ProfiTrace detailed network

report

Pow ered by:

1 General

Location: ER 40
Network name: C2 - 3400 - CP - 009 - PB02
Project details summary: RED PROFIBUS 500 Kbps
MAESTRO PROFITRACE

(This text is applied by the end-customer but may not be complete. Please ref er to
section 'Project details' f or the complete text)

2 Used tools

ProfiCore serial number: 0825405871


ProfiTrace version: V2.9.2

3 Network properties

Transmission speed: 500 kbps


Number of Masters: 1
Number of slaves: 4
Cycle time: Min: 0.00 ms, Avg: 0.00 ms, Max: 0.00 ms

4 Conclusion

No deviations found

Deviations found

5 Remarks summary

None

(The text abov e is not def ined by the end-customer)

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 1 / 16
ProfiTrace detailed network
report

6 Tested subjects:

6.1 Slaves that have been lost at least one time: None

6.2 Slaves that generated diagnostics while in data exchange: None

6.3 Devices that have caused illegal responses: None

6.4 Device found on reserved address 126: None

6.5 Slaves that caused retries: None

6.6 Slaves that caused syncs: 0, 1, 2, 3, 4, 5, 6, 7, 8,


Some types of ABB DCS systems continuously send Sync messages. This does 9, 10, 11, 12, 13, 14,
not influence the b us communication. These Syncs can b e ignored. 15, 16, 17, 18, 19, 20,
21, 22, 23, 24, 25, 26,
27, 28, 29, 30, 31, 32,
33, 34, 35, 36, 37, 38,
39, 40, 41, 42, 43, 44,
45, 46, 47, 48, 49, 50,
51, 52, 53, 54, 55, 56,
57, 58, 59, 60, 61, 62,
63, 64, 65, 66, 67, 68,
69, 70, 71, 72, 73, 74,
75, 76, 77, 78, 79, 80,
81, 82, 83, 84, 85, 86,
87, 88, 89, 90, 91, 92,
93, 94, 95, 96, 97, 98,
99, 100, 101, 102,
103, 104, 105, 106,
107, 108, 109, 110,
111, 112, 113, 114,
115, 116, 117, 118,
119, 120, 121, 122,
123, 124, 125, 126

6.7 Parameters have been sent to the following slaves: None

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 2 / 16
ProfiTrace detailed network
report

7 Project details

RED PROFIBUS 500 Kbps


MAESTRO PROFITRACE

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 3 / 16
ProfiTrace detailed network
report

8 Live list

0 1 2 3 4 5 6 7 8 9
C441 369 MOTOR C441 369 MOTOR
0 0 1 PROFIBUS MANAGEMENT PROFIBUS MANAGEMENT 6 7 8 9
ADAPTER RELAY-DP ADAPTER RELAY-DP
10 10 11 12 13 14 15 16 17 18 19

20 20 21 22 23 24 25 26 27 28 29

30 30 31 32 33 34 35 36 37 38 39

40 40 41 42 43 44 45 46 47 48 49

50 50 51 52 53 54 55 56 57 58 59

60 60 61 62 63 64 65 66 67 68 69

70 70 71 72 73 74 75 76 77 78 79

80 80 81 82 83 84 85 86 87 88 89

90 90 91 92 93 94 95 96 97 98 99

100 100 101 102 103 104 105 106 107 108 109

110 110 111 112 113 114 115 116 117 118 119

120 120 121 122 123 124 125 126

Legend:

No activity 1 No activity
Device is in data exchange 2 Master station
Device is lost 3 Slave station
Device has a parameter error
Device has a configuration error

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 4 / 16
ProfiTrace detailed network
report

9 Address list

Address IdentNo Manufacturer Model name GSD name


1 - - Master -
2 0C98 Eaton Corp C441 PROFIBUS ADAPTER 019D0C98.GSD
3 090C GE POWER MANAGEMENT 369 MOTOR MANAGEMENT RELAY-DP 369_090C.GSE
4 0C98 Eaton Corp C441 PROFIBUS ADAPTER 019D0C98.GSD
5 090C GE POWER MANAGEMENT 369 MOTOR MANAGEMENT RELAY-DP 369_090C.GSE

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 5 / 16
ProfiTrace detailed network
report

10 Bar graph

10.1 Segment (Segment 1)


Segment type: <not set>

10.1.1 Measurement point (Measuring point 1)


AB Diff voltage
Segment / Measuring point: Segment 1 / Measuring point 1 (1/1):
9.0V
8.0V
7.0V 6.68
6.10 6.07
6.0V 5.11 5.07
5.0V
4.0V
3.0V
2.0V
1.0V
0.0V
1 2 3 4 5

AB Diff stable voltage


Segment / Measuring point: Segment 1 / Measuring point 1 (1/1):
9.0V
8.0V
7.0V 6.48
5.83 5.79
6.0V
4.91 4.82
5.0V
4.0V
3.0V
2.0V
1.0V
0.0V
1 2 3 4 5

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 6 / 16
ProfiTrace detailed network
report

11 Device details

11.1 Segment (Segment 1)


Segment type: <not set>

11.1.1 Measurement point (Measuring point 1)


Segment / Measuring point: Segment 1 / Measuring point 1

Address: 1
Device name: Master
Device type: Master
Channel: <not set>

Oscilloscope image of device 1 (AB Diff voltage, Min) :


19-Jul-2015, 11:08:59

Oscilloscope image of device 1 (AB Diff voltage, Max) :


19-Jul-2015, 11:09:04

Oscilloscope image of device 1 (AB Diff voltage, Last) :


19-Jul-2015, 11:09:13

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 7 / 16
ProfiTrace detailed network
report

Oscilloscope image of device 1 (AB Diff stable voltage, Min) :


19-Jul-2015, 11:09:13

Oscilloscope image of device 1 (AB Diff stable voltage, Max) :


19-Jul-2015, 11:08:54

Oscilloscope image of device 1 (AB Diff stable voltage, Last) :


19-Jul-2015, 11:09:13

Address: 2
Device name: Slave
Device type: Slave
Channel: <not set>

IdentNo: 0C98
Manufacturer: Eaton Corp
Model name: C441 PROFIBUS ADAPTER
I/O length (bytes): 0 In, 0 Out
Signal voltage: Min: 6.08 Volt, Max: 6.11 Volt, Last: 6.10 Volt
Diag count while DX: 0
Total retry count: 0
Times lost: 0

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 8 / 16
ProfiTrace detailed network
report

Oscilloscope image of device 2 (AB Diff voltage, Min) :


19-Jul-2015, 11:09:05

Oscilloscope image of device 2 (AB Diff voltage, Max) :


19-Jul-2015, 11:09:12

Oscilloscope image of device 2 (AB Diff voltage, Last) :


19-Jul-2015, 11:09:14

Oscilloscope image of device 2 (AB Diff stable voltage, Min) :


19-Jul-2015, 11:09:02

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 9 / 16
ProfiTrace detailed network
report

Oscilloscope image of device 2 (AB Diff stable voltage, Max) :


19-Jul-2015, 11:08:48

Oscilloscope image of device 2 (AB Diff stable voltage, Last) :


19-Jul-2015, 11:09:14

Address: 3
Device name: Slave
Device type: Slave
Channel: <not set>

IdentNo: 090C
Manufacturer: GE POWER MANAGEMENT
Model name: 369 MOTOR MANAGEMENT RELAY-DP
I/O length (bytes): 0 In, 0 Out
Signal voltage: Min: 5.09 Volt, Max: 5.12 Volt, Last: 5.11 Volt
Diag count while DX: 0
Total retry count: 0
Times lost: 0
Oscilloscope image of device 3 (AB Diff voltage, Min) :
19-Jul-2015, 11:08:56

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 10 / 16
ProfiTrace detailed network
report

Oscilloscope image of device 3 (AB Diff voltage, Max) :


19-Jul-2015, 11:09:00

Oscilloscope image of device 3 (AB Diff voltage, Last) :


19-Jul-2015, 11:09:14

Oscilloscope image of device 3 (AB Diff stable voltage, Min) :


19-Jul-2015, 11:08:49

Oscilloscope image of device 3 (AB Diff stable voltage, Max) :


19-Jul-2015, 11:09:14

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 11 / 16
ProfiTrace detailed network
report

Oscilloscope image of device 3 (AB Diff stable voltage, Last) :


19-Jul-2015, 11:09:14

Address: 4
Device name: Slave
Device type: Slave
Channel: <not set>

IdentNo: 0C98
Manufacturer: Eaton Corp
Model name: C441 PROFIBUS ADAPTER
I/O length (bytes): 0 In, 0 Out
Signal voltage: Min: 6.06 Volt, Max: 6.08 Volt, Last: 6.07 Volt
Diag count while DX: 0
Total retry count: 0
Times lost: 0
Oscilloscope image of device 4 (AB Diff voltage, Min) :
19-Jul-2015, 11:08:55

Oscilloscope image of device 4 (AB Diff voltage, Max) :


19-Jul-2015, 11:08:53

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 12 / 16
ProfiTrace detailed network
report

Oscilloscope image of device 4 (AB Diff voltage, Last) :


19-Jul-2015, 11:09:10

Oscilloscope image of device 4 (AB Diff stable voltage, Min) :


19-Jul-2015, 11:08:49

Oscilloscope image of device 4 (AB Diff stable voltage, Max) :


19-Jul-2015, 11:08:49

Oscilloscope image of device 4 (AB Diff stable voltage, Last) :


19-Jul-2015, 11:09:10

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 13 / 16
ProfiTrace detailed network
report

Address: 5
Device name: Slave
Device type: Slave
Channel: <not set>

IdentNo: 090C
Manufacturer: GE POWER MANAGEMENT
Model name: 369 MOTOR MANAGEMENT RELAY-DP
I/O length (bytes): 0 In, 0 Out
Signal voltage: Min: 5.06 Volt, Max: 5.08 Volt, Last: 5.07 Volt
Diag count while DX: 0
Total retry count: 0
Times lost: 0
Oscilloscope image of device 5 (AB Diff voltage, Min) :
19-Jul-2015, 11:08:59

Oscilloscope image of device 5 (AB Diff voltage, Max) :


19-Jul-2015, 11:09:12

Oscilloscope image of device 5 (AB Diff voltage, Last) :


19-Jul-2015, 11:09:14

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 14 / 16
ProfiTrace detailed network
report

Oscilloscope image of device 5 (AB Diff stable voltage, Min) :


19-Jul-2015, 11:09:07

Oscilloscope image of device 5 (AB Diff stable voltage, Max) :


19-Jul-2015, 11:09:13

Oscilloscope image of device 5 (AB Diff stable voltage, Last) :


19-Jul-2015, 11:09:14

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 15 / 16
ProfiTrace detailed network
report

End of report

Disclaimer
PROCENTEC makes no w arranty w hatsoever regarding the completeness, quality, or adequacy of this automatically
generated document. By using this document, you assume the risk that the content in this document may be
inaccurate, incomplete or may not meet your needs and requirements. Because w e constantly improve our products,
the right is therefore reserved to modify the generated results w ithout prior notice. IN NO EVENT WILL PROCENTEC
BE LIABLE FOR ANY DIRECT OR INDIRECT DAMAGES THAT ORIGINATE FROM THE USE OF THIS DOCUMENT.

Usage of this document is only permitted if the disclaimer on the last page has been accepted.
Name: JAIME MEDINA

Company: SMCV
19/07/2015 11:14 a.m.
Signature: Page 16 / 16

Вам также может понравиться