SITE INSPECTION AND TEST RECORD

Owner Description: Contractor

SEL 787 Transformer Differential


Protection Relay

Name of Substation:

Panel/ Tag No: Date:

1. General Data and Information:

Tag No.: Tag Name:

Serial Number: Manufacturer: SEL-787

Frequency: 50/60 Hz Supply Range: 110-250 VDC

H.V CT Ratio: L.V CT Ratio:

2. Check List:Following are the inspection checklists that shall be perform and record.
Sr. NOT
Check points OK Comments
No OK

Make sure that primary & secondary breakers are isolated before
1 starting PM on relays. Locked & tagged, where applicable as per
YASREF permit procedure.

For starter circuits, apply personal grounding prior to external control


2 power source is connected where applicable. Personal grounding must
remain until completion of the major PM.

3 Verify relay settings are as per As built ETAP setting.

Check wire connections to relays, tighten all screws of the relay


4 terminal on terminal blocks and if necessary check current shorting
links on all secondary current terminal boards.

Inspect PT secondary wiring, fuses and fuse blocks. Verify PT


5
Secondary ground is correct.

Insure that all lockout relays associated with this relay have been test
7
as per their check sheet.

Test / Verify the active functions of the relays with secondary injection
8
current / voltage.

Verify timing with the actual curve. Note any major time difference to
9
actual curves.

10 Checks verify metering display reading on the relay.

11 Clear events recorder and verify date & timing if applicable.

12 Verify that all alarms are operable.

Date Performed By: Witness By:

(ALFANAR) (YASREF COMPANY)

Name

Signature
SITE INSPECTION AND TEST RECORD
Owner Description: Contractor

SEL 787 Transformer Differential


Protection Relay

Name of Substation:

Panel/ Tag No: Date:

13 Checks verify metering display reading on the relay.

Perform trip test on associated breakers from protection relay by


secondary injection.
14
Check lockout is operated.
Check LED on relay and panel is operated

15 Clear events recorder and verify date & timing if applicable.

Update schematic and online diagrams and relay records to reflect the
16
changes found during PM.

17 Change and secure the password as per MSS team.

3. Measurements:
Calculated Value Measurement Value
Phase Iinj (A)
Idiff (PU) Irest (PU) Iprim (A) Idiff (PU) Irest (PU)
A-N
B-N
C-N
A
B 3 phase injection = A
C
- KVG (FACTOR) is according to transformer vector group as per pervious table.

a. For Low voltage side: (STAR -VG=1)


Calculated Value Measurement Value
Phase Iinj (A)
Idiff (PU) Irest (PU) Iprim (A) Idiff (PU) Irest PU)
A-N
B-N
C-N
A
B 3 phase injection = A
C
Measurement accuracy:
Phase Currents: ±1% of reading Differential Quantities: ±5% of reading, ±0.1 A (5 A nominal), ±0.02 A (1 A nominal)
[As per Instruction manual 787_IM_20130426Page 39].

b. NEUTRAL MEASURMENT:
Phase Iinj (A) EXPECTED VALUE (A) MEASURMENT VALUE (A)
Date Performed By: Witness By:

(ALFANAR) (YASREF COMPANY)

Name

Signature
SITE INSPECTION AND TEST RECORD
Owner Description: Contractor

SEL 787 Transformer Differential


Protection Relay

Name of Substation:

Panel/ Tag No: Date:

1N1

4. Testing of differential relay (Minimum Diff element O87P):


a. For High voltage side :
I inj
Setting: O87P= 0.3 and Trip Time=0 sec I differential =|I 1 −I 2|=I 1=0.3=
TAPW X KVG

Fault Type Calculated value (Amp) Pick-up (Amp) Measured time (ms)
A-B-C

b. For low voltage side :


I inj
Setting: O87P= 0.3 and Trip Time=0 sec I differential =|I 1 −I 2|=I 2 =0.3=
TAPW X KVG

Fault Type Calculated value (Amp) Pick-up (Amp) Measured time (ms)
A-B-C
Measurement accuracy:

Pickup Accuracy (A secondary): 5 A Model: ±5% ±0.10 A 1 A Model: ±5% ±0.02 A


Restrained Element (with harmonic blocking): Pickup Time: 1.5/1.6/2.2 cycles (Min/Typ/Max)
Restrained Element (with harmonic restraint):Pickup Time: 2.62/2.72/2.86 cycles (Min/Typ/Max) [As per Instruction
manual 787_IM_20130426, Page 38].

5. Testing of differential relay (Unrestraint element U87P):


a. For High voltage side:
Setting: U87P= (but for testing purpose we assume U87P= ) and Trip Time=0 sec.
Fault Type Calculated value (Amp) Pick-up (Amp) Measured time (ms)
A-B-C

b. For low voltage side:

Fault Type Calculated value (Amp) Pick-up (Amp) Measured time (ms)
A-B-C
Measurement accuracy:
Pickup Accuracy (A secondary): 5 A Model: ±5% ±0.10 A 1 A Model: ±5% ±0.02 A
Unrestrained Element:
- Pickup Time: 0.8/1.0/1.9 cycles (Min/Typ/Max)
6. Second harmonic restrain check setting:

Date Performed By: Witness By:

(ALFANAR) (YASREF COMPANY)

Name

Signature
SITE INSPECTION AND TEST RECORD
Owner Description: Contractor

SEL 787 Transformer Differential


Protection Relay

Name of Substation:

Panel/ Tag No: Date:

Setting: second harmonic ( I 120 HZ/ I 60 HZ) = %


High Voltage side Low Voltage side
Injected I at 60 Hz Measured 120 HZ Injected I at 60 Hz Measured 120 HZ
(Amp) Trip Block (Amp) Trip Block

7. Fourth harmonic restrain check setting:


Setting: fourth harmonic ( I 240 HZ/ I 60 HZ) = %
High Voltage side Low Voltage side
Injected I at 60 HZ Measured 240 HZ Injected I at 60 HZ Measured 240 HZ
(Amp) Trip Block (Amp) Trip Block

8. Fifth harmonic restrain check setting:

Setting: Fifth harmonic (I 300 HZ/I 60 HZ) = %

High Voltage side Low Voltage side


Injected I at 60 HZ Measured 300 HZ Injected I at 60 HZ Measured 300 HZ
(Amp) Trip Block (Amp) Trip Block

Measurement accuracy:
Pickup Accuracy (A secondary): 5 A Model: ±5% ±0.10 A , 1 A Model: ±5% ±0.02 A
Time Delay Accuracy: ±0.5% ±0.25 cycle [As per Instruction manual 787_IM_20130426Page 38].
- The SEL-787 includes common harmonic blocking and harmonic restraint logic; you can select either one or both
of them. The combination of both logic functions provides optimum differential element operating speed and
security. Use the HRSTR = Y setting to enable the harmonic restraint logic and the HBLK = Y setting to enable the
harmonic blocking logic.
- Common harmonic blocking provides superior security against tripping on magnetizing inrush during
transformer energization, yet allows faster differential element tripping for an energized transformer fault.
Differential tripping through the harmonic restraint logic is slightly slower, but provides a dependable tripping
function when energizing a faulted transformer that might otherwise have the differential tripping element
blocked by common harmonic blocking logic.

9. TRIP TEST
Date Performed By: Witness By:

(ALFANAR) (YASREF COMPANY)

Name

Signature
SITE INSPECTION AND TEST RECORD
Owner Description: Contractor

SEL 787 Transformer Differential


Protection Relay

Name of Substation:

Panel/ Tag No: Date:

DISTRUBANCE TRIP
S.NO FUNCTIONS REMARKS
RECORD EXTRACT

1 Minimum Diff element O87P

2 Unrestraint element U87P

3 2nd harmonic Block

4 4th harmonic Block

5 5th harmonic Block

Date Performed By: Witness By:

(ALFANAR) (YASREF COMPANY)

Name

Signature