0020 *** In process inspection & test requirement Specification Details / Notes:
0030
0010
*** X X
Final inspection & test requirements
Explosion Proof Motors
Specification Details / Notes:
Explosion-proof Nameplate by Notified 3rd Party Certification
Agency. Certificates/records to be checked for 4000 V Zone 0
or 1 explosion proof.
0020 X X Max. Heater Surface Temperature Certificates/records to be checked for 4000 V Zone 0 or 1
explosion proof. For non 4000 V Zone 0 or 1 explosion proof
motors, only certificate/data to be provided is applicable.
0030 X Design Type Test One per size or per line item.
0060 X Airborne / Motor Sound Power Levels Shall not exceed 90 dBA. For motors greater than 100 HP.
(note3)
0080 X X a) Current and Power Input (Note 4), (Note 5), (Note 6) and (Note 7).
0090 X X b) Mechanical Vibration Measurements (Note 4), (Note 5), (Note 6) and (Note 7).
0100 X X c) Measurement of Winding Resistance (Note 4), (Note 5), (Note 6) and (Note 7).
0110 X X d) High-Potential Test (Note 4), (Note 5), (Note 6) and (Note 7).
Notes:
(1) May only be waived by the responsible Saudi Aramco, ASC, or AOC Inspection Offices.
(2) See form SA175 - 000003 for instructions on using this form.
(3) Not applicable to Zone 0 or 1 explosion proof.
IR170200 Continued...
INSPECTION & TESTING REQUIREMENTS REVISION: 06/22/2011 CODE NUMBER: PAGE:
SAUDI ARAMCO FORM-175 REPLACES: 08/26/2006 IR170200 2 of 2
(1) VISUAL INSPECTION WITNESSING BY INSPECTOR (Note 1)
(2) CERTIFICATES / RECORDS TO BE CHECKED BY INSPECTOR
(3) CERTIFICATES / DATA TO BE PROVIDED BY VENDOR / SUPPLIER / MANUFACTURER
(4) For 4000 V Zone 0 or 1 explosion proof motors, visual inspection and certificates/records to be checked are applicable.
(5) For motors greater than 250 HP only certificates/records to be checked is applicable.
(6) For motors equal or less than 250 HP, only certificates/records to be provided is applicable.
(7) For Zone 0 or 1 explosion proof motors less than 4000 V, only certificates/records to be provided is applicable.
End of IR170200