SA
INVERTER
PROVEN-LF.SA5101 ~ 5120
PROVEN-LF.SA INVERTERS
MODEL CAPACITY 19" STRUCTURE DC INPUT AC OUTPUT
PROVEN-LF.SA5101 1000VA / 800W
PROVEN-LF.SA5102 2000VA / 1600W
PROVEN-LF.SA5103 3000VA / 2400W
PROVEN-LF.SA5104 4000VA / 3200W
5U Height / 19" Width 48/ 110 / 220
PROVEN-LF.SA5105 5000VA / 4000W 110V / 120V,
PROVEN-LF.SA5106 6000VA / 4800W 220V / 230V /240V
PROVEN-LF.SA5108 8000VA / 6400W
PROVEN-LF.SA5110 10000VA / 8000W
PROVEN-LF.SA5115 15000VA / 12000W
To be advice 110 / 220
PROVEN-LF.SA5120 20000VA / 16000W
Features :
• Heavy duty ferroresonant transformer
• Intelligent microprocessor controlled
• Pure sine wave, THD<2% for linear load, <5% for non-linear
• AC-DC isolation improving system security
• Typical transfer time less than 1/4 quarter
• Max efficiency 85%
• Available in DC input 48VDC, 110VDC and 220VDC
• User’s friendly LED + LCD display
• Complete protection
• Input reverse polarity protection KNOWLEDGE POWER PTE LTD
• RS232 + RS485 communication port and Dry point 69 UBI CRESCENT
• Support 1+1 Redundancy #04-03 CES BUILDING
SINGAPORE 408561
TEL : +65 6844 5215
Fax : +65 6844 1962
URL : www.knoweldge-power.com.sg
Electrical Safety & Environment
PROVEN-LF.SA
5101 / 5102 / 5103 /
Operating
Model 5104 / 5105 / 5106 / : -10C - 50⁰C
Temp.
5108 / 5110 /
5115 / 5120
DC Input Storage Temp. : -40C - 85⁰C
Nominal Volt. 48VDC, Isolation
AC – DC : 2000Vrms
110VDC, 220VDC
Operating -12.5% - +25% (48Vdc)
DC - ground : 2000Vrms
Range -18% - +25% (110/220Vdc)
AC Input AC - ground : 2000Vrms
Voltage range :-25% - +20%
Frequency Display & Communication
: ±10%
range
AC Output
1KVA - 2KVA - 3KVA -
4KVA - 5KVA - 6KVA -
Output power All parameter
8KVA - 10KVA - LED + LCD
15KVA - 20KVA indicator
Wave form Pure sine wave Working mode
Power factor 0.8 Fault
Nominal output 110/120VAC, Communica- RS232 or RS485
voltage 220/230/240VAC tion Interface 6xDry contact
Volt. variation Max ± 2% Cooling forced fan
Output Fre. 50/60Hz ± 0.1% Enclosure IP20
THD <2% liner load Mounting 19"
<5% non-liner load
Crest factor 3:1
Efficiency Max 85%
Overload 150% 1min
125% 10mins
Transfer time 4ms
Dynamic
< 30ms
response time
Standard
Safety EN60950-1
Emission EN55022
Immunity EN55022