Transformer Tap Changer Controller

Automatic voltage regulation,


analysis, and control functions for
transformer applications.

Applications Monitoring and Metering


■ Control power transformer OLTCs to ■ I, V, P, Q, cos j, frequency measurement
regulate voltage ■ Transformer OLTC position
■ Integrated Systems ■ Event recording
■ Counter of the tap position increases and
Protection and Control
decreases for rise and lower operations of tap
■ Automatic voltage regulator changer
■ Automatic/manual operation User Interfaces
■ Three setting tables ■ Rear communication port (plastic or glass
■ Configurable inputs and outputs fiber optic, RS232 or RS485)
■ BCD format inputs to detect tap changer ■ RS232 port, faceplate accessible
position ■ GE-NESIS Windows® based programming
■ Control pulse outputs software
■ Mimic for increasing/decreasing commands
and tap displaying
■ Graphic display and keypad
■ ModBus®, M-Link, and M-Link Plus
communications protocols
■ DDS system compatible

GE Multilin 1
DTR Transformer Tap Changer Controller

DESCRIPTION CONTROL MONITORING


The transformer tap changer Operation AND METERING
controller DTR controls automatically The DTR is used to maintain a
the transformer on load tap changer, constant voltage level at feeders Measures
so that the power supply voltage is busbar. The unit gives commands The voltage regulator DTR displays
practically constant, independently to increase and decrease the trans- instantaneous values of I, V, P and
from the load. In order to achieve this, former OLTC. As these differences Q (three-phase), frequency and cos
the DTR is able to increase and in the tap position are usually ϕ values.
decrease the OLTC in the power trans- discrete, the DTR allows the user to
former. set the percentage of change Event Recorder
The DTR can be applied to any between taps. In addition, a time 165 events are recorded in non-
existing tap changer, as its settings delay is provided by setting, to volatile EEPROM memory. Date
and operation ranges, as well as its allow matching the OLTC time and time (1 ms resolution), type of
inputs and outputs, are fully required to change from one tap to event, voltage and current, and a
compatible with all the OLTC avail- the closest next. relay status snapshot are stored.
able in the market.
Automatic/Manual Operation Digital Inputs and Outputs
The DTR has been designed using Using one of the configurable digi-
the same hardware architecture as The DTR system has 42 digital
tal inputs, the DTR can receive an inputs and 22 outputs. These I/Os
the DDS protection and control order for automatic or manual
system. This means that, besides can be configured by the user by
operation. Manual operation has means of GE-INTRO configuration
being a powerful individual priority over automatic, in order to
element, the DTR is completely software.
avoid performance failures in the
compatible with the system, and case of manual operations. This
can be fully integrated in a substa- command can also be sent to the
tion. unit by means of the communica-
The DTR also provides analysis and tions software, or the MMI.
control functions, such as event
recording. The internal memory Blockings
allows storing up to 165 events. It The transformer tap changer
also includes measuring functions controller DTR blocks its operation
for I, V, frequency, etc. in case that voltage falls below
user defined limits, (undervoltage
As all the units part of the DDS blocking), and also when voltage or
family, the DTR provides easily current exceeds another user
configurable inputs and outputs. defined limit (overvoltage or over-
The user can program these inputs current blocking).
and outputs by means of user-
friendly software programs, part of
GE-NESIS (GE-INTRO, GE-LOCAL). Settings
This software package is Windows® The unit provides three setting
based and it is the same for all the tables. The user can move from one
DDS family. table to another using a digital
input or through communications.
This feature allows the use of
different settings in different
system situations to better main-
tain the actual system needs of
security, etc.

2 www.GEindustrial.com/Multilin
DTR Transformer Tap Changer Controller

Typical Wiring

CONTROL
POWER
SUPPLY

CURRENT INPUTS
B3 D11 C11 Q11 P11
I1
G A12
B4 I1 CONTROL

g
POWER
A1 I5

A2 I5
GE Power Management
VOLTAGE

A7
DTR
V

A8 V
Automatic Voltage Regulator
P1 I1 TAP 1 (BCD) INCREASE Q5
COMMAND O1
P5
Q1 I2 TAP 2 (BCD)
DECREASE Q6
P2 I3 TAP 3 (BCD) O2
INPUTS 1

COMMAND P6
Q2 I4 TAP 4 (BCD) Q7
AUTOMATIC O3
P3 I5 TAP 5 (BCD) P7
5
Q3 I6 TAP 6 (BCD) Q8
MANUAL O4
P8
P4 I7
Q9
Q4 COMMON STOP O5
P9
J1 I8 INTERLOCKING 1 Q10
SYSTEM READY O6
K1 I9 REGULATOR ALARM P10
STOP L5
J2 I10 INTERLOCKING 2
INPUTS 2

COMMAND O7
M5
K2 I11 L6
COMMAND NOT
I12 EXECUTED O8
J3 M6
K3 I13 IRREGULAR L7
TAP CHANGE O9
M7
PROGRAMMABLE OUTPUTS

J4 I14
L8
K4 COMMON UNDERVOLTAGE O10
M8
J5 I15 L9
OVERVOLTAGE O11
K5 I16 M9
J6 I17 L10
INPUTS 3

OVERCURRENT O12 M10


K6 I18
L11
LOCAL O13
J7 I19 M11
K7 I20 L12
REMOTE O14
J8 I21 M12
COMMON SUCCESSIVE N5
K8 OPERATIONS O15
O5
J9 I22
EXCESSIVE N6
K9 I23 OPERATIONS O16
O6
J10 I24 N7
INPUTS 4

BCD 1 TAP O17


K10 I25 O7
N8
J11 I26 BCD 2 TAP O18
O8
K11 I27 N9
BCD 3 TAP O19
J12 I28 O9
K12 COMMON N10
BCD 4 TAP O20
I29 O10
L1 INCREASE
N11
M1 I30 DECREASE BCD 5 TAP O21
O11
L2 I31 AUTOMATIC
INPUTS 5

N12
BCD 6 TAP O22
M2 I32 MANUAL O12
L3 I33
M3 I34
RTU INPUTS

L4 I35 STOP
M4 COMMON
N1 I36 TABLE 1
O1 I37 TABLE 2
N2 I38
INPUTS 6

02 I39
N3 I40
O3 I41
N4 I42
O4 COMMON
EN DTR CON.cdr

www.GEindustrial.com/Multilin 3
DTR Transformer Tap Changer Controller

Technical Specifications Ordering


METERING
Frequency: 50/60 Hz DTR 1 * 0 * * 000 * 00 A
Nominal Phase Current: 1 or 5 A
Nominal Voltage: 100/√3 - 220/√3 VAC DTR Automatic Voltage Regulator
Auxiliary Voltage: 48-125 VDC, ±20% 0 RS232 communications interface
110-250 VDC, ±20%
1 Plastic fiber optic + RS232 communications interface
COMMUNICATIONS
Local Communication: LCD alphanumeric display with 2 Glass fiber optic + RS232 communications interface
two lines of 16 characters per line;
20 button frontal keypad 3 RS485 communications interface
Remote Communication 0 P1, P2: M-Link protocol
(local or remote PC and communications net):
Mode: half duplex 2 P1: M-Link protocol; P2: ModBus® RTU protocol
Speed: 1,200 to 115,000 bps
Physical media: M Spanish language
RS232 (ports 1 and 2)
RS485 (port 2 optional)
D English language
Plastic Fiber Optic (port 2 optional): G 48 - 125 VDC auxiliary voltage
Type of connector: HFBR-4516
Power supplied: 8 dBm H 110 - 250 VDC auxiliary voltage
Receptor’s sensitivity: -39 dBm
Wave length: 660 nm
Glass Fiber Optic (port 2 optional)
Type of connector: STA
Power supplied: 17.5 dBm
Receptor’s sensitivity: -24.5 dBm
Wave length: 820 nm
Synchronization: IRIG-B
• DB9 connector for RS232 ports on the front (1) and on the
rear (2).
• DB9 connector for RS232 port on the rear (3), with 1 mm
plastic fiber optic or 50/125 glass fiber optic option.
INPUTS
THERMAL CAPACITY
Current Circuits:
Continuously: 4 x In
During 3 Sec: 50 x In
During 1 Sec: 100 x In
Voltage Circuits:
Continuously: 2 x Vn
During 1 Min: 3,5 x Vn
BURDENS
Current Circuits: 0.5 VA for In = 5 A
0.1 VA for In = 1A
Voltage Circuits: 0.2 VA, Vn= 63.5 V
DC Burden:
During Operation: 12 W
Per Each Activated Input: 8 mA / 1 W, Vaux: 125 VDC

OUTPUTS
TRIPPING CONTACTS
Contact Capacity:
Maximum Operating Voltage: 440 VAC
Continuous Current: 16 A
Make and Carry: 30 A
Breaking: 4000 VA
ENVIRONMENTAL
Temperature:
Storage: -40 to +85°C
Operation: -20 to +70°C
Humidity: Up to 95% without condensing
MECHANICAL CHARACTERISTICS
• Metallic package in 19” rack and 4 units high.
• Frontal HMI with LCD display and keypad.
• Protection class IP52 (according to IEC 529)
Order online –
TYPE TESTS
Isolation Test Voltage: 2 kV, 50/60 Hz, 1 min
save time
Surge Test Voltage: 5 kV peak, 0.5 J
Interference: Class III according to CEI 255-22-1
Electrostatic Discharge: Class IV according to CEI 255-22 2
Radiointerference: Class III according to CEI 255-22-3 www.GEindustrial.com/pm
Fast Transient: Class IV according to CEI 255-22-4
Sinusoidal Vibration: Class II according to CEI 255-21-1
Shock: Class I according to CEI-22521-2
Radiofrequency Emission: according to CEI 41B (Sec) 81
and EN55022 class B

PACKAGING
Dimensions: H 7.3" x W 19.0" x D 9.1"
(185 mm x 484 mm x 231 mm)
Weight:
Not Packaged: 13.2 lbs (6 kg)
Packaged: 15.4 lbs (7 kg)

APPROVALS
Compliant UL - UL listed for USA and Canada

*Specifications subject to change without notice.