Вы находитесь на странице: 1из 9

324 © IWA Publishing 2016 Water Science & Technology | 74.

2 | 2016

Characterizing shallow secondary clarifier performance


where conventional flux theory over-estimates allowable
solids loading rate
Glen T. Daigger, John S. Siczka, Thomas F. Smith, David A. Frank
and J. A. McCorquodale

ABSTRACT
Glen T. Daigger (corresponding author)
The performance characteristics of relatively shallow (3.3 and 3.7 m sidewater depth in 30.5 m
Department of Civil and Environmental
diameter) activated sludge secondary clarifiers were extensively evaluated during a 2-year testing Engineering,
University of Michigan,
program at the City of Akron Water Reclamation Facility (WRF), Ohio, USA. Testing included hydraulic Ann Arbor, MI,
USA
and solids loading stress tests, and measurement of sludge characteristics (zone settling velocity E-mail: glen.daigger@ch2m.com
(ZSV), dispersed and flocculated total suspended solids), and the results were used to calibrate John S. Siczka
computational fluid dynamic (CFD) models of the various clarifiers tested. The results demonstrated CH2M,
Milwaukee, WI,
that good performance could be sustained at surface overflow rates in excess of 3 m/h, as long as USA

the clarifier influent mixed liquor suspended solids (MLSS) concentration was controlled to below Thomas F. Smith
City of Akron, OH,
critical values. The limiting solids loading rate (SLR) was significantly lower than the value predicted USA

by conventional solids flux analysis based on the measured ZSV/MLSS relationship. CFD analysis David A. Frank
ARCADIS,
suggested that this resulted because mixed liquor entering the clarifier was being directed into the Akron, OH,
settled sludge blanket, diluting it and also creating a ‘thin’ concentration sludge blanket that overlays USA

J. A. McCorquodale
the thicker concentration sludge blanket typically expected. These results indicate the need to
University of New Orleans,
determine the allowable SLR for shallow clarifiers using approaches other than traditional solids flux New Orleans, LA,
USA
analysis. A combination of actual testing and CFD analyses are demonstrated here to be effective in
doing so.
Key words | activated sludge, clarifiers, solids flux theory, step feed, wet weather

INTRODUCTION

Secondary clarifier design practices vary widely, as illus- when the clarifier solids loading rate (SLR) is less than the
trated by Ekama et al. (). Although an older maximum predicted based on the measured or predicted
publication, this consensus document still serves as an inter- zone settling velocity (ZSV)/suspended solids concentration
national reference and reflects the great diversity of relationship for the sludge in question, no substantial sludge
secondary clarifier design practice. North American practice blanket is predicted; and (2) when the SLR exceeds the
has been heavily influenced by experience with relatively maximum predicted value, a sludge blanket at a uniform
deep circular secondary clarifiers (Parker ; Parker & concentration corresponding to the limiting solids flux pre-
Stenquist ; Parker et al. ; Ekama et al. ), leading dicted by solids flux theory develops. Use of relatively
to use of sidewater depths in the 5–6 m or more range for cir- deep circular secondary clarifiers, as described above,
cular secondary clarifiers of around 30 m diameter or coupled with design based on state point analysis, has
greater (WEF , ). The performance of such clari- become the norm in North America (WEF , ).
fiers has been demonstrated to conform to the predictions While the use of deep secondary clarifiers, as defined
of solids flux theory, as presented by Keinath (Keinath above, is common practice in North America for new clari-
et al. ; Keinath ), state point analysis where two sec- fiers, numerous clarifiers constructed in the 1970s and
ondary clarifier operating states are predicted to occur: (1) earlier have side water depths in the 3–4 m range and are

doi: 10.2166/wst.2016.177
325 G. T. Daigger et al. | Flux theory inadequate for shallow secondary clarifiers Water Science & Technology | 74.2 | 2016

considered to have limited treatment capacity. It has been modifications would significantly reduce, or eliminate, the
conventional practice to simply de-rate the hydraulic and need to construct the parallel treatment facility and could
solids loading capacity of such clarifiers based on field save significant capital cost. A consent order negotiated
measurements of capacity (typically via actual stress testing, with USEPA allowed one of the six activated sludge trains
Daigger & Buttz ; Ontario MOE ; Wahlberg ) present at the plant to be modified to provide for a 2-year
and experience. Experience by the authors suggested, how- testing program to optimize the system, with subsequent
ever, that such hydraulic de-rating might not be required potential extension to the other five trains. This testing pro-
in all cases if the hydrodynamic flow pattern within the clari- gram included minor modifications to and extensive testing
fier could be better understood. Considerable experience of the existing secondary clarifiers to maximize hydraulic
exists with the use of dye and solids profile testing to charac- treatment capacity. This testing program also provided a
terize the flow pattern in clarifiers and to modify feed wells, unique opportunity to test the hypothesis stated above.
add peripheral baffles, and make other modest modifi-
cations to increase capacity. Moreover, use of two- and
three-dimensional computational fluid dynamic (CFD) MATERIALS AND METHODS
models, of the type illustrated by McCorquodale et al.
() and Xanthos et al. (), to further assist with flow Treatment facilities
pattern visualization and to evaluate potential modifications
has proven useful in practice. It was hypothesized that de- The existing activated sludge system consists of six parallel
rating the hydraulic capacity of secondary clarifiers might trains with quite similar configuration. Each consists of a
not be necessary, even if the allowable SLR is less than four-pass bioreactor, each pass with a length-to-width ratio
that predicted by state point analysis. of 11.4:1, followed by three 30.5 m diameter secondary clari-
The need for the City of Akron, Ohio, USA to modify its fiers. Unit 6 differs in that it was originally configured for
Water Reclamation Facility (WRF) to increase its peak wet step feed operation (since removed), and all three secondary
weather treatment capacity provided the opportunity to clarifiers have a sidewall depth of 3.7 m. In contrast, two of
upgrade its shallow activated sludge secondary clarifiers the three clarifiers in the other trains have a sidewall depth
and characterize their performance. The City owns and of 3.3 m, with the third having a sidewall depth of 3.7 m. The
operates a WRF with a firm preliminary treatment capacity Unit 6 aeration basin was modified to provide step-feed
of 795,000 m3/day, firm primary treatment capacity of capabilities, while the Units 5 and 6 secondary clarifiers
568,000 m3/day, and firm biological treatment capacity of (final settling tanks (FSTs)) were modified with density cur-
416,000 m3/day. Combined sewers form part of the City’s rent baffles, larger and deeper center wells, and energy
wastewater collection system. As one component of an over- dissipating inlets (EDIs) in various combinations to investi-
all combined sewer overflow abatement program, the City is gate the effectiveness of the improvements considered. All
being required to expand the peak wet weather secondary of the subject clarifiers have full radius (tow-bro type)
treatment capacity of its WRF to 1,060,000 m3/day. Expan- sludge collection. The Unit 5 FSTs were modified because
sion will be accomplished by upgrading its activated the existing Units 1–4 FSTs have the same configuration
sludge system and constructing a parallel process of suffi- (side depth and weir elevations) as the Unit 5 FSTs. Thus,
cient capacity to provide the total required peak wet Unit 5 FST test results would be directly applicable to
weather biological treatment capacity, if approved by the Units 1–4. Construction of the modifications to the Units 5
United States Environmental Protection Agency (USEPA) and 6 activated sludge trains was completed in August
and as required in a proposed consent decree. The existing 2013. Table 1 lists the pertinent design data for all six modi-
plant includes eighteen 30.5 m diameter circular secondary fied clarifiers.
clarifiers with side water depths ranging from 3.3 to 3.7 m,
which were considered to significantly limit secondary treat- Mixed liquor characterization
ment capacity. Preliminary process analysis suggested,
however, that peak wet weather capacity could be signifi- ZSV measurements were conducted in a 1 m tall, 10 cm
cantly increased through modifications to the bioreactors diameter clear PVC column equipped with a 1 revolution
to provide step feed capabilities, which would allow inde- per minute (rpm) stirrer. The height of the sludge/water
pendent control of the clarifier SLR, and some physical interface was measured with time, and the slope of the
modifications to the clarifiers (CHM HILL ). Such linear portion was determined by linear regression to
326 G. T. Daigger et al. | Flux theory inadequate for shallow secondary clarifiers Water Science & Technology | 74.2 | 2016

Table 1 | Units 5 and 6 FST characteristics to the subject clarifier and then collecting samples in a five-
by-five mesh using a sampling apparatus which allowed
Center well Side depth
FST Peripheral baffle EDI depth (m) (m [ft])
samples to be taken at five defined depths (Ontario Ministry
of the Environment & Energy ; Daigger & Buttz ).
FST-5A X 1.80a 3.3
The sampling apparatus was moved quickly from one
FST-5B X X 1.80b 3.3
sampling station to the next along the clarifier bridge; the
FST-5C X 2.21 3.7
time from the first to the last sample was generally less than
FST-6A X X 2.21 3.7 5 min. Samples were analyzed for dye concentration using a
FST-6B X X 2.21 3.7 Turner Designs 10-AU Field Fluorometer, and select samples
FST-6C X X 2.21 3.7 were analyzed for TSS. Water quality and other analyses were
a
Later increased to 2.11 m. conducted in accordance with Water Environment Federa-
b
Later increased to 2.26 m. tion (), either in the field (e.g. sludge settled volume) or
the City of Akron laboratory. Further details on the methods
determine the ZSV. Various mixtures of return activated used are provided elsewhere (Siczka et al. ; CHM ;
sludge (RAS) and secondary effluent were prepared to pro- Siczka et al. ).
duce a range of initial mixed liquor suspended solids Extended high surface overflow rate (SOR) testing was
(MLSS) concentrations which were then added to the also conducted by increasing the hydraulic loading rate to
column for ZSV measurement. The results were fitted to the clarifier to maximum achievable values (limited only
the Vesilind equation (Vesilind ) via linear regression by hydraulic flow capacity) for a period of 6–8 h to deter-
to characterize the settling characteristics of the subject mine whether acceptable performance could be sustained
sludge. Dispersed suspended solids (DSS) were determined over a longer period than during the previous stress tests.
as the total suspended solids (TSS) concentration of the One Unit 6 clarifier and each of the Unit 5 clarifiers were
supernatant of a sample placed in a 1,000 mL graduated tested four times at different times of the year (August
cylinder after 30 min of quiescent settling (Wahlberg ). 2014, November 2014, January 2015, and April 2015) to
Flocculated suspended solids (FSS) were conducted by assess whether seasonal variations might occur.
placing samples in six 2,000 mL beakers in a conventional
jar test apparatus, stirring at 50 rpm (equivalent to a G
value of 30 sec 1) for periods of 0, 2, 5, 10, 15, and 20 min, CFD modeling
allowing the samples to settle for 30 min, and then taking
supernatant samples for TSS analysis (Wahlberg ). CFD modeling was conducted using the software developed
by McCorquodale et al. (). The model solves the non-
Clarifier testing hydrostatic momentum and continuity equations that are
coupled using a density state equation that includes the
Stress tests were conducted by sequentially altering the load- effects of temperature and suspended solids. The model is
ing conditions on the clarifiers while collecting effluent TSS quasi-three dimensional, i.e. it solves the radial and vertical
samples sequentially, and then analyzing the data to develop motion completely but the solution of the tangential velocity
performance versus loading curves (Ontario Ministry of the assumes axisymmetric conditions for all variables in the tan-
Environment & Energy ; Daigger & Buttz ; Wahl- gential direction. The model solves solids transport for up to
berg ). The clarifier influent MLSS concentration was five classes of discrete settling particles, as well as zone
adjusted by the step feed operation mode selected (for Unit settling and compression. The Parker flocculation equations
6), and by transferring mixed liquor into and out of the bio- (Parker et al. ) are included to transfer mass from one
reactor to and from a parallel treatment unit (for Unit 5). class to another. The model includes laminar and turbulent
Influent flow was adjusted by taking parallel clarifiers out of flow, with Newtonian flow in the inlet and clarified zone
service and adjusting the flow to the subject treatment train. and non-Newtonian flow in the sludge blanket. Generic
Each loading condition was sustained for about 2 h on aver- tank modifications such as baffles and EDIs are available
age (the clarifier calculated hydraulic residence time was in the software. The model was calibrated and validated
about 1 h at the maximum hydraulic loading rates applied). using operational and stress test data. The stress tests were
Clarifier flow pattern dye tests were conducted during these accompanied by Vesilind settling tests, used to determine
stress tests by injecting Rhodamine WT dye into the influent the zone settling parameters, as well as DSS and FSS tests.
327 G. T. Daigger et al. | Flux theory inadequate for shallow secondary clarifiers Water Science & Technology | 74.2 | 2016

The calibrated model was applied to investigate several the maximum hydraulic flow that could be achieved, lim-
modifications of the settling tanks. ited only by the hydraulic flow capacity of the treatment
trains (no more flow could be forced to the units). Clarifier
influent MLSS concentrations were relatively low, by
RESULTS AND DISCUSSION design, at around 1,000 mg/L. The result was a sufficiently
low SLR so that thickening failure did not occur (sludge
Initial testing of modified clarifiers blankets did not rise to the effluent weirs). Sludge blanket
depths were generally low throughout, in contrast to the
With modifications to Units 5 and 6 completed in August further results to be presented below. The RAS flow rate
2013, a week-long series of clarifier tests were performed was generally maintained at 21% for clarifier FST-6A and
on the Units 5 and 6 secondary clarifiers in September 14% for FSTs-5A, 5B, and 5C, which is consistent with his-
2013. The testing was conducted to characterize their per- torical plant operation. These results indicated that further
formance, to define the capacity of the modified clarifiers increases in SOR could be applied, while achieving accepta-
in Units 5 and 6, and to provide the data to further calibrate ble performance, if hydraulic bottlenecks were resolved.
the clarifier CFD and overall process models prepared CFD modeling was used to characterize and further
during the preliminary design. The calibrated CFD models assess clarifier performance and capacity, and to investigate
were further used to identify additional improvements to whether some further minor modifications to the clarifiers
the clarifiers and secondary treatment system to potentially might be beneficial (Siczka et al. ; CHM ; Siczka
further increase wet weather treatment capacity. et al. ). The CFD model was first calibrated to the
Figure 1 presents the stress test results from this testing stress test data using the measured ZSV/MLSS relationship
period. All three clarifiers in Unit 5 were tested because of (Figure 2), and considering both effluent quality and the
the differences between them, while only clarifier FST-6A measured FSS and DSS data. The sludge blanket depth
was tested, as all three clarifiers in Unit 6 are of the same measured during the stress test, and the dye and TSS con-
configuration. The curves included in the figure are simply centration profiles collected during the dye testing, were
polynomial fits to the data intended to assist visualization also considered as the model was calibrated. Table 2 sum-
of the trends. The results demonstrate that, with the excep- marizes the model calibration for the four clarifiers. The
tion of clarifier FST-5C, the clarifiers were able to sustain parameters represent setting characteristics for the various
good performance up to a SOR in excess of 3 m/h. The solids fractions considered in the model, and hydraulic cali-
maximum SOR tested for each clarifier generally represents bration. The parameters for zone settling are the Vesilind

Figure 1 | September 2013 secondary clarifier stress test results.


328 G. T. Daigger et al. | Flux theory inadequate for shallow secondary clarifiers Water Science & Technology | 74.2 | 2016

parameters determined by column testing, as described


above. Note that the compression parameters are the same
as the zone setting parameters, reflecting that compression
was relatively unimportant in these simulations as sus-
pended solid concentration throughout the clarifier, and in
the RAS, were generally within the zone settling range. All
data collected were used for calibration, with good corre-
spondence between model predictions and observations
achieved, and overall performance was evaluated by com-
paring predicted and measured effluent TSS
concentrations. As illustrated in Figure 3, which provides
an example calibration (this one for clarifier FST-5A), the
comparison between predicted and actual effluent TSS con-
centrations was generally quite good.
Figure 4 presents CFD modeling results for FST-6A at
Figure 2 | ZSV versus suspended solids concentration from column settling test the highest hydraulic loading rate tested in September
measurements for Akron ML samples collected September 2013. 2013. This clarifier is shown as it achieved the best perform-
ance at the highest SOR (Figure 1), and the flow pattern
exhibited in this clarifier illustrates why, as model results
Table 2 | CFD model parameters
suggest that the energy of influent flow is well dissipated
Parameter FST-5A FST-5B FTS-5C FST-6A and a distinct sludge blanket is formed. Note, however,
V0 (m/h) a
12.51 12.51 12.51 12.44 that influent flow is directed into the settled sludge blanket
in the inlet zone of the clarifier, which would appear to
Ka 0.276 0.276 0.276 0.268
a dilute it. In contrast, Figure 5 shows results from a similar
Vc (m/h) 12.51 12.51 12.51 12.44
high SOR for FST-5A, indicating opportunities for improve-
Kac 0.276 0.276 0.276 0.268
ments. This clarifier was not equipped with an EDI, as
V1 (m/h) 12.51 12.51 12.5 12.44
indicated in Table 1, resulting in less dissipation of the kin-
f1 0.523 0.523 0.380 0.52
etic energy of the influent flow and more flow directed into
V2 (m/h) 8.1 8.1 6.1 8.9 the sludge blanket. Further CFD analysis was conducted on
f2 0.472 0.472 0.642 0.472 the Unit 5 clarifiers, and it was determined that performance
V3 (m/h) 1 1 0.7 0.7 could be further improved by deepening the center well of
f3 0.005 0.005 0.008 0.008 clarifier FST-5A from 1.80 to 2.11 m and of clarifier FST-
Ev factor 0.20 0.20 0.35 0.5 5B from 1.80 to 2.26 m (Siczka et al. ; CHM ;
a
Siczka et al. ). These modifications were subsequently
Based on results from ZSV measurements in test columns.
implemented and completed by July 2014.

Figure 3 | Comparison of the time course of observed and modeled effluent suspended solids concentration for FST-5A for September 2013 stress test.
329 G. T. Daigger et al. | Flux theory inadequate for shallow secondary clarifiers Water Science & Technology | 74.2 | 2016

Figure 4 | CFD modeling result for Clarifier FST-6A simulating conditions at the highest SOR tested during the September 2013 stress test.

Further clarifier testing the value in the September 2013 testing. As a consequence,
a substantial sludge blanket was observed in the clarifier
Stress and dye testing of the further modified clarifiers FST-5A during the July 2014 stress test. The sludge blanket was
and FST-5B were conducted in July 2014 and generally indi- stable, and effluent quality was excellent as the actual effluent
cated modest improvements in performance, as predicted TSS at this overflow rate (3 m/h) ranged from 7 to 16 mg/L.
(CHM ; Siczka et al. ). However, important differ- The sludge blanket height of 1.8 m predicted by the CFD
ences in the distribution of suspended solids through the model agreed well with the measured value. Only modest
clarifier were observed in the dye testing, as compared to changes in the model parameters, reflecting small changes
those observed in 2013. Importantly, the observed differences in sludge settling characteristics, were required to calibrate
were consistent with the CFD analyses. Consider Figure 6, the model to these testing conditions, as the September 2013
where CFD modeling results are presented for clarifier FST- model essentially captured the observed behavior, indicating
5A at the conclusion (highest SOR) of the July 2014 stress the robustness of the models used. The SLR for this operating
test, in contrast to the September 2013 results (Figure 5). condition was 7.5 kg/(m2-h), which is well less than the limit-
The clarifier influent MLSS concentrations in the July 2014 ing SLR predicted based on the measured sludge zone settling
testing averaged 2,150 mg/L, which was more than double characteristics.

Figure 5 | CFD modeling result for Clarifier FST-5A simulating conditions at the highest SOR tested during the September 2013 stress tests.

Figure 6 | CFD modeling result for Clarifier FST-5A simulating conditions at the highest SOR tested during the July 2014 stress tests.
330 G. T. Daigger et al. | Flux theory inadequate for shallow secondary clarifiers Water Science & Technology | 74.2 | 2016

The performance and operational characteristics of the by manipulating the step feed pattern (feeding RAS rather
four clarifiers tested during the extended high SOR testing than wastewater into the downstream passes: a capability
conducted between August 2014 and April 2015 were con- that was uniquely available on this unit). The limiting con-
sistent with the behavior observed during the July 2014 dition occurred when the SLR was increased to between
stress testing. Sludge blankets often developed, although 8.2 and 9 kg/(m2-h) and with an RAS concentration of
the SLRs applied were significantly less than the limiting 12,000 go 15,000 mg/L (more precise values were not poss-
values predicted, based on the measured zone settling ible as this was a highly dynamic situation). This limiting
characteristics. The blanket would consist of a thicker operating condition is plotted on Figure 8, which is the
layer at the bottom of the clarifier, with a more diffuse flux curve for the system developed, based on the zone
layer on top of it (easily observed in the sludge judge used settling characteristics for the sludge at that time. A
to measure the sludge blanket and consistent with the second curve, based on a V0 value which is 80 percent of
CFD modeling results, see Figures 4–6 as examples). Good the measured value, is also presented for comparison.
performance was consistently observed, as long as the North American experience indicates that, for secondary
sludge blanket stabilized and remained below the effluent clarifiers with side water depths in the range of 5–6 m, the
weirs during the progression of the test, but deteriorated if limiting condition would correspond relatively well with
the ‘lighter and fluffier’ blanket approached the effluent those predicted, based on the measured zone settling charac-
weir. Figure 7 presents results from all of the extended teristics (WEF , ).
high SOR tests for all four clarifiers and demonstrates that Returning to the original hypothesis, results from
performance at these elevated hydraulic loading rates was extensive testing at the Akron WRF generally confirms
good, until the sludge blanket approached the effluent weirs. that good performance can be achieved in relatively shal-
A question that arises from these observations is what low secondary clarifiers (less than 4 m side water depth
the maximum allowable SLR might be. This was determined for 30.5 m diameter circular clarifiers), even at relatively
for Unit 6 by increasing the hydraulic loading to clarifier high SORs, as long as the SLR is controlled. These results
FST-6A to the maximum value tested (3.2 m/h) and then demonstrate that the limiting SLR can be significantly
progressively increasing the influent MLSS concentration less than that predicted, simply based on the measured
until a solids loading failure occurred, as evidenced by a sludge zone settling characteristics. Further insight into
rising sludge blanket that approached the effluent weirs. the phenomena creating this result is gained by considering
The clarifier influent MLSS concentration was increased the flow pattern in these clarifiers as determined by

Figure 7 | Effluent TSS versus measured sludge blanket depth for extended high SOR tests.
331 G. T. Daigger et al. | Flux theory inadequate for shallow secondary clarifiers Water Science & Technology | 74.2 | 2016

are also capable of predicting sludge blankets of this type


(Torfs et al. ; Diehl et al.  for recent examples), but
they are not as useful for evaluating clarifier modifications
to improve performance. Relative to the conditions encoun-
tered in this research, it is also important to point out that
the extensive mixing of influent mixed liquor with settled
solids resulted in suspended solids concentrations through-
out the clarifier which remained in the zone settling range
and generally outside of the compression range for the
sludges encountered.

CONCLUSIONS

In summary, an extended series of field-scale tests were con-


ducted over a nearly 2-year period on full-scale secondary
Figure 8 | Operating conditions producing a solids limiting condition for clarifier FST-6A
clarifiers at the Akron WRF. Good performance was
plotted on flux curve based on long-term measurements of Akron sludge achieved at quite high SORs (2.5–3.2 m/h) in these shallow
settling characteristics.
(3.3–3.7 m sidewater depth) secondary clarifiers, as long as
the clarifier sludge blanket was controlled to remain below
clarifier dye flow pattern testing and as further visualized the effluent weirs. A substantial sludge blanket often devel-
via CFD modeling. Consider the results presented in Figures 4– oped in the clarifiers, even though the SLR was significantly
6, and as supplemented by those presented in Figure 9, lower than the limiting value calculated based on the
where a CFD model for clarifier FST-6A loaded at hydraulic measured sludge zone settling characteristics. CFD model-
and solids loadings corresponding to the limiting values ing was used to characterize the hydrodynamic behavior
characterized in Figure 8 is presented. At the relatively of the clarifiers and suggests that the observed performance
high hydraulic loading rates (2.5–3 m/h) applied to these occurs because influent mixed liquor mixes with the settled
relatively shallow clarifiers (3.3–3.7 m sidewall depth), the sludge in these relatively highly loaded and shallow clari-
influent mixed liquor is observed to mix with the settled fiers, partially resuspending the settled solids and creating
sludge layer, resuspending these solids and creating the a more diffuse sludge layer which overlays the thicker
more diffuse, overlying sludge blanket. The CFD results sludge blanket. CFD model predictions are consistent
are consistent with the results of the dye tests conducted with the results from conventional dye testing and obser-
and observations of sludge blanket behavior during all clari- vations during actual clarifier testing. The results are
fier testing. It should be noted that one-dimensional models consistent with the hypothesis that relatively high hydraulic

Figure 9 | CFD model results for clarifier FST-6A loaded to the hydraulic and solids loading limits corresponding to the limiting condition illustrated in Figure 8.
332 G. T. Daigger et al. | Flux theory inadequate for shallow secondary clarifiers Water Science & Technology | 74.2 | 2016

loading rates can be achieved in clarifiers which are rela- Environment Association of Ontario, and Environment
tively shallow compared to current North American Canada Great Lakes 2000 Cleanup Fund, Ontario, Canada.
Parker, D. S.  Assessment of secondary clarification design
practice, as long as the SLR is controlled to prevent
concepts. Journal of the Water Pollution Control Federation
sludge blankets from rising to the level of the effluent weir. 55 (1), 349–359.
Parker, D. S. & Stenquist, D. J.  Flocculation-clarifier
performance. Journal of the Water Pollution Control
ACKNOWLEDGEMENTS Federation 58 (3), 214–219.
Parker, D. S., Kaufman, W. J. & Jenkins, D.  Physical
The authors gratefully acknowledge the assistance of the conditioning of activated sludge floc. Journal of the Water
personnel of the Akron Water Reclamation Facility. The Pollution Control Federation 43 (9), 1817–1833.
Parker, D., Butler, R., Finger, R., Fisher, R., Fox, W., Kido, W.,
research presented here would not have been possible with-
Merrill, S., Newman, G., Pope, R., Slapper, J. & Wahlberg, E.
out their invaluable assistance. In particular, the assistance  Design and operations experience with flocculator-
of the following individuals was especially valuable: Tom clarifiers in large plants. Water Science and Technology 33
Sanderson of the City of Akron, Kathy Richards of the (12), 163–170.
City of Akron, the City of Akron Water Reclamation Facility Siczka, J. S., Smith, T. F., Hanna, E. M., Daigger, G. T., Cooper,
J. P. & Frank, D. A.  Using existing facility to maximize
Operations Staff, and the City of Akron Water Reclamation
the wet weather treatment capacity of the Akron, OH water
Facility Laboratory Staff. The assistance of Jim Cooper of
reclamation facility: optimizing existing secondary clarifiers.
ARCADIS with conducting the column settling tests and In: Proceedings of the 87th Annual Water Environment
the stress and dye tests is also gratefully acknowledged. Federation Technical Exhibition and Conference (WEFTEC),
WEF, New Orleans, LA, USA.
Siczka, J. S., Smith, T. F., Hanna, E. M., Daigger, G. T., Cooper,
REFERENCES J. P. & Frank, D. A.  Using existing facility to maximize
the wet weather treatment capacity of the Akron, OH water
CH2M  Demonstration Testing Evaluation Report for WPCS reclamation facility: sludge settling theory and state point
Step Feed Phase 1 Improvements. Akron Water Reclamation analysis Do Not characterize ultimate capacity of shallow
Facility, Prepared for the City of Akron Department of Public clarifiers. In: Proceedings of the 88th Annual Water
Services, Akron, OH, USA. Environment Federation Technical Exhibition and
CH2M HILL  City of Akron WPCS Step Feed Phase 1 Basis of Conference (WEFTEC), WEF, Chicago, IL, USA.
Design Report. Prepared for the City of Akron Department of Torfs, E., Maere, T., Bürger, R., Diehl, S. & Nopens, I.  Impact on
Public Service, Akron, OH, USA. sludge inventory and control strategies using the benchmark
Daigger, G. T. & Buttz, J. A.  Upgrading Wastewater Treatment simulation model No. 1 with the Bürger-Diehl Settler Model.
Plants. 2nd edn. Technomic Publishers, Lancaster, PA, USA. Water Science and Technology 71 (10), 1524–1535.
Diehl, S., Zambrano, J. & Carlsson, B.,  Steady-state analysis Vesilind, P. A.  Discussion of ‘evaluation of activated sludge
of activated sludge processes with a settler model including thickening theories’ by R. I. Dick and B. B. Ewing. Journal of
sludge compression. Water Research 88C, 104–116. Sanitary Engineering Division, American Society of Civil
Ekama, G. A., Barnard, J. L., Gunthert, F. W., Krebs, P., Engineering 94 (SA1), 185.
McCorquodale, J. A., Parker, D. S. & Wahlberg, E. J.  Wahlberg, E. J.  WERF/CRTC Protocols for Evaluating
Secondary Settling Tanks. IWA Publishing, London. Secondary Clarifier Performance, 00-CTS-1. Water
Keinath, T. M.  Operational dynamics of secondary clarifiers. Environment Research Foundation, Alexandria, VA, USA.
Journal of the Water Pollution Control Federation 57 (7), Water Environment Federation  Clarifier Design, Manual of
770–776. Practice No. FD-8. 2nd edn. Water Environment Federation,
Keinath, T. M., Rychman, M. D., Dana, C. H. & Hofer, D. A.  Alexandria, VA, USA.
Activated sludge – unified system design and operation. Water Environment Federation  Design of Municipal
Journal of the Environmental Engineering Division, ASCE Wastewater Treatment Plants, Manual of Practice No. 8.
103 (EE5, 10), 829–849. Water Environment Federation, Alexandria, VA, USA.
McCorquodale, A., Griborio, A. & Georgiou, I.  A public Water Environment Federation  Standard Methods for the
domain settling tank model. In: Proceedings of the 78th Examination of Water & Wastewater. Water Environment
Annual Water Environment Federation Technical Exhibition Federation, Alexandria, VA, USA.
and Conference (WEFTEC); WEFTEC 2005, Water Xanthos, S., Gong, M., Ramalingam, K., Fillos, J., Deur, A.,
Environment Federation (WEF), Alexandria, VA, USA. Beckmann, K. & McCorquodale, J. A.  Performance
Ontario Ministry of Environment and Energy  Guidance assessment of secondary settling tanks using CFD modeling.
Manual for Sewage Treatment Plant Process Audits. Water Water Resources Management 25, 1169–1182.

First received 25 January 2016; accepted in revised form 30 March 2016. Available online 20 April 2016

Вам также может понравиться