Вы находитесь на странице: 1из 8

providing insights for today’s hvac system designer

Engineers Newsletter
volume 48–2

Selecting Chilled-Water Coils for


ASHRAE 90.1’s New 15°F Delta T Requirement

The 2016 version of ASHRAE Standard


Committee’s intent. Sometimes it is
90.1 requires chilled-water cooling coils
New ASHRAE 90.1 helpful to understand the committee’s
to be selected for at least a 15°F ΔT. Requirement intent when a new requirement like this is
added to Standard 90.1. Other than
This Engineers Newsletter reviews this
Beginning in its 2016 version, ASHRAE attending the committee meetings, the
new requirement, demonstrates how it
affects selection of chilled-water coils, Standard 90.1 now requires chilled-water best way to understand intent is to read
and analyzes the impact of part-load cooling coils be designed for at least a the foreword that is included when an
conditions on coil performance. 15°F temperature difference (ΔT) addendum is released for public review.
between the leaving and entering water;
and the leaving-water temperature must
be no colder than 57°F, at design 6.5.4.7 Chilled-Water Coil Selection.
conditions.1
Chilled-water cooling coils shall be selected
to provide a 15°F or higher temperature
As an example, for the leaving-water difference between leaving and entering
temperature to be 57°F, the coil in Figure water temperatures and a minimum of
1 is selected with a 42°F entering-water 57°F leaving water temperature at design
temperature. This would comply with the conditions.
minimum 15°F ΔT requirement.
Exceptions to Section 6.5.4.7:
1 Chilled-water cooling coils that have an airside
pressure drop exceeding 0.70 in. H2O when
rated at 500 fpm face velocity and dry
Figure 1. Chilled-water cooling coil conditions (no condensation)
2 Individual fan-cooling units with a design
supply airflow rate ≤ 5000 cfm
3 Constant-air-volume systems
4 Coils selected at the maximum temperature
difference allowed by the chiller
5 Passive coils (no mechanically supplied
airflow)
6 Coils with design entering chilled-water
temperature ≥ 50°F
7 Coils with design entering air dry-bulb
temperature ≤ 65°F

©2019 Trane. All rights reserved. 1


As stated in the foreword that coil. But as demonstrated later in this EN, Table 1 compares four coils that could be
accompanied this addendum (see eight rows is not necessarily required to used for this application:
excerpt below), the committee’s intent achieve a 15°F ΔT. It is still a good idea to • Coil #1 has six rows of 3/8-inch
was to encourage the use of coils with select smaller units with a higher ΔT. diameter tubes and turbulators (devices
more heat transfer surface to achieve However, Standard 90.1 does not currently mounted inside the tubes that increase
this higher ΔT.2 It cited a life-cycle cost require it. fluid turbulence to improve heat
analysis that was published in the
transfer).
ASHRAE Journal.3 This analysis showed Per exception 3, if airflow across a cooling
that designing a chilled-water system for coil is constant volume, that coil is also • Coils #2 and #3 have six rows of 1/2-
a higher ΔT reduced first costs—due to exempt from this requirement. For the first inch tubes, one with turbulators and the
smaller valves, piping, and pumps—and analysis in the cited article, the author used other without. Notice that turbulators
also reduced overall system energy cost. a coil selected with more surface area, allow coil #3 to provide the required
The results showed that the increase in resulting in a higher air pressure drop. For capacity with fewer fins than coil #2.
fan energy due to the added coil surface the VAV system analyzed, the resulting This reduces the air pressure drop, but
was more than offset by the pump increase in fan energy was more than increases the water pressure drop.
energy savings. offset by the pump energy savings. (Whether or not this additional water
However, as mentioned above, the article pressure drop impacts the size of
“High ΔT was shown to result in also showed that by using a slightly colder pumps, or pump energy use, depends
optimum energy efficiency and life cycle entering-water temperature, there was no on whether or not this coil is located in
costs in analysis by Taylor in Optimizing change in air pressure drop (zero impact on the “critical circuit” of the piping
Design & Control of Chilled Water Plants, fan energy) compared to the 10°F ΔT system.)
Part 3: Pipe Sizing and Optimizing ΔT baseline. In that analysis, the higher ΔT still
(ASHRAE Journal, December 2011). The • Coil #4 has six rows of 5/8-inch tubes
resulted in lower overall energy use. So and turbulators.
analysis showed that the fan energy even in a constant-volume system, it is a
increase due to the larger coil was more good idea to design for a higher ΔT, but For this example, coil #1 is the least
than offset by the pump energy savings, Standard 90.1 currently does not require it. expensive option. Coil #4 is the best choice
and net first costs were reduced due to
for minimizing both air and water pressure
smaller piping and pumps, offsetting Per exception 6, coils that are selected with drops, but it costs more than the other
higher coil costs. So both first costs and an entering chilled-water temperature of options. Coil #2 or #3 might be selected to
energy costs are reduced by this 50°F or warmer are also exempt. This better balance cost and pressure drops.4
requirement...The intent of this exempts sensible-only cooling equipment,
addendum is to encourage the use of like radiant panels, chilled beams, and
coils with larger heat transfer surface sensible-cooling terminal units, like Trane’s Effect of part-load operating
areas to generate a high ΔT.” CoolSense™. conditions. As explained, Standard 90.1
requires a minimum 15°F ΔT at design
That same article also showed that using conditions. This allows for a lower water
Affected applications. Some examples of flow rate (gpm) and a reduction in installed
a slightly colder entering-water
applications where this requirement does cost due to smaller valves, pipes, and
temperature would allow for a coil
apply include: pumps. But the other motivation is to
selection to achieve the desired higher
ΔT with no impact on supply fan energy • Mixed-air, multiple-zone VAV systems, reduce pump energy use, for which part-
use—that is, no change in surface area since they have variable airflow and are load operation (off-design conditions) also
or air pressure drop compared to the usually larger than 5000 cfm matters.
10°F ΔT baseline. In that case, the • Single-zone VAV air handlers, which
results showed that while the colder For the mixed-air VAV system in this
might be used in larger zones like example, the entering-air conditions will
water does increase chiller energy use, auditoriums, arenas, gymnasiums, or
this was more than offset by the pump change as the outdoor conditions change,
manufacturing areas and the airflow across the coil will change
energy savings.
• Dedicated outdoor-air systems, when as the zone-level VAV dampers modulate.
designed for variable airflow—which Figure 2 shows the resulting water ΔT of
Exceptions. While this is now a
would be the case if demand-controlled these same four coils—each selected to
prescriptive requirement, like other
ventilation is implemented achieve a 15°F ΔT at design conditions—at
sections of Standard 90.1, there are
three different entering-air conditions at
several exceptions listed (see excerpt on
which the cooling coil will still be active,
page 1).
and at two different airflows.
Per exception 2, individual fan-cooling Selecting Cooling Coils At part-load conditions, the coils with
units that supply 5000 cfm or less are for ≥ 15°F ΔT turbulators (#1, #3, and #4) are able to
exempt. This exempts fan-coils, blower-
maintain, or even increase, the water ΔT.
coils, classroom unit ventilators, and The example chilled-water coil in Figure 1 is However, for the coil without turbulators
small air handlers. According to the in a mixed-air VAV air handler that cools (#2), the water ΔT starts to drop at the third
foreword, the committee included this 7000 cfm to 53°F leaving the coil. The part-load condition. And in all cases, the ΔT
exception because most small fan-coils entering chilled-water temperature is 42°F, is not as high in coil #2 as it is in the coils
do not have an option for an eight-row with a 15°F ΔT at design conditions. with turbulators.

2 Trane Engineers Newsletter volume 48-2 providing insights for today’s HVAC system designer
Table 1. Example chilled-water coil selections for 15°F ΔT
coil #1 coil #2 coil #3 coil #4
entering-water temperature, °F 42 42 42 42
leaving-water temperature, °F 57 57 57 57
water ΔT, °F 15 15 15 15
tube diameter, in. 3/8 1/2 1/2 5/8
coil rows 6 6 6 6
fin density, fins/ft 114 159 124 133
fin design high capacity high capacity high efficiency high efficiency
turbulators yes no yes yes
water flow rate, gpm 40 40 40 40
water velocity, ft/s 2.7 2.8 2.8 2.1
water pressure drop, ft. H2O 11.2 4.7 11.1 5.2
air pressure drop, in. H2O 0.81 0.95 0.71 0.71
cost of coil base - 30% base base + 8% base + 15%

Coil selections from Trane Official Product Selection Software (TOPPS™), based on a size 14 Performance Climate Changer™ air handler with coils constructed of copper tubes
and aluminum fins.

Figure 2. Water ΔT at part-load conditions

Entering-air conditions: MA1 = 80°F dry bulb / 67°F wet bulb, MA2 = 75°F dry bulb / 63°F wet bulb, MA3 = 70°F dry bulb / 64°F wet bulb
Coil airflows: 100% airflow = 7000 cfm, 75% airflow = 5250 cfm

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 48–2 3
Turbulators increase fluid turbulence, To demonstrate, Figure 4 plots coil Even though the chiller has to work a little
which improves heat transfer (Figure 3). capacity versus water flow rate and harder to make the 42°F water versus
This allows a coil to provide the required Reynolds Number, using the current 45°F in this example, this is typically more
capacity with a lower water flow rate AHRI 410 performance prediction model. efficient than making the fans and pumps
(higher ΔT), leading to reduced pumping While this does show a slight dip in both work harder to overcome these
energy at part-load conditions. After capacity that is less linear than the rest of higher pressure drops.3,7,8,9
analyzing many coil configurations, this operating range, it is certainly not drastic.
is a consistent trend regarding In summary, laminar flow does not cause Water ΔT higher than 15°F. Note that
turbulators and ΔT. a severe drop-off in capacity. And the Standard 90.1 requires the water ΔT to be
AHRI prediction methods allow coils to 15°F or higher. There are many in the
Impact of laminar flow. The ASHRAE be rated accurately well into the industry who recommend ΔTs even
Handbook suggests that chilled-water transitional and laminar flow regions. higher than this. 3,7,8,9
coils are best selected with water
velocity between 2 to 4 ft/sec, at design Warmer versus colder water In Table 3, the first column is one of the
conditions.5 This recommended range is temperatures. This new requirement in six-row coils from the previous example
intended to provide a good balance Standard 90.1 requires the leaving-water (coil #3), selected with 42°F entering
between coil size and minimizing both temperature be no colder than 57°F, water and a 15°F ΔT. The coil in the
air and water pressure drops. allowing it to be warmer. second column (coil #7) also uses 42°F
entering water, but with a 20°F ΔT. And
But water velocity is also important Table 2 compares coils selected for a the coil in the third column (coil #8) is
because it is one of the key factors for 15°F ΔT, but with different entering-water selected with 40°F entering water and a
determining flow turbulence, depicted temperatures. Coils #2 and #3 are from 25°F ΔT.
by the Reynolds Number. As the the previous example, with 42°F entering
turbulence of a moving fluid increases, water. Coils #5 and #6 are selected with a The larger water ΔTs reduce the water
so does its ability to transfer heat from 45°F entering-water temperature. flow rate even further—from 40 gpm
the tube wall to the fluid. down to 30 gpm or 24 gpm—and also
The coils selected with warmer water (#5 reduce the water pressure drop. This
Some in the HVAC industry express and #6) require eight rows of tubes to significantly lowers pump energy use.
concern that coil heat transfer will provide the necessary capacity. This However, in this example, the higher ΔTs
deteriorate rapidly if the Reynolds results in much higher air and water require more coil surface area, so air
Number falls into the laminar flow pressure drops than the six-row coils pressure drop does increase.
region. The performance prediction selected with colder water (#2 and #3).
methodology prescribed by AHRI And not only will the coil be more
Standard 410 was refined in 2001, expensive due to these additional rows,
allowing coil performance to be the air-handling unit will likely need to be
accurately predicted well into the longer, which increases the cost of the
laminar flow region, without fear of large casing as well.
discrepancies between predicted and
actual performance.6

Figure 3. Turbulators Figure 4. Impact of laminar flow on coil performance

Trane has over 50 years of successful field


experience with turbulators, with performance
certified by AHRI.

4 Trane Engineers Newsletter volume 48-2 providing insights for today’s HVAC system designer
Table 2. Colder versus warmer water temperatures
coil #2 coil #3 coil #5 coil #6
entering-water temperature, °F 42 42 45 45
leaving-water temperature, °F 57 57 60 60
water ΔT, °F 15 15 15 15
tube diameter, in. 1/2 1/2 1/2 1/2
coil rows 6 6 8 8
fin density, fins/ft 159 124 153 113
fin design high capacity high efficiency high capacity high capacity
turbulators no yes no yes
water flow rate, gpm 40 40 40 40
water velocity, ft/s 2.8 2.8 2.8 2.8
water pressure drop, ft. H2O 4.7 11.1 5.8 15.1
air pressure drop, in. H2O 0.95 0.71 1.2 1.0
cost of coil base base + 8% base + 30% base + 35%

Table 3. 15°F versus 20°F versus 25°F ΔT


coil #3 coil #7 coil #8
entering-water temperature, °F 42 42 40
leaving-water temperature, °F 57 62 65
water ΔT, °F 15 20 25
tube diameter, in. 1/2 1/2 1/2
coil rows 6 8 8
fin density, fins/ft 124 114 135
fin design high efficiency high efficiency high capacity
turbulators yes yes yes
water flow rate, gpm 40 30 24
water velocity, ft/s 2.8 2.1 1.6
water pressure drop, ft. H2O 11.1 8.4 5.8
air pressure drop, in. H2O 0.71 0.88 0.92
cost of coil base base + 30% base + 35%

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 48–2 5
But notice that this is at a specific air drop is 0.70 in. H2O, so this coil does
ASHRAE 62.1 Limit on Air velocity (500 fpm), and this limit is comply with the Standard 62.1 limit on
Pressure Drop based on the air pressure drop when air pressure drop.
the coil is dry (not dehumidifying).
As mentioned, the Standard 90.1
committee stated in the foreword to For the example in this EN, the
entering-air conditions are 80°F dry
this addendum that their intent was to Conclusion
encourage the use of coils with more bulb and 67°F wet bulb, which equates
heat transfer surface to achieve this to a 60°F dew point. The air is being ASHRAE Standard 90.1-2016 now
higher ΔT. In some cases, this might cooled to 53°F, which means that water requires chilled-water coils to be
result in a higher air pressure drop. vapor will be condensing out of the air selected for a minimum 15°F ΔT, but
and onto the coil surface. Therefore, there are exceptions. This higher ΔT
ASHRAE Standard 62.1 includes a the air pressure drops listed are for a reduces the water flow rate (gpm),
requirement intended to ensure that wet coil, not dry. which allows installation of smaller
coils can be properly cleaned.10 valves, pipes, and pumps, and also
Deeper coils with more rows, and coils To ensure that a selected coil complies
reduces pumping energy.
with a higher density of fins, can be with this requirement, use the
more challenging to clean. manufacturer’s selection program to To achieve the 15°F minimum ΔT, some
re-run the performance of the coil, but designers may choose to select the
The Standard 62.1 committee change the entering-air conditions so coil with more fins. This will increase
addressed this issue by prescribing a that the coil will be dry, with no the air pressure drop. Other designers
limit on coil air pressure drop, as a condensation. In this example, by may choose to select the coil with
surrogate measure for clean-ability. In lowering the entering wet bulb from turbulators. This will increase the water
other words, coils with higher air 67°F to 55°F, the entering dew point pressure drop, but results in higher
pressure drops are, in general, more drops to 30°F—well below the coil water ΔTs at part-load conditions,
difficult to clean properly. surface temperature, so the coil will which leads to pump energy savings.
operate dry. And designing the system with a
5.11.2 Finned-Tube Coil Selection for
slightly lower entering-water
Cleaning. Individual finned-tube coils or The first column in Table 4 shows coil
temperature can allow the coils to be
multiple finned-tube coils in series #2 from the previous example. The air
selected with little or no impact on air
without intervening access spaces of at pressure drop is 0.95 in. H2O, but this
pressure drop and fan energy use.
least 18 in. shall be selected to result in is when the coil is wet. The second
no more than 0.75 in. H2O combined column shows the same coil, with the Finally, selecting cooling coils for a
dry-coil pressure drop at 500 fpm face entering wet bulb changed to 55°F, so higher ΔT has an impact on the design
velocity. the coil will operate dry. (Note that the and operation of the chiller plant.
airflow was also changed slightly, so These issues are addressed in other
This section of the standard requires that the air velocity is exactly 500 fpm.) Engineers Newsletters.8,11,12
that the air pressure drop of a finned- Under these dry conditions, at the
tube coil cannot exceed 0.75 in. H2O. prescribed air velocity, the air pressure By John Murphy, Trane. To subscribe or view
previous issues of the Engineers Newsletter visit
trane.com/EN. Send comments to
ENL@trane.com.
Table 4. Air pressure drop of a wet versus dry coil
coil #2 coil #2
(wet) (dry)
coil airflow, cfm 7000 6820
coil face velocity, fpm 513 500
entering dry-bulb temperature, °F 80 80
entering wet-bulb temperature, °F 67 55
entering dew point temperature, °F 60 30
leaving dry-bulb temperature, °F 53 53
tube diameter, in. 1/2 1/2
coil rows 6 6
fin density, fins/ft 159 159
fin design style high capacity high capacity
turbulators no no
air pressure drop, in. H2O 0.95 0.70

6 Trane Engineers Newsletter volume 48-2 providing insights for today’s HVAC system designer
References
[1] ANSI/ASHRAE/IES, Standard 90.1-2016,
Energy Standard for Buildings Except Low-
Rise Residential Buildings. Atlanta: ASHRAE.

[2] ASHRAE. Addendum BJ to Standard 90.1-


2013, First Public Review Draft. July 2015.

[3] Taylor, S. “Optimizing Design & Control of


Chilled Water Plants, Part 3: Pipe Sizing and
Optimizing ΔT," ASHRAE Journal. December
2011.

[4] Trane. Chilled-Water Coil Selection and


Optimization white paper. CLCH-PRB062A-
EN. 2016.

[5] ASHRAE. ASHRAE Handbook—HVAC


Systems and Equipment, Chapter 23 (Air-
Cooling Coils). 2016.

[6] Air-Conditioning, Heating, and Refrigeration


Institute (AHRI). AHRI Standard 410-2001:
Standard for Forced-Circulation Air-Cooling and
Air-Heating Coils. 2001.

[7] ASHRAE. ASHRAE GreenGuide: Design,


Construction, and Operation of Sustainable
Buildings. 5th edition. ASHRAE, 2018.

[8] Trane. Chiller System Design and Control


application manual. SYS-APM001-EN. 2011.

[9] Kelly, D.W. and T. Chan. “Optimizing Chilled-


Water Plants,” Heating/Piping/Air Conditioning.
January 1999.

[10]ANSI/ASHRAE Standard 62.1-2016: Ventilation


for Acceptable Indoor Air Quality. Atlanta:
ASHRAE. 2016.

[11]Schwedler, M. “Chilled-Water Systems Design


Issues—Learning from Past Mistakes”
Engineers Newsletter. ADM-APN051-EN.
Trane. 2014.

[12] Schwedler, M. “Variable-Primary-Flow


Systems Revisited” Engineers Newsletter.
ADM-APN005-EN. Trane. 2002.

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 48–2 7
Join your local Trane office for the 2019 Engineers Newsletter LIVE!
Mark your calendar!
Air and Waterside Economizing Reviews air- and waterside economizing
advantages, drawbacks and considerations when using one versus the other.
ASHRAE Standard 90.1 requirements and exceptions will also be discussed.

Design Considerations for Hydronic Heating Systems. Investigates various


methods of providing efficient hydronic heating, including the use of heat-recovery
chillers, heat pumps, and boiler systems.

Contact your local Trane office for dates and details.

Updates now available for


TRACE® 3D Plus!
Download the latest trial version of TRACE 3D Plus to experience system, control
and calculation performance improvements and many additional updates and fixes.
Now available on the Trane HVAC Design and Software Download Center.
Visit Trane.com/TRACE3DPlus.

TRACE® 3D Plus Online Training Now Available!


Both days of TRACE 3D Plus eLearning training are now available! Enjoy both Load
Design and Energy & Economics training in video format! This self-paced training
offers video modules, practice exercises, and an assessment portion to earn
professional development hours upon successful completion. Please contact
CDSAdmin@trane.com or call (608) 787-3936 for purchasing details.

Earn PDH credit - no charge and on-demand!


NEW Online Courses Available!
View all courses at www.trane.com/ContinuingEducation
Chilled-Water System Design Trends reviews recent advancements in
technology and trends due to these developments, system strategies that can take
advantage of the latest technology and when various system strategies should be
used.

Trane, the Circle Logo, and TRACE are trademarks of Trane in the United States and other countries. ASHRAE is a regis-
tered trademark of the American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc. Trane is a brand
of Ingersoll Rand, a world leader in creating comfortable, sustainable and efficient environments. Ingersoll Rand's family
of brands includes Club Car®, Ingersoll Rand®, Thermo King® and Trane®.

Trane, This newsletter is for informational purposes only and does not constitute legal advice.
A business of Ingersoll Rand Trane believes the facts and suggestions presented here to be accurate. However, final design and
application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
For more information, contact your local Trane
the material presented.
office or e-mail us at comfort@trane.com

8 Trane Engineers Newsletter volume 48–2 ADM-APN070-EN September 2019 (Supersedes ADM-APN070-EN June 2019)

Вам также может понравиться