Вы находитесь на странице: 1из 231

ORISSA POWER TRANSMISSION

CORPORATION LIMITED

CONSTRUCTION OF SUBSTATION ALONG


WITH TRANSMISSION LINE & ASSOCIATED
SYSTEMS

TECHNICAL SPECIFICATION

VOLUME-IIA
BID DOCUMENT NO: NESCL/OPTCL/CS-OS-616-01
(PACKAGE-1)

NTPC ELECTRIC SUPPLY COMPANY LIMITED


IMPORTANT INSTRUCTION TO
BIDDERS

• This volume (Volume-IIA) of technical


specification comprises of two parts- Scope of
Works & Guaranteed Technical Particulars (GTP)
& shall be read in conjunction with technical
specification Volume-II as they are integral parts
of Technical Specification.

• Bidders shall fill up complete Guaranteed


Technical Particulars (GTP) & shall submit along
with Technical Bid(Part-1).
SCOPE OF WORKS

FOR

(PACKAGE-1)
ON TURNKEY BASIS

SUBSTATION & TRANSMISSIONN

LINE PACKAGE

PACKAGE REF. NO:- NESCL/OPTCL/CS-OS-616-01


IMPORTANT NOTE

THE BIDDERS ARE ADVISED TO VISIT THE SITE BEFORE QUOTING


THE BID. THEY SHOULD ASCERTAIN ALL THE REQUIRED DATA
FOR TURNKEY COMPLETION OF THE SUBSTATION AND
ASSOCIATED TRANSMISSION LINES SUCH AS;

1. SOIL BEARING CAPABILITY.

2. REQUIRED BENCHING AND FILLING FOR SITE LEVELLING.

3. TYPE OF STRUCTURES FOR BOTH LINE & SUBSTATION.

4. TOTAL QUANTITY OF ATERIALS/STRUCTURES/EQUIPMENTS.

5. TYPE OF FOUNDATIONS FOR ERECTION OF LINE TOWERS &


SUB STATION EQUIPMENTS/STRUCTURES.

6. ASCERTAINING THE LENGTH OF THE REQUIRED BOUNDARY


WALL, FENCING AND ROADS.

7. ANY OTHER DATA REQUIRED FOR DESIGNING OF THE LINE


& SUBSTATION.
SCOPE OF WORK
1. General
The Employer is strengthening their Transmission and Distribution systems by way of
constructing 220kV and 132kV transmission lines, their associated terminal bays & new
substations at various locations in the state of Odisha as outlined in the detailed scope of work.
The entire works are to be carried out on Turnkey Basis up to final commissioning of all
substations and transmission lines and handing over the same to the Employer,
M/S ORISSA POWER TRANSMISSION CORPOTATION LIMITED.

The broad scope of work under this package covers

i) Establishment of new substations.


ii) Extension of existing substations where ever required.
iii) Construction of new transmission lines.
as per the specification & details provided in the contract documents .
The out line of the works includes

i) Design, manufacture, testing, supply & commissioning of all equipments for different
substations and transmission lines, as detailed in the specifications and schedule of
quantities and in subsequent clauses except supply of power transformer and
PLCC indoor equipments which shall be supplied by the Employer. The contractor
shall load, unload, transport, erect, connect to the system, test and commission the power
transformer & the PLCC equipments. Since there will be LILO on existing lines, the
installations of PLCC equipment at remote (existing) end and proposed end of the sub-
stations shall be under the scope of the contractor. A general single line diagram showing
installations, removing and erection of PLCC equipments has been provided in the
technical specification. An indicative structural layout of the substation has been provided
in the technical specification which may be followed as a basis for finalization of the
substation structural layout in consultation with OPTCL.

ii) Execution of all civil works as per schedule for erection of all substation equipments,
structures and foundation of transformers, control rooms, store sheds, pump house, D&E
type quarters, roads, culverts, rain water harvesting arrangements etc. , construction of
earth mat, cable trench, drainage system, boundary wall etc.

iii) Erection, testing, commissioning of all equipment and handing over of the substation
bays complete in all respect as per approved scheme and to the satisfaction of the
Employer including statutory inspection.

iv) The makes of the equipments/components/materials shall be approved by the employer


before placement of the order with the contractor/manufacturer with necessary
credentials.

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-1 of 23
v) The contractor (s) has the responsibility to arrange construction power supply for
construction of the project. The expenditure for such arrangement till completion of the
project shall be to the contractors account.

vi) The contractor(s) has the responsibility to arrange clean water for construction and curing
to the civil works.

vii) The work as mentioned in the price schedule shall generally be considered for the
evaluation of the bid.

viii) The contractor shall have to engage his own security at his own cost for security of all the
materials including owners supply materials (handed over to him for the site) that are
required for successful completion of the project till final handing over of the entire work
to OPTCL.

ix) Contractor has to obtain Project License in respect of the projects from the competent
authority at his own cost, prior to commencement of works.

x) The scope of work includes the provision of one official copy of each Standard listed in
the appropriate schedule.

2. Detailed Scope of work


The contractor shall be fully responsible for providing all equipment, material, systems and
services which are required to complete the construction and successful commissioning of the
works in all respects excepting those specifically excluded under the clause “1.2 - Specific
exclusions” in the chapter “General Clauses”. The Contractor shall also refer to the Technical
Specification (Vol.-II), for proper understanding of the works involved in respect of each
substation.

The scope of work on Turnkey basis includes design, engineering, manufacture, type testing,
(factory testing) supply on FOR destination site basis, transportation, handling, storage at site,
erection, site testing, commissioning complete in all respects and maintenance of plant and
equipment until handing over of works in accordance with Conditions of Contract and the
stipulations under various chapters of this specification at the prices stated in the Price Schedule
for the following

(a) At SAMUKA BEACH , (District-PURI)

i. 132/33 KV sub station comprising of (1X20 MVA + 1X40 MVA transformers) as


per single line diagram attached for the purpose.
ii. Associated 132 KV LILO transmission line of 11.01 kM on double circuit towers.

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-2 of 23
(b) At CHANDPUR (District-KHURDA)

i. 132/33 KV sub station comprising of (2X12.5 MVA) sub-station as per single line
diagram attached for the purpose.
ii. Associated 132 KV LILO transmission line of 3.21 kM on double circuit towers.

(c) At PURUSHOTAMPUR(District-GANJAM)

i. 132/33 KV sub station comprising of 132/33 KV (2X12.5 MVA)


ii. Associated 132 kV LILO transmission line of 2.5kM on double circuit towers.

A power map of Odisha is enclosed at the end of this chapter to help


bidders locate the proposed work site.
2.1. Substations
2.1.1. Electrical

The scope includes but is not limited to

i) Supply erection, testing & commissioning of the following equipments:


1. Circuit breakers
2. Isolators
3. Current transformers
4. Voltage transformers (capacitive and electromagnetic)
5. CT, CVT, IVT console boxes with aluminium alloy having minimum three mm thickness.
6. All other out door kiosks/boxes, BMKs shall be MS sheet of minimum 2mm thickness
with aluminium alloy canopy of 3mm thickness.
7. Surge arresters
8. Post insulators
9. Protection, control, and metering systems
10. PLCC systems
11. Insulator strings and other hardware
12. Busbar, circuit conductor and all conductor accessories
13. Power and control cables, cabling accessories, cable trays etc.
14. ACDC systems including all distribution boards, battery and charger systems, auxiliary
transformers.
15. Air conditioning plant and systems for control room
16. Fire fighting systems and equipment

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-3 of 23
17. Steel structures for switchyard gantries and portals (lattice type); and equipment (pipe or
lattice type) including those for lightning protection
18. Earthing system and conductors
19. Testing and maintenance equipment
20. Lighting of substation area and substation buildings. Illumination and emergency lighting
system at different locations.
21. Control and relay panels as proposed.
22. Installation of 220 V battery sets and 48 Volts Battery sets as proposed with suitable
Battery chargers for the above batteries.
23. Event logger panel
24. AC and DC distribution boards as per requirement and as proposed.
25. Bus bar protection scheme (for 220kV SS only).
26. Disturbance recorder with Time synchronization.
27. Sub station level PC/Lap top provision for Relay configuration with their software.
28. The scope covers supply, delivery, installation and commissioning of exhaust fans to
provide ventilation of Control Room building. Exhaust fans as specified below are to be
provided in the following locations of Control Room building above lintel level :

i. Battery Room 8 No.


ii. Toilet 1 No.

The exhaust fans will be having 600 mm. Diameter for battery room and 450 mm diameter
for the toilet, propeller type conforming to IS: 2312 and designed for continuous use. The
exact locations of fixing the exhaust fans will be finalized while approving drawing for
control room building. The supply voltage of exhaust fans shall be 230 V A.C. depending
on rating of the fan. Exhaust fans will be having 4 poles to obtain a speed of 1440 r.p.m,
29. Any other items required for completion of the project are also in the scope of this
contract in order to complete the sub-station in all respect.
ii) Erection, testing & commissioning of the following equipments:
1. Power transformers /auto transformers
2. Indoor PLCC equipments at both the ends
iii) Only supply of the following equipments:
1. Mandatory spares for substation equipment being supplied under this contract as perBid
proposal Sheet( BPS) schedule-3.
2. Maintenance & testing equipment etc as per the list provided in relevant chapter of
technical specifications.

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-4 of 23
2.1.2. Civil works
The design, engineering, supply of all materials including cement and steel, consumables, as per
specification and approved drawings for civil works of the substations including but not limited
to the following:

1) Designing, fabrication, galvanizing and erection of structures on respective foundations


detailed in specification for civil works. Supply of all structural materials (columns &
beams, hardware & fasteners etc) as per requirement. The contractor shall preferably
adopt OPTCL designed standard structures for use in various substation, the details of
which are given at “Clause no 12” of this chapter.

2) Supply of all clamps, connectors and hardware required for commissioning of the
substation. The quantity and rating of the connectors and clamps are dependent on the
layout and requirement of the substation.

3) Soil testing for soil resistivity and soil bearing capacity before designing.

4) Site development including leveling, filling & compacting of the sub-station area to the
desired height.

5) Construction of sub-station retaining wall and fencing by GI heavy-duty goat mesh


fencing and brick masonry retaining walls as per site requirement.

6) Construction of boundary wall along the property line of the substation with Main gate,
security shed and two nos. switch yard gates in the sub-station. Provisions of a security
shed near the main gate. The structure shall be RCC framed structure. There shall be
provision of electrical illumination facilities.

7) Fencing of substation area and other areas

8) There shall be provision of plantations of fruit bearing plants and water tap provision for
watering the plants in the sub-stations.

9) Construction of all foundations for columns , gantries ,all switchgear such as circuit
breakers and isolators, CT’s, CVT’s and other substation equipment such as line traps, bus
bar post insulator, etc.

10) Construction of foundation of transformer and reactors including supply and putting of
rail from the service bay to the transformer plinth, all foundations of columns, equipment
structures. Separate foundations for the marshalling boxes of the isolators are to be
considered.

11) Anti termite treatment of switch yard and colony buildings.

12) Switchyard buildings such as control room, DG set room and fire fighting pump house.
There shall be provision of a water cooler including water purifier inside the control room
building. Provision of split type air conditioners inside the control room & PLCC room of
Control Room building and conference area.

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-5 of 23
13) There shall be provision of store shed, one Ramp with winch for lifting the materials and
lowering the materials up to 5 MT and out side platform to store the materials like
transformer bushing, CT, CVT and other equipments.

14) Construction of D-type, E-type quarters.

15) Supply and spreading of uniform 20mm nominal size HG metal of 100mm thick inside
both the switch yard area of the Sub- Stations. The spreading will be done above a
finished level of switch yard land by plain cement concrete of thickness 75 mm (ratio
1:4:8). Anti weed treatment of the switch yard area to be made as per prevailing practice
before spreading of PCC.

16) Construction of drainage system of the sub-stations and the newly constructed quarters &
flood water discharge systems. Miscellaneous works like manholes soak pits, RCC,
trench, fencing, etc. within the switchyard.

17) Construction of rain water harvesting arrangements in the substation.

18) Construction of cable trenches with trays & covers & sump pit with pump, as per
requirement.

19) Construction of approach road to the new sub-stations as per requirement. Construction of
periphery roads inside the fencing. The roads inside the switchyard & at the periphery
shall be of 3.75 mtrs wide & the road inside switch yard shall be of concrete road as per
technical specification. The other roads main and approach road shall be 7 mtrs wide and
shall be bitumen grading.

20) Supply and putting of sub-station illumination system. All the light fittings shall be metal
halide type & these fittings shall be mounted on switch yard portal structures such as
columns & beams. No separate lighting mast is required. Entire substation lighting system
in the switch yard & colony shall be designed using under ground cables only. No over
head conductors are permitted for this purpose. For street lighting one outdoor lighting
kiosk with two incomers of 200A rating switch fuse units (SFU) & with six feeders of
32A rating fitted with MCB shall be considered. Similar type of out door kiosk shall be
considered for colony power supply with 200A SFU & ten out going feeder of 32A rating
fitted with MCB shall be considered

21) Designing and providing the earth mat and earthing of the sub-station lighting protection,
equipment earthing etc. Earth mat shall be designed using 75X10mm GI flat. For
lightening protection individual spike not less than 2.5mtrs shall be provided on each
column of the switchyard. Water tap provision shall be provided for pouring water into the
earth pits constructed inside & around the periphery fence the switchyard. The earthing
shall be extended beyond 2 mtrs from the fencing and the fencing earthing are also to be
taken care.

22) Boring of two nos. new bore wells at a suitable location including construction of RCC
pump house with 5 HP submersible pumps and its control inside the new proposed sub-
station area. Making water supply arrangement for the colony and the Substation area

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-6 of 23
including supply & erection of PVC pipe & its fittings, from pump house to Over head
tank & from over head tank to all the distributaries system as per approval of the layouts.

23) Township colony, residential quarters for staff and employees of the Employer including
electrification, water supply & other amenities for quarters.

24) Civic amenities for the township including drainage and sewerage systems.

25) All other materials, which the contractor feels to be required for completion of the sub-
station.

2.2. Transmission lines.


i) Survey & ROW issues

1. Detailed line Survey works as per specification.

2. The contractor shall have to solve the entire right of way problem at his own cost.
Contractor shall also resolve the issues related to the tree cutting in the transmission
line and sub-station at his own cost. However the details of ROW issues has been
indicated in Special Condition of Contract (SCC) –Vol.-1A.

ii) Design & Manufacturing (as applicable), supply, storage, erection, testing & commissioning
of following materials

1. Galvanized Structural materials of towers as per requirement. OPTCL adopted standard


towers shall preferably be used for the transmission line, the details of which is given at
“Clause no.-13” in this chapter. However no standard design is available with OPTCL for
multi circuit towers for 132kV line. The bidders shall use their own type tested design for
multi circuit towers for 132kV line.

2. Foundation for various types of towers including revetment and piling (including under
Rim piling & river bed piling as per requirement) works if required.

3. Insulators, hard wares.

4. ACSR conductors, GI earth wire etc and its stringing.

5. Commissioning of transmission lines.

6. Any other items required are also in the scope of this contract in order to complete the
proposed transmission lines in all respect.

3. Electrical System Data of 400/220/132/33


1. Nominal System Voltage (KV) 400/220/132/33

2. Highest System Voltage (kV) 420/245/145/36

3. System Neutral Earthing. Effectively earthed

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-7 of 23
4. Basic Insulation Level (KVP)

i) Bus 1550/1050/650/170

ii) Equipment other than Transformer 1550/1050/650/170

iii) Transformer 1300/1050/650/170

5. Power Frequency withstand voltage (KV rms) 520/460/275/80

6. System fault level KA 40/40/31.5/25

7. Creepage distance for insulators (mm) 10500/6125/3625/900

8. Min. recommended clearance in air(mm)as per CBIP

i) Phase-to-phase 4200/2100/1300/320

ii) Phase-to-earth 4000/2100/1300/320

iii) Sectional clearance 6500/5000/4000/3000

9. Min. ground clearance (as per IE Rules) 8500/5500/5000/4000

10. Bus configuration for 400/220/132/33 kV

Selection of ACSR conductor shall be Chosen from Moose, Zebra and panther as per
requirement and decision of employer.

11. Phase-to-phase distance:

i) Along the bay (mm) 7000/4500//3000/1500

ii) Strung bus (mm) 7000/4500/3000/1500

12. Reference design temperature 50 Deg. Centigrade.

Detailed technical particulars of different equipments have been specified in the


respective specifications in the subsequent section. If any technical particulars are missed
from this volume the same may please be referred from relevant IS: specification for
bidding purpose.

4. Design work
The Bidder shall furnish detailed design of the substations & transmission lines. The
design work shall include but not limited to technical calculations, preparation of
drawings and bill of materials and specifying equipments not specified in the
specification but necessary for the completion of the substations & transmission lines on
the turnkey basis. The technical calculation design drawings, etc. shall be submitted to

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-8 of 23
the Employer for approval. However the layout drawing furnished by OPTCL shall be
taken as a guide line.

5. Standards
All materials and equipments shall generally comply in all respects with the latest
edition of the relevant Indian Standards. International Electro-Technical Commission
(IEC) or any other internationally accepted Standard equivalent or better than relevant
Indian Standard. Equipment complying with all other authoritative standards such as
British, ASA, VDE, etc. will also be considered if performance equivalent or superior to
Indian Standard is ensured.

In the event of supply of equipment confirming to any International or internationally


recognized Standard other than the Standard listed in the Specification. The salient
features of comparison shall be brought out and furnished along with the bid.

In case of adopting any standard other than that IS or IEC, a complete set of adopted
standard shall be supplied by the bidder. However it is desirable and preferred that the
equipment offered shall comply with one consistent set of standard unless other than
exceptional cases.

The equipment shall also comply with the latest revision of Indian Electricity Act and
Indian Electricity Rules and any other Electrical Statutory Provision, Rules and
Regulations.

6. Reference Drawings
Drawings showing indicating scope of work are enclosed. Drawings are complementary
to specifications and shall be referred to for better understanding as well as for estimation
of quantities and bill of materials for arising at lump sum bid price on turnkey basis.

The bidder shall submit with the tender, plan of the substation showing broadly the scope
of work incorporated as per technical specification. All the drawings shall be submitted in
quadruplicate, enumerated in conformity with relevant clause stipulated in the Technical
Section.

These drawings shall show proposed layout plan with section. Drawings sufficient overall
dimension, clearance etc. required for assembling and dismantling and space
requirements of all the apparatus to be supplied to enable the Employer to examine the
design and layout at the installation.

7. Packing and Marking


The bidder shall include and provide for securely protecting and packing the plant so as
to avoid damage in transit under proper condition and shall be responsible for all loss or
damage caused by any defect in packing.

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-9 of 23
Large and heavy items such as 400 KV, 220 kV, 132 kV and 33 KV equipments and
structural steel shall be packed and shipped as per standard international practice.

Container/Cartoons, boxes, trunks and other packages shall be strong and sturdy in
construction to withstand Ocean shipping. Several times loading and unloading, transport
on rough roads, and storage in tropical area and hauling and handling during erection etc.
Boxes and packages shall also be protected by suitable lagging or galvanized steel strips.

A layer of waterproof material shall be provided inside the cartoon/boxes/packages to


protect the equipment from water seepage and to avoid rust.

The following information shall be marked on the container/boxes/packages etc.

a. Contractor’s/manufacturer’s name, project title and contract reference.

b. Plant/accessory identification No. and title.

c. Net/gross weight.

d. Employer’s name with other dispatch particulars such as destination.

The employer shall take no responsibility for any damage done to the plant on route to
the site of work or place of delivery whichever is applicable.

8. Tests
i. Unless otherwise specified in respective section, all equipment shall be subjected
routine and type test as covered and specified in any standard in presence of the
authorized representative of the employer.

ii. Bidder shall submit type test report from a recognized laboratory along with the
bid.

iii. At least 15 days advance notice shall be given by the contractor to the employer
for witness the tests.

9. Compliance to IE rule 1956


i) The construction agency shall posses a safety manual duly approved by
competent authority in the Govt. of his State Governing the safety in work by the
personnel and staff.

ii) The agency shall posses valid contractor’s license issued by the Electrical
Licensing Board of Odisha (ELBO) failing which he will not be allowed to start
the work.

iii) All supervisory of works shall posses appropriate valid supervisory certificate of
competency issued ELBO, Odisha.

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-10 of 23
iv) At least 50% of electrical workmen employed in the project shall posses valid
workmen permit by ELBO.

10. Bidder has to follow submission of drawings, data, document as per the
format given below.

Post Order Final Document


For For Transpa Prints Electr
Sl. No. Description With Bids Review Records rency (Photostat) onic

1. Switchyard single line


diagram including
relay metering
2. Switchyard layout,
plan, section & sizing
of various equipments
3. Switchyard earthing
and lightning
protection calculations.
4. Battery, battery
charger, DCDB
sizing calculations.
5. Switchyard lighting
calculations
6. Switchyard earthing
and lightning layout.
7. Switchyard lighting
layout.
8. Switchyard control
room equipment
and cable layout.
9. Switchyard clamps
and connector details.
10. Relay, metering and
control panel block
logic diagram.
11. Control panel
schematic drawings.

12. Logic for castle key


interlock between
breaker and isolator.

13. Relay, metering &


Control panel and
ACDB,DCDB GA
drawings.
14. Switchyard equipment
GA drawings and
control schematics.
15. Cable schedule.

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-11 of 23
Post Order Final Document
For For Transpa Prints Electr
Sl. No. Description With Bids Review Records rency (Photostat) onic

16. Interconnection
diagrams.
17. Relay setting
calculations and
Coordination
drawings.
18. SLDs of ACDB
and DCDB.
19. Soak pit and waste
oil pit layout and
sizing calculation.
20. Structural design
calculations
super structures.
21. Civil drawings for
foundation and
cable trenches.
22. Structural fabrication
drawings of
equipments gantries
etc.
23. Filled in equipment
data sheets as per
enclosed format.
24. Complete literature,
leaflets for all
equipments.
25. Operational/
maintenance manual.
26. Deviation schedule
w.r.t.
a) Specification
b) Document/
attachments.
27. List of spare parts for
each major
equipment.
28. List of special tools
and tackles.
29. List of sub-vendors.
30. QA plan of vendor
31. Installation operating
and maintenance
instruction.
32. Inspection Plan and
Testing Procedure.
33. Test Records.

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-12 of 23
Post Order Final Document
For For Transpa Prints Electr
Sl. No. Description With Bids Review Records rency (Photostat) onic

34. List of commissioning/


maintenance spares.
35. Data Book/Manual
a)Installation Manual
b) Operating/Mainte-
nance.
c)Catalogues/
Brochures.

11. Minimum clearance for substation design shall be as per details given in
the table below.
Highest Insulation Switching Sectional Minimum clearance Ground
system level Impulse Clearance Clearanc
voltage (kVP) Voltage (mm) e (mm)
(kV) (KVP)
Between Between
phase & phases
ground

36KV 170 - 3000 320 320 3700


145KV 550 - 4000 1300 1300 4600
650
245KV 950 - 4500 2100 2100 5500
1050 5000
420KV 1425 1050 6500 3500 4200 8000

12. OPTCL adopted standard switchyard structure:


The bidders may adopt their own type tested design for switchyard structures with
approval from OPTCL. However the standard switchyard structures adopted in OPTCL
switchyards system in different voltage levels are given below.

A 220 KV SIDE:
1. COLUMN: P1S TYPE,- HEIGHT-21.5 MTRS,WEIGHT-4.464MT
2. BEAM:Q1 TYPE,-LENGTH-18 MTRS, WEIGHT-1.473MT
B 132 KV SIDE:
1. COLUMN: T1S TYPE,- HEIGHT-15 MTRS,-WEIGHT-1.193 MT
2. COLUMN: T4S TYPE,-HEIGHT-11 MTRS,-WEIGHT-0.924 MT
3. BEAM:G1 TYPE,-LENGTH-10.4 MTRS,-WEIGHT-0.613 MT
4. BEAM:G2 TYPE,-LENGTH-14.9875 MTRS,-WEIGHT-0.906 MT
5. BEAM:G1X TYPE,-LENGTH-10.4 MTRS,-WEIGHT-1.370 MT

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-13 of 23
6. BEAM:G1,2 TYPE,-LENGTH-10.4 MTRS,-WEIGHT-1.25 MT
C 33 KV SIDE:
1. COLUMN: T8S TYPE,- HEIGHT-10.5 MTRS,WEIGHT- 0.777 MT
2. COLUMN: T9S TYPE,-HEIGHT-7.5 MTRS,WEIGHT - 0.592 MT
3. BEAM:G4 TYPE,-LENGTH-5.5 MTRS,WEIGHT-0.306 MT
4. BEAM:G4X TYPE,-LENGTH-5.5 MTRS,WEIGHT-0.306 MT
5. BEAM:G6 TYPE,-LENGTH- MTRS,WEIGHT-7.25 MT

THE BAY WIDTH OF DIFFERENT VOLTAGE LEVEL ARE AS


D BELOW
1. 220 KV SYSTEM SHALL BE 18 MTRS
2. 132 KV SYSTEM SHALL BE 10.4/13.1MTRS.
3. 33 KV SYSTEM SHALL BE 5.5 MTRS

13. OPTCL adopted standard Tower structure for transmission line:


The bidders may adopt their own type tested design for transmission line
structures/towers with approval from OPTCL. However the standard tower structures
adopted in OPTCL for different voltage levels are given below.

A. 132 KV Transmission line.


(i) “PA” type: Unit weight: 3.430 MT.
(ii) + 3 mtrs: Unit weight: 0.537 MT.
(iii) + 6 mtrs: Unit weight: 1.349MT.
(iv) “PB” type: Unit weight: 4.973 MT.
(v) + 3 mtrs: Unit weight: 1.018 MT.
(vi) + 6 mtrs: Unit weight: 2.104 MT.
(vii) “PC” type: Unit weight: 6.214 MT.
(viii) + 3 mtrs: Unit weight: 1.119 MT.
(ix) + 6 mtrs: Unit weight: 2.342 MT.
(x) Templates for PA- Unit weight: 0.665 MT
(xi) Templates for PB- Unit weight: 0.602 MT
(xii) Templates for PC- Unit weight: 1.904 MT

B. 220 KV Transmission line.


(i) “OA” type: Unit weight: 4.351 MT.
(ii) + 3 mtrs: Unit weight: 0.727 MT.
(iii) + 6 mtrs: Unit weight: 1.448 MT.
(iv) “OB” type: Unit weight: 7.574 MT.

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-14 of 23
(v) + 3 mtrs: Unit weight: 1.305 MT.
(vi) + 6 mtrs: Unit weight: 2.242 MT.
(vii) “OC” type: Unit weight: 9.839 MT.
(viii) + 3 mtrs: Unit weight: 1.436 MT.
(ix) + 6 mtrs: Unit weight: 2.599 MT.
(x) +15 mtrs: Unit weight: 6.670 MT
(xi) “UR” : Unit weight: 13.585 MT.
(xii) “UR” + 3 mtrs type: Unit weight: 17.316 MT.
(xiii) “UR” + 6 mtrs type: Unit weight: 4.249 MT.
(xiv) Templates for OA- Unit weight: 0.597 MT
(xv) Templates for OB- Unit weight: 0.815 MT
(xvi) Templates for OC- Unit weight: 1.172 MT
(xvii) Templates for UR- Unit weight: 1.509 MT

C. No. of Bolts & Nuts used in each of the Tower

Type of Normal +3 mtrs +6 mtrs


Tower
PA 1002 142 276
PB 1097 273 542
PC 1654 313 592
OA 1147 180 228
OB 1299 236 372
OC 1877 254 402
UR 2283 357 588

14. Approved Make Of Switchgear And Equipments.


The following make of the equipments/materials shall be supplied with prior
approval from OPTCL.

1. Breakers-Alstom /Siemens /ABB/ Crompton /BHEL.

2. CT,PT&CVT- Areva /Siemens/ABB/ Compton/ BHEL.

3. SA- Areva /CGL/Oblum.

4. CR Panels-Siemens/ Areva/ABB.

5. Battery and charger- Exide for Battery, Caldyne for Charger

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-15 of 23
6. Isolator- ABB/Siemens/Switch gear and structural /GR Power/Areva .

7. Station transformer-Alstom / Crompton

8. Hardware fittings-Rashtriya Udhyog / Eritech /IAC.

9. Conductors- APAR/Gupta Cables/ Hightech Powercon / Eritech / Cabcon / Sterlite

10. Fire fighting: Mini Max, Cease Fire.

11. Lighting fixtures: Philips, Bajaj, CGL.

12. Wave trap: BPL, ABB, AREVA.

13. Tower Structure: Either from the OPTCL Rate contract holders or from Reputed make
to be approved by OPTCL

14. PVC insulated Control and XLPE insulated Power cable- Nicco, Gloster, CCI, KEI,
Crystal, Poly Cab

15. Insulators: BHEL, WS, MGK Birla, Modern Insulator

16. Earth Wire: Bharat Wire ropes, Usha Martin, UIC Wires.

17. Cement: OPC Grade 43: ACC, Ultra Tech, Lafarge.

18. Steel: SAIL, TISCO (TATA), RINL

19. GI Pipe: TATA, JINDAL

20. Air Conditioners: Hitachi, Carrier, Blue Star.

21. PVC wires (FRLS type): L&T, Finolex

22. All Switches-Anchor/ABB/ Cona

23. All MCB-L&T(Hager)/MDS/ indo Asian


24. ACB and MCCB-L&T, Siemens/Merlin Gerin
25. All PVC Wires-FRLS type –Anchor/L&T/ Finolex /KDK/ Indo Asian
26. All Clamps and Connectors- Heavy duty type of reputed make to be approved by
OPTCL.
27. All Civil Engineering Materials- reputed make to be approved by OPTCL.
28. Foundation Bolts- Reputed make
29. GI Bolts and Nuts-Nexo or reputed make to be approved by OPTCL

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-16 of 23
Any other items required for completion of the project shall be considered as included &
the make of such items shall be subject to approval by OPTCL.

15. Portable Fire Extinguisher


Portable fire extinguishers of the following types shall be supplied to each sub-station.
Sl Description of Unit capacity Quantity Required
No Items At each At each At each
132/33 220/132/33 220/33
kV S/S kV S/S kV S/S
1 Soda Acid Type Nos 9 ltrs 2 4 4
2 Foam Type Nos 9 ltrs 2 4 4
3 Dry chemical Nos 22.5 2 4 2
Powder Kgs
Type(Trolley
mounted)
4 Dry Powder Type Nos 5 Kgs 2 4 2
5 Carbon dioxide Nos 9Kgs 5 10 5
(CO2
6 Carbon Dioxide Nos 4.5Kgs 5 10 5
(CO2)

7 Carbon dioxide Nos 22.5 2 4 2


(CO2) Kgs
Trolley mounted
8 Fire bucket with (a Set 3 5 3
set comprises of
six nos Bucket in
each stand & one
stand )
• The quantities are indicative. Bidders are advised to design as per the requirement.

16. Maintenance & Testing Equipment


Maintenance & testing equipments shall be supplied & installed for each
substation as per the list given below.
Srl. No Description of Items Unit Quantity Required
At each At each At each
132/33 220/132/33 220/33
KV S/S KV S/S KV S/S
1 100 kv transformer oil Nos 1 1 1
breakdown voltage test set
2 Insulation resistance tester Nos 1 1 1
(megger)
3 Oil sampling bottle Nos 4 4 4
4 SF6 gas leak detector Nos 1 1 1
5 LCD, digital multimeter Nos 2 2 2
6 Analogue Multimeter(features Nos 1 2 1
same as digital multimeter)
7 LCD, clamp on meter Nos 2 2 2

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-17 of 23
Srl. No Description of Items Unit Quantity Required
At each At each At each
132/33 220/132/33 220/33
KV S/S KV S/S KV S/S
8 Digital earth tester Nos 1 1 1

9 Discharge rod as per standard Nos 6 6 6


for carrying out the switch yard
maintenance work
10 Rubber gloves of operation of Pairs 2 2 2
isolators and earth switch
11 Relay tools kit Sets 1 1 1
12 Portable emergency light Nos 4 4 4
13 Latest version desktop PC of Set 1 1 1
reputed make with all its
accessories including CPU,
Monitor, UPS and having all
latest loaded software and also
its back up in shape of CD and
separate pen drive . Suitable
for loading of software as
recommended by the relay
manufacturer. It includes
supply of one no portable laser
printer of reputed make.
Make of PC and printer:
HP/DELL

** The multimeters (both digital and analogue), clamp on meters, earth tester shall
preferably of “Motwane” make. Prior approvals of OPTCL for all the testing equipments are
to be taken.

17. Other Tools and Plants (T&P’s) Requirement:


Following T&P’s of reputed make shall be supplied & installed at each substation.

Sl Description of Items unit Quantity Required


No
At each At each At each
132/33 220/132/33 220/33
KV S/S KV S/S KV S/S
1 Set of “D” spanner(6mm – Set 1 1 1
42mm)
2 Set of “Ring” spanner(6mm Set 1 1 1
– 42mm)
3 Socket wrench with sockets, Set 1 1 1
handles, and other
attachment(6mm-42mm)
4 Insulated cutting plier Nos 2 2 2
5 Insulated nose plier Nos 2 2 2

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-18 of 23
Sl Description of Items unit Quantity Required
No
At each At each At each
132/33 220/132/33 220/33
KV S/S KV S/S KV S/S
6 Monkey plier Nos 1 1 1
7 Circlip plier Nos 1 1 1
8 Pipe wrench 1 1 1
a)12 inch – 1 no Set
b)18 inch – 1 no
9 Sly wrench 1 1 1
a)12inch – 2 nos Set
b)18inch – 1 no
Insulated handle screw Set 1 1 1
drivers of different sizes as
per required
a)12inch plain head – 2 nos
b)8inch plain head – 2 nos
c) 12inch star head – 1 no
d) small size6inch plain and
star head – 2 each
e)Complete set of different
head in one box/set -1set

11 “L”-N keys set of different Set 1 1 1


sizes in one box/set
12 M.S Files(12inch and 6inch set 1 1 1
sizes)
Round files and flat files-one
each of different sizes)
13 Hammar with handle Set 1 1 1
a)1 lb – 2 nos
b)1/2 lb-2 nos
c)2 lb-1 no
14 Crow bar set 1 1 1
a)5 ft – 2nos
b)3ft-2 nos
15 Steel scale(12inch) Nos 2 2 2
16 Steel tape Set 1 1 1
a)5 mtrs-2 nos
b)30mtrs-1 no
17 Oil cane Nos 2 2 2
18 Spirit level (8inch) No 2 2 2
19 Plumb head with string and No 1 1 1
attachment
20 Maintenance safety belt with Set 3 4 3
all attachment and
helmets(complete one set)
21 Hand drill machine with No 1 1 1
different bits and key.(Wolf
make)
22 Vacuum cleaner having hot No 1 1 1
blower provision with all
attachments (Eureka Forbes
make)

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-19 of 23
Sl Description of Items unit Quantity Required
No
At each At each At each
132/33 220/132/33 220/33
KV S/S KV S/S KV S/S
23 230-250VAC,80W,450mm No 2 4 2
sweep,1400 rpm
stand(rugged) FAN
Make: Almonard,CGL

** All the T&P’s shall be of Taparia make. The hand drill and vacuum cleaner shall be wolf
and Eureka Forbes make.

18. Office Furniture:

Office furniture shall be supplied & installed at each substation as per the list given below. All
the furniture shall be of Godrej make. Before supply of the furniture to the sub-station,
approval from OPTCL is required. Details of the scope of supply are as indicated below.

Sl Description of Items unit Quantity Required


No At each At each At each
132/33 220/132/33 220/33 KV
KV S/S KV S/S S/S

1 5ftX3ft executive table Nos 5 6 5


with drawer both sides
2 3ftX2&1/2ft Table with Nos 7 8 7
one side drawer
3 Computer table suitable Set 1 1 1
keeping monitor,
CPU,UPS and printer
with two nos revolving
arm chair suitable for
computer use.
4 Executive revolving Nos 5 6 5
,adjustable(height) chairs
with arm
5 Cane gutting “S” type Nos 18 24 18
steel chairs with arm
6 6ftX3ft conference table Nos 1 1 1
7 Cushion arm steel chairs Nos 6 8 6
for conference table
purpose
8 6ft height steel almirah Nos 4 6 4
(only with selves) for
keeping records and
other valuable items

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-20 of 23
Sl Description of Items unit Quantity Required
No At each At each At each
132/33 220/132/33 220/33 KV
KV S/S KV S/S S/S

9 6ft height steel almirah Nos 2 2 2


with glass doors for
library purpose
10 6ft height (having Nos 2 2 2
minimum 6 lockers
facility) steel cupboard
with locking arrangement
11 4ft steel rack (minimum Nos 8 10 8
three selves) for keeping
the files and other items

NESCL/OPTCL/CS-OS-616-01 SCOPE DETAILS PACKAGE-1


Page-21 of 23
INDICATIVE STRACTURAL NETWORK OF 132/33 KV SUB STATION
132 KV SIDE
R O A D R O A D
10.4 13.1 10.4 13.1 10.4
T1S G1 T1S G1 T1S T1S G1 T1S G1 T1S

G2 10.4 G1 G1 G2 R
R 14.9875 14.9875
T4S T4S O
O T4S T4S
A
A
G2 T4S G2 D
D 14.9875 14.9875
G1
G1 G1 G1 G1
T1S T1S
TIS TIS T1S T1S T1S
8.4 8.4
Transf Transf
ormer ormer
3.5 3.5
G1,2 G1,2
T1S TIS T1S T1S
4.5 10.4 10.4 4.5
R O A D R O A D

R 4.5 R
33 KV SIDE T9S
O T9S T9S T9S O

A G4X G4X G4X G4X 5.5 A

D T9S T9S T9S T9S D

7.05
T8S G4 G4 G4 G4 T8S T8S G4 G4 G4

G6 T8S T8S T8S G6 T8S T8S G6


7.25
T9S T9S T9S

5.5 5.5

R O A D R O A D

* ALL THE DIMENSIONS ARE IN MTRS

Page 1 of 1
SLD FOR 132/33kV SUB-STATION AT PURI FOR SAMUKA BEACH

Feeder-1 Feeder 2

132kV MAIN BUS


132 KV BAYS
FEEDER 02 NOS.
TRANSF 02 NOS.
BUS COU 01 NO.

132kV RESERVE BUS

40MVA, 20MVA,
132/33kV 132/33kV

PVC CABLE
33kV MAIN BUS
33KV BAY
FEEDER 05 NOS. PVC CABLE
TRANSF 02 NOS.
BUS COU 01 NO. AB SW HG FUSE STN TFR
33/0.4KV
250KVA

33kV RESERVE BUS

F1 F2 F3 F4 F5

Page 1 of 3
132/33kV SUB-STATION AT PURI FOR SAMUKA BEACH
SYMBOLS USED

SURGE ARRESTOR
AUTO TRANSFORMER

WAVE TRAP

CURRENT TRANSFORMER POWER TRANSFORMER

IND VOLTAGE TRANSFORMER SA


PVC CABLE STATION AUXILIARY SYSTEM

CAP VOLTAGE TRANSFORMER AB SWI HG FUSE STN TFR CABLE

ISOLATOR

EARTH SWITCH

CKT BKR

Page 2 of 3
132/33kV SUB-STATION AT PURI FOR SAMUKA BEACH

SCOPE OF WORK OTHER IMPORTANT INFORMATIONS


► 132kV Feeder bay -2Nos. ► 132kV BUS CONDUCTOR- MAIN-- TWIN ACSR MOOSE
► 132kV Transfoprmer Bay-2 Nos. ► 132kV BUS CONDUCTOR- RESERVE-- SINNGLE ACSR MOOSE
► 132kV Bus Couplar Bay-1 No. ► 33kV BUS CONDUCTOR- MAIN-- TWIN ACSR MOOSE
► 132/33kV, 40MVA-1 No & 20 MVA-1 No. ► 33kV BUS CONDUCTOR- RESERVE-- SINNGLE ACSR MOOSE
► 33kV Feeder bay -5Nos. ► BUS CONFIGURATION: MAIN & TRANSFER BUS SYSTEM.
► 33kV Transfoprmer Bay- 2 Nos.
► 33kV Bus Couplar Bay-1 No.

REQUIREMENT OF EQUIPMENT/MATERIALS
132kV EQUIPMENTS / MATERIALS 33kV EQUIPMENTS / MATERIALS
Sl No. Items Qty Sl No. Items Qty
1 SF6 Circuit Breake 5 1 Vaccum C Breaker 8
2 Current Transform 15 2 Current Transform 24
3 CVT 6 3 IVT 3
4 IVT 3 4 Surge Arrester 21
5 Surge Arrester 12 5 BPI 16
6 Wave Trap 4 6 SI w/o ES 9
7 BPI 16 7 DI w/o ES 2
8 SI w/o ES 8 8 DI with ES 5
9 DI w/o ES 2 9 SI with BM 2
10 DI with ES 2 10 NCT 4 For Tfr
11 D Ten Insulator str 18 11 D Ten Insulator str 18
12 S.Ten Insulator str 42 12 S.Ten Insulator str 39
13 Sus Insulator string 21 13 Sus Insulator string 36
14 BMK 3 14 BMK 3
15 Lighting Board 1 15 Lighting Board 1
16 Receptical Board 1 16 Receptical Board 1
17 Receptical Tfr oil fi 1 17 T9S 11
18 T1S 16 18 T8S 9
19 T4S 5 19 G4 7
20 G1 7 20 G4X 4
21 G2 4 21 G6 3
22 G1,2 2 22 250 KVA STN TFR 2 For Stn Tfr
23 G1X 4 23 HG FUSE SET 2 For Stn Tfr
24 AB Switch 2 set For Stn Tfr
25 Surge Arrester 6 For Stn Tfr

Page 3 of 3
CHANDPUR

SLD FOR 132/33 KV DUB-STATION, CHANDPUR

132 KV 132 KV
FDR FDR
BUS PT

132 KV BAYS
FEEDER 02 NOS. 132kV MAIN BUS
TRANSF 02 NOS.
BUS COU 01 NO.

132kV RESERVE BUS

12.5MVA, 132/33kV
TRANSFORMER 12.5MVA, 132/33kV
TRANSFORMER

33kV MAIN BUS


33KV BAY PVC CABLE
FEEDER 04 NOS.
TRANSF 02 NOS.
BUS COU 01 NO. AB SW HG FUSE STN TFR PVC CABLE
33/0.4KV
250KVA

33kV RESERVE BUS


F1 F2 F3 F4

Page 1
PURUSOTTAMPUR

SLD FOR 132/33 KV DUB-STATION, PURUSOTTAMPUR

132 KV 132 KV
FDR FDR
BUS PT

132 KV BAYS
FEEDER 02 NOS. 132kV MAIN BUS
TRANSF 02 NOS.
BUS COU 01 NO.

132kV RESERVE BUS

12.5MVA, 132/33kV
TRANSFORMER 12.5MVA, 132/33kV
TRANSFORMER

33kV MAIN BUS


33KV BAY PVC CABLE
FEEDER 05 NOS.
TRANSF 02 NOS.
BUS COU 01 NO. AB SW HG FUSE STN TFR PVC CABLE
33/0.4KV
250KVA

33kV RESERVE BUS


F1 F2 F3 TFR1 B/C F4 TFR2 F5

Page 1
SCHEMATIC LAYOUT FOR SPEECH,PROTECTION & DATA CONNCWETIVITY RELATED TO LILO OF 132KV KHURDA-PURI SAMUKA BEACH

Chandaka Khurda Samuka Puri


R WT R WT R WT

Y Y Y
B WT WT B WT B WT

CVT
CVT CVT CVT CVT CVT

LMU LMDU LMDU LMU LMDU LMU LMU LMDU LMU LMDU LMU LMDU

ETL-41 ETL-41 ETL-42 PUNCOM ETL-21 ETL-21 ETL-42 ETL-42


ETL-42
N PLCC PLCC PLCC PLCC PLCC PLCC PLCC N PLCC PLCC PUNCOM
S Data # Ch1 # Ch1 # Ch1 # Ch1 S RTU # Ch1 # Ch1 (Existing)
K Data Data Data Data K Sp+Prot. Sp+Prot. Sp+Data
5 5
(Samuka) (Samuka) # Ch2 Existing Existing Existing # Ch2 # Ch2 # Ch2
Sp+Prot. Sp+Prot. Speech Speech

48V/300AH FCBC
BATT (75A)

S
STALLION MODULE
M R P
(CFE-1)
U A L
ULDC PROJECT'S X C I
R WIDEBAND NETWORK T
A MUX T
C 1511 E STALLION MODULE
BA R (CFE-2)
(SP100)
M

BBSR SUB-LDC
SCHEMATIC LAYOUT FOR SPEECH,PROTECTION & DATA CONNECTIVITY RELATED TO LILO OF 132 KV KHURDA-BALUGAON AT CHANDPUR

CHANDAKA KHURDA CHANDPUR BALUGAON


132kV WT
WT 220kV R WT R WT
Y
B
Y
WT R WT
B WT WT
Y
B

CVT CVT CVT CVT CVT CVT CVT

LMDU LMU LMU LMDU LMD LMU LMDU LMU LMDU LMU LMDU
LMDU

ETL-41 ETL‐41   ETL‐42 *ETI‐22 * ETI-21 * ETI-21   *ETI‐22 ETL‐42 ETL‐42 ETL‐42 ETL‐41    ETL‐41 ETL‐42
N PLCC PLCC PLCC PLCC PLCC EPBAX PLCC PLCC PLCC N PLCC PLCC PLCC PLCC
S # Ch1 Exsting SLDC- SLDC- existing # Ch1 S RTU # Ch1 SLDC- SLDC- # Ch1
K Data Data Sp+Data Balugaon Balugaon Sp+Data K Prot. BAM BAM Sp+Prot.
5 Speech Speech 5 Speech Speech
# Ch2 Khurda- Khurda- # Ch2 # Ch2 # Ch2
Prot. Balugaon Balugaon Prot. Khurda- Khurda-
Speech Speech Balugaon Balugaon
Speech Speech

48V/300AH FCBC
* Marked ETI21/ETI22 PLCC sets working at  BATT (75A)
Balugaon for Khurda direction
will be shifted  to Chandpur & 
used  for  SLDC‐Balugaon speech & Khurda‐
S STALLION MODULE
Balugaon Exp communication.
P
M R L CFE-1
R ULDC PROJECT'S U A I
A MUX WIDEBAND NETWORK X C T
C 1511 1511 T STALLION MODULE
BA BA E
R CFE-2
(SP
Sub-LDC,BBSR

GENERAL MANAGER
TELECOMMUNICATION
SCHEMATIC LAYOUT FOR SPEECH,PROTECTION & DATA CONNECTIVITY RELATED TO LILO OF 132 KV CHHATRAPUR-ASKA AT PURUSOTTAMPUR

Narendrapur Chhatrapur Purusottampur


WT
Aska
WT 220kV R WT 132kV R WT
Y
B
Y
WT R WT
B WT WT
Y
B

CVT CVT CVT CVT CVT CVT CVT

LMDU LMU LMU LMDU LMD LMU LMDU LMU LMU LMDU
LMU LMDU

ETL-41 ETL‐41   ETL‐42 *ETI‐21   *ETI‐21 ETL‐42 ETL‐42 ETL‐41    ETL‐41 ETL‐42
N PLCC PLCC PLCC PLCC PLCC PLCC N PLCC PLCC PLCC PLCC
S # Ch1 Exsting existing # Ch1 S RTU # Ch1 # Ch1
K Data Data Data Data K Data Speech
5 Speech Speech 5 Speech Prot
EPBAX # Ch2 # Ch2 Speech
# Ch2 Prot. Speech. # Ch2
Prot.

* Marked ETI PLCC set working
48V/300AH FCBC
at Aska for Chhatrapur direction BATT (75A)
will be shifted  to Chhatrapur & 
used  for  Purusottampur‐Chhatarpur
Speech.
S STALLION MODULE
P
M R L CFE-1
R ULDC PROJECT'S U A I
A MUX WIDEBAND NETWORK X C T
C 1511 1511 T STALLION MODULE
BA BA E
R CFE-2
(SP
Sub-LDC,Jayanagar

GENERAL MANAGER
TELECOMMUNICATION
GUARANTEED TECHNICAL
PARTCULARS

(TO BE FILLED AND SUBMITTED BY BIDDERS WITH


THE TECHNICAL BID)
GUARANTEED TECHNICAL PARTICULARS
IVT AND CVT

NESCL/OPTCL/CS-OS-616 GTP- Page 1 of 196


GUARANTEED TECHNICAL PARTICULARS.
Sl. Description. 220KV 132KV 33KV IVT 400 132KV
No IVT IVT KV/220 CVT
. KV
CVT
3P/0.2 3P/0.2 0.2 3P/3P/0. 3P/3P/0.2
Accuracy Accuracy Accuracy 2 Accuracy
Class Class Class Accurac Class.
y Class.
1 Bidder’s name and address.
2 Name and address of the Manufacturer.
3 Manufacturer’s type and designation.
4 Standards applicable.
5 Type of IVT/CVT
6 Rated primary voltage (kv).
7 Rated secondary voltage (volts).
7.1 Winding-I.
7.2 Winding-II.
7.3 Winding-III.
8 Rated frequency [HZ].
9 Rated burden:-
Protection Winding
Protection Winding
Metering Winding
10 Number of secondary windings.
11 Accuracy class.
[I] [protection] Winding
[II] [metering] Winding
12 Rated voltage factor for continuous
operation at rated frequency.
13 Rated voltage factor for 30 seconds at
rated frequency.
14 One minute dry and wet power
frequency withstand voltage for primary
side
[kv] rms.
15 One minute power frequency withstand
voltage for secondary winding [kv] rms.
16 1.2/50 micro- second impulse withstand
test voltage for primary side
17 Temperature rise over an ambient
temperature of 50°C

[a] With 1.2 times rated primary voltage at


rated frequency and at rated burdens.
[I] Winding [°C]
[II] Oil [°C]
[III] Other parts [°C]
[b] With 1.5 times rated primary voltage for
30 seconds at rated frequency and at
rated burdens.
NESCL/OPTCL/CS-OS-616 GTP- Page 2 of 196
Sl. Description. 220KV 132KV 33KV IVT 400 132KV
No IVT IVT KV/220 CVT
. KV
CVT
3P/0.2 3P/0.2 0.2 3P/3P/0. 3P/3P/0.2
Accuracy Accuracy Accuracy 2 Accuracy
Class Class Class Accurac Class.
y Class.
[I] Winding [°C]
[II] Oil [°C]
[III] Other parts [°C]
18 Class of insulation.

19 Total creepage distance in (mm)


20 Maximum radio interference voltage at
1.1 times maximum line to ground
voltage (micro volts)
21 Corona inception and extinction voltage
(kv) rms
22 Partial discharge level (piccocoulombs)
23 Primary.[For 220KV, 132KV & 33KV
IVT]
(a) No. of primary turns
(b) Material of primary
(c) Size of the primary conductor
bare/insulated.
(d) Cross sectional area of primary
conductor (sq.mm)
(e) Current density adopted for primary
winding(A/sq.mm)
(f) Type of primary winding.
(g) Name of the insulating materials
used for primary conductor.
(h) Weight of primary winding.

24 Secondary. [For 220KV, 132KV &


33KV IVT]
(a)No. of secondary turns
(b) Material of secondary
© Size of the secondary conductor bare
/insulated.
(d)Cross sectional area of secondary
conductor (mm2)
(e)Current density adopted for
secondary winding(A/mm2)
(f)Type of secondary winding
(g)Name of the insulating materials
used for secondary conductor.
(h)Weight of secondary winding.
25. Core. [For 220KV, 132KV & 33KV
IVT]
(a)Shape of the core

NESCL/OPTCL/CS-OS-616 GTP- Page 3 of 196


Sl. Description. 220KV 132KV 33KV IVT 400 132KV
No IVT IVT KV/220 CVT
. KV
CVT
3P/0.2 3P/0.2 0.2 3P/3P/0. 3P/3P/0.2
Accuracy Accuracy Accuracy 2 Accuracy
Class Class Class Accurac Class.
y Class.
(b)Material and grade of the core
laminations
(c)Thickness of the core lamination
(mm)
(d)Maximum flux density adopted
(Tesla)
(e)Net iron area of the core
(f)Watt loss/kg. for the core materials at
the operating flux density(W/kg)
(g) Total weight of the core(kg)
(h)Whether B-H curve for core material
enclosed?
(i)Whether specific loss vrs. Flux
density curve enclosed ?
26 INSULATION. .[For 220KV, 132KV &
33KV IVT]
(a) Insulation between core and
secondaries.
(b) Insulation between secondaries.
© Insulation between secondary and
primary.
(d) Insulation between primary .and
core.
27 DIMENSIONS OF CORE AND
WINDINGS. .[For 220KV, 132KV &
33KV IVT]
(a)Diameter of the core (mm)
(b)Inner diameter of the secondary
windings(mm)
(c) Outer diameter of the secondary
windings (mm)
(d) Inner diameter of the primary
winding(mm)
(e) Outer diameter of the primary
winding(mm)
(f) Minimum clearance from primary
winding to tank(mm)
(g) Minimum clearance from secondary
winding to tank(mm)
28. Percentage voltage ratio (error)/phase ,
displacement (min.)at 100% rated .
burden at 0.8PF lagging for measuring
winding.
(a) 80% of rated voltage at frequency:-
(b) 120% of rated voltage at
frequency:-
NESCL/OPTCL/CS-OS-616 GTP- Page 4 of 196
Sl. Description. 220KV 132KV 33KV IVT 400 132KV
No IVT IVT KV/220 CVT
. KV
CVT
3P/0.2 3P/0.2 0.2 3P/3P/0. 3P/3P/0.2
Accuracy Accuracy Accuracy 2 Accuracy
Class Class Class Accurac Class.
y Class.
(c) Accuracy of standard PT to be
used. during determination of errors
(0.05 or better.
29. Percentage Voltage ratio /phase .
displacement (min.)at 25% rated burden
at 0.8PF lagging for measuring winding.
(a) 80% of rated voltage at rated
frequency:-
(b) 120% of rated voltage at rated
frequency:-
30. Percentage voltage (ratio)error /phase
displacement (min.) at 100% rated
burden at 0.8PF lagging for protection
winding
(a)5% of rated voltage.
(b)1.2 times rated voltage
( c)1.5 times rated voltage
(d) 2% of rated voltage..
31. Percentage voltage (ratio) error /phase
displacement (min) at 25% of rated
burden at 0.8PF lagging for protection
winding
(a)5% of rated voltage
(b)1.2 times rated voltage.
©1.5 times rated voltage.
(d) 2% of rated voltage.
32. Whether IVT/CVT is suitable for
horizontal transportation.
33. Quantity of oil per IVT/ CVT (Ltrs/kg)
34. Standard to which oil conforms.
35. Characteristic of oil(Prior to filling)
35. Breakdown voltage (kv-rms)
1.
35. Dielectric dissipation constant tan delta)
2.
35. Water content(PPM)
3
35. Gas content(PPM)
4
35. Interfacial tension at 27 degree C(N/m)
5
35. Specific resistance.
6
35. At 90 deg.C(ohm-cm)

NESCL/OPTCL/CS-OS-616 GTP- Page 5 of 196


Sl. Description. 220KV 132KV 33KV IVT 400 132KV
No IVT IVT KV/220 CVT
. KV
CVT
3P/0.2 3P/0.2 0.2 3P/3P/0. 3P/3P/0.2
Accuracy Accuracy Accuracy 2 Accuracy
Class Class Class Accurac Class.
y Class.
6.1
35. At 27 deg.C(ohm-cm)
6.2
36. Whether IVTS are hermetically sealed ?
If so how ?
37. Total Weight (kg)
38. Transport weight (kg)
39. Dimensional details.
40 Whether IVT characteristic curves
enclosed?
41. TANK AND SECONDARY
TERMINAL BOX.
41. Material of the IVT/ CVT tank
1
41. Material of the secondary terminal box.
2
41. Thickness of the IVT/ CVT tank
3 material.
41. Thickness of the secondary terminal
4 box material.
41. Zinc coating of IVT/ CVT tank(g/sq.m)
5
41. Zinc coating of the secondary terminal
6 box (g/sq.m)
41. Weather proof rating of secondary
7 terminal box.
41. Weight of tank fitting and other
8 accessories.
TERMINAL CONNECTORS
01. Manufacturer’s name
02. Applicable standards.,
03. Type.
04. Material of connector.
(a)Clamp body.
(b)Bolts and Nuts.
(c ) Spring Washers
05. Rated current.
06. (a) Rated terminal load(kg)
(b) Factor of safety.
07. Minimum thickness of any part(mm)
08. Weight of connector complete with
hardware.

NESCL/OPTCL/CS-OS-616 GTP- Page 6 of 196


Sl. Description. 220KV 132KV 33KV IVT 400 132KV
No IVT IVT KV/220 CVT
. KV
CVT
3P/0.2 3P/0.2 0.2 3P/3P/0. 3P/3P/0.2
Accuracy Accuracy Accuracy 2 Accuracy
Class Class Class Accurac Class.
y Class.
09. Type test reports as per IS enclosed.
10. OGA drawing enclosed.
BUSHING/SUPPORT INSULATOR
01 Manufacturer’s name
02. Type.
03. Applicable standards.
04 Dimensions:
(i)Height(mm)
(ii)Diameter(top)(mm)
(iii)Diameter( bottom)(mm)
05 Total creepage distance (mm).
06. Rated voltage(KV)(rms)
07. Power frequency withstand voltage for
(1 minute dry and wet(KV/rms)
08. 1.2/50 micro-second Impulse withstand
voltage (KVP)
09. Corona Extinction voltage(kv)
10. Weight(kg)
11. Maximum allowable span (mm)
12. Cantilever strength(kg)
13. OGA drawing enclosed.

NESCL/OPTCL/CS-OS-616 GTP- Page 7 of 196


ADDITIONAL TECHNICAL REQUIREMENT FOR 400 KV,220KV & 132KV CVT

1. Rated capacitance of the CVT


2. High frequency capacitance for entire
carrier frequency range.

3. Equivalent series resistance over the entire


frequency.

4. Stray capacitance and stray conductance of the


LV terminal over entire carrier frequency range.

5. Capacitance (PF) /Tan delta between:-


a) HV-HF point
b) HF point-Ground point of
International Transformer.
c) HV-Ground point of Intermediate
Transformer winding.

6. Capacitive reactance of the two parts of


the divider i.e. High voltage capacitor,
and Intermediate voltage capacitor,
connected in parallel.

7. Total Inductive reactance, offered by CVT.

8. Voltage ratio of the capacitor divider.

9. Open circuit Intermediate voltage.

10. Rated open circuit Intermediate voltage.

11. Reference range of temperatures within


which the CVT complies with the relevant
accuracy requirements.

12. Protective device, in-corporate in the CVT


for limiting over voltages and/or to prevent
sustained Ferro resonance.

13. Rated voltage of Surge Arrester, connected


at the secondary of CVT.

14. Natural frequency of coupling (KHZ).


15. Self tuning frequency of CVT (KHZ).

16. Bandwidth (KHZ).


NESCL/OPTCL/CS-OS-616 GTP- Page 8 of 196
17. Temperature rise over ambient.

18. One minute power frequency test voltage


of secondary winding (KV).

19. One minute power frequency test voltage


of H.F. terminal (KV).

20. One minute power frequency test voltage


of capacitor (dry & wet) (KV).

21. 1.2/50/micro second Impulse withstand test voltage


of capacitor (KVP).

22. 250/2500 micro second switching surge


withstand voltage of capacitor (dry & wet).

23. Literature
Whether the followings are enclosed?

23.1 Type Test reports as per IEC 186.

23.2 OGA drawing of CVT and terminal


connector.

23.3 Characteristic curves.

23.4 Drawing showing clearance from


earthed object.
23.5 Details of Surge Arrester, connected
at secondary winding of CVT.

24. ELECTROMAGNENIC UNIT:-

24.1 CORE:-
a) Core diameter (mm)
b) Window Weight (mm)
c) Leg centre (mm)
d) Net cross sectional area of iron
In the core (mm² )
e) Core lamination thickness (mm)
f) Type & grade of core.
g) Design flux density at rated voltage.
And rated frequency (Tesla)
h) Design flux density at highest system voltage
& lowest system frequency (Tesla).
i) Minimum knee point voltage (volts).

NESCL/OPTCL/CS-OS-616 GTP- Page 9 of 196


24.2 PRIMARY WINDING:-
a) No. of turns.
b) Bare size of conductor
c) Insulated size of conductor.
d) Area of cross section.
e) Current density (A/ mm²).
f) Conductor material.
g) Class of insulation.
h) Power frequency withstand level.
(KV-rms).
i) Impulse withstand level (KVP).

24.3 Secondary Winding Protection Protection Metering


Winding Winding Winding.

a) No.of turns
b) Bare conductor size (mm)
c) Insulated conductor size (mm)
d) Cross-sectional area (sq.mm)
e) Current density (A/ mm²)
f) Conductor material.
g) Class of Insulation.’
h) Power frequency withstand
Level (KV-rms).

Signature of the Tenderer


with seal and date.

NESCL/OPTCL/CS-OS-616 GTP- Page 10 of 196


ANNEXURE –B.
CALIBRATION STATUS OF TESTING EQUIPMENTS AND INSTRUMENTS/METERS.
Name Meters Date of Due date Name of Whether Whether Whether Whether Whether Inspite of Rema-
of the and Calibra- of Cali- the Cali- Calibrat- documents the the calibra green sticker imposed rks
test. equipment tion. bration. brating ing relating to meters/ ting or blue sticker limitations,,
s required Agency. Agency Govt. equipment agency or yellow whether the
for the is Govt. Approval fulfill the has put sticker has particular
correspon Approv- of the cali- accuracy any been affixed meter/equip
di-ng test ed. brating class as limitation on the body of ment can
with Agency per towards the particular still be used
range, furnished ? calibration the use equipment/me ? Justify its
accuracy, report of the ter. State the use for
make and particular colour of the correspondi
Sl. No. meter/equi affixed ng test(s).
pment. If sticker.
yes, state
the
limitations
.
1 2 3 4 5 6 7 8 9 10 11 12

Signature of the tenderer with seal and date.

NESCL/OPTCL/CS-OS-616 GTP- Page 11 of 196


1
Name of the Type Test.

Date of Test.

2
Name of the Laboratory where the Test has

3
been conducted.

Whether the Laboratory is Government

NESCL/OPTCL/CS-OS-616
Approved.

Whether the Test reports are valid as per

5
Clause No.8.1 of T.S.

Whether the copy of Test Report in complete


shape alongwith drawings etc. furnished or

6
not ?
ANNEXURE-C

Whether the Tested I.V.T. fulfills the technical

7
require-ments as per TS.

If the type tested I.V.T


does not fulfill the technical requirements as per
this specification, whether the bidder agrees to
conduct the particular test(s) again at their own
8

cost without any financial liability to OPTCL in


the presence of OPTCL’s representative within
the specified delivery period.

E27-GTP- Page 12 of 169


seal and date.
CHECK LIST TOWARDS TYPE TEST REPORTS.

Re mark

Signature of the Tenderer with


GUARANTEED TECHNICAL PARTICULARS

BATTERY AND BATTERY CHARGER

NESCL/OPTCL/CS-OS-616 13 E27-GTP- Page 13 of 196


ANNEXURE – I
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS
FOR 220V LEAD ACID PLANTE STORAGE BATTERY.
[To be filled in by the bidder]
350AH/550AH
Values/Others
1. Manufacturer’s Name and address
alongwith Fax No. & Tele phone No.
2. Conforming to standards
3. Type and designation as per ISS
4. Manufacturer’s type and designation
5. AH capacity and voltage of the battery
at 27 deg.C.
[a] At 10 hour rate of discharge.
[b] At 5 hours rate of discharge.
[c] At 1 hour rate of discharge
[d] At 1 minute rate of discharge.
[e] At ½ hour rate of discharge.
6. Open circuit voltage of each battery
cell.
[a] Fully charged
[b] Floating condition.
[c] When completely discharged at.
[i]. 10hr. rate.
[ii]. 5 hour rate
[iii] 1 hour rate
[iv] ½ hr. rate
[v]. 1 minute rate
[vi] 1-second rate.
7. Recommended float charging voltage
[volts] across the battery terminals.
8. Recommended boost charging
voltage [volts].
9. Time required for boost charging from
discharged conditions [in hours]
10. Trickle charging
Current range/cell
11. AH capacity at 10 hour rate at 10 hour
rate at room temperatures of :
[a] 15 deg C.
[b] 27 deg C.
[c] 50 deg C.
12. CELL DETAILS

NESCL/OPTCL/CS-OS-616 14 E27-GTP- Page 14 of 196


[i]. No. of cells per battery
[ii]. Total nos. of plates per cell.
[iii] No. of positive plates per cell.

(iv) Type of positive plate


(v) No. of negative plates per cell
(vi) Type of negative plate
(vii) Surface area of plates in sq. mm.
(viii) CONSTRUCTIONAL DETAILS AND DIMENSIONS OF
(a) Positive plate
(b) Negative plate
(c) Material of the container
(d) Thickness of the container
(e) Overall dimensions of each cell
(LxBxH)
ix. Weight per Cell (Kg)
(a) Active elements-positive
(b) Active elements-Negative
(c) Container
(d) Net dry weight
(e) Weight with electrolyte
x. Distance between centre of cells
where erected.
xi. Nominal cell voltage.
xii. Internal resistance of each cell at
(a) Fully charged condition
(b) Fully discharged condition
(c) Floating condition
13. Type, Thickness and materials of
the separators
14. Containers
(a) Type
(b) Material
(c) Outside dimensions (LxBxH)
15. Cover and its type and material
16. Clearance in mm between
(a) Top of plates and top of container
(b) Bottom of plates and bottom of
container
(c) Edges of plates and inner surface of
container.

NESCL/OPTCL/CS-OS-616 15 E27-GTP- Page 15 of 196


17. Sediment space (depth) in mm
18. ELECTROLYTE
(a) Amount of electrolyte and specific
gravity at 27 deg. C for first filling.
(b) First filling per set with 10% of
extra furnished.
(c) Electrolyte conforms to standard
(d) Rated specific gravity of electrolyte
when fully charged at room’s
temperature of
(i) 15 deg. C
(ii) 27 deg. C
(iii) 50 deg C.
(e) Specific gravity of electrolyte at
the end of discharge at 10 hour
discharge rate.
(f) Maximum electrolyte temp. that
the cells can withstand without
injurious effect.
(i) Continuously
(ii) For short period
19. INTER CELL CONNECTOR
(a) Whether Inter-cell connector to be
furnished ? (Yes / No)
(b) Type of inter-cell connector (bolted
or others)
(c) Materials of inter cell connector
20. Inter row, inter-tier connectors and
(a) end take-off furnished ? (Yes / No)
(b) Description, size, current rating,
type and material.
21. RACKS
(a) No. of racks per battery
(b) No. of cells per rack
(c) Type of racks (rows and tiers)
(d) Material of the rack
(e) Racks provided with
(i) Numbering tags for cell
(ii) Teak wood clamps for cables
(f) Whether anti-acid coating provided
?
(g) Description of rack insulators

NESCL/OPTCL/CS-OS-616 16 E27-GTP- Page 16 of 196


(h) Outline dimensions of racks
(i) Net weight of racks
(j) Shipping weight
22. Recommended rate for charging Start Finish
the battery in 8 hours.
(a) Current
(b) Voltage
23. Recommended float charge rate
24. Resistance of the battery including
inter-connector between the cells in
ohms.
25. Maximum short circuit current per
(a) battery
(b) Allowable duration of short circuit
26. Short circuit current for a dead
short across the battery terminals
when
(a) Float at 2.1 volts per cell.
(b) Boost charge to 2.75 volts per cell.
27.(a) Time to full charge at finishing rate
only
(b) Time to full charge at higher
starting rate
(c) Time for full charge to charge by
two step charging at starting up and
finishing rates
28. Guaranteed AH efficiency at 10
hour rate of discharge in percent.
29. Guaranteed WH efficiency at 10
hour rate of discharge in percent.
30. Instructions for filling and initial
charging of the battery with
finishing and two step charging
rates.
31. Recommended interval at which
battery should be discharged at 10
hour rate and quick charged.
32. Recommended floating voltage per
cell and the minimum variation.
33. Recommended maximum period of
storage before the first charge.
34. Average life in years

NESCL/OPTCL/CS-OS-616 17 E27-GTP- Page 17 of 196


35. Guaranteed life of battery in years.
36. Estimated life of battery in years.
37. Total shipping weight of battery
units
38. Dimensioned lay-out drawings of
the rack and battery to be attached
with the tender. (Whether furnished
? Yes / No)
39. The following characteristic
curves, to be furnished alongwith
the tender (whether furnished)
(a) Battery discharge curves at various
rates between one minute and 10
hour rate. (Yes / No.)
(b) Curves showing the relation
between the specific gravity and
amount of charge in the battery for
both charging and discharging
conditions. (Yes / No)
(c) Curves showing the relation
between cell voltage and charging
current when charged at
(i) Finishing rate (Yes/ No)
(ii) High starting rate (Yes/ No)
(iii) Two step charging by starting and
finishing rate (Yes / No)
(d) Curve of internal resistance at the
end of various discharge rates
(Whether furnished (Yes / No)

NESCL/OPTCL/CS-OS-616 18 E27-GTP- Page 18 of 196


ANNEXURE – II

GUARANTEED TECHNICAL PARTICULARS FOR


BATTERY CHARGER (220 V D.C. SYSTEM) SUITABLE
FOR SPECIFIED LEAD ACID PLANTE STORAGE BATTERY

(To be filled in by the Bidder)

Values/ Others
1. Manufacturer’s Name
2. Rated output of the charger
2.1 Voltage (volts)
2.2 Current (amps)
2.3 Power factor
3. Short time rating
4. Type of cooling
5. Hottest stack temperature (0C)
6. Charger dimensions
6.1 Height (mm)
6.2 Depth (mm)
6.3 Width (mm)
6.4 Sheet thickness (mm)
7. Charger weight
8. Charger rated output current
8.1 Float charging mode
8.2 Boost charging mode
9. Load limiter current setting range (Trickle mode)
10. RECTIFIER TRANSFORMER Float Boost

NESCL/OPTCL/CS-OS-616 19 E27-GTP- Page 19 of 196


Charger Charger
10.1 Make
10.2 Type
10.3 Rated KVA
10.4 Over current impedance (ohms)
10.5 Input line winding connection
in vector representation
10.6 Rated primary voltage (volts)
10.7 Rated secondary voltage (volts)
10.8 Rated frequency (Hertz.)
10.9 Rated output (amps)
10.10 Turn ratio
10.11 Insulation level
10.12 Impulse withstand test voltage (KVP)
10.13 One minute power frequency over voltage.
(a) Primary winding (KV-rms).
(b) Secondary winding (KV-rms)
10.14 Material of primary winding conductor
10.15 Material of secondary winding conductor
10.16 Size, Cross-sectional area and current density of primary winding conductor.
10.17 Size, cross-sectional area and current density of secondary winding conductor
10.18 No. of turns of primary / phase
10.19 No. of turns of secondary / phase
10.20 Name of the insulating materials used and class
10.21 Core
10.21.1 Name of the core material
10.21.2 Grade of the core
10.21.3 Thickness of core material (mm)
10.22 Maximum temperature rise over an ambient temperature of 500C

NESCL/OPTCL/CS-OS-616 20 E27-GTP- Page 20 of 196


(a) Primary Winding (0C)
(b) Secondary Winding (0C)
(c) Core (0C)
10.23 standards applicable

11.0 RECTIFIER ASSEMBLY :


11.1 Make
11.2 Type of semi conductor material
11.3 Rated direct current per cell (A)
11.4 Rated direct voltage (V)
11.5 Rated input voltage (V)
11.6 Type of connections of rectifier elements.
11.7 Forward power loss and reverse power loss (watts).
11.8 Forward voltage drop and reverse voltage drop (volts)
11.9 Conversion efficiency (%)
11.10 Rated DC output voltage (V)
11.11 Rated AC input voltage (V)
11.12 Rated output current (A)
11.13 Ripple factor
11.14 Voltage factor
11.15 Current factor
11.16 Maximum temperature rise over an ambient temperature of 500C (0C)
11.17 Maximum permissible ambient temperature for guaranteed rating (0C)
11.18 Maximum and minimum permissible humidity rating (%)
11.19 Life expectancy (years)
11.20 Standard(s) applicable
11.21 Characteristic curve of DC output plotted against output current (Whether
submitted ?) Yes / No.
12.0 AUTOMATIC VOLTAGE REGULATOR
12.1 manufacturer’s name

NESCL/OPTCL/CS-OS-616 21 E27-GTP- Page 21 of 196


12.2 Manufacturer’s type
12.3 Percentage stabilisation of the rectifier with the help of AVR when
(a) Input voltage changes with ± of its nominal value.
(b) DC output of the rectifier varies from no-load to full load.
12.4 Rated output voltage
12.5 Allowable AC frequency fluctuations
12.6 Voltage setting range
12.7 Response time of automatic voltage regulator
13.0 Manual voltage regular (float mode)
13.1 Type
13.2 Voltage setting range
14.0 Boost charging current setting range
15.0 Boost charging limit setting range
16.0 DIODES
16.1 Manufacturer’s name
16.2 Type of circuit
16.3 Method of construction
16.4 Continuous current rating (Amps.)
16.5 Short time current rating (Amps)
16.6 Type of cooling
16.7 Forward power loss and reverse power less (W)
16.8 Life expectancy
16.9 Forward voltage drop on rated current
16.10 Resistance offered for reverse current flow
16.11 Maximum temperature rise over an ambient temperature of 500 C.
17.0 CONTACTORS / MOULDED CASE CIRCUIT BREAKERS
17.1 Type
17.2 Make
17.3 Rated voltage (V)

NESCL/OPTCL/CS-OS-616 22 E27-GTP- Page 22 of 196


17.4 Rated continuous currents (A)
17.5 Contact material
17.6 Operating coil
17.6.1 Voltage (V)
17.6.2 Voltage range and power for closing and holding
17.6.3 Voltage range and power for drop off.
17.7 Thermal trip rating
17.8 Thermal trip time
17.9 Details of CT if any
17.10 Auxiliary contacts
17.10.1 Number
17.10.2 Current rating
17.11 Characteristics of back-up HRC fuse
18.0 RELAYS :
18.1 Make and type of protective and alarm relays
(a) Thermal overload relay
(b) Input under voltage relay
(c) Single phasing alarm relay
(d) Phase reversal relay
(e) D.C. output over-voltage relay
(f) D.C. output under voltage relay
(g) Charger failure relay
(h) Battery earth fault relay
(i) A.C. input failure relay (for connecting the D.C. load)
(j) Fuse failure relay
(k) Alarm accept relay
18.2 Rated voltage of each of the above
(a) AC/DC
(b) Permissible variation
(c) Frequency

NESCL/OPTCL/CS-OS-616 23 E27-GTP- Page 23 of 196


18.3 VA burden of each of the above
18.4 Operating time of each of the above
18.5 Time vs current curves of each of the above.
(to be enclosed alongwith the offer)
18.6 Reset time
18.7 Accuracy
18.8 Setting range
18.9 Reset factor
18.10 Number of contacts
(a) Normally open
(b) Normally closed
18.11 Rating of contacts
(a) Rated Voltage (V)
(b) Rated making and breaking
(c) Continuous rating
18.12 No. of operations
18.13 Operation indicator
19.0 INDICATING LAMPS
19.1 Manufacturer’s name
19.2 Type and designation
19.3 Permissible voltage variation
19.4 Rated power consumption (watts).
19.5 Series resistance, if any
20.0 SWITCHES:
20.1 Manufacturer’s name
20.2 Ratings
(a) Continuous current
(b) Short circuit – making capacity
(c) Breaking capacity

NESCL/OPTCL/CS-OS-616 24 E27-GTP- Page 24 of 196


(d) Voltage
20.3 Operating mechanism details
20.4 Type of visual indication
(a) OFF and ON position
(b) Fuse blow out
21.0 FUSES
(a) Make
(b) Type
(c) Rating (Amps)
(d) Interrupting rating (KA)
22.0 INSTRUMENTS
22.1 Manufacturer’s Name
(a) Ammeter
(b) Voltmeter

22.2 Type
(a) Ammeter
(b) Voltmeter

22.3 Standard
(a) Ammeter
(b) Voltmeter

22.4 Scale range

22.4.1 Ammeter
(a) Float charger
(b) Boost charger
(c) Battery float
(d) Battery boost

22.4.2 Volt meter


(a) Input supply
(b) Charger output
(c) Load

NESCL/OPTCL/CS-OS-616 25 E27-GTP- Page 25 of 196


22.5 Size of dial
(a) Volt meter
(b) Ammeter

22.6 Accuracy class


(a) Volt meter
(b) Ammeter
22.7 Temperature at which calibrated
22.8 Limit of errors
22.9 Out line dimensions
22.10 Type of mounting
22.11 Selector switch for volt meter (AC & DC)
(a) Make
(b) Rating
23.0 CAPACITOR
23.1 Manufacturer’s name
23.2 Type
23.3 Capacitance (Farad)
23.4 Maximum temperature rise over an ambient temperature of 500C.
24. Reference float voltage at ambient temperature of 270C
25. Whether protection is given for float voltage to Avoid low battery voltage due
to sensor or circuit Malfunction. (Yes/ No)

NESCL/OPTCL/CS-OS-616 26 E27-GTP- Page 26 of 196


ANNEXURE – IV-A
(For Testing of Battery)
(To be filled in by the bidder)

CALIBRATION STATUS OF TESTING EQUIPMENTS AND INSTRUMENTS/ METERS

Name of Meters & Date of Due date of Name of Whether Whether Whether the Whether the Whether the Inspite of Remarks
the Test Equipments Calibr- Calibration the Calibrating documents meters/ calibrating calibrating imposed
required for the ation Calibratig Agency is relating to Govt. equipments agency has agency has put limitations.
corresponding Agency Govt. approval of the fulfil the put any any limitation Whether the
test with range, approved calibrating accuracy limitation towards the use particular meter
accuracy, make Agency class as per towards the of the / equipment can
& Sl. No. furnished calibration use of the particular still be used ?
report. particular meter/equip- Justify its use
meter/ ment/ meter. for
equipment. If State the colour corresponding
yes, state the of the affixed test(s)
limitations sticker
1 2 3 4 5 6 7 8 9 10 11 12

Signature of the tenderer with seal & date

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 27 of 196


ANNEXURE – IV-B
(For Testing of Battery Charger)
(To be filled in by the bidder)

CALIBRATION STATUS OF TESTING EQUIPMENTS AND INSTRUMENTS/ METERS


Name of Meters & Date of Due date of Name of Whether Whether Whether the Whether the Whether the Inspite of Remarks
the Test Equipments Calibr- Calibration the Calibrating documents meters/ calibrating calibrating imposed
required for the ation Calibratig Agency is relating to Govt. equipments agency has agency has put limitations.
corresponding Agency Govt. approval of the fulfil the put any any limitation Whether the
test with range, approved calibrating accuracy limitation towards the use particular meter /
accuracy, make Agency class as per towards the of the equipment can
& Sl. No. furnished calibration use of the particular still be used ?
report. particular meter/equip- Justify its use for
meter/ ment/ meter. corresponding
equipment. If State the colour test(s)
yes state the of the affixed
limitations sticker
1 2 3 4 5 6 7 8 9 10 11 12

Signature of the tenderer with seal & date

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 28 of 196


ANNEXURE V – A
(To be filled in by the bidder)
CHECK LIST TOWARDS TYPE TEST REPORTS FOR BATTERY

Name of the Date of Name of the Whether the Whether the Whether the Whether the If the type tested battery does not Remarks
Type Test Test Laboratory where Laboratory is Test report is Test report in type tested fulfill the technical requirements as
the Test has been Government valid as per complete Plante lead per this specification, whether the
conducted approved Spn. shape acid battery bidder agrees to conduct he particular
alongwith fulfills the type test again at their own cost
drawings etc. technical without any financial liability to
furnished or requirements OPTCL in the presence of OPTCL’s
not ? as per TS representative within the specified
delivery period
1 2 3 4 5 6 7 8 9

Signature of the tenderer with seal & date

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 29 of 196


ANNEXURE V – B

(To be filled in by the bidder)


CHECK LIST TOWARDS TYPE TEST REPORTS FOR BATTERY CHARGER

Name of Date of Name of the Whether the Whether the Whether the Whether the If the type tested battery charger does not Remarks
the Type Test Laboratory Laboratory is Test report is Test report type tested fulfill the technical requirements as per this
Test where the Test Government valid as per in complete battery specification, whether the bidder agrees to
has been approved Spn. shape charger conduct he particular type test again at their
conducted alongwith fulfills the own cost without any financial liability to
drawings technical OPTCL in the presence of OPTCL’s
etc. requirements representative within the specified delivery
furnished or as per TS period
not ?

1 2 3 4 5 6 7 8 9

Signature of the tenderer with seal & date.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 30 of 196


GUARANTEED TECHNICAL
PARTICULARS

FOR

SF6 AND VACUUM CIRCUIT BREAKERS

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 31 of 196


GUARANTEED TECHNICAL PARTICULARS FOR CIRCUIT
BREAKERS

( To be filled in & furnished by the Bidder , separately for 245kv &145 KV SF6
Circuit Breakers)

1. (a) Maker’s name and country of


manufacture

(b) Manufacturer’s type Designation

1. Applicable technical standards

2. (a) Rated voltage(kV)

(b) Rated frequency(Hz)

4. Number of Poles

5. Class

6. Rated normal current

(a) Under site conditions(Amps)

(b) Rated (Amps)

7. (a) Rated short circuit breaking current

(i) Rms value of AC component of rated


short circuit current (KA)
(ii) Percentage DC component
(iii) Assymetrical Breaking Current at Highest System Voltage
(iv) Certificate or report no
(iii) Oscillogram no.
(b) Rated short circuit making current (KA peak)
(i) At Higher rated Voltage
(ii) At Lower rated Voltage
(c) (i) Maximum Breaking capacity Under Phase
Opposition(KAP)
(iii) Max Pole discrepancy(ms)
(iv) Max arc duration & Corresponding current under lockout
pressure

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 32 of 196


8. First pole to clear factor

9. Rated transient recovery voltage for terminal faults


(kV peak)

10. Rated characteristics for short line faults.

11. Rated operating sequence

12. Rated duration of short circuit(Sec.)


13. Rated out of phase making & breaking current (kA)

14. (a) Opening time (ms)


(i) Maximum Opening time under any condition
(ii) With limiting Voltage & Pressure.
(b) Arcing time (ms)
(i) At 100% rated breaking current (ms)
(ii) At 50% rated breaking current (ms)
(iii) At 25% rated breaking current (ms)
(iv) At 10% rated breaking current (ms)
(v) Maximum arcing time at lowest
fault current (ms).
(c) Break Time (ms)
(i) At 100% rated breaking current (ms)
(ii) At 50% rated breaking current (ms)
(iii) At 25% rated breaking current (ms)
(iv) At 10% rated breaking current (ms)
(v) Maximum break time at lowest
fault current (ms).
(v) Maximum Total Break Time under any duty condition
For any current up to rated breaking current with limiting
condition of Voltage & Pressure(ms)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 33 of 196


(d) Closing time (ms)
(e) Minimum dead time for 3 phase reclosing
(f) Maximum Close Open Time under any condition
With limiting Voltage & Pressure.
(g) Minimum Time Interval between each make/ Break Operation.

15. Rated line charging breaking current (kA)

16. Rated small inductive breaking current (kA)

17. (i)Max. rise of temperature over ambient for


current rating under sl. 6.
(ii)Max. rise of temperature for
Main contacts over design ambient temperature of 50deg C.

18. Interrupting capacity based on duty cycle as per sl. 11.


(a) AC ;component (kA)
(b) Percentage DC component.

19. Latching current (kA)

20. No. of breaks in series per pole.

21. Length of contact travel (mm)

22. Total length of break per pole (mm)

23. Rate of contact travel:


(a) At tripping (metres/sec.)
(b) At closing (metres/sec.)

24. Type of devices, if any, used to obtain


uniform voltage distribution between breaks.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 34 of 196


25. Recovery voltage distribution between
breaks in percent of rated voltage.

(a) Single line to ground fault


(b) Interruption on short lines.
(c ) Switching off an unloaded, transformer

26. (i) Type of main contact.


(ii) Number of auxiliary contacts per pole for normal operation(NO & NC)
(iii)Number of auxiliary contacts per pole provided for Owner’s use(NO &
NC)
(iv) Current rating of Auxiliary contacts
27. Type of arcing-contacts and/or arc
control device

28. Material of contacts:


i. Main
ii. Arcing
iii. Whether contacts are silver plated
iv. Thickness of silver coating mm
v. Contact pressure, kg/sq. mm.

29. Insulation level of the breaker:

(a) 1 minute power frequency withstand


voltage kV rms(Dry & Wet)
(i) Between live terminals & Ground
(ii) Between terminals with Breaker contacts open
(b) Switching surge withstand test
Voltage kV (peak)
- To earth
- Across open contacts

(c ) Lightning impulse withstand test


voltage, kV(peak)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 35 of 196


- To earth
- Across open contacts

(d) Max. dynamic power frequency over voltage


withstand kV (peak)

30. i) RIV level (Max)


ii) Corona inception voltage (kV rms)
iii) Corona extinction voltage (kV rms)

31. Minimum clearances


(a) Between phases (live parts)(mm)
(b) Between live parts and earth (mm)
( c) Total Creepage Distance (i) To ground
(ii) Between Terminals
32. Whether the circuit breaker is fixed trip or trip free

33. Method of closing


(a) Normal
(b) Emergency
34. Type of closing mechanism

35. (a) Normal voltage of closing


(b) Pick up range (volts DC)

36. (a) Power at normal voltage of closing


mechanism (watts)
(b) Power at 85% of normal voltage of closing mechanism(watts)
(c) No of closing coils in operation

37. Type of tripping mechanism


Number of Tripping Coil
38. (A) Normal voltage of tripping coils(volts)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 36 of 196


(a) Power at normal voltage for
Tripping coils (watts)
(b) Power at 70% normal voltage for
Tripping coils (watts).
(c) No. of tripping coils in operation
(d) Pick up range (V DC)
(B) Number of close open operation
(i) possible after failure of AC supply to motor
(ii) Time required for motor to charge the closing spring(Sec)
(iii) Wheather indication of spring charged condition will be provided in control
cabinet.

39. Arc duration at 100% (ms)

40. Interruption capacity:

a) Opening
Arcing time no. of loops and time
including resistor current duration
(cycle)

Resistor current duration (cycle)

Total length of the arc (mm)

Max. length of the arc (mm)

Total interrupting time measured


from instant of trip coil
energisation to arc extinction of
resistor current (cycles)

b) Closing time measured from


instant of application of power to

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 37 of 196


closing device upto arcing contacts
touchings (cycles)

41. Critical current (current giving the longest


arc
when a break takes place) (kA)

a) Recovery voltage when circuit breaker


tested at 100% rated breaking capacity
(kV inst.)

b) Rate of rise of restriking voltage at breaking

i) for 30% breaking capacity


(kV/microsecs.)
ii) for 100% breaking capacity
(kV/microsecs.)

c) Maximum over-voltage factor of


the circuit breaker when switching off.

i) Unloaded transformers
ii) Loaded transformer
iii)Open circuited lines
42. When switching of synchronous systems:
(a) Max. current (kA)
(b) Max. contacts of 1 pole (kV)

43. No. of openings the circuit breaker is capable of


performing without inspection, replacement of
contacts or other main parts.

(a) at 50% rated current


(b) at 100% rated current
(c ) at current corresponding to 50%
rated breaking capacity.
(d ) at current corresponding to 100%
rated breaking capacity.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 38 of 196


44. (A)a) W eight of complete circuit breaker (Kg).

b) Impact loading for foundation design, to


include deed load plus impact value on
opening at maximum interrupting ratings, in
terms of equivalent static load (Kg.)

c ) Overall dimensions:
Height (mm)
Width (mm)
Length (mm)
(B)- Type & Material of Gasket used to
ensure gas tight joints for
(i)Metal to Metal Joint
(ii) Metal to Porcelain Joints
(C ) Type & Make of
a) Density Monitor
b)Pressure Gauge
(D) Density Monitor Setting
a) Lock Out
b) Alarm
45. Porcelain:

a) Make
b) Type
c) Descriptive pamphlet no.
d) Weight (kg.)
e) Transport dimensions (mm)
f) Height above floor, required to remove
porcelain (mm).
g) Insulation class
h) One minute power frequency withstand,
kV (rms) (dry & wet)
i) Flash over voltage (kV)
j) Lightning impulse withstand voltage kV
(peak) (dry & wet)
k) Switching surge withstand voltage kV
(peak) (wet)
l) Corona discharge voltage (kV rms)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 39 of 196


m) Creepage distance, total protected (mm)
n) Permissible safe cantilever loading on
installed porcelain (Kg.m)

46. (i)Rated pressure of SF6 gas in the circuit breaker


(Kg/sq.cm )
(ii) Rated Pressure of SF6 in operating
Chamber(kg/cm2) at 20deg C
(iii) Limits of Pressure of extinguishing medium
47. Rated pressure of SF6 gas in the gas cylinders
(Kg/sq.cm )

48. (i)Quantity of SF6 gas required per single pole


unit (Kg.) at rated Pressure & at 20 deg C
(ii) Guaranteed Maximum Leakage rate per Year.

49. Quantity of SF6 gas per cylinder (Kg.)


Standard to which SF6 Gas Complies.

50. (i) Weight of empty cylinder (Kg.)


(ii) Wheather Breakers are dispatched filled with SF6
Gas or filled at site.
51. Quantity of absorbent required per pole (Kg.)
52. Recommended interval for renewal of
absorbent in case of outdoor circuit breakers
operating in tropical conditions.
53. Chemical composition of absorbent
54. Quantity of absorbent covered in the scope of
supply
(including spare quantities)
55. Limits of gas pressure for pressure operation of
circuit breaker – (Kg/sq.cm )
56. Pressure and temperature at which the
temperature compensated gas pressure switch will
a. give alarm (Kg/sq.cm., deg. C)
b. cut off (Kg/sq.cm. deg. C)
57. Name of SF6 supplier and country of origin.
58. Quantity of SF6 gas supplied for
a. Actual use in breakers (Kg.)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 40 of 196


b. As spare (Kg.)
59. Chemical composition of gas:
a. Qty. of air by weight (ppm)
b. Qty. of H20 by weight (ppm)
c. Qty. of CF4 by weight (ppm)
d. Qty. of free acid by weight (ppm)
e. Density
f. Oil Content
g. Resistivity

60. Motor For Circuit Breaker


a) Manufacture’s name & address
b) Eqipment driven by motor or not.
c) Motor Type
d) Country of Origin
e) Type of Duty
f) Type of Enclosure & Method of Cooling
g) Applicable Standard to which motor confirms
h) Type of mounting
i) Direction of rotations as viewed from non driving end.
j) Standard Continuous rating at 50deg C
k) Rated Voltage
l) Rated Speed at rated Voltage & Frequency(rpm).
m) Full Load current at rated voltage & frequency.
n) Power Factor at rated load.
o) Rating of the Motor.
p) Time for fully charging the closing spring

61. Control Cabinet


(a) Material of enclosure
(b) Thickness of sheet steel
(c) Painting for control cubicle
(d) Paint shade
(e) Degree of protection
(f) Dimension
(g) Material of gasket

Name of the firm…………………. Signature of Bidder………………..

Designation & Seal ……………….. Date ……………………………….

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 41 of 196


SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 36 KV

CIRCUIT BREAKERS

1. Name of Manufacturer.

2. Manufacturer’s type designation.

3. Rated Voltage. - KV

4. Maximum (continuous) service rated Voltage - KV

5. Normal current rating.

a) Under normal conditions.

b) Under site conditions.

6. Short time current rating for seconds (rms)

7. Maximum temperature rise over ambient. -°C

8. Breaking capacity.

a) Symmetrical. KVA

b) Assymmetrical. MVA

9. Making capacity. KA

10. Total break time in ms.

a) at 10% rated interrupting capacity - MS

b) at rated interrupting capacity - MS

11.Arcing time. - M.S.

12. Make time. - M.S.

13. Minimum reclosing time at full rated - M.S. Interrupting MVA from
the instant ofTrip coil energisation.

14. Minimum dead time for 3 phase reclosing.- M.S.

15. Whether restricting free. - Yes/No

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 42 of 196


16. One minute dry power frequency
Withstanding test voltage (KV rms)

Between line terminal and ground objects. - KV rms.

Between terminal with breaker contacts open. -KV rms.

17. 1.2/50micros full wave impulse withstand test voltage for the two cases above.

i) Between line terminal & grounded objects. -KV(Peak)

ii) Between terminal with breaker Contacts open. -

18. Busing or Insulators :

i) Type of bushing. -

ii) Dry 1 minute power frequency - KV rms

withstand test voltage.

iii) Dry flashover value. - KV rms.

iv) Wet flashover value. - KV rms.

V) 1.2/50 impulse withstand - KV(Peak)

vi) Creepage distance. - mm

vii) Puncture value of bushing. - KV

viii) Weight of bushing. - Kg.

19. Minimum clearance in air.

i) Between phases. - mm

ii) Live parts to earth. - mm

iii) Live parts to ground level - mm

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 43 of 196


iv) Between live parts & grounded object. - mm

20. Number of poles of circuit breaker.

21. Number of breaks per phase.

22. Total length of break per phase.

23. Type of main contacts.

24. Type of Aux. Contacts.

25. Materials of auxiliary contacts.

26. Contacts silver plated or not.

27. Thickness of silver plating.

28. Contact pressure.

29. Voltage distribution between breaker.

30. Type of device if any, used to limit

the rate of rise or restricting voltage.

31. Voltage grading device if any used.

32. Number of auxiliary contacts provided.

i) Those closed when breaker is closed.

ii) These open when breaker is closed.


iii) Those adjustable with respect to
the position of main contacts.

33. Type of operating mechanism.

i) Operning

ii) Closing.

34. Control circuit voltage.

35. Power required for trip coil - Watts

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 44 of 196


at 220V D.C.
36. Power required for close coil
At 220V D.C. - Watts
37. Frequency at which contacts are
To be replaced.
38. Nos. of terminal connector.

39. Steel support structure galvanized - Whether


With foundation – Nuts & Bolts to be provided yes or no
40. Type test certificate Furnished - Yes/No

41. Circuit Breaker weight. - Kg.

42. Quantity. - Nos.

Name of the
Firm:-

Signature of
the bidder:-

Designation &
seal:-

Date:-

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 45 of 196


GUARANTEED TECHNICAL PARTICULARS

FOR

CURRENT TRANSFORMER

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 46 of 196


GUARANTEED TECHNICAL PARTICULARS FOR CURRENT
TRANSFORMER TO BE FILLED BY THE BIDDER.

Sl. Description 33KV 132KV 220KV


No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

1. Bidder’s name
and address
2. Name and
address of the
Manufacturer
3. Manufacture’s
type designation
4. Standards
applicable
5. Rated frequency
(HZ)
6. Rated Voltage
(KV)
7.0 Rated current
(A)
7.1 Rated
continuous
current (A)
7.2 Rated extended
primary current
(A)
8. Short time
thermal current
withstand for
stipulated time
duration (KA)
9. Dynamic current
withstand (KAP)
10. 1.2/50 μs
impulse
withstand
voltage (KVP)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 47 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

11. One minute dry


and wet power
frequency
withstand
voltage (KV-
rms)
12. No. of cores per
CT
13. Transformation
Ratio

14. No. of
secondary turns

15. Rated output at


all ratios for
metering core
(VA)
16. Accuracy class
17. Minimum Knee
point voltage at
different taps
for all ‘PS’ class
cores (V)
18. Secondary
winding
resistance at
different taps for
all cores (Ω)
(750C)
19.0 Maximum
exciting current
at all ratios (for
all PS class
cores)
19.1 100% KPV

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 48 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

(Knee point
voltage) (mA)
19.2 25% KPV (Knee
point voltage)
(mA)
19.3 20% KPV (Knee
point voltage)
(mA)
19.4 10% KPV (Knee
point voltage)
(mA)
20. Instrument
security factor at
different ratios.
21. Radio
interference
voltage at 1.1 Vr
/ 31/2 at 1.0 MHZ
(Micro volts)
22. Whether
auxiliary CT
provided for
metering
winding
23. Corona
extinction
voltage (KV
rms)
24. Partal discharge
level (PC)
25. Total creepage
distance (mm)
26. Primary
26.1 No. of primary
turns
26.2 Material and
cross-section of
primary (mm2)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 49 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

26.3 Type of primary


27. Whether CT is
suitable for
transportation
horizontally.
28. Percentage
current (ratio)
error and phase
displacement in
minutes at rated
burden and at
28.1 5% rated
current
28.2 10% rated
current
28.3 20% rated
. current
28.4 120% rated
. current
29. Percentage
current (ratio)
error and phase
displacement in
minutes at 25%
rated burden
and
29.1 At 5% rated
current
29.2 At 10% rated
current
29.3 At 20% rated
. current
29.4 At 120% rated
. current
30. Quantity of oil
per CT (Litres)
31. Standard to
which oil

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 50 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

conforms
generally.
32. Characteristics
of oil (prior to
filling)
32.1 Breakdown
voltage (KVrms)
32.2 Dielectric
dissipation
constant (tan
delta)
32.3 Water content
(ppm)
32.4 Gas content
32.5 Interfacial
tension at 270C
(N/m)
32.6 Specific
resistance
32.6 At 900C (Ωcm)
.1
32.6 At 270 C (Ωcm)
.2
33. Whether current
transformers are
hermetically
sealed. If so,
how ?
34. Total weight
(Kg)
35. Transport
weight (Kg)
36.1 Temperature
rise over an
ambient
temperature of
500C for
continuous

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 51 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

operation at
rated
continuous
thermal current.
36.1 Winding
36.2 Oil
36.3 External surface
of the core,
metallic parts in
contact with or
adjacent to
insulation.
37. Whether CT
characteristic
curves
enclosed.
37.1 Ratio and phase
angle curve
37.2 Magnetisation
curves
37.3 Ratio correction
factor curves.
38. DATA ON
PRIMARY
WINDING
38.1 Rated primary
current (A)
38.2 No. of
conductors in
one turn
38.3 No. of turns of
primary
38.4 Material of the
primary
conductors
38.5 Size of the
primary
conductor

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 52 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

(Bare/ Insulated
(mm x mm)
38.6 Cross-sectional
area of each
conductor
(mm2)
38.7 Total cross-
sectional area of
primary winding
(mm2)
conductors
38.8 Current
density(A/mm2)
(i) At highest
ratio
(ii) At
intermediate
ratio
(iii) At lowest
ratio
38.9 Short circuit
current densiry
(A/mm2)
(i) At highest
ratio
(ii) At
intermediate
ratio
(iii) At lowest
ratio
38.1 Ampere-turn of
0 Primary (AT)
(i) At highest
ratio
(ii)At
intermediate
ratio
(iii) At lowest

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 53 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

ratio
38.1 Length of
1 primary
conductor (m)
38.1 Weight of
2 primary winding
(kg.)
39. CORE
39.1 Material and
grade of the
core
39.2 Thickness of
core (mm)
39.3 Net Iron cross-
sectional area of
core (mm2)
39.3 Core-1
.1
39.3 Core – 2
.2
39.3 Core – 3
.3
39.3 Core – 4
.4
39.3 Core – 5
.5
39.4 Mean magnetic
path length (cm)
39.4 Core – 1
.1
39.4 Core – 2
.2
39.4 Core – 3
.3
39.4 Core – 4
.4
39.4 Core – 5
.5

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 54 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

39.5 Whether B-H


curve for the
core material,
used, furnished
? (B-wb/m2, H-
AT/cm)
39.6 Whether
specific loss vs.
flux density
graph for the
core material
used furnished
?
39.7 Axial length of
core (mm)
39.7 Core – 1
.1
39.7 Core – 2
.2
39.7 Core – 3
.3
39.7 Core – 4
.4
39.7 Core – 5
.5
39.8 Inside diameter
/ outside
diameter of the
cores (mm)
39.8 Core – 1
.1
39.8 Core – 2
.2
39.8 Core – 3
.3
39.8 Core – 4
.4
39.8 Core – 5

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 55 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

.5
39.9 Weight of the
core (kg)
39.9 Core – 1
.1
39.9 Core – 2
.2
39.9 Core – 3
.3
39.9 Core – 4
.4
39.9 Core – 5
.5
40. SECONDARY
WINDINGS
40.1 Rated
secondary
current (A)
40.2 Material of the
secondary
windings
40.3 Size of the
. secondary
conductor [Bare
/ Insulated]
[mm]
40.3 Core – 1
.1
40.3 Core – 2
.2
40.3 Core – 3
.3
40.3 Core – 4
.4
40.3 Core – 5
.5
40.4 Cross sectional
area of the

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 56 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

secondary
conductor
(mm2)
40.4 Core – 1
.1
40.4 Core – 2
.2
40.4 Core –3
.3
40.4 Core – 4
.4
40.4 Core – 5
.5
40.5 Current density
of secondary
windings
(A/mm2)
40.5 Core – 1
.1
40.5 Core – 2
.2
40.5 Core – 3
.3
40.5 Core – 4
.4
40.5 Core – 5
.5
40.6 No. of
secondary turns
40.6 Core – 1
.1
40.6 Core – 2
.2
40.6 Core – 3
.3
40.6 Core – 4
.4
40.6 Core – 5

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 57 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

.5
40.7 No. of layers
40.7 Core – 1
.1
40.7 Core – 2
.2
40.7 Core – 3
.3
40.7 Core – 4
.4
40.7 Core – 5
.5
40.8 No. of turns /
layer
40.8 Core – 1
.1
40.8 Core – 2
.2
40.8 Core – 3
.3
40.8 Core – 4
.4
40.8 Core – 5
.5
40.9 Average length /
turn of
secondary
windings (mm)
40.9 Core – 1
.1
40.9 Core – 2
.2
40.9 Core – 3
.3
40.9 Core – 4
.4
40.9 Core – 5
.5

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 58 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

40.1 Resistance of
0 the conductor
used for
secondary
winding per
meter length at
750C (Ω/M)
40.1 Weight of
1 secondary
windings (kg)
40.1 Core – 1
1.1
40.1 Core – 2
1.2
40.1 Core – 3
1.3
40.1 Core – 4
1.4
40.1 Core – 5
1.5
41 INSULATION
41.1 Name and class
of insulating
material
between core
and secondary
winding.
41.2 Name/s of
Insulating
materials
between
secondary
winding and
primary
windings.
41.3 Insulating
materials used
to achieve

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 59 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

grading of
capacitance.
42. DIAMETER OF
WINDINGS
42.1 Inside / outside
diameter of
secondary
windings (mm)
42.1 Inside / outside
.1 diameter of
secondary
windings (mm)
42.1 Core – 1
.1
42.1 Core – 2
.2
42.1 Core – 3
.3
42.1 Core – 4
.4
42.1 Core – 5
.5
42.2 Inside / outsde
diameters of
primary winding
(mm)
42.3 Minimum
clearance from
tank (mm)
42.4 Minimum
clearance from
secondary to
tank (mm)
43. TANK AND
SECONDARY
TERMINAL
BOX
43.1 Material of the

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 60 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

CT tank
43.2 Material of the
CT secondary
terminal box
43.3 Thickness of CT
tank material
(mm)
43.4 Thickness of CT
secondary
terminal box
material (mm)
43.5 Zinc coating of
the CT tank
(gm/m2) as per
relevant upto
date ISS
43.6 Zinc coating of
the CT
secondary
terminal box
(gm/m2) as per
the relevant
upto date ISS.
43.7 Ingress
protection rating
of the
secondary
terminal box.
43.8 Weight of the
tank, fittings and
other
accessories (kg)
44. TERMINAL
CONNECTOR
44.1 Manufacturer’s
name
44.2 Applicable
standard

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 61 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

44.3 Type
44.4 Material of
connector
44.4 Clamp body
.1
44.4 Bolts and Nuts
.2
44.4 Spring washers
.3
44.5 Rated current
(Amp)
44.6 Rated terminal
load (Kg)
44.7 Factor of safety

44.8 Minimum
thickness of any
part (mm)
44.9 Weight of clamp
complete with
hardwares (kg)
44.1 Type test
0 reports as per
IS enclosed
44.1 OGA drawing
1 enclosed
45. INSULATOR
45.1 Manufacturer’s
name
45.2 Type
45.3 Applicable
standards
45.4 Height (mm)
45.5 Diameter (top)
(mm)
45.7 Total creepage
distance (mm)
45.8 Rated voltage

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 62 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

. (KV)

45.9 Power
frequency
withstand
voltage for 1
min. dry and
wet.
(KV – rms)

45.1
0 1.2/50 micro-
sec impulse
withstand
voltage (KVP)

45.1 Corona
1 extinction
vollage (KV)
45.1 Weight (Kg)
2
45.1 Maximum
3 allowable span
(mm)
45.1 Cantilever
4 strength (Kg)
45.1 The drawing
5 enclosed.
46. Dielectric
dissipation
factor at
245/1.732KV
(for 220KV C.T)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 63 of 196


Sl. Description 33KV 132KV 220KV
No.
a)400- b) 800- a) 800- b)600- c) 400- d)400- 1200-600-
200A- 400- 400- 300- 200- 200A/ 300A/
100/ 200A-/ 200A/ 150A/ 100A/ 1-1-1-1-1A
1-1-1A 1-1-1A 1-1-1- 1-1-1- 1-1-1- 1-1-1-
1A 1A 1A 1A

and 145/1.732
KV (for 132 kv
C.T.) at ambient
temperature.
47. Accuracy class
of standard C.T.
to be used
towards
determination of
ratio errors and
phase angle
errors for
metering cores.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 64 of 196


GUARANTEED TECHNICAL PARTICULARS

FOR

CONTROL CABLE & POWER CABLE

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 65 of 196


PART 4: SCHEDULES
25. TECHNICAL DATA SCHEDULES
3. 650/1100V Cable Schedule
The Contractor must complete a schedule for each size of cable supplied
ITEM NO. DESCRIPTION UNITS BIDDERS
OFFER
1 Standards to which the cable conforms IS-1554/IEC 502

2 Catalogue Number -

3 Conductor Material -

4 Conductor Strands Number

5 Conductor Shape -

6 Conductor cross sectional area mm2

7 Outer Diameter of Conductor mm

8 Number of Cores —

9 Reduced neutral conductor cross sectional area mm2

10 Insulation Material -

11 Minimum thickness of insulation mm

12 Nominal thickness of insulation mm

13 Outer Diameter over insulation mm

14 Nominal thickness of inner sheathing mm

15 Sheath Material -

16 Type of armouring —

17 Number and diameter/size of armour wires/strips No/mm

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 66 of 196


18 Minimum outersheath thickness mm

19 Nominal outersheath thickness mm

20 Overall diameter of cable mm

21 Minimum Bending Radius mm

650/1100V Cable Schedule (Continued)


ITEM NO. DESCRIPTION UNITS BIDDERS
OFFER
22 Cable identification per Clause 9 -

23 Rated Voltage per IEC 502/IS - 1554 kV

24 Conductor DC resistance per km at 20°C ohm/km

25 Conductor AC resistance per km at 20°C and ohm/km


50Hz

26 Maximum continuous rating of cable in the A


conditions outlined in Clause 4: System
Conditions

27 Minimum insulation resistance per km at 90°C Mohm/km

28 Maximum permissible continuous conductor °C


temperature

29 Maximum permissible continuous outersheath °C


temperature

30 DC test voltage for 15 mins. after installation kV

31 Delivery length per drum m

32 Weight of conductor per km kg/km

33 Weight of cable per km kg/km

34 Gross weight of full cable drum kg

35 Outer diameter of the cable drum mm

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 67 of 196


36 Width of cable drum mm

37 Maximum permissible cable pulling tension kg

38 Maximum permissible cable side wall pressure kg

39 Manufacturers Name -

40 Country of Origin -

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 68 of 196


GUARANTEED TECHNICAL PARTICULARS

FOR

CONDUCTOR, EARTH WIRE,


INSULATORS

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 69 of 196


A P P E N D I X - IV

Guaranteed Technical Particulars of Conductor


ACSR CONDUCTOR: MOOSE ZEBRA PANTHOR

Sl. Description To be specified


No. by Tenderers

1. Code Word

2. Maker’s name address and


Country.
a) Aluminum rods
b) Steel Wire/rods
c) Complete conductor

3. Stranding and wire diameter


a) Aluminum.
b) Steel.

4. Standard nominal copper


area in sq. mm

5. Calculated equivalent
aluminum area in sq. mm

6. Actual aluminum area

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 70 of 196


in sq. mm.
7. Standard area of cross
section in sq. mm.
a) Aluminum strand
b) Steel strand
c) Conductor

8. Diameter of complete
conductor in mm.

9. Minimum ultimate tensile


stress of strand, in Kg/sq. mm.
Before stranding and after stranding for

a) Aluminum strand.
b) Steel strand

10. Guaranteed ultimate tensile


strength of conductor in Kg.

11. Minimum breaking load in Kg.


Before stranding and after
stranding for

a) Aluminum strand.
b) Steel strand.

12. Purity of aluminum rods.


13. Zinc coating of steel strand.

a) Uniformity of coating
number and/duration of dips.
b) Minimum weight of coating gm/sq. mm.

14. Weight in Kg. per K.M.


a) Aluminum.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 71 of 196


b) Steel.
c) Conductor.
15. Resistance in ohms per Km. at 20° c.

16. Continuous maximum current


rating of conductor in still
air at 45° C ambient temperature,
considering temp. rise of 50°C.

17. Modulus of elasticity of :


Conductor.

18. Co-efficient of linear expansion


per degree centigrade of.
a) Aluminum strand.
b) Steel Strand.
c) Conductor.

19. Percentage of carbon in


steel wire.
20. Standard length of each
peace in Km.
21. Initial and final sags and
tension and stringing charts,
whether furnished.
22. Tolerance, if any on standard length.

23. Number of standard length


in one reel.
24. Dimensions of the reel in cms.
25. Weight of the Conductor

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 72 of 196


in one reel in Kg.
26. Weight of the reel in Kg.
27. Gross weight of the reel
including weight of the conductor.
28. Wheather the conductor will be manufactured
as per the relevant Indian Standard Specification
& as per Section-IV ‘Technical specification’ of this specification.
29. Wheather the conductor will be Tested
as per the relevant Indian Standard Specification
& as per Section-IV ‘Technical specification’ of this specification.
( Cause-12 of Section –IV of Technical Specification)
29. Other particulars, if any.

Signature of the Tenderer

Address
Fax No. Ph. No.
Seal

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 73 of 196


GUARANTEED TECHNICAL PARTICULARS OF THE
GALVANIZED STEEL G.I. EARTH WIRE TO BE FURNISHED
BY THE BIDDER(For 7/3.15 and 7/3.66mm)
1. Maker’s name, address and :
country
2. Percentage of carbon content :
of the steel wire.
3. Particular of steel strands
a) Number of strands.
b) Diameter : Mm
c) Standard sectional area Sq.mm
d) Minimum ultimate tensile N/mm2
strength.
e) Minimum breaking land N/mm2
f) Final stress in steel wires KN/mm2
4. (a) Uniformity of coating of : Minutes Number of dips.
number and duration of dips.
1.
2.
b) Minimum weight of : GM/m2
coating
5. Standard overall diameter of : Sq.mm
ground wire.
6. Area of cross section of : Mm
ground wire.
7. Guaranteed ultimate tensile : N/mm2
strength of ground wire.
8. Maximum working tension : N/mm2
9. Resistance in ohms per KM at :
200C.
10. Standard length of ground : Km.
wire.
11. Modulus of elasticity of : Kg / cm2 Final Initial
ground wire.
12. Co-efficient of linear :
expansion.
13. Zinc coating :-
a) Number of one minute dip :
b) Number of half minute dip.
c) Quality of zinc :
14. Weight of coating on wire :
15. Process of galvanising :

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 74 of 196


GUARANTEED TECHNICAL PARTICULARS FOR INSULATORS
(SEPARATE SHEETS MAY BE FILLED IN FOR EACH VOLTAGE
RATING)
Sl. Description. Single Double Single Double
No. Suspension suspensi Tension Tension.
on
1. 2. 3. 4. 5. 6.
1. Makers name
and address and
country.
2. Size and
designation of
Ball and socket
and standard to
which if will
conform mm.
3. No. of insulator
discs per string.
4. Outside dia of
the disc. Mm
5. Spacing –
mm
6. Creepage
distance of the
single disc –mm
7. Electro-
mechanical
strength of
single disc. Kg.
8. Withstand
voltage of single
disc.
8.1 Power
frequency:
a) Dry-kV
(rms)

b) Wet-kV
(rms

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 75 of 196


Sl. Description. Single Double Single Double
No. Suspension suspensi Tension Tension.
on
8.2 Impulse voltage
1.2/50 micro
second.

a) Positive-
kV (peak)

b) Negative-
kV (peak)
9. Withstand
voltage for the
complete string.
9.1 Power
frequency:

With and
a) Dry-kV without
(rms) corona ang.

b) Wet kV
(rms)
9.2 Lighting impulse
voltage 1.2/50
micro second.

-do-
a) Positive
kV(peak)
b) Negative
Kv(Peak)
9.3 Switching surge
voltage
250/2500 micro
second (for
400KV only)

-do-
a) Dry-kV

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 76 of 196


Sl. Description. Single Double Single Double
No. Suspension suspensi Tension Tension.
on
(rms)

b) Wet kV
(rms)
10. Flashover
voltage for the
disc.
10.1 Power
frequency:

a) Dry-kV
(rms)

b) Wet kV
(rms)
10.2 Lighting impulse
voltage 1.2/50
micro second.

a) Positive
kV(peak)

b) Negative
Kv(Peak)
11. Flashover
voltage for the
complete string.
11.1 Power
frequency:

With and
a) Dry-kV without
(rms) corona ring.

b) Wet kV

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 77 of 196


Sl. Description. Single Double Single Double
No. Suspension suspensi Tension Tension.
on
(rms)
11.2 Lighting impulse
voltage 1.2/50
micro second.
a) Positive
kV(peak)
b) Negative
Kv(Peak)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 78 of 196


GUARANTEED TECHNICAL PARTICULARS

FOR

ISOLATORS

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 79 of 196


GUARANTEED TECHNICAL PARTICULARS FOR DISCONNECTOR
(ISOLATORS)

(To be filled in separately for Disconnectors of different voltage classes and


types)
400/220/132/33 KV
1. Type / installation
2. Manufacturer’s Name and
Country of manufacure
3. standard/s according to which
the isolator are manufactured
4. Maximum design voltage at which
the isolator can operate (kv)
5. frequency (Hz)
6. Rated Voltage (kv)
7. Max. current that can be safely interrupted by the isolator
Inductive (A & % PF)
Capacitive (A & % PF)
8. Continuous current rating (Amps)
9. Rated short time current
(i) For 3 second (KA rms)
(ii) Rated peak short time current (kVp)
10. Current density at the minimum cross-section of
a) Moving blade (Amps/Sq.mm)
b) Terminal pad
c) Contacts
d) Terminal Connector

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 80 of 196


11. Max. temp rise of current carrying parts when carrying rated current
continuously. (deg. C)
12. factor for specified site conditions.
13. Derating Insulation levels.
i) Impulse withstand voltage (kV peak)
a) Phase to Earth
b) Across isolating Distance
ii) Switching surge withstand voltage (kV peak)
(a) Phase to Earth
(b) Across isolating Distance
iii) Power frequency withstand voltage (kV rms)
(a) Phase to Earth
(b) Across isolating distance

iv) Radio interference voltage at 1.1 times maximum line to ground voltage
(micro volts)
v) Corona inception voltage (kV rms)

vi) Corona extinction voltage (KV rms)

14. Minimum clearance in air:


i) Between poles (mm)
ii) Between live parts and earth (mm)
iii) Between live part when switch is open
(a) On the same pole (mm)
(b) Between adjacent poles (mm)
15. Rated mechanical terminal load
a) Load along the terminal connector side (kg)
ii) Load across the terminal connector side(kg)
16. Torque required to operate the switch in Kg. m.
14. Contact zone
(i) Horizontal deflection (mm)
(ii) Vertical deflection (mm)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 81 of 196


(iii) Total amplitude of longitudinal movement w.r.t. conductor supporting
fixing contact (mm)
15. Design and Construction
i) No. of Insulators per pole
ii) Contacts
a) Material and grade
b) Cross-sectional area in sq.mm
i) Moving Blades
a) Material and grade
b) Cross sectional area
ii) Contact Support
a) Material and size of channel / block
b) Material and size of plate
iii) Rain hood – Material grade and size
iv) Turn and twist mechanism
a) Material and size of clamps
b) Material and size of springs
c) Whether springs are encased
v) Nuts and Bolts.
a) Size, material and grade in live parts.
b) Size material and grade in other parts
viii) Insulator base plate
Material and size of plate below insulators
ix) Bearings.
a) Material and size of housing
b) No. of bearings, location and size
x) Tandem pipe
a) Size class and no. of pipes
b) Size of shackle, screw
c) No. of bearings / bush and its material and size
xi) Type of inter lock

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 82 of 196


xii) Down pipe size and class
xiii) Type of universal / swivel joint
a) Between bearing and down pipe
b) Between down pipe and operating mechanism
xiv) Operating mechanism
a) Control cabinet
Material and thickness
Degree of protection
Type size and no. of cable glands
Whether removable gland plate provided.
b) Make type, rating and qty. of motors per isolator
Gears
Limit switches
Contactors
Over load relay
Single phase preventor
Auxiliary switch
Terminal blocks
Insuiator wires
HRC fuses
Pole discrepancy relay
Timer
Space Heater
Interlocks
xv) Insulators
a) Type
b) No. of units per insulator stack.
c) Rating of insulator (kV)
d) Height of each insulator stack (mm)
e) Bolt circle diameter (mm)
f) Tensile strength (kg)
g) Compressive strengh

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 83 of 196


h) Torsional strength (kg. m)
i) Cantilver strength upright (kg)
j) Power frequency dry flash over voltage (kV) rms
k) Power frequency wet flash over voltage (kV) rms
l) Power frequency puncture voltage (kV) rms
m) Impulse flash over voltage (positive wave) (kV) peak
n) Impulse withstand voltage (kV) peak
o) Power frequency withstand voltage (kV) rms
p) Visual discharge voltage level (kV) rms
q) Creepage distance
Total (mm)
Protected (mm)
r) Dry arcing distance (mm)
xvi) Base
a) Size of steel sections used
b) Overall size
c) Total weight
xvii) Terminal connectors
a) Clamp Body
Alloy Composition
Plating if any
Area at min. cross section
b)Bolts and nuts size
Alloy composition
Tensile strength
c)Type of washers used
d)Materials of braids
e)Temperature rise when carrying rated current at 50 deg. C ambient
(deg.C)
f)Weight of each type of clamp (kg)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 84 of 196


List of bought out items.

Sl Particulars of components Qty. Rat Make Ty


. ing pe
N
o.

19.0 List of test certificates (Type and routine)


20.0 List of drawings furnished.

Name of the firm …………………….


Signature of Bidder ………………….
Designation and seal ………………..
Date …………………………………….

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 85 of 196


GUARANTEED TECHNICAL PARTICULARS

FOR

SURGE ARRESTORS

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 86 of 196


ANNEXURE-A.
GUARANTEED TECHNICAL PARTICULARS.

390 KV 216 KV 120 KV


30KV
1 Bidder’s Name and Address.
2 Manufacturer’s Name.
3 Manufacturer’s type designation.
4 Applicable standards.
5 Arrester class and type.
6 Rated Arrester Voltage (KV rms).
7 Maximum continuous operating
voltages (MCOV) at design ambient
temperature (KV-rms).
8 Nominal discharge current (8/20 micro
second wave) (KA).
9 Minimum discharge capability referred
to rated voltage at minimum of
discharge characteristics (KJ/KV).
10 Line discharge class as per IEC.
11 Maximum switching surge residual
voltage at 1 KA (KVP) for
390KV,216KV, 120KV and for 30KV
at 500A.
12 Maximum switching surge residual
voltage at 1 KA for 216 KV.
13 Maximum residual voltage for 8/20
micro-second current wave.
(a) At 50 % nominal discharge current.
(b) At 100 % nominal discharge
current.
(c) At 200 % nominal discharge
current.
14 Maximum residual voltage with 1
micro-second current wave at 10 KAP

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 87 of 196


(KVP).
15 One minute power frequency (dry) &
(wet) withstand voltage of arrester
(KV-rms).
16 Impulse withstand test voltage of
arrester housing with 1.2/50 micro-
second wave (KVP).
17 High current short duration (4/10
micro-second impulse wave) (KAP).
18 Low current long duration (KAP).
19 Reference voltage and corresponding
reference current of arrester (KV)(mA).

20 Maximum internal leakage current by


its rms or peak value and both resistive
and capacitive component separately at
(a) COV (resistive/capacitive) (mA).
(b) 1.1 COV (resistive/capacitive)
(mA).
(c) COV at 150°C
(resistive/capacitive) (mA).
(d) Reference voltage
(resistive/capacitive)(mA).
21 Pressure relief class.
22 Are the protection levels affected by
pollution of external insulation.
23 Energy absorption capability per
operation of the arrester, during a
switching surge discharge (KJ).
24 Maximum amount of energy that may
be despatched into the arrester during
discharge assuming that discharge takes
place within 1 minute period and state
the switching surge current (KJ/KA).
25 Internal pressure required to operate
pressure relief device as a percentage of
burst pressure of porcelain (KJ) & %.
26 Dynamic over-voltage withstand
capability (KV-rms).
(a) For 0.1 Second.
(b) For 1 Second.
(c) For 10 Seconds.
(d) For 100 Seconds.
27 Minimum prospective symmetrical
fault current (KA).
28 Rejection rate of ZnO blocks during

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 88 of 196


manufacturing and operation for the
past three years (%) separately.
(a) 2004-2005.
(b) 2005-2006.
(c) 2006-2007.
29 ZnO DISC DATA.
(a) Rated voltage of ZnO disc. (KV-
rms).
(b) No. of ZnO discs in a unit (Nos.)
(c) No. of units of arrester (Nos.)
(d) Height/thickness of ZnO discs
(mm).
(e) Diameter of ZnO disc (mm).
30 EXTERNAL INSULATION.
(a) Type.
(b) Applicable standard.
(c)(i) Lightning Impulse withstand test
voltage of housing with 1.2/50 micro
sec. Wave (KVP).
(ii) Wet switching impulse test voltage
(KVP)
(d) One minute power frequency
withstand voltage of arrester housing
KV rms.
[i] Dry.
[ii] Wet.
(e) Total creepage distance of arrester
housing (mm).
(f) Cantilever strength of complete
arrester (Kg-m).
31 OVER ALL DIMENSIONS.
(a) Overall Height (mm).
(b) Height upto top of terminal pad
from mounting plane (mm).
(c) Material of terminal pad.
(d) Size of terminal pad (mm).
(e) Mounting dimensions and diameter
of mounting holes (mm).
(f) Diameter of insulator (mm).
(g) Total weight of complete arrester
(Kg.)
32 TERMINAL CONNECTOR.
(a) Manufacturer’s Name.
(b) Applicable standards.
(c) Type.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 89 of 196


(d) Material of connector.
[i] Clamp body.
[ii] Bolts and Nuts.
[iii] Spring washers.
(e) Rated current (Amps.)
(f) Rated terminal load (kg.)
(g) Factor of safety.
(h) Minimum thickness of any part
(mm).
(i) Weight of clamp complete with hard
ware (kg.)
(j) Type test report as per IS enclosed.
(k) OGA Drawing enclosed.
33 INSULATORS.
(a) Manufacturers Name.
(b) Type.
(c) Applicable standards.
(d) Height (mm).
(e) Diameter (top)(mm).
(f) Diameter (bottom) (mm).
(g) Total creepage distance (mm).
(h) Rated voltage (KV – rms).
(i) Power frequency withstand voltage
for 1 min. dry and wet (KV – rms).
(j) 1.2/50 micro - second impulse
withstand voltage (KVP)
(k) Corona Extinction voltage (KV-
rms)
(l) Weight (kg.)
(m) Maximum allowable span (mm).
(n) Cantilever strength (Kg – m).

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 90 of 196


GUARANTEED TECHNICAL PARTICULARS

FOR

33/0.433 KV,250 KVA STATION


TRANSFORMER

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 91 of 196


GUARANTEED TECHNICAL PARTICULARS FOR 33/0.433 KV ,STATION
TRANSFORMER:-

1. Name of the manufacturer.

2. Service.

3. KVA Rating:-

a) H.V. Winding. KVA


b) L.V. Winding. KVA

4. Highest system voltage/Nominal voltage.


a) H.V. Winding. KV
b) L.V.Winding KV

5. Rated frequency. Hz

6. Number of phases.

7. Connections:-
a) H.V. Winding.
b) L.V. Winding.

8. Connection symbol (See IS: 2026 (Part-IV-1977).

9. Tappings:-
a) Range
b) Number of steps for high

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 92 of 196


voltages variation.

10. Reference ambient temperature:-


a) Maximum ambient air/temperature. ºC.
b) Maximum daily average ambient air ºC.
temperature.
c) Maximum yearly average ambient ºC.
air temperature.
d) Minimum ambient air temperature. ºC.
e) Maximum cooling water temperature. ºC.

11. Type of cooling (See IS-2026 (Part-II)/1977.)

12. Temperature rise (See 2026 (Part-II)/1977)


a) Temperature of oil ºC.
b) Winding. ºC.

13. i) Total loss at rated nominal voltage KW


at normal tap & rated frequency.
ii) Stray loss at 75ºC.
iii) % Regulation.

14. (A) Component losses.


a) No-load loss at rated nominal voltage KW
and normal frequency.
b) Load loss at rated current and rated frequency
at normal tapping at 75ºC. & at extreme taps.

(B) Resistance at normal tap & at 75ºC.


i) H.V.
ii) L.V.

15. Impedance voltage & percentage Impedance

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 93 of 196


at full rated current at 75ºC. for the
a) Normal tap.
b) Lowest tap position
c) Highest tap position.

16. Reactance at rated current and Percentage.


rated frequency.

17. No load current at rated nominal voltage and rated


frequency and at 50%, 75%, 100%, 110% & 121%
voltage & at rated frequency.

18. Insulation level (See IS-2026 (Part-III/1977).


a) Separate source power frequency voltage withstand
i) H.V. Winding KV rms.
ii) L.V. Winding. KV rms.
b) Induced over voltage withstand.
i) H.V. Winding. KV rms.
ii) L.V. Winding. KV rms.
c) Full wave lighting impulse withstand voltage
with time vrs. peak voltage characteristic curves.
i) H.V. Winding. KV Peak.
ii) L.V. Winding. KV Peak.
d) P.I. value.

19. Efficiencies at 75ºC at unity power factor.


a) At full load. Percent
b) At ¾ full load -do-
c) At ½ full load -do-
d) At 120% of full load.

20. Regulation at full load at 75ºC


a) At unity power factor. -do-
b) At 0.8 power factor loading & lagging. -do-

21. Equipment for ONAN cooling.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 94 of 196


a) State.
i) No.of Radiators on main tank.
ii) Make & type
iii) Total radiating surface
iv) Thickness of radiator fins
v) Clear distance between fins
vi) Width of radiator fins

22. Number of coolers or cooler banks per transformer

23. Rating of each cooler or cooler bank.

24. Terminal arrangement.


a) High voltage.
b) Low voltage.
c) Neutral.

25. Approximate masses:-


a) Core Kg.
b) Winding. Kg.
c) Tank, fittings & accessories. (Name of Kg.
accessories to be mentioned).
d) Oil. Kg.
e) Core coil assembly Kg.
f) radiators Kg.
g) Total mass Kg.

26. a)Approximate quantity of oil required Ltrs.


for first filling.
b)Name of the manufacturer of oil used

27. Approximate tank dimensions for


over all dimensions.
a) Length mm
b) Breadth. mm
c) Height. mm
d) Thickness of main tank cover plate, mm
side & bottom plate.
e) Tank inside & outside dimension. mm

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 95 of 196


Length/breadth/height. No. of tubes in each
rediator. Tube length in copper, thickness
& dia. Each side tubes (Nos.).

28. Despatch details.


a) Approximate mass of heaviest package. Kg.
b) Approximate dimensions of largest package.
i) Length. mm
ii) Breadth. mm
iii) Height. mm

29. Un-tanking height. mm

30. Additional technical particulars.


i) (a) i. Maximum flux density at highest system Tesla or Wo/m².
voltage & 48.5 c/s frequency.
ii) Maximum flux density at rated system
voltage & rated frequency.
(b) Maximum current density in windings. Amps/Sq.Cm
(c) Size of conductor used. HV/LV
High voltage.
Low voltage.
ii) Efficiency at 75ºC and 0.8 P.F. lagging
At full load. Percent.
At ¾ full load -do-
At ½ full load -do-
Over loading capacity & efficiency.
iii) Load at which maximum efficiency occurs. -do-
iv) Maximum efficiency. Percent.
v) Impulse level with 1/50 Micro.S. Wave.
High voltage KV
Low voltage KV
vi) No-load loss at 110% rated nominal

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 96 of 196


voltage and rated frequency. KV
vii) No load current at 110% & 121% of nominal
voltage & rated frequency. Percentage.
viii) Type of winding.
High voltage.
Low voltage.
No. of turns of H.V.
No. of turns of L.V.
ix) Insulation materials.
Turn insulation high voltage.
Turn insulation low voltage.
Insulation core to low voltage.
Insulation high voltage to low voltage.
x) Clearance:-
Minimum clearance between phases.
a) In oil. mm
b) Out of oil. mm
Maximum clearance high voltage to
tank in oil. mm
Minimum clearance high voltage to
earth in oil. mm
xi) Minimum clearance height for lifting
core & windings from rank. mm.

31. CORE :-
(i) Core materials used. (grade & thickness).
(ii) Loss in watts/Kg. of core materials corres- (Watts/Kg. curve
to be
ponding to desired flux densities. furnished along
with
the bid.).

(iii) EMF per turn

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 97 of 196


(iv) Core circumcircle dia (d).
(v) No. of core bolt holes per phase.
(vi) Dia of each core bolt holes in mm.
(vii) Net iron section (cm²). Limb/Yoke.
(viii) Weight (Kg.)
(ix) Total GI (Kg.)
(x) Total (KW).

No. of steps. 1 2 3
4

Stack in mm.

Width of core in mm.


Stacking factor of core.
-------------------------------------------------------------------------------------------------------
-----------------
32.(a) WINDING :-
Current per phase (Amp.) LV HV HV
regulating.
conductor bare (mm) No. of
conductor insulation (mm).
Conductor section (mm²)
Current density (A/mm²)
Turns per phase (T).
Coils per limb.
Arranged.
Turns per coil.
Turns per layer.
Layers per coil.
Winding depth.
Coil dia inside.
Coil dia outside.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 98 of 196


Length of mean turns.
Resistance at 75ºC,
Total 1² R including stray at 75ºC,
Weight of copper with/without
insulations.
(b) Radiators provided (Nos.).
No. of fins provided.
Radiator size in mm (Length x wide x fin Nos.)
Loss to be dissipated by Radiators in KW.
Dissipation per fin at 50ºC.
Thermal head in mm.
Radiator area.

33. Oil data:-


1. Quantity for first filling. Ltr.
2. Grade of oil used.
3. Maker’s name.
4. BOV at the time of filling.
5. Type of oil.
34. Make of breather and type with capacity
of silica gal filled in grams.

35. Inter layer insulation provided in design for:-


1. Top and bottom layer. mm
2. In between all layers. mm
3. Details of insulation. mm
4. Whether wedges are provided at
50% turns of the coil.

36. Insulation materials.


a) For conductors. H.V.
b) For core. L.V.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 99 of 196


37. Particulars of bushings:-
1. Maker’s name.
2. Type IS-3347/IS-1180.
3. Rating as per I.S.
4. Dry flash over voltage
KV
5. We flash over voltage
KV.
38. I.R. value at 30ºC.
HV/E
LV/E
HV/LV

39. Polarisation Index :-


Measurement of Insulation resistance at
10 minutes/1 minute.

HV/E.
LV/E.
HV/LV.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 100 of 196


GUARANTEED TECHNICAL PARTICULARS

FOR

Surge Arrestor

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 101 of 196


ANNEXURE-A.
GUARANTEED TECHNICAL PARTICULARS.

390 KV 216 KV 120 KV 30KV


1 Bidder’s Name and Address.
2 Manufacturer’s Name.
3 Manufacturer’s type designation.
4 Applicable standards.
5 Arrester class and type.
6 Rated Arrester Voltage (KV rms).
7 Maximum continuous operating
voltages (MCOV) at design ambient
temperature (KV-rms).
8 Nominal discharge current (8/20 micro
second wave) (KA).
9 Minimum discharge capability referred
to rated voltage at minimum of
discharge characteristics (KJ/KV).
10 Line discharge class as per IEC.
11 Maximum switching surge residual
voltage at 1 KA (KVP) for
390KV,216KV, 120KV and for 30KV
at 500A.
12 Maximum switching surge residual
voltage at 1 KA for 216 KV.
13 Maximum residual voltage for 8/20
micro-second current wave.
(a) At 50 % nominal discharge current.
(b) At 100 % nominal discharge
current.
(c) At 200 % nominal discharge
current.
14 Maximum residual voltage with 1
micro-second current wave at 10 KAP
(KVP).

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 102 of 196


15 One minute power frequency (dry) &
(wet) withstand voltage of arrester
(KV-rms).
16 Impulse withstand test voltage of
arrester housing with 1.2/50 micro-
second wave (KVP).
17 High current short duration (4/10
micro-second impulse wave) (KAP).
18 Low current long duration (KAP).
19 Reference voltage and corresponding
reference current of arrester (KV)(mA).

20 Maximum internal leakage current by


its rms or peak value and both resistive
and capacitive component separately at
(a) COV (resistive/capacitive) (mA).
(b) 1.1 COV (resistive/capacitive)
(mA).
(c) COV at 150°C
(resistive/capacitive) (mA).
(d) Reference voltage
(resistive/capacitive)(mA).
21 Pressure relief class.
22 Are the protection levels affected by
pollution of external insulation.
23 Energy absorption capability per
operation of the arrester, during a
switching surge discharge (KJ).
24 Maximum amount of energy that may
be despatched into the arrester during
discharge assuming that discharge takes
place within 1 minute period and state
the switching surge current (KJ/KA).
25 Internal pressure required to operate
pressure relief device as a percentage of
burst pressure of porcelain (KJ) & %.
26 Dynamic over-voltage withstand
capability (KV-rms).
(a) For 0.1 Second.
(b) For 1 Second.
(c) For 10 Seconds.
(d) For 100 Seconds.
27 Minimum prospective symmetrical
fault current (KA).
28 Rejection rate of ZnO blocks during
manufacturing and operation for the

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 103 of 196


past three years (%) separately.
(a) 2004-2005.
(b) 2005-2006.
(c) 2006-2007.
29 ZnO DISC DATA.
(a) Rated voltage of ZnO disc. (KV-
rms).
(b) No. of ZnO discs in a unit (Nos.)
(c) No. of units of arrester (Nos.)
(d) Height/thickness of ZnO discs
(mm).
(e) Diameter of ZnO disc (mm).
30 EXTERNAL INSULATION.
(a) Type.
(b) Applicable standard.
(c)(i) Lightning Impulse withstand test
voltage of housing with 1.2/50 micro
sec. Wave (KVP).
(ii) Wet switching impulse test voltage
(KVP)
(d) One minute power frequency
withstand voltage of arrester housing
KV rms.
[i] Dry.
[ii] Wet.
(e) Total creepage distance of arrester
housing (mm).
(f) Cantilever strength of complete
arrester (Kg-m).
31 OVER ALL DIMENSIONS.
(a) Overall Height (mm).
(b) Height upto top of terminal pad
from mounting plane (mm).
(c) Material of terminal pad.
(d) Size of terminal pad (mm).
(e) Mounting dimensions and diameter
of mounting holes (mm).
(f) Diameter of insulator (mm).
(g) Total weight of complete arrester
(Kg.)
32 TERMINAL CONNECTOR.
(a) Manufacturer’s Name.
(b) Applicable standards.
(c) Type.
(d) Material of connector.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 104 of 196


[i] Clamp body.
[ii] Bolts and Nuts.
[iii] Spring washers.
(e) Rated current (Amps.)
(f) Rated terminal load (kg.)
(g) Factor of safety.
(h) Minimum thickness of any part
(mm).
(i) Weight of clamp complete with hard
ware (kg.)
(j) Type test report as per IS enclosed.
(k) OGA Drawing enclosed.
33 INSULATORS.
(a) Manufacturers Name.
(b) Type.
(c) Applicable standards.
(d) Height (mm).
(e) Diameter (top)(mm).
(f) Diameter (bottom) (mm).
(g) Total creepage distance (mm).
(h) Rated voltage (KV – rms).
(i) Power frequency withstand voltage
for 1 min. dry and wet (KV – rms).
(j) 1.2/50 micro - second impulse
withstand voltage (KVP)
(k) Corona Extinction voltage (KV-
rms)
(l) Weight (kg.)
(m) Maximum allowable span (mm).
(n) Cantilever strength (Kg – m).

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 105 of 196


GTP FOR
CONTROL & RELAY PANEL

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 106 of 196


TECHNICAL DATA REQUIREMENTS

CONTROL AND RELAY PANELS


-------------
----------
(Bidder’s
Name )

1. Name and address of Manufacturer of panels 1.


…………………….
2. Manufacturer’s type and designation 2.
…………………….
3. Type of construction (Simplex /duplex) 3.
……………………
4. Thickness of sheet steel 4.
(i) Front i)
………………………
(ii) Back ii)
……………………..
(iii) Sides iii)
……………………..
5. Degree of protection 5.
……………………..
6. Name of the manufacturer of relays. 6.
……………………..
7. DC voltage of the relays 7.
…………………….
8. Make and Model of static (o.2 accuracy class 8.
…………………….
Type ) energy meters
9. Confirm whether offered manufacturer of C&R
9………………………
Panels and protective relays have tested
Commissioned & they are in successful operation
For at least two years in 400 /220/132/33 kV system.
For 400/220/132 KV Sub-Station

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 107 of 196


1).
(A) TYRANSMISSION LINE PROTECTION

Numerical Distance protection Scheme

1. Name and address of Manufacturer of Relay/panels 1.


…………………….
2. Manufacturer’s type and designation 2.
…………………….
3. Switched or Non-switched type (is 3.
…………………….
It with separate measurements for
Single/three phase faults)
4. Setting range of off set feature
4………………………
5. Whether the relay is having self 5.
……………………..
Monitoring feature.
6. Whether relays is compatible for 6.
………………………
PLCC equipment and can be used
for Permissive Under reach/over
reach /Blocking scheme etc.
7. Suitable for single and three phase Trip? 7.
……………………..
8. Type of shaped characteristic 8.
……………………..
9. Whether it is communicable to other relays
9...............................
of different manufacturer. Also mention the
communicating protocol.
10. Features like broken conductor,SOTF,Distance
10............................
to fault locater & other features as per Tech Spec
are available or not.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 108 of 196


11. No of tripping contacts with making 11.
……………………
Capacity of 30 amp for 0.2 seconds.
12. In case 16 contacts as per above 12.
…………………..
Clause are not available with the distance relay
Offered, type tripping relays being offered.
13. Maximum operating time for at 50% of the 13.
…………………..
Reach setting of 2 ohms and 10/20 ohms
(with CVT) including all trip relays, if any
(Bidder is required to enclose isochronic
Curve with CVT on line)
a) at SIR=4 a)
…………………….
b) at SIR=15, (3 phase faults) b)
…………………..
c) at SIR=15 (other faults) c)
…………………….
14. IDMT earthy fault relay meeting Normal 14.................
Inverse Characteristics as per IEC 60253
Is being offered as built in feature for 400/220/132 KV lines.
15. If no, type of IDMT relay being offered
15.......................
16. Built in feature offered with the relay (YES/NO) 16........
a) Disturbance recorder a)
……………………
b) Fault locater b)
……………………
c) Over voltage (one stage only) c)
……………………
d) Auto recluse along with Dead line d)
………………….
e) Charging and check synchronizing. e)
………………….
17. Indicate the no. of Binary Input & Out put contacts
17........................

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 109 of 196


(B) STATIC DISTANCE PROTECTION SCHEME
1. Name and address of Manufacturer 1.
…………………….
2. Manufacturer’s type and designation 2.
…………………….
3. Switched or Non-switched type (is 3.
…………………….
it with separate measurements for
Single/three phase faults)
4. Setting range of off set feature.
4………………………
5. Whether the relay is compatible for PLCC 5.
…………………….
Equipment and can be used for permissive
Under reach/over reach/Blocking scheme etc.
6. Suitable for single and three phase Trip 6.
………………………

7. Type of shaped characteristic 7.


………………….
8. No of tripping contacts with making 8.
……………………
Capacity of 30 amp for 0.2 seconds.
9. In case 16 contacts as per above 9.
…………………..
Clause are not Available with the distance relay
Offered, type of tripping relays being offered.
10. Maximum operating time for at 50% of the 10.
…………………..
Reach setting of 2 ohms and 10/20 ohms
(with CVT) including all trip relays, if any
(Bidder is required to enclose isochronic
Curve with CVT on line)
a) at SIR=4 a)
…………………….
b) at SIR=15, (3 phase faults) b)
…………………..
c) at SIR=15 (other faults) c)
………………….
11. Built in feature offered with the relay (YES/NO)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 110 of 196


a) Disturbance recorder a)
……………………
b) Fault locator b)
……………………
c) Over voltage (one stage only) c)
……………………
d) Auto recluse along with Dead line d)
………………….
Charging and check synchronizing.

(C) BACKUP DIRECTIONAL OVER CURRENT


AND EARTH FAULT PROTECTION SCHEME( Numerical)
1. Name and address of Manufacturer 1.
…………………….
2. Manufacturer’s type and designation 2.
…………………….
3. Three over current and one E/F elements 3.
…………………..
Are whether independent or composite unit
4. Type of relay (Numerical) 4.
………………….
5. Directional sensitivity. 5.
…………………..
6. Whether characteristics conform to IEC 255-3 6.
…………………..
7. Over current unit setting range inverse time
7……………………
8. Earth fault unit setting range inverse time 8.
………………..
9. VT Fuse failure relay/ feature included 9.
………………….
For alarm.
10. Whether it is communicable to other relays
10...............................
of different manufacturer. Also mention the
communicating protocol.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 111 of 196


(D) LINE OVER VOLOTAGE PROTECTION RELAY
1. Name and address of Manufacturer. 1.
…………………….
2. Manufacturer’s type and designation 2.
…………………….
3. Type of relay (Electromechanical/static/Numerical) 3.
…………………..
4. Operation indicator provided? 4.
………………….
5. Operating time 5.
………………….
6. Resetting time 6. ……………….
7. Whether monitors all three phases? 7.
………………..
8. Built in feature of Main/Main 2 distance 8.
………………….
Relay is offered. If so, which stage is
Offered as built in

(E) DISTANCE TO FAUALT LOCATOR

1. Name and address of Manufacturer of panels 1.


…………………….

2. Manufacturer’s type and designation 2.


…………………….
3. Built in feature of Main/Main 2 distance 3.
………………….
Relay is offered
4. Maximum registering time 4.
………………….
5. Whether direct display unit provided? 5.
………………….
6. Whether both phase to phase fault and 6.
…………………..
Phase to earth fault measuring units included?

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 112 of 196


7. Whether-On-Line type 7. ………….....

8. Accuracy for the typical conditions defined 8.


………………..
Under technical specification.

(F) DISTURBANCE RECORDER


a. Acquisition unit.

1. Name and address of Manufacturer . 1.


…………………….
2. Manufacturer’s type and designation 2.
…………………….
3. No. of analogue channels 3.
…………………..
4. No. of digital recording channels. 4.
……………………
5. Built in feature of Main 1/ Main 2 distances. 5.
…………………..
Relay is offered.

6. Pre-fault memory (milli seconds) 6. ……………….


7. Post fault memory (seconds) 7. …………….
8. Total storage memory is seconds. 8.
…………….
9. Sampling Frequency. 9. …………….
10. Resolution of the event channels (ms) 10. …………….
11. Time display present? 11.
………………
12. Data out put in COMTRADE is available. 12.
………………
b. Evaluation Unit.
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 113 of 196


3. No. of acquisition unit that can be connected` 3.
To one evaluation unit.
4. Technical parameters of evaluation unit 4.
A. Processor and speed. A.
B. RAM and hard disk capacity. B.
C. Additional facilities. C.
D. Details of printer. D.
5. Details of power supply arrangement for 5.
Acquisition unit (including printer).

(G) AUTO RECLOSE RELAY


1. Name and address of Manufacturer. 1……………
2. Manufacturer’s type and designation. 2. ……….

3. Electromechanical/ static /numerical. 3……………


4. Auto re closure relay along with Dead line charging 4.
And check synchronizing relay (For 132 KV
Lines) offered as a part of distance relay.
5. Built in feature of Main 1/ Main 2 distances. 5.
…………………..
Relay is offered.
6. Suitable for single and three phase? 5. …………..
7. Single phase dead time setting Range. 6. ……………
8. Three phase dead time setting range. 7. ………….
9. Reclaim time setting range. 8……………

2.)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 114 of 196


TRANSFORMER PROTECTION
a) Differential relay.
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Second harmonic restraint provided. 3. ………….
4. Whether three instantaneous units provided 4. ………….
5. Operating current setting range. 5…………..
6. Bias setting range,. 6. ………..
7. Operating time at 5X setting current. 7. ………..
8. Resetting time. 8. ……….
9. How ratio / phase angle corrections are being 9. ……………
done (inter posting transformer/ internal feature
in the relay)
10. Whether numerical or not 10.................
11. Fifth Harmonic restraint feature. 11................
12. Communication protocol 12..............

b) Restricted Earth Fault Protection


1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Operating time at 2 x setting. 3. ……………..
4. Whether numerical 4.................
5. Whether suitable for all type of transformer 5.............
windings or not.

c) Over Fluxing relays.

1. Name and address of Manufacturer 1. …………….


2. Manufacturer’s type and designation 2………………
3. Whether inverse time operating characteristics 5. ………….
4. Maximum operating time. 6. …………….
5. Accuracy of operating time. 7.
………….
6. Resetting time. 8. ………….

d) Directional O/C and E/F relays.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 115 of 196


1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Whether Characteristic will confirm to IEC 255-3 3…………….
4. Directional sensitivity. 4………………
5. Over current unit setting range 5. …………..
a) Inverse time a) ……
b) High set b) ………….
6. Earth fault unit setting range. 7. ……………
a) Inverse time a) ……………
b) High set b) …………..
7. Whether numerical 7................
8. Features of disturbance recording 8..............

3)
GENERAL PROTECTION / MONITORING EQUIPMENT
a) Trip Circuit Supervision relay.
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Whether pre-closing and post closing 3. ……………
Supervision provided?
4. Time delay. 4. ……………

b) High Speed Trip Relays.

1. Name and address of Manufacturer 1. …………….


2. Manufacturer’s type and designation 2………………
3. Contact rating. 3. ……………
a) Making and carry continuously a) ………….
b) Make and carry for 0.5 sec. b)………….
c) Break. c) …………..
i) Resistive load. I) ……………
ii) Inductive load. Ii) ……………
(With L/R= 40 milli sec.).

4. Operating time at rated voltage (maximum) 4. ……………


5. Resetting time .. 5. ………….

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 116 of 196


6. Whether supervisory relays included. 6. ……………

c) Local breaker back-up protection.

1. Name and address of Manufacturer 1. …………….


2. Manufacturer’s type and designation 2………………
3. Operating time 3. …………….
4. Resetting time. 4. ……………
5. Setting ranges 5. ……………
a) Current a) …………..
b) Time. b) …………..

4)
BUS BAR PROTECTION
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Type of relay
(Numerical) 3. ……………

4. Principle of operation (Biased.High/Low impedance) 4. ………….


5. Operating time 5. …………….
6. Resetting time. 6. …………..

7. Resetting ranges. 7. …………..


(i) Current. (i) ………..
(ii) Time. (ii) ……………

8. Whether will it cause tripping for the differential 8. ……………..


Current below the load current of heavily
Loaded feeder (Bidder shall submit application
Check of the same).
9. Whether LBB protection features available. 9......................
10. Features of disturbance recording 10..................
11. Communication protocol 11..............
5)
Meters and Instruments Indicating meters.
1. Name and address of Manufacturer 1. …………….

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 117 of 196


2. Manufacturer’s type and designation 2………………
3. Operating principle or type of movement. 3. …………..

4. Range: 4. …………….
(i) Voltage. (i) ……………
(ii) Current (ii) ………….
(iii) Frequency (iii) ……………
iv) Megawatt (iv) …………….
v) Megavar (v) ……………..
5. Accuracy class. 5. ……………….
6. Total deflection angle 6. ………………
7. Overall dimensions in mm. 7. ………………
8. Burden 8. …………….
(i) Current coil (i) ……………
(ii) Voltage coil. (ii) …………..
9. Digital type 9...............
a) Recording Meter for voltage
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Accuracy class. 3. ……………
4. Full span response time 4. …………..
5. Is it strip type recorder/ digital type 5. ……………
6. If it is digital type 6……………
i) No of channels beings used. I) ………………..
ii) Whether time tagged information is available ii) ……………..
iii) Whether EMNC./EMI compatibility is tested iii) …………….
b) Recording Meter for Current
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Accuracy class. 3. ……………
4. Full span response time 4. …………..
5. Is it strip type recorder/ digital type 5. ……………

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 118 of 196


6. If it is digital type 6……………
i) No of channels beings used. I) ………………..
ii) Whether time tagged information is available ii) ……………..
iii) Whether EMNC./EMI compatibility is tested iii) …………….
c) Recording Meter for MW
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Accuracy class. 3. ……………
4. Full span response time 4. …………..
5. Is it strip type recorder/ digital type 5. ……………
6. If it is digital type 6……………
i) No of channels beings used. I) ………………..
ii) Whether time tagged information is available ii) ……………..
iii)Whether EMC./EMI compatibility is tested i ii) …………….
d) Recording Meter for MVAR
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Accuracy class. 3. ……………
4. Full span response time 4. …………..
5. Is it strip type recorder/ digital type 5. ……………
6. If it is digital type 6……………
i) No of channels beings used. I) ………………..
ii) Whether time tagged information is available ii) ……………..
iii)Whether EMC./EMI compatibility is tested iii) …………….
e) Recording Meter for frequency.

1. Name and address of Manufacturer 1. …………….


2. Manufacturer’s type and designation 2………………
3. Accuracy class 3. …………..
4. Full span response time. 4. …………..
5. Is it strip type recorder/ digital type 5. …………..
6. If it is digital type 6……………

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 119 of 196


i) No of channels beings used. I) ………………..
ii) Whether time tagged information is available ii) ……………..
iii) Whether EMC./EMI compatibility is tested iii) …………….

6) OTHERS:
a) Terminal Block
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Rated current. 3. ……………
4. Rated voltage. 4. ……………
5. Minimum no. of conductors of area 5.
2.5mm² suitable for connection.
(i) All circuits except CT./P.TCircuits.
(i)……………
(ii) C.T. Circuits. (ii) ………….
b) Switches.
i) Control Switches.
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. No.of contacts. 3. ……………
4. Type of handle. 4. ……………..
5. Rating of handle. 5. …………….
6. Rating of contacts. 6. ……….. …….
a) Make and carry continuously. a) …………..
b) Make & carry for 0.5 sec. b) …………….

c) Break resistive load, in Amps (d.c) c) ………..


d) Break inductive load with L/R=40 m.sec d) …………..
inn Amps. (d.c)

7. Life of switch in terms of million mechanical 7.


operations
ii) Synchronizing switch
1. Name and address of Manufacturer 1. …………….

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 120 of 196


2. Manufacturer’s type and designation 2………………
3. Contact ratings. 3. …………..
4. No.of positions. 4. ……………
5. Removable handle type? 5. ……………
6. No.of contacts 6. ……………
iii) Indicating Lamps.
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Ratings
(i) Current (i) …….
(ii) Voltage (ii) …………
(iii) Wattage (iii) …………
4. Whether series resistors are provided? 4. ……………
5. If series resistors provided, give 5. ……………
(i) Ohmic value (i) ……..
(ii) Wattage (ii) …………..
6. Life of Lamps in burning hours. 6. ……………
7. Permissible voltage variation 7. …………..
8. Whether LED type 8...............
iv) Push Buttons.
1. Name of Manufacturer. 1.
…………………….
2. Manufacturer’s type and designation 2………………
3. Contact ratings. 3. …………..
4. No.of contacts 4. ……………
v) Semaphore Indicators.
1. Name and address of Manufacturer 1. …………….
2. Manufacturer’s type and designation 2………………
3. Is colour similar to mimic? 3. ………….
4. No.of positions 4. …………….
5. Burden DC 5. …………..

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 121 of 196


6. Is the coil continuously rated? 6. …………..
vi) Trransducers.
1. Make 1. …………….
2. type & Model No. 2. ……………..
3. Nominal AC input voltage. 3. …………….
4. Frequency. 4. ……………..
5. Input measuring Range 5. ………………
6. Output current range. 6. ……………..
7. Accuracy range. 7.
8. Response time. 8……………….
9. A.C. ripple on output 9. ……………….
10. Load Resistance (Maxm.) 10.
……………….
11. Auxiliary supply voltage.. 11.
……………….
vii) Annunciators.
1. Make 1. ………………
2. Type & Model No. 2. ………………
3. Static/electromechanical 3. ……………….
4. No. of lamps per window 4. ………………
5. Lamps 5.
……………….
a) Voltage a) ………………
b) Wattage. b) ……………..

6. Minimum duration of impulse for initiating. 6. ……………


Contact in millisecond

7. Type of reset self/manual. 7……………..


Bidders Name:

Bidders Signature:

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 122 of 196


GTP FOR
LIGHTING

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 123 of 196


LYGHTING SYSTEM
A Lighting System & Accessories A

1. Manufacturer’s Name and address


1…………………………………………..
a) Fixture
a)………………………………………….
b) Accessories
b)………………………………………….

2. Applicable Standards for


2……………………………………………
a) Fixture
a)………………………………………….
b) Accessories
b)………………………………………….

3. Manufacturer’s Name type and catalogue no. for 3.


………………………………………….
a) Fixture
a)………………………………………….
b) Accessories
b)………………………………………….

4. maximum permissible supply voltage


Variation for satisfactory operation of
a) Fixture
a)………………………………………….

b) Accessories
b)………………………………………….
 
B.  Conduits & Accessories        B. 
  (For each type & size) 
 
1. Manufacturer’s Name and address    1. ………………………………………… 

2. Manufacturer’s type, designation      2. …………………………………………. 

3. Applicable standard       3. ………………………………………… 

C.  Junction Boxes          C 
  (For each type & size) 
 
1. Manufacturer’s Name and address    1. ………………………………………… 

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 124 of 196


2. Manufacturer’s type, designation      2. …………………………………………. 

3. Type of enclosure          3. ………………………………………… 

D.  Lighting panels          D. 


  (For each type & size) 
 
 
1. Manufacturer’s Name and address      1. ………………………………………… 

2. Type              2. 
………………………………………… 

3. Degree of Protection          3. 
………………………………………… 

E. Lighting Transformer E.
1. Manufacturer’s Name and address      1. ………………………………………… 

2. Type              2. 
………………………………………… 

3. Rating (KVA)            3. 
………………………………………… 

4. Standards Applicable          4. 
………………………………………… 

5. Degree of protection for enclosure      5. ………………………………………… 

F. Lighting Ploes
1. Manufacturer’s Name and address      1. ………………………………………… 

2. Type              2. 
……………………………………….. 

3. Dimensions           3. ………………………………………..   

G. Lighting Wires. G.

1. Manufacturer’s Name & Address. 1.


………………………………………..

2. Voltage grade 2.
………………………………………..

3. Cross section of conductor. 3.


………………………………………..

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 125 of 196


4. Insulation Thickness. 4.
………………………………………

Bidders Name:

Bidders Signature:

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 126 of 196


GTP FOR
DISTRIBUTION
BOARD

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 127 of 196


DISTRIBUTION BOARD
L.T. Switchgear
1. Manufacturer’s Name 1.
…………………………………
2.  Whether Manufacturer’s have supplied      2.        YES    NO 
  50 Nos. draw out Air circuit breaker  
panel out of which 5 Nos. are with CT  
and relaying scheme.  
 
3.     Whether manufacturer’s have supplied      3.  YES    NO 
50 Nos. MC panels similar to the offered panels. 
 
4. Whether 100 nos. (at least ) circuit breakers of    4.  YES    NO 
the make and type being offered are already  
been operating satisfactorily.  
 
5. Rated short circuit current          5.  
 
5.1 Symmetrical short circuit withstand      5.1 
……………………………………… 
Current at rated voltage of switchgear 
cubicle. 
 
5.2  Peak short circuit withstand current      5.2 ………………………………… 
 
6. Degree of protection.          6. 
……………………………………….. 
 
6.1  Breaker / MCC/ AC & DC          6.1. 
………………………………….. 
 
6.2  Distribution Cubicles.          6.2 ………………………………….. 
 
6.3  Busbar Chamber            6.3 
………………………………….. 
 
7. Standard height, width & depth of typical panel  7.  
 
7.1  Circuit Breaker Panel          7.1 ………………………………….. 
 
7.2  MCC panel              7.2 
………………………………… 

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 128 of 196


 
7.3  AC/DC Distribution Board.          7.3 
………………………………… 
 
8. Width of cable alley           8. …………………………………… 
 
9. Whether equipment are type tested as per IS    9.  YES    NO 

Bidders
Name:

Bidders
Signature:

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 129 of 196


GUARANTEED TECHNICAL PARTICULARS

FOR

TRANSMISSION LINE
400/220/132 KV

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 130 of 196


GUARANTED TECHNICAL PARTICULARS TO BE FIILED BY THE BIDDERS
SCHEDULE : B
Manufacturers And Place Of Manufacture,
Testing And Inspection
(To be filled up by Bidder)

Item Manufacturer Place of Place of testing


manufacture and inspection
Line conductors (ACSR) : SUPPLIED BY THE EMPLOYER

Earthwire (galvanised steel) :


Steel billets
Drawing steel wires
Stranding complete conductors

Insulator units

HV testing laboratory - -

Insulator set fittings

Earthwire fittings

Conductor joints

Conductor spacers/spacer dampers

Vibration dampers (for earthwires and


conductors)

Steel towers :
Design
Steel billets, etc.
Steel sections
Fabrication
Galvanising
Check assembly
Tower tests - -

Bolts and nuts

Tower fittings

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 131 of 196


Earthing materials

SCHEDULE : C
General Technical Particulars And Guarantees
(Parameters considered and guaranteed by the Bidder for the purpose of
this Contract. The data filled in shall form the part of the Contract,
in case of Award and shall be binding on the Contractor )

C. 1 - Span Lengths
(To be filled up by the Bidder )

Unit 132kV 220kV 400kV

Normal span m

Tower design spans:

Wind spans:

Suspension towers m

Tension towers m

Maximum weight spans:

Suspension towers m

Tension towers m

Minimum weight spans:

Suspension towers m

Tension towers (uplift net) m

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 132 of 196


C . 2 - Line Conductor : 132 kV Construction
(To be filled up by the Bidder )

Unit
Complete line conductor:

Actual area (total) per single conductor mm2

Number of conductors per phase

Horizontal distance between conductor centres of one phase mm

Each single conductor:


ACSR conductor of code name

IEC STANDARD No

INDIAN STANDARD No

Material of conductor

Number and diameter of wires:


Aluminium No./mm

Total area of conductor mm2

Overall diameter of stranded conductor mm

Mass of conductor per kilometre kg

Ultimate strength of conductor Newton

Maximum tension of conductor at 5°C and 36% full wind Newton


pressure

Maximum tension of conductor at 32°C with full wind pressure Newton

Maximum tension of conductor in still air at minimum Newton


temperature of 5°C

Assumed equivalent modulus of elasticity of conductor N/mm2

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 133 of 196


Assumed equivalent coefficient of linear expansion of per °C
conductor

C . 2 - Line Conductor : 132 kV Construction (Continued)


(To be filled up by the Bidder)

Unit
Vibration damping system:

*Maximum span for:


One vibration damper at each end of span m
Two vibration dampers at each end of span m
Three vibration dampers at each end of span m

Dimensions from clamp mouth to vibration damper attachment:


First damper mm
Second damper when required mm
Third damper when required mm

* Delete as appropriate and fill in details for selected damping system

(After placement of order, the Contractor has to carry-out vibration analysis and furnish a
detailed vibration damper placement chart, as has been specified at Clause No. 2.3.14, for the
approval of the Project Manager. )

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 134 of 196


C . 3 - Line Conductor : 220 kV Construction
(To be filled up by the Bidder)

Unit
Complete line conductor:

Actual area (total) per single conductor mm2

Number of conductors per phase

Horizontal distance between conductor centres of one phase mm

Each single conductor:


ACSR conductor of code name

IEC STANDARD No

INDIAN STANDARD No

Material of conductor

Number and diameter of wires:


Aluminium No./mm

Total area of conductor mm2

Overall diameter of stranded conductor mm

Mass of conductor per kilometre kg

Ultimate strength of conductor Newton

Maximum tension of conductor at 5°C and 36% full wind Newton

Maximum tension of conductor at 32°C with full wind Newton

Maximum tension of conductor in still air at minimum Newton


temperature of 5°C

Assumed equivalent modulus of elasticity of conductor N/mm2

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 135 of 196


Assumed equivalent coefficient of linear expansion of per °C
conductor

C . 3 - Line Conductor : 220 kV Construction (Continued)


(To be filled up by the Bidder)

Unit
Vibration damping system:

*Maximum span for:


One vibration damper at each end of span m
Two vibration dampers at each end of span m
Three vibration dampers at each end of span m

Dimensions from clamp mouth to vibration damper attachment:


First damper mm
Second damper when required mm
Third damper when required mm

* Delete as appropriate and fill in details for selected damping system

(After placement of order, the Contractor has to carry-out vibration analysis and furnish a
detailed vibration damper placement chart, as has been specified at Clause No. 2.3.14, for the
approval of the Project Manager. )

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 136 of 196


C . 4 - Line Conductor : 400 kV Construction
(To be filled up by the Bidder)
Unit
Complete line conductor:

Actual area (total) per single conductor mm2

Number of conductors per phase

Horizontal distance between conductor centres of one phase mm

Each single conductor:


ACSR conductor of code name

IEC STANDARD No

INDIAN STANDARD No

Material of conductor

Number and diameter of wires:


Aluminium. No./mm

Total area of conductor mm2

Overall diameter of stranded conductor mm

Mass of conductor per kilometre kg

Ultimate strength of conductor Newton

Maximum tension of conductor at 5°C and 36% full wind Newton

Maximum tension of conductor at 32°C with full wind Newton

Maximum tension of conductor in still air at minimum Newton


temperature of 5°C

Assumed equivalent modulus of elasticity of conductor N/mm2

Assumed equivalent coefficient of linear expansion of per °C


conductor

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 137 of 196


C . 4 - Line Conductor : 400 kV Construction (Continued)
(To be filled up by the Bidder)

Unit
Vibration damping system and Spacing system:

*Maximum span for:


One vibration damper at each end of span m
Two vibration dampers at each end of span m
Three vibration dampers at each end of span m

Dimensions from clamp mouth to vibration damper attachment:


First damper mm
Second damper when required mm
Third damper when required mm

Mean sub span for spacers m

If spacer dampers are to be offered:

Mean sub span for spacer dampers m

* Delete as appropriate and fill in details for selected damping system

(After placement of order, the Contractor has to carry-out vibration analysis and furnish a
detailed vibration damper placement chart, as has been specified at Clause No. 2.3.14, for the
approval of the Project Manager. Also ,for spacer and spacer damper the Contractor shall
furnish placement chart, for the approval of the Project Manger, as per the Clause No. 2.4.3.2
and 2.5.20 respectively. )

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 138 of 196


C . 5 - Earth Wire : 132 kV and 220 kV Constructions
(To be filled up by the Bidder)

Unit GSW
Complete earth conductor:

Appropriate Indian Standard No

Appropriate IEC Standard No

Material of conductor

Number and diameter of wires No./mm

Overall diameter of conductor mm

Mass of conductor per kilometre kg

Ultimate strength of conductor Newton

Lay length mm
Direction of the lay of the outer layer
Chemical composition of the steel wire

Carbon %
Manganese
Phosphorous
Sulphur
Silicon
Purity of Zinc for galvanising

Steel strands after galvanising


Diameter %
Minimum breaking load of one strand
Galvanising

a) Minimum weight of Zinc coating per sq.m. of the mm


uncoated wire surface after galvanising
kN
gms

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 139 of 196


C . 5 - Earth Wire : 132 kV and 220 kV Constructions (Continued)
(To be filled up by the Bidder)

Unit GSW

b) Minimum no. of one minute dips that the galvanised Nos.


strand can withstand after stranding in Standard
Preece Test

Maximum tension at 5°C and 36% full wind Newton

Maximum tension at 32°C with full wind Newton

Maximum tension of conductor in still air at 5°C Newton

Assumed equivalent modulus of elasticity of


Conductor hbar

Assumed equivalent coefficient of linear expansion


of conductor per °C

Maximum length of conductor on drum # km

D.C. resistance at 20 o C ohms/km

Maximum span for:


One vibration damper at each end of span m
Two vibration dampers at each end of span m
Three vibration dampers at each end of span m

Dimensions from clamp mouth to vibration damper


attachment
First damper mm
Second damper when required mm
Third damper when required mm

# It is permitted to supply two lengths of 2 kms each, in a single drum.

(After placement of order, the Contractor has to carry-out vibration analysis and furnish a
detailed vibration damper placement chart, as has been specified at Clause No. 3.3 , for the
approval of the Project Manager. )

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 140 of 196


C . 6 - Earth Wire : 400 kV Construction (To be filled up by the Bidder)

Unit GSW
Complete earth conductor:

Appropriate Indian Standard No

Appropriate IEC Standard No

Material of conductor

Number and diameter of wires No./mm

Overall diameter of conductor mm

Mass of conductor per kilometre kg

Ultimate strength of conductor Newton

Lay length mm

Chemical composition of the steel wire %

Carbon
Manganese
Phosphorous
Sulphur
Silicon

Purity of Zinc for galvanising %

Steel strands after galvanising

Diameter mm
Minimum breaking load of one strand kN

Galvanising

a) Minimum weight of Zinc coating per sq.m. of the gms


uncoated wire surface after galvanising

b) Minimum no. of one minute dips that the galvanised


strand can withstand, after stranding in Standard
Preece Test.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 141 of 196


C . 6 - Earth Wire : 400 kV Construction (Continued)
(To be filled up by the Bidder)

Unit GSW

Maximum tension at 5°C and 36% full wind pressure Newton

Maximum tension at 32°C with full wind pressure Newton

Maximum tension of conductor in still air at 5°C Newton

Assumed equivalent modulus of elasticity of


Conductor hbar

Assumed equivalent coefficient of linear expansion


of conductor °C

Maximum length of conductor on drum # km

D.C. resistance of the complete earthwire at 20OC ohms/km.

Direction of lay of the outer layer

Maximum span for:


m
One vibration damper at each end of span
m
Two vibration dampers at each end of span
m
Three vibration dampers at each end of span

Dimensions from clamp mouth to vibration damper


attachment
First damper mm
Second damper when required mm
Third damper when required mm
# It is permitted to supply two lengths of 2kms each, in a single drum.

(After placement of order, the Contractor has to carry-out vibration analysis and furnish a
detailed vibration damper placement chart, as has been specified at Clause No. 3.3 , for the
approval of the Project Manager.)

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 142 of 196


C . 7 - Earthwire Fittings and Accessories
(To be filled up by the Bidder)

Unit GSW:7/3.15 GSW:7/3.66

Suspension Clamps

Total drop mm

Weight of the assembly kg

Breaking load kN

Slipping strength kN

Tightening torque kN

Galvanising

a) Minimum weight of Zinc coating per Sq.m. of gms./sq.m


uncoated surface

b) No. of one minute dips all the galvanised


parts can withstand in Standard Preece test

c) Purity of Zinc used for galvanising %

Tension Clamps

Total weight of the assembly kg

Weight of the steel parts kg

Weight of the Aluminium encasing kg

Slipping strength of the clamp kN

Minimum breaking load of the assembly kN

Compression pressure Tonne


a) Steel sleeve
b) Aluminium encasing

Inside diameter ( Before compression ) mm


a) Steel sleeve
b) Aluminium encasing

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 143 of 196


C . 7 - Earthwire Fittings and Accessories (continued )
(To be filled up by the Bidder)

Unit GSW:7/3.15 GSW:7/3.66

Outside dimension of the steel sleeve mm


a) Before compression
b) After compression
i) Corner to corner
ii) Surface to surface

Outside diameter of the Aluminium encasing (Before mm


compression )

Outside dimension of the clamp after compression of the mm


Aluminium encasing

Length of the steel sleeve mm


a) Before compression
b) After compression

Final dimension of the clamp after compression with mm


Aluminium encasing

Brinnel hardness no. of the steel sleeve (range)

Resistance of the completed tension clamp ohms

Galvanising :

a) Minimum weight of Zinc coating per gms./sq.m


Sq.m. of uncoated surface

b) No. of one minute dips all the galvanised


parts can withstand in Standard Preece test

c) purity of Zinc used for galvanising %

Mid-span compression joints for earthwire

Total weight of the joints kg

Weight of the steel sleeve kg

Weight of the aluminium sleeve kg

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 144 of 196


C . 7 - Earthwire Fittings and Accessories (continued )
(To be filled up by the Bidder)

Unit GSW:7/3.15 GSW:7/3.66

Inside diameter before compression mm


a) Steel sleeve
b) Aluminium encasing

Outside diameter before compression mm


a) Steel sleeve
b) Aluminium encasing

Outside dimensions of the joint after compression mm


a) Steel sleeve
i) Corner to corner
ii) Surface to surface
b) With aluminium encasing

Length of the steel sleeve mm


a) Before compression
b) After compression
Final length of the joint after compression with mm
aluminium encasing

Compression pressure Tonne

Slipping strength kN

Resistance of the completed joint ohms

Galvanising :
a) Minimum weight of Zinc coating per gms./sq.m
Sq.m. of uncoated surface

b) No. of one minute dips all the galvanised


parts can withstand in Standard Preece test

c) Purity of Zinc for galvanizing %

Flexible copper bonds

Resistance of the Cu-bond ohms

Total weight of the Cu-bonds kg

Slipping strength kN

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 145 of 196


C . 8 - Conductor(ACSR) Fittings and Accessories
(To be filled up by the Bidder)

Unit PANTHER ZEBRA MOOSE


Mid-span compression joints for
Conductors

Weight of the joints kgs

Slipping strength kN

Resistance of the completed joints ohms

Material of the joints


(specify alloy type and its aluminium
contents )

Before compression dia. of sleeve mm

a) Inner diameter

b) Outer diameter

Dimensions after compression mm

a) Corner to corner

b) Surface to surface

Length of the sleeve mm

a) Before compression

b) After compression

Compression pressure Tonne

Whether designed for intermittent or


continuous compression

Minimum corona extinction voltage kV


under dry conditions

Radio interference voltage under Micro


conditions Volts

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 146 of 196


C . 8 - Conductor(ACSR) Fittings and Accessories (continued )
(To be filled up by the Bidder)

Unit PANTHER ZEBRA MOOSE


Repair sleeve for conductors

Weight of the sleeve kgs

Before compression dia. of sleeve mm

a) Inner diameter

b) Outer diameter

Dimensions after compression mm

a) Corner to corner

b) Surface to surface

Length of the sleeve mm

a) Before compression

b) After compression

Compression pressure Tonne

Minimum corona extinction voltage kV


under dry conditions

Radio interference voltage under Micro


conditions Volts

T-connector (only for ACSR


MOOSE)
Weight of the T-connector kgs

Axial tensile strength of the welded kN


portion of the T-connector

Breaking strength of the T-connector kN

Resistance of the completed T- ohms


connection

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 147 of 196


C . 8 - Conductor(ACSR) Fittings and Accessories (continued )
(To be filled up by the Bidder)

Unit PANTHER ZEBRA MOOSE

Before compression dia. of the T- mm


connector
a) Inner diameter

b) Outer diameter

Dimensions after compression mm

a) Corner to corner

b) Surface to surface

Length of the T-connector mm

a) Before compression

b) After compression

Compression pressure Tonne

Minimum corona extinction voltage kV


under dry conditions

Radio interference voltage under Micro


conditions Volts

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 148 of 196


C . 9 - Vibration Damper For Conductor and Earthwire
( To be completed by the Bidder )

Vibration Dampers for ACSR PANTHER Unit

Total weight of the damper kgs

Left Right
Weight of each damper mass kgs

Resonance frequencies

1) First frequency Hz

2) Second frequency Hz

Dimension of each damper mass mm

Material of :

1) Damper mass

2) Messenger cable

No. of strands in messenger cable

Lay ratio of the messenger cable strands

Min. tensile strength of messenger cable kg/sq.mm.

Mass pull-off strength kN

Clamping torque kg.-m

Slipping strength of the damper clamp kN

1) Before fatigue test

2) After fatigue test

Magnetic power loss per vibration damper Watts

Min. corona extinction voltage under dry kV


conditions

Radio interference voltage under dry conditions Micro


at 1MHz , at 105 kV Volts

Percentage variation in reactance after fatigue %


test in comparision with that before the fatigue
test

Percentage variation in power dissipation after %


fatigue test in comparision with that before the
fatigue test

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 149 of 196


C . 9 - Vibration Damper For Conductor and Earthwire (Continued )
( To be completed by the Bidder )

Vibration Dampers for ACSR PANTHER Unit

Galvanising of ferrous parts (if any )

1) Minimum weight of Zinc coating per gm/sq.m


Sq.m. of the uncoated surface

2) Minimum No. of one minute dips the Nos.


ferrous parts can withstand in the
Standard Preece Test

3) Purity of Zinc used for galvanizing %

Vibration Dampers for ACSR ZEBRA

Total weight of the damper kgs

Left Right
Weight of each damper mass kgs

Resonance frequencies

1) First frequency Hz

2) Second frequency Hz

Dimension of each damper mass mm

Material of :

1) Damper mass

2) Messenger cable

No. of strands in messenger cable

Lay ratio of the messenger cable strands

Min. tensile strength of messenger cable kg/sq.mm.

Mass pull-off strength kN

Clamping torque kg.-m

Slipping strength of the damper clamp kN

1) Before fatigue test

2) After fatigue test

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 150 of 196


C . 9 - Vibration Damper For Conductor and Earthwire (Continued )
( To be completed by the Bidder )

Vibration Dampers for ACSR ZEBRA Unit

Magnetic power loss per vibration damper Watts

Min. corona extinction voltage under dry kV


conditions

Radio interference voltage under dry conditions Micro


at 1MHz, at 154 kV Volts

Percentage variation in reactance after fatigue %


test in comparision with that before the fatigue
test

Percentage variation in power dissipation after %


fatigue test in comparision with that before the
fatigue test

Galvanising of ferrous parts (if any )

1) Minimum weight of Zinc coating per gm/sq.m


Sq.m. of the uncoated surface

2) Minimum No. of one minute dips the Nos.


ferrous parts can withstand in the
Standard Preece Test

3) Purity of Zinc used for galvanizing %

Vibration Dampers for ACSR MOOSE

Total weight of the damper kgs

Left Right
Weight of each damper mass kgs

Resonance frequencies

1) First frequency Hz

2) Second frequency Hz

Dimension of each damper mass mm

Material of :

1) Damper mass

2) Messenger cable

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 151 of 196


C . 9 - Vibration Damper For Conductor and Earthwire (Continued )
( To be completed by the Bidder )

Vibration Dampers for ACSR MOOSE Unit

No. of strands in messenger cable

Lay ratio of the messenger cable strands

Min. tensile strength of messenger cable kg/sq.mm.

Mass pull-off strength kN

Clamping torque kg.-m

Slipping strength of the damper clamp kN

1) Before fatigue test

2) After fatigue test

Magnetic power loss per vibration damper Watts

Min. corona extinction voltage under dry kV


conditions

Radio interference voltage under dry conditions Micro


at 1MHz , at 305 kV Volts

Percentage variation in reactance after fatigue %


test in comparision with that before the fatigue
test

Percentage variation in power dissipation after %


fatigue test in comparision with that before the
fatigue test

Galvanising of ferrous parts (if any )

1) Minimum weight of Zinc coating per gm/sq.m


Sq.m. of the uncoated surface

2) Minimum No. of one minute dips the Nos.


ferrous parts can withstand in the
Standard Preece Test

3) Purity of Zinc used for galvanizing %

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 152 of 196


C . 9 - Vibration Damper For Conductor and Earthwire (Continued )
( To be completed by the Bidder )

Vibration Dampers for 7/3.15mm Earthwire Unit

Total weight of the damper kgs

Left Right
Weight of each damper mass kgs

Resonance frequencies

1) First frequency Hz

2) Second frequency Hz

Dimension of each damper mass mm

Material of :

1) Damper mass

2) Messenger cable

No. of strands in messenger cable

Lay ratio of the messenger cable strands

Min. tensile strength of messenger cable kg/sq.mm.

Mass pull-off strength kN

Clamping torque kg.-m

Slipping strength of the damper clamp kN

1) Before fatigue test

2) After fatigue test

Percentage variation in reactance after fatigue %


test in comparision with that before the fatigue
test

Percentage variation in power dissipation after %


fatigue test in comparision with that before the
fatigue test

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 153 of 196


C . 9 - Vibration Damper For Conductor and Earthwire (Continued )
( To be completed by the Bidder )

Vibration Dampers for 7/3.15mm Earthwire Unit

Galvanising of ferrous parts (if any )

1) Minimum weight of Zinc coating per gm/sq.m


Sq.m. of the uncoated surface

2) Minimum No. of one minute dips the Nos.


ferrous parts can withstand in the
Standard Preece Test

3) Purity of Zinc used for galvanizing %

Vibration Dampers for 7/3.66mm Earthwire

Total weight of the damper kgs

Left Right
Weight of each damper mass kgs

Resonance frequencies

1) First frequency Hz

2) Second frequency Hz

Dimension of each damper mass mm

Material of :

1) Damper mass

2) Messenger cable

No. of strands in messenger cable

Lay ratio of the messenger cable strands

Min. tensile strength of messenger cable kg/sq.mm.

Mass pull-off strength kN

Clamping torque kg.-m

Slipping strength of the damper clamp kN

1) Before fatigue test

2) After fatigue test

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 154 of 196


C . 9 - Vibration Damper For Conductor and Earthwire (Continued )
( To be completed by the Bidder )

Vibration Dampers for 7/3.66mm Earthwire Unit

Percentage variation in reactance after fatigue %


test in comparision with that before the fatigue
test

Percentage variation in power dissipation after %


fatigue test in comparision with that before the
fatigue test

Galvanising of ferrous parts (if any )

1) Minimum weight of Zinc coating per gm/sq.m


Sq.m. of the uncoated surface

2) Minimum No. of one minute dips the Nos.


ferrous parts can withstand in the
Standard Preece Test
3) Purity of Zinc used for galvanizing %

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 155 of 196


C . 10 - Bundle Spacers For 400kV Line Conductors
(To be filled up by the Bidder)
Unit
Material of component parts(indicate type of alloy)

1) Insert

2) Main body

3) Retaining rods ( if any )

Manufacturing process for


1) Insert

2) Main body

3) Retaining rods ( if any )

Retaining rods (if used )


1) Type of alloy used

2) No. of retaining rods used for each spacer

3) Diameter of the rod mm

4) Length of the rod mm

5) Total weight of one set of the rods kgs

Elatomer
1) Supplier

2) Type

3) Moulded on the insert or not

4) Shore hardness

5) Thickness on the insert mm


o
6) Temperature for which designed C

Minimum strength of the spacer


1) Compressive load kN

2) Tensile load kN

Weight of the spacer kgs

Designed clamping torque (if applicable ) kg-m

Slipping strength of spacer clamp


1) Before vibration test kN

2) After vibration test kN

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 156 of 196


C . 10 - Bundle Spacers For 400kV Line Conductors (Continued )
(To be filled up by the Bidder)

Unit

Magnetic power loss per spacer Watts

Galvanising of ferrous parts (if any )

1) Minimum weight of Zinc coating per gm/sq.m


Sq.m. of the uncoated surface

2) Minimum No. of one minute dips the Nos.


ferrous parts can withstand in the
Standard Preece Test

3) Purity of Zinc used for galvanising %

Min. corona extinction voltage under dry conditions kV

Radio interference voltage under dry conditions Micro Volts

Electrical resistance of the elastomer cushioned ohms


spacer (specify the range )

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 157 of 196


C.11 - Bundle Spacers For Jumpers Of 400kV Lines
(To be filled up by the Bidder)
Unit
Material of component parts (indicate type of alloy)
1) Insert

2) Main body

Manufacturing process for


1) Insert

2) Main body

Elatomer
1) Supplier

2) Type

3) Moulded on the insert or not

4) Shore hardness

5) Thickness on the insert mm


o
6) Temperature for which designed C

Minimum strength of the spacer for jumpers


1) Compressive load kN

2) Tensile load kN

Weight of the spacer for jumpers kgs

Designed clamping torque for spacer for jumpers kg-m

Slipping strength of spacer clamp for jumpers kN

Magnetic power loss per spacer for jumpers Watts

Galvanising of ferrous parts (if any )


1) Minimum weight of Zinc coating per gm/sq.m
Sq.m. of the uncoated surface

2) Minimum No. of one minute dips the Nos.


ferrous parts can withstand in the
Standard Preece Test

3) Purity of Zinc used for galvanising %

Min. corona extinction voltage under dry conditions kV

Radio interference voltage under dry conditions MicroVolt

Electrical resistance of the elastomer cushioned spacer for ohms


jumpers (specify the range )

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 158 of 196


C.12 - Spacer Dampers For 400kV Line Conductors
(To be filled up by the Bidder)
Unit
Material of component parts (indicate type of alloy /
rubber component)
1) Insert

2) Main body

3) Retaining rods ( if any )

4) Damping ball

Manufacturing process for

1) Insert

2) Main body

3) Retaining rods ( if any )

4) Damping ball

Retaining rods (if used )

1) Type of alloy used

2) No. of retaining rods used for each unit

3) Diameter of the rod mm

4) Length of the rod mm

5) Total weight of one set of the rods kgs

Elatomer

1) Supplier

2) Type

3) Moulded on the insert or not

4) Shore hardness

5) Thickness on the insert mm


o
6) Temperature for which designed C

Minimum strength of the spacer damper

1) Compressive load kN

2) Tensile load kN

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 159 of 196


C.12 - Spacer Dampers For 400kV Line Conductors ( Continued )
(To be filled up by the Bidder)

Unit

Weight of the spacer damper kgs

Designed clamping torque (if applicable ) kg-m

Slipping strength of spacer damper clamp

1) Before vibration test kN

2) After vibration test kN

Galvanising of ferrous parts (if any )

1) Minimum weight of Zinc coating per gm/sq.m


Sq.m. of the uncoated surface

2) Minimum No. of one minute dips the Nos.


ferrous parts can withstand in the
Standard Preece Test

3) Purity of Zinc used for galvanising %

Min. corona extinction voltage under dry conditions kV

Radio interference voltage under dry conditions Micro Volts

Magnetic power loss per spacer damper Watts

Electrical resistance of the elastomer cushioned ohms


spacer damper (specify the range )

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 160 of 196


C.13 - Disc Insulator Units ( Standard Type )
(To be filled up by the Bidder)

Unit 70kN 90kN 120kN 160kN

Weight of the single disc unit kg

Size and designation of the ball pin mm


shank

Diameter of the disc mm

Tolerance on the diameter +/-mm

Ball to ball spacing between disc mm

Tolerance on ball to ball spacing +/-mm

Minimum creepage distance of a mm


single disc

Positive tolerance on the minimum +mm


creepage distance

Shell material ( Glass/Porcelain )

Power frequency flashover voltage


(rms) of single disc unit

1) Dry kV

2) Wet kV

Power frequency withstand voltage


(rms) of single disc unit

1) Dry kV

2) Wet kV

Power frequency puncture voltage kV


(rms) of single disc unit

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 161 of 196


C.13 - Disc Insulator Units ( Standard Type ) ( Continued )
(To be filled up by the Bidder)

Unit 70kN 90kN 120kN 160kN

Impulse flashover voltage ( peak ) of


single disc unit ( dry )

1) Positive

2) Negative

Impulse withstand voltage ( peak ) of


single disc unit ( dry )

1) Positive

2) Negative

Steepness of the impulse voltage kV per


which the disc unit can withstand in micro
Steep Wave Front Test sec.

Corona extinction voltage ( rms )


under dry condition, for single unit

Maximum RIV at 1 MHz and at Micro


10 kV (rms) for single unit Volts.

Purity of Zinc used for galvanising %

No. of dips in Standard Preece Test


1) Cap socket

2) Ball pin

Axial and radial run-out (According to


IEC )

1) As per pointer A mm

2) As per pointer B mm

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 162 of 196


C.13A - Composite Insulator Units ( Standard Type )
(To be filled up by the Bidder)

Unit 70kN 90kN 120kN 160kN

Weight of the single insulatort unit kg

Size and designation of the ball pin mm


shank / clevis and tongue

Diameter of (along with tolerance) mm


1) central core without housing
sleeve cover

2) central core with housing


sleeve cover

3) weather shed

Length of single insulator unit mm

Tolerance on unit insulator length +/-mm

Minimum creepage distance of a mm


single insulator unit

Positive tolerance on the minimum +mm


creepage distance

Core material

Shed material

Power frequency flashover voltage


(rms) of single disc unit

1) Dry kV

2) Wet kV

Power frequency withstand voltage


(rms) of single disc unit

1) Dry kV

2) Wet kV

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 163 of 196


C.13A - Composite Insulator Units ( Standard Type ) ( Continued )
(To be filled up by the Bidder)

Unit 70kN 90kN 120kN 160kN

Impulse flashover voltage ( peak ) of


single disc unit ( dry )

1) Positive

2) Negative

Impulse withstand voltage ( peak ) of


single disc unit ( dry )

1) Positive

2) Negative

Steepness of the impulse voltage kV per


which the disc unit can withstand in micro
Steep Wave Front Test sec.

Corona extinction voltage ( rms )


under dry condition, for single unit

Maximum RIV at 1 MHz and at Micro


10 kV (rms) for single unit Volts.

Purity of Zinc used for galvanising %

No. of dips in Standard Preece Test


1) Cap socket

2) Ball pin

Note : Any other parameters which Bidder feels are necessary to define the offered composite
insulator unit, shall be indicated and guaranteed in the above format.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 164 of 196


C.14 - Disc Insulator Units ( Anti-fog Type )
(To be filled up by the Bidder)

Unit 70kN 90kN 120kN 160kN

Weight of the single disc unit kg

Size and designation of the ball pin mm


shank

Diameter of the disc mm

Tolerance on the diameter +/-mm

Ball to ball spacing between disc mm

Tolerance on ball to ball spacing +/-mm

Minimum creepage distance of a mm


single disc

Positive tolerance on the minimum +mm


creepage distance

Shell material ( Glass/Porcelain )

Power frequency flashover voltage


(rms ) of single disc unit

1) Dry kV

2) Wet kV

Power frequency withstand voltage


(rms ) of single disc unit

1) Dry kV

2) Wet kV

Power frequency puncture voltage kV


(rms) of single disc unit

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 165 of 196


C.14 - Disc Insulator Units ( Anti-fog Type ) ( Continued )
(To be filled up by the Bidder)

Unit 70kN 90kN 120kN 160kN

Impulse flashover voltage ( peak ) of


single disc unit ( dry )

1) Positive

2) Negative

Impulse withstand voltage ( peak ) of


single disc unit ( dry )

1) Positive

2) Negative

Steepness of the impulse voltage kV per


which the disc unit can withstand in micro
Steep Wave Front Test sec.

Corona extinction voltage ( rms )


under dry condition, for single unit

Maximum RIV at 1 MHz and at Micro


10 kV (rms) for single unit Volts.

Purity of Zinc used for galvanising %

Purity of Zinc used for sleeve %

No. of dips in Standard Preece Test


1) Cap socket

2) Ball pin

Axial and radial run-out (According to


IEC )

1) As per pointer A mm

2) As per pointer B mm

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 166 of 196


C.14A - Composite Insulator Units ( Anti-fog Type )
(To be filled up by the Bidder)

Unit 70kN 90kN 120kN 160kN

Weight of the single insulatort unit kg

Size and designation of the ball pin mm


shank / clevis and tongue

Diameter of (along with tolerance) mm


1) central core without housing
sleeve cover

2) central core with housing


sleeve cover

3) weather shed

Length of single insulator unit mm

Tolerance on unit insulator length +/-mm

Minimum creepage distance of a mm


single insulator unit

Positive tolerance on the minimum +mm


creepage distance

Core material

Shed material

Power frequency flashover voltage


(rms) of single disc unit

1) Dry kV

2) Wet kV

Power frequency withstand voltage


(rms) of single disc unit

1) Dry kV

2) Wet kV

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 167 of 196


C.14A - Composite Insulator Units ( Anti-fog Type ) ( Continued )
(To be filled up by the Bidder)

Unit 70kN 90kN 120kN 160kN

Impulse flashover voltage ( peak ) of


single disc unit ( dry )

1) Positive

2) Negative

Impulse withstand voltage ( peak ) of


single disc unit ( dry )

1) Positive

2) Negative

Steepness of the impulse voltage kV per


which the disc unit can withstand in micro
Steep Wave Front Test sec.

Corona extinction voltage ( rms )


under dry condition, for single unit

Maximum RIV at 1 MHz and at Micro


10 kV (rms) for single unit Volts.

Purity of Zinc used for galvanising %

No. of dips in Standard Preece Test


1) Cap socket

2) Ball pin

Note : Any other parameters which Bidder feels are necessary to define the offered composite
insulator unit, shall be indicated and guaranteed in the above format.

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 168 of 196


C . 15 - Insulator Strings (Suspension Sets For 132 kV Lines )
(To be filled up by the Bidder)

Unit Single “I” Double “I” Pilot


Suspension Suspension Suspension
Strings Strings Strings

Power frequency withstand voltage of kV(rms)


the string with arcing horns and corona
control rings / grading rings under wet
conditions

Impulse flashover voltage (peak)


under dry conditions

1) Positive kV

2) Negative kV

Impulse withstand voltage (peak)


under dry conditions

1) Positive kV

2) Negative kV

Salt-fog pollution withstand voltage kV(rms)


(only for strings with anti-fog disc units)

Minimum corona extinction voltage kV(rms)


under dry conditions

Radio interference voltage under dry Micro


conditions at 1MHz, at 105kV Volts

Mechanical strength of the complete kN


insulator string along with all hardware
fittings

Maximum voltage (in percentage ) %


across any disc in the complete
insulator string under phase to earth
voltage ( not applicable for string with
composite insulator units )

Number of insulator units in each string

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 169 of 196


C . 15 - Insulator Strings (Suspension Sets For 132 kV Lines ) ( Continued )
( To be filled up by the Bidder )

Unit Single “I” Double “I” Pilot


Suspension Suspension Suspension
Strings Strings Strings

Overall length of the set including mm


clamp and all fittings (specify the
tolerance also )

Weight of the set, complete with all kg


fittings and arcing horns

Weight of the counter-weights kg

Minimum arcing gap distance mm

Maximum magnetic power loss of the Watts


suspension assembly

Slipping strength of the suspension kN


assembly (clamp torque Vs. slip curve
shall be enclosed )

Particulars of Standard/AGS pre- Standard Standard Standard


formed armour rod set for suspension Or, Or, Or,
assembly AGS AGS AGS

1) No. of rods per set No.

2) Direction of the lay

3) Overall length after fitting on the mm


conductor
4) Actual length of each rod along its mm
helix
5) Diameter of each rod mm

6) Tolerance in

a) Diameter of each rod +/- mm

b) Length of each rod +/- mm

c) Difference of length +/- mm


between the longest and
shortest rod in a set

7) Type of Aluminium alloy used


for manufacture of PA rods

8) UTS of each rod kg/mm 2

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 170 of 196


C . 15 - Insulator Strings (Suspension Sets For 132 kV Lines ) ( Continued )
( To be filled up by the Bidder )

Unit Single “I” Double “I” Pilot


Suspension Suspension Suspension
Strings Strings Strings

Particular of Elastomer
(for AGS clamps only )

1) Supplier of elastomer

2) Type of elastomer

3) Shore hardness of elastomer


o
4) Temperature range for which C
elastomer is designed

5) Moulded on insert yes/no

Purity of Zinc used for galvanising %

Minimum No. of one minute dips the No.


ferrous parts can withstand in Standard
Preece Test

Minimum weight of Zinc coating per gm/sq.m


Sq.m. of the uncoated surface

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 171 of 196


C . 16 - Insulator Strings ( Tension Sets For 132 kV Lines )
( To be filled up by the Bidder )

Unit Single Double


Tension Tension
Strings Strings

Power frequency withstand voltage of the string kV(rms)


with arcing horns and corona control rings / grading
rings under wet conditions

Impulse flashover voltage (peak) under dry


conditions

1) Positive kV

2) Negative kV

Impulse withstand voltage (peak) under dry


conditions

1) Positive kV

2) Negative kV

Salt-fog pollution withstand voltage ( only for strings kV (rms)


with anti-fog units )

Minimum corona extinction voltage under dry kV(rms)


conditions

Radio interference voltage under dry conditions at Micro


1MHz, at 105kV Volts

Mechanical strength of the complete insulator string kN


along with all hardware fittings

Maximum voltage (in percentage ) across any disc %


in the complete insulator string under phase to
earth voltage ( not applicable for string with
composite insulator units )

Number of insulator units in each string

Overall length of the set including clamp and all mm


fittings (specify the tolerance also )

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 172 of 196


C . 16 - Insulator Strings ( Tension Sets For 132 kV Lines ) ( Continued )
( To be filled up by the Bidder )

Unit Single Double


Tension Tension
Strings Strings

Weight of the set, complete with all fittings and kg


arcing horns

Minimum arcing gap distance mm

Electrical resistance of the complete tension ohms


assembly along with jumper connection

Slipping strength of the tension assembly kN

Purity of Zinc used for galvanising %

Minimum No. of one minute dips the ferrous parts No.


can withstand in Standard Preece Test

Minimum weight of Zinc coating per Sq.m. of the gm/sq.m


uncoated surface

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 173 of 196


C . 17 - Insulator Strings (Suspension Sets For 220 kV Lines )
( To be filled up by the Bidder )

Unit Single “I” Double “I” Pilot


Suspension Suspension Suspension
Strings Strings Strings

Power frequency withstand voltage of kV(rms)


the string with arcing horns and corona
control rings / grading rings under wet
conditions

Impulse flashover voltage (peak)


under dry conditions

1) Positive kV

2) Negative kV

Impulse withstand voltage (peak)


under dry conditions

1) Positive kV

2) Negative kV

Salt-fog pollution withstand voltage kV(rms)


(only for strings with anti-fog disc units)

Minimum corona extinction voltage kV(rms)


under dry conditions

Radio interference voltage under dry Micro


conditions at 1MHz, at 154kV Volts

Mechanical strength of the complete kN


insulator string along with all hardware
fittings

Maximum voltage (in percentage ) %


across any disc in the complete
insulator string under phase to earth
voltage ( not applicable for string with
composite insulator units )

Number of insulator units in each string

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 174 of 196


C . 17 - Insulator Strings (Suspension Sets For 220 kV Lines ) ( Continued )
( To be filled up by the Bidder )

Unit Single “I” Double “I” Pilot


Suspension Suspension Suspension
Strings Strings Strings

Overall length of the set including mm


clamp and all fittings (specify the
tolerance also )

Weight of the set, complete with all kg


fittings and arcing horns

Weight of the counter-weights kg

Minimum arcing gap distance mm

Maximum magnetic power loss of the Watts


suspension assembly

Slipping strength of the suspension kN


assembly (clamp torque Vs. slip curve
shall be enclosed )

Particulars of Standard/AGS pre- Standard Standard Standard


formed armour rod set for suspension Or, Or, Or,
assembly AGS AGS AGS

1) No. of rods per set No.

2) Direction of the lay

3) Overall length after fitting on the mm


conductor
4) Actual length of each rod along its mm
helix

5) Diameter of each rod mm

6) Tolerance in

a) Diameter of each rod +/- mm

b) Length of each rod +/- mm

c) Difference of length +/- mm


between the longest and
shortest rod in a set

7) Type of Aluminium alloy used


for manufacture of PA rods

8) UTS of each rod kg/mm 2

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 175 of 196


C . 17 - Insulator Strings (Suspension Sets For 220 kV Lines ) ( Continued )
( To be filled up by the Bidder )

Unit Single “I” Double “I” Pilot


Suspension Suspension Suspension
Strings Strings Strings

Particular of Elastomer
(for AGS clamps only )

1) Supplier of elastomer

2) Type of elastomer

3) Shore hardness of elastomer


o
4) Temperature range for which C
elastomer is designed

5) Moulded on insert yes/no

Purity of Zinc used for galvanising %

Minimum No. of one minute dips the No.


ferrous parts can withstand in Standard
Preece Test

Minimum weight of Zinc coating per gm/sq.m


Sq.m. of the uncoated surface

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 176 of 196


C . 18 - Insulator Strings ( Tension Sets For 220 kV Lines )
( To be filled up by the Bidder )

Unit Single Double


Tension Tension
Strings Strings

Power frequency withstand voltage of the string kV(rms)


with arcing horns and corona control rings / grading
rings under wet conditions

Impulse flashover voltage (peak) under dry


conditions

1) Positive kV

2) Negative kV

Impulse withstand voltage (peak) under dry


conditions

1) Positive kV

2) Negative kV

Salt-fog pollution withstand voltage ( only for strings kV (rms)


with anti-fog units )

Minimum corona extinction voltage under dry kV(rms)


conditions

Radio interference voltage under dry conditions at Micro


1MHz, at 105kV Volts

Mechanical strength of the complete insulator string kN


along with all hardware fittings

Maximum voltage (in percentage ) across any disc %


in the complete insulator string under phase to
earth voltage ( not applicable for string with
composite insulator units )

Number of insulator units in each string

Overall length of the set including clamp and all mm


fittings (specify the tolerance also )

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 177 of 196


C . 18 - Insulator Strings ( Tension Sets For 220 kV Lines ) ( Continued )
( To be filled up by the Bidder )

Unit Single Double


Tension Tension
Strings Strings

Weight of the set, complete with all fittings and kg


arcing horns

Minimum arcing gap distance mm

Electrical resistance of the complete tension ohms


assembly along with jumper connection

Slipping strength of the tension assembly kN

Purity of Zinc used for galvanising %

Minimum No. of one minute dips the ferrous parts No.


can withstand in Standard Preece Test

Minimum weight of Zinc coating per Sq.m. of the gm/sq.m


uncoated surface

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 178 of 196


C . 19 - Insulator Strings (Suspension Sets For 400 kV Lines )
( To be filled up by the Bidder )

Unit Single “I” Pilot


Suspension Suspension
Strings Strings

Power frequency withstand voltage of the string kV(rms)


with arcing horns and corona control rings / grading
rings under wet conditions

Switching surge withstand voltage (peak) under wet


conditions

1) Positive kV

2) Negative kV

Impulse flashover voltage (peak) under dry


conditions

1) Positive kV

2) Negative kV

Impulse withstand voltage (peak) under dry


conditions

1) Positive kV

2) Negative kV

Salt-fog pollution withstand voltage ( only for strings kV (rms)


with anti-fog units )

Minimum corona extinction voltage under dry kV(rms)


conditions

Radio interference voltage under dry conditions at Micro


1MHz, at 305kV Volts

Mechanical strength of the complete insulator string kN


along with all hardware fittings

Maximum voltage (in percentage) across any disc %


in the complete insulator string under phase to
earth voltage ( not applicable for string with
composite insulator units )

Number of insulator units in each string

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 179 of 196


C . 19 - Insulator Strings (Suspension Sets For 400 kV Lines ) ( Continued )
( To be filled up by the Bidder )

Unit Single “I” Pilot


Suspension Suspension
Strings Strings

Overall length of the set including clamp and all mm


fittings (specify the tolerance also )

Weight of the set, complete with all fittings and kg


arcing horns

Weight of the counter-weights kg

Minimum arcing gap distance mm

Maximum magnetic power loss of the suspension Watts


assembly

Slipping strength of the suspension assembly kN


(clamp torque Vs. slip curve shall be enclosed )

Particulars of Standard/AGS pre-formed armour Standard Standard


rod set for suspension assembly Or, Or,
AGS AGS

1) No. of rods per set No.

2) Direction of the lay

3) Overall length after fitting on the conductor mm

4) Actual length of each rod along its helix mm

5) Diameter of each rod mm

6) Tolerance in

a) Diameter of each rod +/- mm

b) Length of each rod +/- mm

c) Difference of length +/- mm


between the longest and
shortest rod in a set

7) Type of Aluminium alloy used


for manufacture of PA rods

8) UTS of each rod kg/mm 2

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 180 of 196


C . 19 - Insulator Strings (Suspension Sets For 400 kV Lines ) ( Continued )
( To be filled up by the Bidder )

Unit Single “I” Pilot


Suspension Suspension
Strings Strings

Particular of Elastomer
(for AGS clamps only )

1) Supplier of elastomer

2) Type of elastomer

3) Shore hardness of elastomer


o
4) Temperature range for which C
elastomer is designed

5) Moulded on insert yes/no

Purity of Zinc used for galvanising %

Minimum No. of one minute dips the ferrous parts No.


can withstand in Standard Preece Test

Minimum weight of Zinc coating per Sq.m. of the gm/sq.m


uncoated surface

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 181 of 196


C . 20 - Insulator Strings ( Tension Sets For 400 kV Lines )
( To be filled up by the Bidder )

Unit SingleTension Double


Strings Tension
(Low Duty) Strings

Power frequency withstand voltage of the string kV(rms)


with arcing horns and corona control rings / grading
rings under wet conditions

Switching surge withstand voltage (peak) under


wet conditions

1) Positive kV

2) Negative kV

Impulse flashover voltage (peak) under dry


conditions

1) Positive kV

2) Negative kV

Impulse withstand voltage (peak) under dry


conditions

1) Positive kV

2) Negative kV

Salt-fog pollution withstand voltage ( only for strings kV (rms)


with anti-fog units )

Minimum corona extinction voltage under dry kV(rms)


conditions

Radio interference voltage under dry conditions at Micro


1MHz, at 305kV Volts

Mechanical strength of the complete insulator string kN


along with all hardware fittings

Maximum voltage (in percentage ) across any disc %


in the complete insulator string under phase to
earth voltage ( not applicable for string with
composite insulator units )

Number of insulator units in each string

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 182 of 196


C . 20 - Insulator Strings ( Tension Sets For 400 kV Lines ) ( Continued )
( To be filled up by the Bidder )

Unit SingleTension Double


Strings Tension
(Low Duty) Strings

Overall length of the set including clamp and all mm


fittings (specify the tolerance also )

Weight of the set, complete with all fittings and kg


arcing horns

Minimum arcing gap distance mm

Electrical resistance of the complete tension ohms


assembly along with jumper connection

Slipping strength of the tension assembly kN

Purity of Zinc used for galvanising %

Minimum No. of one minute dips the ferrous parts No.


can withstand in Standard Preece Test

Minimum weight of Zinc coating per Sq.m. of the gm/sq.m


uncoated surface

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 183 of 196


C . 21 - Tower Design Particulars : 132 kV Construction
(To be filled up by the Bidder)
Unit

Maximum tension per phase, for purposes of tower design and application

Suspension towers Newton

Tension towers Newton

Slack span side downleads, `per individual conductor' Newton

Maximum uplift per phase on each crossarm for purpose of


tension tower design Newton

Maximum tension of earth conductor for purpose


of tower design and application:

Suspension towers Newton

Tension towers Newton

Earthwire slack span side downleads Newton

Maximum uplift of each earth conductor on the tower for


purpose of tower design Newton

Minimum clearance between live metal and tower steelwork:

i. with suspension insulator set swing 0° mm

with suspension insulator set swing 15° mm

with suspension insulator set swing 30° mm

with suspension insulator set swing 45° mm

with suspension insulator set swing 60° mm

ii. with jumper loop swing 0° mm

with jumper loop swing 10° mm

with jumper loop swing 20° mm

with jumper loop swing 30° mm

with jumper loop swing 40° mm

Insulator suspension set, unobstructed transverse swing angle degrees


from vertical

Earth conductor suspension clamps, unobstructed transverse degrees


swing angle from vertical

Earth conductor maximum shielding angle from vertical at degrees


tower attachment point over outer line conductors

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 184 of 196


C . 22 - Tower Design Particulars : 220 kV Construction
(To be filled up by the Bidder)

Unit

Maximum tension per phase, for purposes of tower design and application

Suspension towers Newton

Tension towers Newton

Slack span side downleads, `per individual conductor' Newton

Maximum uplift per phase on each crossarm for purpose of


tension tower design Newton

Maximum tension of earth conductor for purpose


of tower design and application:

Suspension towers Newton

Tension towers Newton

Earthwire slack span side downleads Newton

Maximum uplift of each earth conductor on the tower for


purpose of tower design Newton

Minimum clearance between live metal and tower steelwork:

i. with suspension insulator set swing 0° mm

with suspension insulator set swing 15° mm

with suspension insulator set swing 30° mm

with suspension insulator set swing 45° mm

with suspension insulator set swing 60° mm

ii. with jumper loop swing 0° mm

with jumper loop swing 10° mm

with jumper loop swing 20° mm

with jumper loop swing 30° mm

with jumper loop swing 40° mm

Insulator suspension set, unobstructed transverse swing angle degrees


from vertical

Earth conductor suspension clamps, unobstructed transverse degrees


swing angle from vertical

Earth conductor maximum shielding angle from vertical at degrees


tower attachment point over outer line conductors

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 185 of 196


C . 23 - Tower Design Particulars : 400 kV Construction
(To be filled up by the Bidder)

Unit

Maximum tension per phase, for purposes of tower design and


application

Suspension towers Newton

Tension towers Newton

Slack span side downleads, `per individual conductor' Newton

Maximum uplift per phase on each crossarm for purpose of


tension tower design Newton

Maximum tension of earth conductor for purpose


of tower design and application:

Suspension towers Newton

Tension towers Newton

Earthwire slack span side downleads Newton

Maximum uplift of each earth conductor on the tower for


purpose of tower design Newton

Minimum clearance between live metal and tower steelwork:

i. with suspension insulator set swing 0° mm

with suspension insulator set swing 15° mm

with suspension insulator set swing 30° mm

with suspension insulator set swing 45° mm

with suspension insulator set swing 60° mm

ii. with jumper loop swing 0° mm

with jumper loop swing 10° mm

with jumper loop swing 20° mm

with jumper loop swing 30° mm

with jumper loop swing 40° mm

Insulator suspension set, unobstructed transverse swing angle degrees


from vertical

Earth conductor suspension clamps, unobstructed transverse degrees


swing angle from vertical

Earth conductor maximum shielding angle from vertical at degrees


tower attachment point over outer line conductors

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 186 of 196


C . 24 - Tower Design Particulars (Common for all Towers)
(To be filled up by the Bidder)

Unit

Maximum ratio of unsupported length of steel compression


member to their least radius of gyration:

Leg members, ground wire peak members and lower members of


the crossarms in compression

Other members carrying computed stresses


Redundant members

Tension only members

Mild High yield


steel steel
Maximum ultimate stresses, for checking tower designs not
subjected to test (unless otherwise approved) :

Compression members, Bidder to indicate his design


Assumptions N/mm2

Tension members (elastic limit) N/mm2

Shear on bolts N/mm2

Bearing on bolts N/mm2

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 187 of 196


C . 25 - Particulars Of Double Circuit Towers : 132 kV Construction
(To be filled up by the Bidder)

TYPE OF TOWER Unit DA DB DC DD

Type of insulator sets Suspension Tension Tension Tension

Maximum angle of deviation degree

Normal span length m

Minimum ground clearance of line


conductor at 85°C, normal ground m

Sag of line conductor in normal


span length at 85°C m

Maximum distance of line conductor


below crossarm m

Height above ground of bottom conductor


Crossarm m

Minimum height of earth conductors above


upper line conductor : at tower m

: at mid-span m

Vertical spacing between line conductors


at tower :
Minimum m

Actual m

Overall tower height m

Maximum differential foundation movement


permitted under ultimate loads mm

Clearance between conductors of one circuit and


tower climbing leg of the other circuit :
Minimum m

Actual m

Horizontal distance, from tower centre line of


insulator attachments m

Horizontal distance, from tower centre line of


earth conductors m

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 188 of 196


C . 25 - Particulars Of Double Circuit Towers : 132 kV Construction ( Continued )
(To be filled up by the Bidder)

TYPE OF TOWER Unit DA DB DC DD

Tower body dimensions at bottom crossarm level


(transverse x longitudinal) m

Overall tower base dimensions at ground line


(transverse x longitudinal) :
Maximum for standard height m
towers

Actual for standard height towers m

Total transverse overturning moment at ground kN-m.


line of standard height tower.

Mass of complete standard height tower above kg


ground line (including bolts/nuts; bolts/nuts to be
indicated separately )

Mass of tower body extension above ground line


:
3 metre body extension only kg

6 metre body extension only kg

9 metre body extension only kg

12 metre body extension only kg - - -

18 metre body extension only kg - - -

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 189 of 196


C . 26 - Particulars Of Double Circuit Towers : 220 kV Construction
(To be filled up by the Bidder)

TYPE OF TOWER Unit DA DB DC DD

Type of insulator sets Suspension Tension Tension Tension

Maximum angle of deviation degree

Normal span length m

Minimum ground clearance of line


conductor at 85 °C, normal ground m

Sag of line conductor in normal


span length at 85 °C m

Maximum distance of line conductor


below crossarm m

Height above ground of bottom conductor


crossarm m

Minimum height of earth conductors above


upper line conductor : at tower m

: at mid-span m

Vertical spacing between line conductors


at tower :
Minimum m

Actual m

Overall tower height m

Maximum differential foundation movement


permitted under ultimate loads mm

Clearance between conductors of one circuit and


tower climbing leg of the other circuit :
Minimum m

Actual m

Horizontal distance, from tower centre line of


insulator attachments m

Horizontal distance, from tower centre line of


earth conductors m

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 190 of 196


C . 26 - Particulars Of Double Circuit Towers : 220 kV Construction ( Continued )
(To be filled up by the Bidder)

TYPE OF TOWER Unit DA DB DC DD

Tower body dimensions at bottom crossarm level


(transverse x longitudinal) m

Overall tower base dimensions at ground line


(transverse x longitudinal)
Maximum for standard height towers m

Actual for standard height towers m

Total transverse overturning moment at ground kg-m.


line of standard height tower

Mass of complete standard height tower above kg


ground line (including bolts/nuts; bolts/nuts to be
indicated separately )

Mass of tower body extensions above ground line

3 metre body extension only kg

6 metre body extension only kg

9 metre body extension only kg

12 metre body extension only kg - - -

18 metre body extension only kg - - -

25 metre body extension only kg - - -

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 191 of 196


C . 27 - Particulars Of Double Circuit Towers : 400 kV Construction
(To be filled up by the Bidder)

TYPE OF TOWER Unit DA DB DC DD

Type of insulator sets Suspension Tension Tension Tension

Maximum angle of deviation degree

Normal span length m

Minimum ground clearance of line


conductor at 85 °C, normal ground m

Sag of line conductor in normal


span length at 85 °C m

Maximum distance of line conductor


below crossarm m

Height above ground of bottom conductor


crossarm m

Minimum height of earth conductors above


upper line conductor : at tower m

: at mid-span m

Vertical spacing between line conductors


at tower :
Minimum m

Actual m

Overall tower height m

Maximum differential foundation movement


permitted under ultimate loads mm

Clearance between conductors of one circuit and


tower climbing leg of the other circuit :
Minimum m

Actual m

Horizontal distance, from tower centre line of


insulator attachments m

Horizontal distance, from tower centre line of


earth conductors m

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 192 of 196


C . 27 - Particulars Of Double Circuit Towers : 400 kV Construction ( Continued )
(To be filled up by the Bidder)

TYPE OF TOWER Unit DA DB DC DD

Tower body dimensions at bottom crossarm level


(transverse x longitudinal) m

Overall tower base dimensions at ground line


(transverse x longitudinal)
Maximum for standard height m
towers

Actual for standard height towers m

Total transverse overturning moment at ground kg-m.


line of standard height tower

Mass of complete standard height tower above kg


ground line (including bolts/nuts; bolts/nuts to be
indicated separately )

Mass of tower body extensions above ground line

3 metre body extension only kg

6 metre body extension only kg

9 metre body extension only kg

12 metre body extension only kg - - -

18 metre body extension only kg - - -

25 metre body extension only kg - - -

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 193 of 196


C . 28 - Foundation Design Particulars
(To be filled up by the Bidder)

Unit

Assumed density of Plain Cement Concrete (PCC) for foundation in dry kg/m3
soil

Assumed density of Plain Cement Concrete (PCC) for foundation in kg/m3


presence of sub-soil water

Assumed density of Re-inforced Cement Concrete (RCC) for foundation kg/m3


in dry soil

Assumed density of Re-inforced Cement Concrete (RCC) for foundation kg/m3


in presence of sub-soil water

28 day concrete cube strength (characteristic strength for M-20 N/mm2


concrete )

28 day concrete cube strength (characteristic strength for M-15 N/mm2


concrete )

Minimum proportion of stub load to be allowed for in the design of stub %


cleats

Density of all type of soils :


1) under dry conditions kg/m3

2) in presence of surface water kg/m3

3) in presence of sub-soil water kg/m3

Ultimate bearing capacity of the soil :


1) normal soil under dry condition kN/m2

2) normal soil in presence of surface as well as sub-soil water kN/m2

3) wet black cotton soil kN/m2

4) fissured rock ( both for dry and wet ) kN/m2

5) hard rock kN/m2

Angle of repose for :


1) dry soil Degree

2) wet soil due to presence of surface/ sub-soil water Degree

3) wet black cotton soil Degree

4) dry fissured rock Degree

5) wet fissured rock Degree

Ultimate bond between steel and concrete kN/m2

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 194 of 196


C . 29 - Quality Of Materials
(To be filled up by the Bidder)

Particulars Unit
Towers: Mild steel High tensile steel
Steel Steel nuts Steel Steel nuts
members and bolts members and bolts

Grade/standard

Tensile breaking stress N/mm2


Elongation on breaking %

Gauge length of specimen mm

Diameter of specimen mm

Yield point as percentage


of breaking stress

Insulators and fittings: Insulator unit metalwork Phase and earth


conductor metal
fittings
Steel Malleable Insulator Steel Malleable
cast iron caps cast iron

Grade/standard

Tensile breaking stress N/mm2

Elongation on breaking %

Gauge length of specimen mm

Diameter of specimen mm

Yield point as percentage


of breaking stress %

NESCL/OPTCL/CS-OS-616 E27-GTP- Page 195 of 196