DISPLAY shows Possible reason(s): Try to:
Warning 1 The 10 volt supply from Disconnect terminal 50 If
Under 10 volts terminal 50 is below 10 volt. problem continue, change
(10 VOLT LOW) The power supply is control card.
overloaded If problem continue, the
Max 17 mA/min. 590 Ohm power supply on the power
board is defective.
Warning/Alarm2 The current signal on Check the:
Live zero fault terminal 60 is less than 50% Signal wires are not broken
(LIVE ERROR ZERO) of the value set in parameter Your current source is
315 terminal 60 min scaling working properly
and the time set in parameter Check the settings of
317 time out is elapsed and Parameter 315, 317 an d 318
“stop and Trip” is chosen in
Parameter 318 Function
after time out .
Warning/Alarm 3 The “motor check function” s Check the motor cable. Is any
No motor chosen in Parameter 122, wires broken. Is the repair
(NO MOTOR) and the VLT® 5000 cannot switch open, check if you can
detect a motor. close it SAFETY
Check the motor vindings
Warning/Alarm 4 One input phase to the VLT® Disconnect all power supply
Phase fault 5000 is missing. to the VLT® 5000. Remember
(MAINS PHASE LOSS) There is unsymmetri between the separate 24 Volt supply
the input phases terminal 35 & 36. When the
display is black”, check all
supply wires to the VLT ® .
Check the symetry on the 3
Ph power supply for the VLT®
The voltage difference
betwen the phases must not
exceed 2%.
Warning 5 The intermidiate circuit Check if the voltage supply is
Voltage warning high voltage (DC) is higher than up to specifications.
(DC LINK VOLTAGE the limit given by the controls Check the voltage sypply for
HIGH) for the drive. transients.
With brake Check the motor for running
3X220 Volt units: 384 Volt generatoric (supplies voltage
3X400 Volt units: 801 Volt back to VLT® :
Without brake  Extend the Ramp-down
3X220 Volt units: 405 Volt time
3X400 Volt units 840 Volt  Change to a unit with
The VLT® is still active brake.
Warning 6 The intermidiate voltage (DC) Check the sypply voltage.
Voltage arning low is below the limit given by the If the VLT® is unloaded,
(DC LINK VOLTAGE controls for the drive. check if one phase is missing.
LOW): 3X220 Volt units: 211 Volt
3X400 Volt units: 423 Volt
Warning/Alarm 7 The intermidiate voltage (DC) Check if the voltage supply is
Overvoltage has exceeded the limit given up to specifications.
(DC LINK by the inverter hardware, and Check the voltage sypply for
OVERVOLTAGE) the VLT® will trip after the transients.
time set in Parameter 410 Check the motor for running
has passed. generatoric (supplies voltage
The voltage at trip is stated in back to VLT® :
the display  Extend the Ramp-down
The limits are: time
3X220 Volt units: 425 Volt  Change to a unit with
3X400 Volt units: 855 Volt brake.
 Check if the brake is
working properly.

Tip. After reset and restart,


monitor the DC voltage. (in
display or Parameter 614
Data Log DC link voltage). If
the DC voltage is steadily
increasing, the problem may
be transients.
Warning/Alarm 8 The intermidiate voltage (DC) Check the sypply voltage.
Undervoltage is below the limit given by the Tolerance - 10%
(DC LINK inverter hardware, and the If the VLT® is unloaded,
UNDERVOLTAGE) VLT® will trip after the a check if one phase is missing.
given time depending on the
unit. Tip: You can monitor the DC
The voltage at trip is stated in voltage in Parameter 614
the display Data log DC link voltage
The limits are:
3X220 Volt units: 211 Volt
3X400 Volt units: 402 Volt
Warning/Alarm 9 The termal inveter protection This alarm can only e reset,
Inverter overload reports overload in the when the counter is balow
(INVERTER TIME) inverter. 90%
The warning comes, when
the electronic counter After reset, and restart you
(counting current and time) can correct the data given
has reached 98% of max, about the motor, Parameter
and the alarm comes, when 102, 103, 104, 105, 106.
the counter has reached You can reduce the switching
100% frequency i Parameter 411.
This warning/alarm can be If the motor cables is longer
caused by: than specified in the Design
 Wrong motor data Guide, you can probalby
 Defect motor solve the problem by using a
 VLT® overloaded LC filter.
 To long motor cables You can monitor the thermal
 To high switching load of the inverter in the
frequency display during operation .
Warning/Alarm 10 The VLT® trips when the Switch off the power supply to
Motor overtemperature motor has been running too the VLT® . Don*t forget to
(MOTOR TIME) long time with too high switch of the separate 24Volt
current. power supply for the control
This alarm is only relevant, if Board, af applied.
“ETR Warning” is choosed in Check the motor conditions,
Parameter 128. this function is for protection
of the motor. If everything is
OK, start again.
The counter for motor thermal
load will be set to 0% when
you disconnect the power
supply.
You can monitor the thermal
load of the inverter in the
display during operation .
Warning/Alarm 11 The thermistor in the motor Check, that the motor is not
Motor thermistor has been opened by too high too warm.
/MOTOT THERMISTOR) winding temperature, r the Check the thermistor, and its
connection has been broken. connections
This alarm is only relevant, if Check the parameters 308 &
”thermistor Warning” or 311 for correct setting.
“thermistor trip is chosed in
parameter 128.
The parameters 308 and 311
must be programmed for
“thermistor”
Warning/Alarm 12 The torque is higher than the Check the settigs of
Warning/Alarm 12 limit in Parameter 221 & 222. Parameter 221 &222.
Overcurrent Please note, there can be a Check the motor data.
time delay before trip, set in Check the parameters for
parameter 409. ramps (207, 208, 209 and
Too short Ramp times 210)
The Parameter 308, 311 or Check the parameters 308,
314 can be set for “torque 311 and 314, and the
limit” relevant control signals.
Warning/Alarm 13 The inverter peak current Switch of all power supply.
Torque limit (app. 200% of nominal) has Check the motor load
(TORQUE LIMIT) been exceeded. There will be Check the ramps, (Parameter
a very short warning period 207,208,209, and 210)
(app. 1 sec.) , and then a Check parameter motor data.
trip.This time can be reduced Check the Parameter 119.
in Parameter 119. The time
can not be extended.
Alarm 14 There is an earth leaking Check the motor cables and
Earth fault current on the output from the the motor
(EARTH FAUL) VLT® .
This leaking current can be in
the motor cable or in the
motor
Alarm 15 Fault in the switch mode Change the power card.
Switch mode fault power supply.
(SWITCH MODE FAULT)
Alarm 16 There is a shortcircuit on the Disconnect the motor
Short-circutting VLT® output termianls. terminal, and reset and
(CURR.SHORT CIRCUIT) restart the VLT® .
Warning/Alarm 17 The connection via seriel Check the electrical
Standard bus timeout communication (terminal connection to terminal 68/69.
(STD BUSTIMEOUT 68/69) is missing. Check the bus dress in
This warning is only relevant Parameter 501.
if Parameter 514 is set to Check the baud-rate.
anothe value than “off” and Parameter 502
only after the communication
has been missin for a period
longer than the value set in
Parameter 513
Warning/Alarm 18 Connection to High Check the connections for
HPFB bus timeout Performance Field Bus is HPFB.
(HPFB BUS TIMEOUT) missing.
Only relevant, if a bus
communication option is build
in to the VLT®
Warning 19 The VLT® has recognised a Change the power board.
Fault in the EEprom on failure in the EEprom on the
the powercard. power card. The VLT® will
(EE ERROR POWER proberly not restart after
CARD) power of.

Alarm 20 The VLT® has recognised a Change the control board


Fault in the EEprom on failure in the EEprom on the
the control card. control card. The VLT® will
(EE ERROR CTRL CARD) proberly not restart after
power of.
Alarm 21 This is not an alarm, but a Reset the VLT®
Auto-optimisation OK notice, that everything is
(AUTO MOTOR ADAPT OK
OK)