Datasheets Water system for scrubber & hydrator

FP00484-FME-103

Comments Resolution Sheet

Sl. No. JITF COMMENTS BOLDROCCHI REPLY DTD 28.11.18 Jindal reply

Check PID number, it shall match relevant PID. We understand that it shall be
1 NOTED & REVISED Noted and Ok
FP00484FME-103-10. Typical comment applicable for all datasheets.

2 LEVEL SWITCH

2.A Please check if it is better than SS304. Else minimum SS 304 is required. NOTED & MOC IS SS304 Checked and Ok

1 SPDT CONSIDERED FOR NON CRITICAL APPLICATION. KINDLY


2.B Please provide 2 numbers of SPDT contacts. 1 SPDT is not acceptable.
CONSIDER.

2.C Ensure contact rating is suiable for PLC. NOTED & IT IS COMPATIBLE WITH PLC. Checked and Ok

2.D Furnish Model ordering code. NOTED & SAME SHALL BE INCORPORATED IN AS BUILT. Checked and Ok

TYPOGRAPHICALLY ERROR IN PID, LOW LOW LEVEL => PUMP TRIP,


LOW LEVEL => OPEN TANK INLET ON-OFF VALVE, HIGH LEVEL =>
2.E Only two alarms H & L as per P&ID Ok
CLOSE TANK INLET ON-OFF VALVE. AS BUILT P&ID WILL BE
SUBMITTED WITH CORRECTION.

3 AIR BLOWER

3.A Mention Details NOTED & SAME is INCORPORATED IN DATA SHEET. Ok

NOTED & SAME IS ALREADY SELECTED. MOTOR DATA SHEET IS


Insulation Class: F, Temperature rise class : B, IP: 55, Efficiency : IE2 Ok
ALREADY SUBMITTED.

4 BALL VALVE - FLANGED

WE AGAIN REQUEST YOU TO PLEASE CONSIDER MARCK MAKE WHICH


4.A Make shall be as per approved vendor list IS EQUALLY REPUTED. ATTACHED CATALOGUE OF MARCK MAKE FOR Supply as per the PO
YOUR READY REFERENCE (WWW.MARCKENGINEERS.CO.IN)

40NB BALL VALVES ARE FLANGED TYPE. IT IS CASTING GRADE VALVE,


4.B Shall be forged CS for 40 NB
SO MATERIAL ASTM A216 GR. WCB

00F-BV-30 WILL BE IN BI DATAHSHEETS, BI WILL CONSIDER THE SAME.


4.C 00F-BV-30, 00F-BV-28, 00F-BV-37,00F-BV-36, Data sheet not found 00F-BV-28, 00F-BV-36, 00F-BV-37 REFER REVISED DATASHEETS PAGE NO. Checked and Ok
26 OF 38.

5 BALL VALVE - SCREWED


NOTED & VALVE BODY IS FORGED CS FOR THESE VALVES. IT IS
5.A Shall be forged CS for 40 NB
TYPOGRAPHICAL ERROR. SAME IS INCORPORATED.

5.B 00F-BV-35,37,38,39,40 Data sheet not provided REFER DATASHEETS PAGE NO. 25/26 OF 38. Checked and Ok

6 BLOCK & BLEED VALVE

6.A 20F-BBV-1 Not Found in the P&ID IT IS SHOWN FOR PRESSURE GAUGE 20F-PG-10. Include in data sheet

7 MOTOR FOR VERTICAL PUMP

IT IS VERTICAL PUMP WITH MOTOR & IT IS CONSIDERED AS ONE UNIT.


7.A Test Certificate to be provided SO VENDOR PROVIDES WARRENTY CERT. FOR WHOLE PUMP WITH
MOTOR & NO INDIVIDUAL TEST CERT. IS PROVIDED.

8 CENTRIFUGAL PUMP & MOTOR

BEARING MATERIAL IS SIC (Silicon Carbide) WHICH IS STANDARD


8.A Bearing MOC Shall be SS MATERIAL FOR VERTICAL PUMPS. THIS IS SUITABLE FOR WATER
APPLICATION.

8.B Write Unit=meter NOTED & SAME IS INCORPORATED.

9 CONTROL VALVE AIR & WATER


WE HAVE CONSIDERED STANDARD MAKE WHICH IS MOST
COMPATIBLE WITH OUR SYSTEM AND IS BEING USED FOR ALL EXPORTS
9.A Make shall be Rotork, Auma as per approved vendor list Supply as per the PO
PROJECTS AS WELL. WE REQUEST YOU TO CONSIDER THE SAME . REFER
WEBSITE - WWW.PNEUCONVALVES.COM

THIS ABB MAKE SMART TYPE ELECTRO-PNEUMATIC POSITION


9.B Preferred is Siemens TRANSMITTER IS EQUIVALENT TO SIEMENS MAKE SMART TYPE Prefferd is siemens
ELECTRO-PNEUMATIC POSITION TRANSMITTER IN ALL RESPECT.

9.C provide the Make and mode, preferred is SHAVO model: 11-4SN NOTED & SAME IS PROVIDED Checked and Ok

10 DIFFERENTIAL PRESSURE INDICATING SWITCH

10.A Specify which SS. SENSOR ELEMENT IS SS316 & SENSOR HOUSING IS SS304. Sensor housing not given in the datasheet

THIS IS NOT CRITICAL OPERATION. THIS IS ONLY TO INDICATE FILTER


10.B Please provide 2 numbers of SPDT contacts. 1 SPDtTis not acceptable. Noted and Ok
CHOCKING.
compatible is 24 V DC but in data sheet
10.C Ensure contact rating is suiable for PLC. NOTED & IT IS COMPATIBLE WITH PLC.
given as 120V Dc
DP SWITCH IS PROVIDED WITH FLYING LEADS CONNECTIONS, SO
10.D Double compression cable gland. GLAND IS NOT REQUIRED. LEAD CONNECTIONS ARE TAKEN OUT FROM Consider the cable glands
DP SWITCH.

11 DIFFERENTIAL PRESSURE TRANSMITTER

AS PER MOM DATED 17.09.18, ALL PRESSURE RELATED INSTRUMENTS


All pressure instruments shall have 3 Valve manifold as accessory while DP shall have 5
11.A SHALL HAVE 2 WAY VALVE MANIFOLD WHILE DPT SHALL BE 5 WAY Modify the same in the datasheet
Valve manifold. (Typical comment)
MANIFOLD.

11.B At least IP 66 for Transmitters (Typical Comment) NOTED & SAMES IS IP66. DATA SHEET IS REVISED Checked and Ok

IT IS STANDARD ABB MAKE M. NO. 266DSHH D.P. TRANSMITTER WITH


11.C should be smart type with Local Display indicator Checked and Ok
LOCAL DISPLAY INDICATIOR.

11.D Local LCD display is provided on Transmitter. NOTED & SAME IS AVAILABLE. Checked and Ok

11.E Confirm that Square rot extractor is provided in transmitter. NOTED & CONFIRMED Checked and Ok

12 DOUBLE BALL VALVE


12.A Shall be A105 (Forged) NOTED & MATERIAL IS A105. SAME IS REVISED IN DATA SHEET. Checked and Ok

12.B tag not found in the P&ID IT IS PART OF LANCE, SO NOT SHOWN SEPARATELY. Checked and Ok

13 DUPLEX FILTER
Not found in the datasheet.Kinldy
13.A Tag not found NOTED & SAME IS INCORPORATED IN DATA SHEET.
incorporate
14 ELECTRO-MAGNETIC FLOWMETER
Local disply with key pad for
14.A should be with Local display indicator NOTED & SAME IS AVAILABLE.
configuration required
THIS IS USED TO MEASURE TOTAL WATER FLOW TO EACH SCUBBER.
14.B Furnish Service description (Typical comment).
THIS ONLY FOR INDICATION.

15 GLOBE VALVE

15.A Shall be A105 NOTED & MATERIAL IS A105. SAME IS REVISED IN DATA SHEET. Checked and Ok

16 NON RETURN VALVE - SANDWICH

16.A Shall be A105 (forged) NOTED & MATERIAL IS A105. SAME IS REVISED IN DATA SHEET. Checked and Ok

16.B Shall be SS 304 NOTED & MATERIAL IS SS304. SAME IS REVISED IN DATA SHEET. Checked and Ok

17 ORIFICE PLATE ASSEMBLY

17.A Submit the Flow VS DP curve. NOTED & ATTACHED. Noted and Ok

17.B Submit the calculation sheet NOTED & ATTACHED. Noted and Ok

17.C Ensure that this much of permanent pressure loss is acceptable. NOTED & CONFIRMED

18 PRESSURE GAUGE

100 MM DIAL SIZE IS SUITABLE FOR THIS APPLICATION. WE HAVE


18.A Minimum 150 MM, typical comment. Kindly chage it to 150mm
CONSIDERED 4" & 6" AS PER THE APPLICATION REQUIRMENTS.

18.B Provide LFB Model number NOTED & SAME IS UPDATED IN DATA SHEET. Checked and Ok

18.C 00F-PG-13 data sheet not provided PROVIDED IN HYDRATING SYSTEM PG. PLEASE REFER PAGE 34 OF 38. Checked and Ok

18.D Bezel ring shall be SS304 minimum and bayonet type. SS304 BAYONET TYPE BEZEL Checked and Ok

18.E Overrange shall be at least 125%. OVERRANGE IS 130% OF FSD. Checked and Ok

18.F Furnish Span adjustment. ZERO RESET IS PROVIDED MICROMETER POINTER (INTERNAL). Checked and Ok
AS PER MOM DATED 17.09.18, ALL PRESSURE RELATED INSTRUMENTS
18.G Add 3 valve manifold in accessory. SHALL HAVE 2 WAY VALVE MANIFOLD WHILE DPT SHALL BE 5 WAY Checked and Ok
MANIFOLD.
19 PRESSURE SWITCH

19.A Double comp cable gland. NOTED & SAME SHALL BE USED. Checked and Ok

19.B Ensure contact rating is suiable for PLC. NOTED & CONFIRMED Checked and Ok

20 PRESSURE TRANSMITTER

20.A with Local display Indicator NOTED & SAME IS AVAILABLE. Checked and Ok

20.B Furnish body material and repeatability. BODY MATERIAL ALUMINIUM. Accuracy shall be +/- 0.075% Checked and Ok

20.C Accuracy shall be +/- 0.075% or better. please select suitable model. NOTED & ACCURACY IS +/- 0.075% AS PER CATALOG. Checked and Ok

21 SHUT DOWN VALVE - BALL TYPE


AFR IS TECHNO MAKE & MODEL NO. KAW2000-02. SAME IS
21.A preferred is SHAVO model: 11-4SN not incorporated
INCORPORATED IN DATA SHEET.

22 BALL VALVE
WE AGAIN REQUEST YOU TO PLEASE CONSIDER MARCK MAKE WHICH
22.A Supply as per the PO make IS EQUALLY REPUTED. ATTACHED CATALOGUE OF MARCK MAKE FOR
YOUR READY REFERENCE (WWW.MARCKENGINEERS.CO.IN)

22.B Shall be A105 NOTED & MATERIAL IS A105. SAME IS REVISED IN DATA SHEET.. Checked and Ok

23 CENTRIFUGAL PUMP & MOTOR

1.9M IS LOW LOW LEVEL IS FROM TOP OF TANK (ie. FROM TOP OF LEVEL
Water Tank Level Low Low is 1.9 m so NPSHR is expected to be less than 1.9 m, please
23.A SWITCH). TANK LEVEL IS ALREADY ABOVE THE CENTRE OF PUMP
recheck
WHICH SHALL PROVIDE ALWAYS FLOODED SUCTION TO THE PUMP.

24 DIFFERENTIAL FLOW-METER FOR HYDRATING

POWER SSUPPLY 24VDC WE CONSIDERED Code H {FOR SAFE AREA Provide the code for display with
24.A In place of "H" it may be "C", Kindly recheck
CONSIDERED} configuration key

24.B add "Y17" for tag name plate in SS WE WILL PROVIDE SS TAG PLATE LOCAL FOR TAG Ok

The provided make do not include local


24.C with Local display indicator module NOTED & CONFIRMED
display indicator
FOR FLOW METER STANDARD ACCURACY IS 0.4 OR 0.2 AND WE
24.D Accuracy +/- 0.075% or better. Checked and Ok
OFFERED BETTER ACCURACY 0.2%

24.E Boldrocchi to ensure that suitable power supply is provided. (Typical comment). NOTED & CONFIRMED Checked and Ok

24.F service description. MEASURING TOTAL WATER CONSUMPTION FOR HYDRATING SYSTEM.

24.G Local LCD indicator required on flow transmitter. NOTED & SAME IS AVAILABLE. Display with configuaration keys

24.H Square root extractor shall be provided in transmitter. NOTED & CONFIRMED

24.I Furnish and confirm repeatability as +/-0.1%. NOTED & CONFIRMED

25 CONTROL VALVE WATER HYDRATING

25.A With Local display NOTED & SAME IS AVAILABLE.

25.B preferred is SHAVO model: 11-4SN NOTED & SAME IS PROVIDED

26 GLOBE VALVE - SOCKET WELD

AS PER APPROVED DATA SHEET STEM IS 13% CR STEEL ie. SS410 WHICH
26.A shall be SS 316
IS SUFFICIENT & REGULAR MOC FOR WATER APPLICATION.

28 SOLENOID VALVE - 2 WAY


THIS IS SOLENOID VALVE (DIRECT ON-OFF VALVE), THERE IS NO
28.A Span adjustment? Noted ok
PROVISION FOR SPAN ADJUSTMENT.