P R OT E C T I O N

MiCOM P114D
Numerical CT and auxiliary voltage
powered overcurrent relays
with easy setting

THE MICOM P114D IS A NUMERICAL RELAY DESIGNED


TO OFFER OVERCURRENT AND EARTH FAULT PROTECTION
WITHOUT REQUIRING ANY EXTERNAL AUXILIARY SUPPLY.

The relay can be applied to medium and high voltage


electrical systems as either main or backup protection.

The MiCOM P114D can be ordered as a self-powered


or as a dual-powered version.

All protection settings can be made easily using simple


DIP switches only without the need of setting software.

The MiCOM S1 Studio setting software allows


customised digital input/output configuration via a USB
port on the relay.

The relay offers additional measurement, monitoring


and recording functions which are available through
the communications port.

The capacitance discharge output is capable of


discharching sufficient power to a low-energy trip coil
of a circuit breaker.

An external flag indicator is used for remote or local


indication of a trip.

The rear RS485 port allows CB control with the close


Customer benefits and trip commands.
• No need for guaranteed
auxiliary power supply Flush panel or wall mounting is optionally available to
• Small dimensions of the provide a flexible solution for easy integration into a
relay substation.
• Easy setting using DIP
switches
• USB port for local
communication with self-
powering facilities
• Excellent for retrofit of old
technology relays
• FRAM memory: no back-up
battery inside.

AREVA T&D
APPLICATION GLOBAL FUNCTIONS

The MiCOM P114D numerical overcurrent protection The power supply to the electronic circuits of the
relay provides a simple and cost efficient solution MiCOM P114D has been optimised so that it can trip
where no external auxiliary power supply is available or the circuit-breaker with a load current of 0.2 In on at
guaranteed. least one phase.
The following features are generally available in the
Typical applications are: MiCOM P114D:
> A cost optimized MV switchboard with small > CT powered
dimensions > DIP switches for settings
> HV back up protection (HV/MV transformers) > Two types of case (HxWxD): flush panel
> Utility and industrial substations (183x160x107) or wall (203x138x95) mounting
> Retrofit of old technology relays > Settings referred to nominal current

The MiCOM P114D is connected to 1A or 5A CTs,


separately defined for phase and earth fault analog
inputs.

FUNCTIONS OVERVIEW

ANSI FEATURES

Auxiliary supply voltage (ordering option)


50/51 Three-phase overcurrent I>> (DT)
50/51 Three-phase overcurrent I> with DT or IDMT
(IEC SI, VI, EI, UK LTI, STI, RI, IEEE: MI, VI, EI, US: CO2, CO8)
50N/51N Earth fault overcurrent IN>> (DT)
50N/51N Earth fault overcurrent IN> with DT or IDMT
(IEC SI, VI, EI, UK LTI, STI, RI, IEEE: MI, VI, EI, US: CO2, CO8)
Instantaneous or IDMT delayed reset for IEC, IEEE and US characteristics
Blocking logic and selective relay scheme logic (Note 1)
External trip using a digital input (AUX) (Note 1)
Changeover output contacts for auxiliary supply operated trip coil (RL1 and RL2)
Output for low energy CB coil (24VDC, 0.1J) or striker (12VDC, 0.02J) (ordering option)
Output for flag indicator (24V, 0.01J)
2 changeover + 2 normally open (option) relay output contacts (RL1, RL2, RL3, RL4)
86 Latching relay output contacts (Note 1)
Two digital opto isolated inputs (L1, L2) (Note 1)
Switchable input/output configuration: Front panel (DIP switch) or setting software
Fault records for the five most recent trips
Event records (up to 100 events) (Note 1)
Front USB port for local downloading settings, events and fault records with self-power facility
Rear port RS485 communications (Modbus RTU or IEC103) (Note 1)
Setting software MiCOM S1 Studio
Measurements (true RMS) available through communication ports (Note 1)

(Note 1): Function not available if auxiliary power supply fails

Easy and accurate settings


2>3
using DIP switches
MAIN FUNCTIONS FUNCTIONS

The hardware architecture and software algorithms


> Three Phase Overcurrent Protection (50/51)
have been designed to provide fast protection
operation when self powered from a low level of load The MiCOM P114D relay has a three-phase current
current. input for overcurrent protection. Two independent
overcurrent protection stages are available
The MiCOM P114D relay is optionally equipped with a (I> and I>>).
circuit breaker trip output (24VDC, 0.1J) or striker For the first stage (I>) the user may independently
output (12VDC, 0.02J) (the striker K1 is offered by select a definite time delay or an inverse time delay
Areva). The capacitance discharge output is capable of with different types of IDMT curve (IEC SI, VI, EI, UK
discharging sufficient power to a low-energy trip CB LTI, STI, RI, Rect, IEEE: MI, VI, EI, US: CO2, CO8).
coil. The second stage (I>>) is definite time only.
The IDMT (IEC, IEEE, US) characteristics can be set
The self powered MiCOM P114D changeover output with instantaneous or IDMT reset for the I> and IN>
contacts can be used to trip the CB where the CB trip stages.
coil is auxiliary powered.
An external Flag Indicator can be connected to an > Earth Fault Overcurrent Protection (50/51N)
independent energy output (24VDC, 0.01J).
For the first stage (IN>) the user may independently
select a definite time delay or an inverse time delay
The six LEDs indicate the relay healthy status as well
with different types of IDMT curve (IEC SI, VI, EI, UK
as other protection status information.
LTI, STI, RI, Rect, IEEE: MI, VI, EI, US: CO2, CO8).
Communication using the USB port (Modbus RTU
protocol) and rear RS485 port (Modbus RTU or The second stage (IN>>) is definite time only.
IEC 103 protocol) allows the readout of settings,
configuration of inputs/outputs, download of fault
records and event records.

FUNCTIONAL OVERVIEW

Local Remote
communication communication

Low Energy Trip Coil


Setting via
USB RS485 DIP switches
X Flag Indicator
port port
Fault records
5
Contact Output RL4
Communication Event records
100 Contact Output RL3

Contact Output RL2


I> I>> I> I>>
50/51 50/51 50/51N 50/51N Contact Output RL1

I
Binary Input L2

Binary Input L1

(Description of ANSI code nos. see Functions Overview)

MiCOM P114D
provides optimized solutions for small spaces
> I/O Configuration AREVA TRACK RECORD - SIMPLE OVERCURRENT
All protection settings are available using DIP and EARTH FAULT PROTECTION
switches only. Two pre-defined input/output >> Px1x family of simple overcurrent relays - P111, P114S, P114D, P115.
configurations can be selected using DIP switches or
>> MiCOM P111: First released Dec 2001. Over 6000 devices installed.
a customised configuration can be selected using
>> MiCOM P114/5: First released 2008.
the setting software. The DIP switches on the front
panel are a simple and visual way of setting the
relay's configuration without the need for additional
equipment. The setting software allows every input
and output to be freely configured to available
functions, such as blocking of protection elements,
> Fault Recording
resetting LEDs or outputs, starting, and tripping of
every protection element. This allows inputs and The last five faults are stored in non-volatile FRAM
outputs to be configured for specific applications. memory.

> Remote Trip Via Digital Input > Event Recording

AUTOMATION-L3-P114D-BR-05.08-1845-GB - © - AREVA - 2008. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA. MiCOM is a registered trademark of AREVA.
Opto isolated digital inputs can be configured for a 100 logic events are stored in non-volatile FRAM
Remote Trip function which allows a circuit breaker to memory. All events are time stamped to 1 ms.
be opened using the MiCOM P114D with signalling.
This function works if powering of the relay is
guaranteed. > MiCOM S1 Studio Support Software
Support Software MiCOM S1 Studio is available for
the entire MiCOM family, including P114D relays.
> Blocking and Selective Scheme Logic
MiCOM S1 Studio is fully Windows TM compatible.
The scheme logic depends on the input/output

All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
configuration: This support software allows the readout of settings,
• DIP switch I/O configuration: L1 input can be used configuration of inputs/outputs, download of fault
to block I>> stage records and event records.

• Setting software configuration: logic inputs can be PC connection with the P114D is available via a
freely configured to block any selected protection USB port on the front panel of relay or rear RS485
stages. port (Modbus)

Our policy is one of continuous development. Accordingly


AREVA T&D Worldwide Contact Centre: the design of our products may change at any time. Whilst
http://www.areva-td.com/contactcentre/ every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is
Tel.: +44 (0) 1785 250 070 intended for information purposes only. Its contents do not
constitute an offer for sale or advise on the application of
any product referred to in it. We cannot be held responsible
for any reliance on any decisions taken on its contents
www.areva-td.com without specific advice.
www.areva-td.com/protectionrelays

Вам также может понравиться