Академический Документы
Профессиональный Документы
Культура Документы
Abstract. This paper presents the comparative results of load flow studies on HVAC and hybrid HVAC-HVDC
transmission lines. Three different software packages are used to conduct this investigation, namely DigSilent,
Matlab PST and Matlab PSAT. A two-area four-machine system model is used to validate the results obtained
from the three software packages.
1. INTRODUCTION
With the increase in power demand, HVDC has
become a preferred alternative for the conventional
AC transmission system to transmit bulk power over
long distances. This is due to its economical and
technical advantages in long distance power transfer.
HVDC links offer suitable solutions for
interconnecting HVAC systems with different
frequencies and it can deliver more power over Figure 1: HVAC transmission equivalent model
longer distances with fewer losses. HVDC systems From figure 1, the following equations are deduced:
also offer high controllability on the power
transmitted.
Since HVDC is a relatively new technology when ZY (1)
VS 1 VR ZI R
compared to HVAC for power transmission, not all 2
existing software packages can model this type of
system accurately and reliably. For this reason only 1 2 1 (2)
a limited number of packages that allow HVDC IS Y Y Z VR 1 YZ I R
4 2
modeling are used in this research. where,
Two scenarios are investigated. The first one is an VS- sending -end voltage
HVAC system and the second is a combination of VR - receiving-end voltage
the HVAC in parallel with the HVDC system (i.e, IS - sending end current
hybrid (HVAC-HVDC). IR - receiving end current
To validate the results obtained by the software Z - equivalent impedance
packages, the HVAC load flow results are compared Y - equivalent admittance
to the results given in reference [1]. The results for
the Hybrid network are compared between the For the above circuit, the transfer matrix for the
software packages. ABCD parameters becomes
The paper is organized as follows: Section 2 gives a 1
brief introduction of the transmission models; A B
1 YZ Z (3)
2
section 3 describes the software packages used to C D 1 2 1
conduct the simulations. Section 4 discusses the Y Y Z 1 YZ
4 2
different case studies and their respective results and therefore,
section 5 gives a conclusion to the paper.
VS A B VR
(4)
2. BASIC PRINCIPLES OF TRANSMISSION IS C D IR
LINES
The different scenarios of power transmission 2.2 HVDC system
systems are discussed below. The power transfer on a DC system is a function of
the voltage magnitude between the sending and
2.1 HVAC system receiving end. On a DC system, power flows from
Conventionally, electric power is transferred from high to low voltage magnitudes.
generating stations to the consumer ends through Fig. 2 shows a monopolar HVDC configuration with
HVAC transmission lines. Fig.1 depicts the HVAC a rectifier station and its transformers, the
transmission system, in its equivalent π circuit with transmission line and an inverter station and its
lumped parameters, used for the study. transformers. The transformers at the rectifier
station connect to area 1 side and the transformers
on the inverter station are connected to the area 2
side. The DC transmission line is modeled as a π
equivalent circuit.
gives a choice of built-in configurations that are
already modeled.
3. SOFTWARE PACKAGES
The software packages used are briefly described
below:
3.1 DigSilent
DigSilent stands for Digital Simulation and
Electrical Network calculation program. It is a
computer aided engineering tool that is widely used
for industrial, utility, commercial and academic
applications.
Figure 3: HVAC two area multi machine system
DIgSILENT has the ability to simulate load flow,
fault analysis, harmonic analysis and stability
analysis for AC-DC systems. The generators have been modelled using the 6th
The load flow is performed using Newton Raphson order machines. Each machine is rated 900 MVA set
method for power flow solutions [4]. to supply 700 MW (see appendix for machine data).
DigSilent does not however allow the user to model Two machines connected to buses 1 and 2 are in
the components from basic component levels, but area 1 and the other two machines connected to
buses 3 and 4 are in area 2.These two area are
connected through a weak tie. For the HVAC Table 3: HVAC two-area multi machine reactive power
transmission line, Machine 3 is set to be the slack profile
bus of this system and all other machines are Element Reactive Power (Mvar)
modelled as PV buses. The machines are rated at 20 DigSilent PST PSAT Ref[1]
kV and transmission lines are rated to 230 kV. Gen 1 184.64 185.26 185.01 185.00
There are 2 loads in the system, Load 1 = 976 + j100 Gen 2 233.77 234.84 234.59 235.00
MVA in area 1 and Load 2 = 1767 + j100 MVA in Gen 3 175.6 176.26 176 176
Gen 4 201.18 202.35 202.05 202.00
area 2. To boost up the voltage in the system, HVAC 1 -53.17 -53.79 -53.56 *
capacitor banks Cap 1 = 200 Mvar and Cap 2 = 350 HVAC 2 -53.17 -53.79 -53.56 *
Mvar are connected to the same buses as the loads . Load 1 100 100 100 100
Area 1 and area 2 are connected by a double set of Load 2 100 100 100 100
transmission lines that are 220 km long. The lines Cap 1 200 200 200 200
are modelled as π equivalent circuits. The Cap 2 350 350 350 350
parameters of the transmission lines are given in the *: Not displayed in reference [1]
Appendix. Power is transferred from area 1 to area
2 to supply Load 2 that is much bigger than the total All generators supply 700 MW except generator 3
generator capacity of area 2. which supplies close to 719 MW. The total power
generated is approximately (2819 + j798) MVA for
Table 1: HVAC two area multi machine system voltage all the software packages, from which about half of
profile this power is generated in each area. Since the 1767
Elemen Rated Voltage magnitude and angle (pu) MW load in area 2 cannot be fully supplied by what
t Voltage DigSile PST PSAT Ref[1] is generated in area 2, about 380 MW is imported
(kV) nt from area 1. Approximately 185Mvar is supplied
Bus 1 20 1.03 2 1.03 2 1.03 2 1.03 2 from generator 1, 234Mvar from generator 2, 176
0.25 0.25 0.27 0.20
Bus 2 20 1.01 1 1.01 1 1.01 1 1.01 1
Mvar from generator 3 and 202 Mvar from generator
0.49º 0.51º 0.5º 0.5º 4. Each of the lines carries half of the power to area
Bus 3 20 1.03 - 1.03 - 1.03 - 1.03 - 2. The negative sign on the transmission lines
6.8º 6.8º 6.8º 6.8º reactive power indicates that the respective lines are
Bus 4 20 1.01 - 1.01 - 1.01 - 1.01 - absorbing reactive power. The power generated in
16.99º 16.99º 16.99º 17º
the different packages by all machines is very close
Bus 5 230 1.01 1 1.01 1 1.01 1 *
3.79º 3.79º 3.8º to the values presented in the literature.
Bus 6 230 0.98 3 0.98 3 0.98 3 *
.71º .71º .72º 4.2 HVDC system (scenario 2)
Bus 7 230 0.96 - 0.96 - 0.96 - *
4.7º 4.69º 4.68º
The HVDC system is a monopolar 500 kV, 230
Bus 8 230 0.95 1 0.95 1 0.95 1 * MVA, 0.46 kA link with 12 pulse converters on both
8.56º 8.57º 8.56º rectifier and inverter sides. This HVDC system is
Bus 9 230 0.97 - 0.97 - 0.97 - * modified from the CIGRE benchmark model [7, 8].
32.15º 32.17º 32.15º The HVDC line is modeled as a π equivalent circuit.
Bus 10 230 0.98 - 0.98 - 0.98 - *
Each converter has its own converting transformer.
23.73º 23.73º 23.73º
Bus 11 230 1.01 - 1.01 - 1.01 - * The HVDC transmission line is 220km long and its
13.43 13.44 13.43 parameters are given in the Appendix. To control the
*: Not displayed in reference [1] power transmitted across the HVDC link the
rectifier is modelled using current control. Apart
from the HVDC system, the rest of the structure of
Table 2: HVAC two-area multi machine system active
the system and the parameter is similar to the HVAC
power profile system.
Element Active Power (MW)
DigSilent PST PSAT Ref[1]
Gen 1 700 700 700 700
Gen 2 700 700 700 700
Gen 3 719.05 719.11 719.09 719
Gen 4 700 700 700 700
HVAC 1 190.69 190.67 190.67 *
HVAC 2 190.69 190.67 190.67 *
Load 1 967 967 967 967
Load 2 1767 1767 1767 1767
Cap 1 0 0 0 0
Cap 2 0 0 0 0
*: Not displayed in reference [1]