Академический Документы
Профессиональный Документы
Культура Документы
Figure 1 - Three Zones of Phase Quadrilateral Distance Protection on the R-X diagram
Figure 1 illustrates the generic R-X diagram for three zones of Phase quadrilateral distance
elements. Quadrilateral Distance elements are complements of Mho distance elements in SEL
relays. The SEL relays with distance elements have implemented both mho and quadrilateral
elements SEL philosophy is to always have the Mho distance elements enabled, especially for
single pole trip (SPT) applications. The subject of this application guide, however, is the discussion
of the quadrilateral element.
Phase distance elements are designed to detect multiphase faults (AB, BC,CA, ABG, BCG, CAG
and ABC). Ground distance elements are designed to detect single phase to ground faults (AG, BG
and CG).
There are six quadrilateral distance units per zone, and these are named: XABn, XBCn, XCAn,
XAGn, XBGn and XCGn (n = 1-5). The purpose of this Application guide is to test each these
elements for phase to phase faults, phase to ground faults and three phase faults.
Figure 1shows the setting parameters for the phase quadrilateral element. Similar parameters are
available for the Ground quadrilateral distance elements.
3
Z1ANG Z1ANG Positive Sequence Impedance Line Angle Line Parameter common to both Phase and
Ground.
XPn XGn Line Reach This is the reach of the distance element on the
line angle. It is not a parameter that plots on the
Imaginary X axis. (n := 1-5)
RPn RGn Resistive Reach This is the setting on the R axis. Review the
discussion below for the differences between
ARESE :=Y and ARESE:=N.
TANGP TANGG Non-Homogeneity correction factor Review the discussion below on this parameter.
- K0M/K0A Zero sequence compensation factor Review the discussion below on this parameter
- XPOL Polarizaing Quantity for the Reactance Line and Review the discussion below on this parameter
the reverse flow resistance line
ARESE Enable the Adaptive RESistance Element Review the discussion below on this parameter.
Notice that the characteristic denoted in Figure 1 does not show the traditional directional element line.
Showing it is theoretically incorrect, as the direction to the fault is determined by the measurement of the
source impedance (- Zs for a forward fault) or the system impedance ( + Zx for a reverse fault). The
quadrilateral distance element will operate properly for a fault in the forward direction with a capacitor in
front of it.
Based on the parameters on table 1and Figure 1, the following are discussion points to keep in mind:
For the intent of this application guide, the discussion will center on the testing for ARESE := Y.
4
b) K0M / K0A
The zero sequence compensation factor applies to the ground elements only. It compensates the
influence of the zero sequence current on the measurement of the apparent impedance for ground
faults (Iphase + K0 3I0).
𝑍𝐿0 − 𝑍𝐿1
𝐾0 =
3𝑍𝐿1
For static tests, the difference in angles of the zero sequence impedance ZL0 and the positive
sequence impedance ZL1, affects the tilt of the reactance line, as described in reference [3].
To properly account for the influence of the different angles of ZL1 and ZL0, the following angle
needs to be added to the tilt of the reactive element
𝑍𝐿0
𝐶𝐴𝑁𝐺 = −arg(2 + )
𝑍𝐿1
If the angles of ZL0 and ZL1 are the same, CANG=0. This small compensation factor most of
the times is insignificant; however, when the angles of the two characteristic impedances are
drastically different, they will make a noticeable influence.
c) XPOL := I2, IG
For the static tests, the choice between polarizing the quadrilateral ground distance element with I2
(Negative sequence current) or IG (Zero sequence current) is transparent to the user. The default
and recommended polarization is with I2.
5
If XPOL := I2, then the relay forces TANGP = TANGG. IF XPOL := IG, then TANGP and
TANGG can have different values.
The TANGP and TANGG parameters directly affect the tilt of the reactance element in the
respective quadrilateral distance elements, as described also in the instruction manual (Figure 4).
Figure 3 Instruction Manual Illustration of the effect of TANGP and TANGG in the reactance element
If the parameter estimation cannot be done due to several reasons (lack of system data for example)
leave the parameter to its default value (-7 degrees).
6
1-All test values applied must exceed any supervising overcurrent element settings to allow the
Corresponding distance elements to operate.
2-Assertion of a loss-of-potential condition (LOP) can disable the distance element under test.
So please disable LOP before testing by setting ELOP = N.
3-Pole open logic can internally disable distance elements. So always be sure the CB close
condition asserted during the test (ensure that the appropriate breaker status is being provided to
the relay so that distance elements can assert).
4- The bottom blinder line (line 1) represents the directional element for the all zones
(Represented for the simplicity at R, X plan). This line is dynamically changed for the different
power flow conditions. In addition directional element may respond to different input signal (for
example, negative – or zero sequence currents and voltages) than reactance and resistance
elements. Its actually F32P and R32P elements which are derived from F32Q and R32Q
So it’s complicated to simulate the faults on this line and it shouldn’t testing during zone reach
test.
5- Z1, Z2 always Forward direction but Z3, Z4, Z5 are setting adjustable for reverse or forward,
it’s recommended to keep Z3 reverse.
6- For the ground element if the XGPOL=IG, then the TANGG value should be added to 180 o in
line 3 of the ground zone c/cs.
7- keep the fault impedance constant while increasing the sequence impedance to achieve the
desired directional determination.(constant source impedance system to be selected in Omicron).
8- Ensure that k0 values inserted correctly in test device for the ground zone reach test.
7
jX
TANG + CANG
XG1
Z1ANG RG1
R
It is should be possible to test the SEL quadrilateral distance elements with any test set that is properly
applying and calculating the test voltages and currents.
To illustrate an example for testing the quadrilateral ground distance elements, the following steps should
be followed up to create the zone in the test kit.
A- ARESE= Y ( Left blinder fixed at –RG1 FOR ALL ZONES OVER ANGLE 90)
Element Line 1 (Bottom blinder) Line 2 (Right blinder) Line 3 (Top blinder) Line 4 (Left blinder)
Using a particular test set software (from OMICRON, Inc.), the following are screen captures for the setup
of the Zone 1 test:
10
B- ARESE= N
Element Line 1 (Bottom blinder) Line 2 (Right blinder) Line 3 (Top blinder) Line 4 (Left blinder)
R 0 (RG1/1+k0) 0 -(RG1/1+k0)
XG1 * SIN Z1ANG
X 0 0 0
Z1ANG-90
ø Z1ANG 180+TANGG Z1ANG
Using a particular test set software (from OMICRON, Inc.), the following are screen captures for the setup
of the Zone 1 test:
11
R 0 RP1 0 -RP1
XP1 * SIN Z1ANG
X 0 0 0
Z1ANG-90 180+TANGP
ø Z1ANG 90
12
Using a particular test set software (from OMICRON, Inc.), the following are screen captures for the setup
of the Zone 1 test:
13
The forward three-phase element is supervised by the phase directional element (F32P). This
element declares a forward fault when the line impedance is between Z1ANG – 90 and 120 degrees.
During a balanced three-phase fault, the relay reduces the reach of the reverse phase quadrilateral
element characteristic by reducing the left blinder to 25 % of the original RPn setting (where n = 3, 4, 5).
The reverse three-phase element is supervised by the phase directional element (R32P). This
element declares a reverse fault when the line impedance is between Z1ANG + 90 and300 degrees.
The relay has fixed direction range which is from 120 up to -60 degrees.
The actual forward direction is the intersection between this area and The positive sequence line angle
which is Z1ANG added to of(+90;-90)degrees.
Example: if Z1ANG=80 So the direction range will be from (80+90=170) up to (80-90=-10) the range
will be from 170 up to -10. However the relay fixed direction range is from 120 up to -60.
So the intersection between both is from 120 up to -10 and this is the actual forward direction value which
can tested
Element Line 1 (Bottom blinder) Line 2 (Right blinder) Line 3 (Top blinder) Line 4 (Left blinder)
RP1 * 0.25
R 0 0 -RP1
XP1 * SIN Z1ANG
X 0 0 0
Z1ANG-90 180+TANGP
ø Z1ANG 90
14
Using a particular test set software (from OMICRON, Inc.), the following are screen captures for
the setup of the Zone 1 test: