 mm
Make Up Valve
MDBFP

Nama Set Point Unit Remark


HHH 2650 Mm Alarm
HH 0.9 MPa Alarm
Dearator
Feedwater Pump
LL 1150 mm
Trip
Feedwater Inlet Filter DP H 0.06 MPa Alarm
HH 50 um Trip
MDBFP Vibration
H 40 um Alarm
MDBFP Lube Oil Filter DP H 0.08 MPa Alarm
Interlock Stop Aux
H 0.26 MPa
Pump
Allowed Start
N 0.17 MPa
MDBFP Lube Oil Pressure MDBFP
Interlock Start Aux
L 0.12 MPa
Pump
LL 0.08 MPa Trip MDBFP
HH 90 um Trip
BFP C Radial Bearing Temp.
H 75 um Alarm
HH 90 um Trip
BFP C Thrust Bearing Temp.
H 75 um Alarm
HH um
BFP C Shell Temp. Alarm
H um
HH 95 um Trip
BFP C Seal Water Temp.
H 80 um Alarm
Booster C Motor Wiring Phase Temp. HH 145 um Trip
H 135 um Alarm
Booster C Motor Radial Bearing Temp. HH 90 um Trip
H 75 um Alarm
Booster C Radial Bearing Temp. HH 90 um Trip
H 75 um Alarm
Couple Radial Bearing Temp. HH 95 um Trip
H 90 um Alarm
Couple Working Oil Cooler Inlet Temp. HH 130 um Trip
H 110 um Alarm
Couple Working Oil Cooler Outlet Temp HH 85 um Trip
H 75 um Alarm
Couple Lube Oil Cooler Inlet Temp. HH 70 um Trip
H 65 um Alarm
Couple Lube Oil Cooler Outlet Temp. HH 60 um Trip
H 55 um Alarm
BFPT

Nama Set Point Unit Remark


HHH 2650 Mm Alarm
HH 0.9 MPa Alarm
Dearator
Feedwater Pump
LL 1150 mm
Trip
Feedwater Inlet Filter DP H 0.06 MPa Alarm
BFPT Exhaust Steam Presure H -60 kPa Alarm
0 Interlock Full Open
HH 120 C
BFPT Exhaust Steam Temp. Spray
0
H 80 C Alarm
HH 6300 Rpm Trip
BFPT Speed H 3000 Rpm Alarm
L 1 Rpm Alarm
BFPT Eccentricity H 0.8 mm Alarm
HH 1.2 mm Trip
H 0.9 mm Alarm
BFPT axial Displacement
L -0.9 mm Alarm
LL -1.2 mm Trip
HH 125 um Trip
BFPT Vibration
H 76 um Alarm
BFPT Oil Tank Level LL 500 mm Alarm
Interlock Start
L 0.12 MPa
Standby Oil Pump
BFPT Lube Oil Pressure Interlock Start DC Oil
LL 0.09 MPa
Pump
0.06 MPa Trip (MEH)
BFPT Vacuum Low L -63 kPa Trip (MEH)
BFPT Safety Oil Pressure H 0.45 MPa Trip (MEH)
L 0.25 MPa Latch
BFPT EH Oil Pressure L 10 MPa Alarm
BFPT Filter DP H 10 kPa Alarm
0
HH 95 C Trip
BFP Seal Water Temp. 0
H 80 C Alarm
0
HH 95 C Trip
BFP Radial Bearing Temp. 0
H 80 C Alarm
0
HH 95 C Trip
BFP Thrust Bearing Temp. 0
H 80 C Alarm
0
HH C Alarm
BFP Shell Temp. 0
H C Alarm
0
HH 145 C Trip
Booster Motor Wiring Phase Temp. 0
H 135 C Alarm
0
HH 95 C Trip
Booster Motor Radial Bearing Temp. 0
H 85 C Alarm
0
Booster Radial Bearing Temp. HH 80 C Trip
0
H 70 C Alarm
VACUUM

Nama Set Point Unit Remark


0
HH 135 C Trip
Vacuum Pump Motor Winding Temp. 0
H 120 C Alarm
0
HH 90 C Trip
Vacuum Pump Bearing Temp. 0
H 80 C Alarm
L -83.3 kPa Alarm
Condenser Vacuum
LL -79 kPa Trip
Allowed Open Inlet
High -88 kPa
Valve
Allowed Stop Stanby
Vacuum Inlet Pressure H -82 kPa
Pump
Allowed Start Stanby
L -90 kPa
Pump
Interlock Close
Vacuum Separator Level H 165 mm
Make Up Valve
Interlock Open
L 120 mm
Make Up Valve

GLAND SEAL STEAM


Nama Set Point Unit Remark
LP Gland Seal Drain Pit Level HH 2/3 L Interlock Open Drain
H 1/3 L Interlock Close Drain
Gland Steam Condensor Level H 200 mm Alarm
Turbin Connection Pipe Press. H 0.0395 MPa Alarm

OCCW PUMP
Nama Set Point Unit Remark
0
HH 135 C Trip
OCCWP Motor Stator Winding Temp. 0
H 130 C Alarm
0
HH 90 C Trip
OCCWP Motor Bearing Temp. 0
H 85 C Alarm
OCCWP Outlet Pressure L 0.06 MPa Alarm
Motor Driven Filter DP H 7 kPa Alarm

CCCW PUMP
Nama Set Point Unit Remark
0
HH 135 C Trip
CCCWP Motor Stator Winding Temp. 0
H 130 C Alarm
0
HH 90 C Trip
CCCWP Motor Bearing Temp. 0
H 85 C Alarm
CCCWP Outlet Pressure L 0.3 MPa Alarm
CCCWBP Outlet Pressure L 0.25 MPa Alarm
TURBIN LUBE OIL

Nama Set Point Unit Remark


Interlock Start DC
DC Oil Pump Auto Start Test Press No. 1,2 L 0.069 MPa
Oil Pump
Interlock Start AC
AC Oil Pump Auto Start Test Press No. 1,2 L 0.075 MPa
Oil Pump
AC & DC Oil Pump Outlet Press. H 0.069 MPa Alarm
Lube Oil Press. No. 1,2,3,4 L 0.045 MPa Trip
L 0.05 MPa Allowed Start JOP
JOP Inlet Press.
LL 0.02 MPa Interlock Stop JOP
HH 6.5 MPa Alarm
JOP Outlet Header Press.
H 4,2 MPa Alarm
0
Thrust Bearing Return Oil Temp. H 107 C Alarm
0
Bearing 1,2,3,4 Return Oil Temp. H 60 C Alarm
0
H 55 C Alarm
Lube Oil Temp. 0
L 23 C Alarm
H 2054 mm Alarm
Lube Oil Tank Level L 1750 mm Alarm
LL 1339 mm Alarm
Main Oil Tank Vacuum No. 1,2 L -0.5 kPa Alarm
Turning Gear Device Disengaged H 0.14 MPa Interlock Stop Gear
Turning Gear Lube Oil Press. L 0.031 MPa Interlock Stop Gear

EH OIL

Nama Set Point Unit Remark


H 558.8 mm Alarm
Not Allow Start
L 438.14 mm
Heater
EH Oil Tank Level
Interlock Stop EH Oil
LL 295.15 mm
Pump
LLL 193.54 mm
0
H 65 C Alarm
EH Oil Tank Temp 0
L 21 C Alarm
0 Interlock Start EH Oil
H 50 C
Pump
EH Oil Temp.
0 Interlock Stop EH Oil
L 35 C
Pump
EH Oil Pump A & B Outlet Filter DP H 0.69 MPa Alarm
Interlock Stanby EH
EH Oil Pump Outlet Header Press. L 11.03 MPa
Oil Pump
EH Oil Press. No. 1,2,3,4 LLL 9.31 MPa Trip (ETS)
OPC Oil Press. Ready H 6.89 MPa
H 9.3 MPa AST 1 or 3 Leak Oil
AST Oil Press.
L 4.14 MPa AST 2 or 4 Leak Oil

HIDROGEN
Nama Set Point Unit Remark
H 0.45 MPa Alarm
Generator Hidrogen Press. L 0.37 MPa Alarm
L 0.42 MPa Alarm (Switch)
Generator Hidrogen Purity L 95 % Alarm
0
Hidrogen Temp. Sisi Exciter & Tubin End H 50 C Alarm
No. 1,2,3,4 Liquid Detector H 1 L Alarm
Hidrogen Leakage Detector H 2 % ALarm

SEAL OIL
Nama Set Point Unit Remark
Air Side Seal AC Pump Inlet & Outlet DP L 35 kPa Alarm
Air Side Seal DC Pump Inlet & Outlet DP H 35 kPa Alarm
Interlock Start
Air Side Seal Oil & Hidrogen DP L 35 kPa
Stanby Pump
Air Side Seal Oil DP Filter H 50 kPa Alarm
Defoaming Tank Oil Level Sisi Exciter Turbin End H 2/3 Alarm
Interlock Start
Hidrogen Side AC Pump Inlet & Outlet DP L 35 kPa
Stanby Pump
Hidrogen Side DC Pump Inlet & Outlet DP H 35 kPa Alarm
Hidrogen Side Seal Oil DP Filter H 50 kPa Alarm
Hdrogen Side Drain Regulator Level H 105 mm Alarm
Smoke Exhaust Fan Inlet & Outlet DP H 3.4 kPa Alarm

GSCW
Nama Set Point Unit Remark
Interlock Start
GSCWP Inlet & Outlet DP L 140 kPa
Stanby Pump
H 165 / 159 kPa Alarm
GSCW Inlet & Outlet DP
L 86 / 87 kPa Alarm
Low Water
GSCW Inlet & Outlet DP No. 1,2,3 LL 66 / 64 kPa
Protection
GSCW Inlet & Outlet DP Filter H 50 kPa Alarm
H 600 mm Alarm
GSCW Tank Level
L 500 mm Alarm
GSCW Make Up Water Flow H 45 L/min Alarm
GSCW Tank Pressure H 42 kPa Alarm
Generator Hidrogen & Water DP L 35 kPa Alarm
0
GSCW Water Inlet Generator Temp. H 53 C Alarm
0
GSCW Water Outlet Generator Temp. H 85 C Alarm
Conductivity Demin Water Output H 1.5 us/cm Alarm
Conductivity 1 GSCW Inlet H 5 us/cm Alarm
Conductivity 2 GSCW Inlet HH 9.5 us/cm Alarm