Вы находитесь на странице: 1из 12

1/4/2020 Directional Over Current Relay [67]: Numerical Relays

 MENU

Directional Over Current Relay [67]:


 phanibabu  July 1, 2019  No Comments

In this post operation of Directional current relay along with its settings explained. The detailed explanation about Directional relay settings with Characteristic
angle, Maximum Torque angle and Polarisation voltages are given.

https://electengmaterials.com/directional-over-current-relay-67/ 1/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

Numerical Directional Over Current Relay

Operating Principle of Directional Over Current Relay:

Directional over current relays operate in either forward or reverse directions with over current protection.

https://electengmaterials.com/directional-over-current-relay-67/ 2/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

Ad closed by
Stop seeing this ad

Why this ad?

Introducing daily direct ight from Dhaka


to Delhi. Enjoy great fares, best deals &…

SpiceJet Book Now

If the directional relay set in Forward direction means if a fault occurs in forward zone then only relay operates. Conversely, if the relay set in Reverse direction
means if a fault occurs in reverse zone then only relay operates.

Conventionally denotes that forward direction refers to power flow away from the busbar (towards the protected zone), while reverse direction refers to power
flowing towards the busbar.

Directional Relay Characteristics:

The directional relays identify the zone of operation with the help of polarising voltage and characteristic angle.

https://electengmaterials.com/directional-over-current-relay-67/ 3/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

Directional Relay Operating Characteristics

Polarising Voltage:

https://electengmaterials.com/directional-over-current-relay-67/ 4/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

Directional relays needed reference voltage to identify the direction of currents. This is the voltage taken from Potential Transformers. The reference voltage is
called polarising voltage. The relay operates for the defined direction when the fault current is in the same direction and exceeds the over current setting value.

Relay Characteristic Angle: RCA

The characteristic angle is the phase angle by which reference or polarising voltage is adjusted such that the directional relay operates with maximum sensitivity.

Characteristic Angle is also called Directional angle as it decides the direction of operation of the relay.

Maximum Torque Angle: MTA

Maximum torque angle is the angle made by fault current with respect to its phase voltage. This is expected fault angle, and completely predictable. This angle is
different for phase faults and earth faults.

Center of Zone or Maximum Torque Line:

Center of zone is the line formed by Char Angle where relay exhibits maximum sensitivity. At this line relay current is in phase with the reference or polarising
voltage.

Zero Torque Line:

It is the boundary line which separates the plane into Operate and Inhibit regions.

Forward Zone:

Forward zone is+/- 85° either side of the Maximum Torque line or Centre of forward zone line.

Reverse Zone:


Reverse operate zone is the mirror image of the forward zone.

https://electengmaterials.com/directional-over-current-relay-67/ 5/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

Changes Occur during Fault condition:

Whenever, fault occurs on transmission line or busbars the voltage reduces proportional to the severity of fault and current increases larger than the normal
currents. The fault current is lagging in nature. Healthy phase magnitudes and angles not changed.

Directional Over Current Protection Settings:

It is to be noticed that the directional over current operation is different for phase and earth faults. The variation is in selection of polarising voltages.

1.Directional Over Current Protection for Phase Faults [67]:

Polarising Voltages:

The directional phase fault elements, work with a Quadrature connection to prevent loss of polarising quantity for phase faults. That is, each of the current elements
is directionalised by a voltage derived from the other two phases.

This connection introduces a 90° Phase Shift (Current leading Voltage) between reference and operating quantities.

Each phase current is compared with the voltage between other two phases. Like IL1 is compared with V23.

These Polarising voltages are defined internally in the relay itself. No need to set externally.

Maximum Torque Angle:

The Expected fault angle is called Maximum Torque angle in Electromechanical Relays.

(This angle is usually -30o for overhead lines and -45o for underground cables for phase faults.)


It is used to calculate Characteristic angle and identify center of zone. There is no setting for maximum torque angle in numerical relays.

https://electengmaterials.com/directional-over-current-relay-67/ 6/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

Characteristic Angle Setting:

The Relay Characteristic Angle RCA is given in relay Phase fault protection settings. The range is (-95 to +95 Degrees). The Char Angle setting must be specified
while configuring Directional over current relay.

Example:

For Example consider a phase fault occurs at angle of -30o. Fault current Lags the voltage by 30o.[This is the Maximum Torque Angle]

Characteristic Angle= 90 o [Angle of Quadrature] – Maximum Torque Angle

Characteristic Angle = 90-30=60 o.

Characteristic Angle Setting for Phase Faults


https://electengmaterials.com/directional-over-current-relay-67/ 7/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

Center of the forward zone:

It is the zone where the relay operates with maximum sensitivity.

Centre of forward zone = Vref Angle + Char Angle

= 0 o + 60 o

= 60 o

Minimum Voltage Setting:

When the measured polarising voltage falls below this setting level, no directional output is given and hence direction protection will be inhibited.

Minimum voltage setting prevents mal-operation of the relay when fuse failure/MCB tripped conditions.

Directional Over Current Protection for Earth Faults:

Each earth faults in relay computed as either Measured or Direct earth faults. The Selection of Polarising voltage is different for these two types of earth faults.

To understand the difference between Measured Earth Faults and Derived Earth Faults Read here.

2. Directional Current Protection for Measured Earth faults: [67G]

Polarising Voltages:

https://electengmaterials.com/directional-over-current-relay-67/ 8/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

The directional earth fault elements, to sense Earth faults Zero phase sequence polarising technique is used. Voltage polarisation is achieved for the earth-fault
elements (they are different from phase faults) by comparison of the appropriate current I0 with its equivalent voltage V0.

These voltages are available only during earth fault conditions. The voltage of faulty phase drops and other phases remain healthy.

These Polarising voltages are defined internally in the relay itself. No need to set externally.

Maximum Torque Angle:

The Expected fault angle is called Maximum Torque angle in Electromechanical Relays.

(This angle is usually varies from 0o to -90o depends on the type of Neutral Earthing employed.)

For Resisted Earth Systems = 0o

Earthing Transformer with Resistor= – 15o

Solidly Earthed Distribution System= -45o

Solidly Earthed Transmission System= -65o

Reactance Earthed Systems = -90o

It is used to calculate Characteristic angle and identify center of zone. There is no setting for maximum torque angle in numerical relays.

Characteristic Angle Setting:

The Relay Characteristic Angle RCA is given in relay Earth fault protection settings. The range is (-95 to +95 Degrees). The Char Angle setting must be specified
while configuring Directional OC relay. 

https://electengmaterials.com/directional-over-current-relay-67/ 9/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

Example:

For Example consider an earth fault occurs at angle of -15o on a resistance earthed system. Fault current Lags the voltage by 15o. [This is the Maximum Torque
Angle]

Characteristic Angle= 0 o– Maximum Torque Angle

Characteristic Angle = 0-15=-15 o.

Characteristic Angle Setting for Earth


Faults

Center of the forward zone:

It is the zone where the relay operates with maximum sensitivity.

Centre of forward zone = Vref Angle + Char Angle 

https://electengmaterials.com/directional-over-current-relay-67/ 10/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

= 0o-15o

= -15o

Minimum Voltage Setting:

This is the common setting for any type of faults. As mentioned earlier, when the measured polarising voltage falls below this level no directional output is given and
hence direction protection will be inhibited.

Minimum voltage setting prevents mal-operation of the relay when fuse failure/MCB tripped conditions.

3.Directional Current Protection for Derived Earth faults: [67G]

To sense Earth faults Zero phase sequence or Negative Phase sequence polarising technique is used.

Zero phase sequence polarising:

Zero sequence voltages are available whenever PT is a FIVE limb PT that can provide a zero sequence path or Open-delta Connected PT. This type of connection
provides zero sequence polarising voltages.

In this case Zero sequence voltages V0 and zero sequence currents I0 are used for polarization.

Negative phase sequence polarising:

When a two phase (phase to phase) PT or three limb PT is installed Zero Sequence voltages are not available. In this case Negative Phase sequence voltages V2
and Negative sequence currents I2 are used for polarization.

The selection of Relay characteristic angle, Maximum torque angle and Minimum voltage settings are same as Measured earth faults as explained above.

https://electengmaterials.com/directional-over-current-relay-67/ 11/12
1/4/2020 Directional Over Current Relay [67]: Numerical Relays

Let me know if you are interested, check the Application of Directional Over Current Relays in transmission lines explained by Mr. Chris in detail.

More from this site

Under voltage [27]/Over voltage [59] Relay:

Over current/Earth fault Relays [50/51]:

Differential Protection Relay [87]:

 Numerical Relays  Directional Over Current Relay, Directional Relay Settings, Maximum Torque Angle , Numerical Relay, Polarising Voltage, Relay
Characteristic Angle

https://electengmaterials.com/directional-over-current-relay-67/ 12/12

Вам также может понравиться