Академический Документы
Профессиональный Документы
Культура Документы
By:
MATERIAL REQUISITION FOR FLOW METERS Rev.: 0
1. SCOPE
This document covers the technical and commercial requirements for the flow
metering and registering instruments to be installed in the fuel supply system
within the scope of Reconstruction of the International Airport Astana.
2. DEFINITIONS
Supplier: The Bidder becomes the Supplier when his Bid is accepted and a
Purchase Order or a Supply Agreement is made between the Bidder and the
Contractor.
Contract: The main Contract between the Employer and the Contractor.
3. TECHNICAL REQUIREMENTS
4. COMMERCIAL REQUIREMENTS
Page 1 / 6
Doc. No. Reconstruction Of The International Airport Astana Prep.By:
MATERIAL REQUISITION FOR FLOW METERS Rev.: 0
APPENDIX – I
General requirements related with the manufacture and supply of the flow
meters shall include:
The flow metering and registering instruments within the scope of this
specification shall in all respects be suitable for reliable and continuous
operation in the service conditions at the Astana Airport.
Operating and design temperature range for the instruments shall be:
Low: -40°C
High: +50°C
1.4. Material:
Page 2 / 6
Doc. No. Reconstruction Of The International Airport Astana Prep.By:
MATERIAL REQUISITION FOR FLOW METERS Rev.: 0
2. CONSTRUCTION
The flow meters within the scope of this specification shall be positive
displacement type with mechanical head. The medium being measured shall
move a rotor, placed in a measuring chamber, with vanes vertically placed
with respect to the flow direction. The fluid, while moving through the
measuring chamber, forces the vanes, made of self-lubricating material,
against the internal surface of the measuring chamber, hence minimises the
product leakage and turns the rotor.
The rotor shaft shall protrude from the chamber cover and connect,
through a calibration mechanism to the mechanical meter. Couplings shall be
magnetic drive.
2.2. Materials:
Vanes : Teflon
Gaskets : CAF
2.3. Installation:
2.4. Meter:
3. ACCURACY:
Page 3 / 6
Doc. No. Reconstruction Of The International Airport Astana Prep.By:
MATERIAL REQUISITION FOR FLOW METERS Rev.: 0
The Bidder shall calculate the required size for the flow rates mentioned in
Appendix II hereto. The sizes given are for reference only.
The connecting flanges shall be sized and drilled as per ANSI B16.5.
5. CERTIFICATION:
7. MARKING:
Each flow meter shall be marked with a 100mm x 100mm stainless steel tag
plate. Pressure class and connection size shall be clearly marked on the tag
plate.
1. Supplier
2. Connection size
3. Max. Flow Capacity (m3/h)
4. Maximum Pressure (Barg)
5. Pressure Design Standard
6. Tag number
Supplier shall insure that the flange finishes are protected from damage
during shipping and storage. The ends of socket, threaded and weld ends
fittings and flanges shall be protected by securely fastened tight fitting plastic
caps.
The meter heads shall be shipped separately from the flow meters and shall
be packed securely against impacts.
Page 4 / 6
Doc. No. Reconstruction Of The International Airport Astana Prep.By:
MATERIAL REQUISITION FOR FLOW METERS Rev.: 0
Installation and maintenance manuals for the flow meters shall be provided
by the Supplier in digital format and three fold hard-copies.
10.1 Provision
10.2 Availability
The Bidder shall confirm in writing that spare parts for the suggested
equipment will be available for a minimum of twelve years following sale.
Where special tools are required to operate and maintain any part of the
supplied equipment, the Supplier shall provide two sets of such tools with
casing. List of special tools shall be prepared by the Supplier and shall be
subject to the approval of the Engineer.
Page 5 / 6
Doc. No. Reconstruction Of The International Airport Astana Prep.By:
MATERIAL REQUISITION FOR FLOW METERS Rev.: 0
APPENDIX-II
COMMERCIAL DOCUMENTS
1. BID BASIS
The Bidder will propose their best prices, best possible delivery, transport and
payment.
FLOW RATE
S/N DESCRIPTION TAG NUMBER MEDIUM SIZE
(m3/h)
1 FLOW METER FIQ-101 JET A-1 120 6”
2 FLOW METER FIQ-106 JET A-1 30 4”
3. COMPLIANCE STATEMENT
The Bidder shall certify submittals forwarded to SMLA with the following
certifying statement: "I hereby certify that the (equipment) (material) (article)
shown and marked in this bid is that proposed to be incorporated with Astana
Airport Reconstruction Project, is in compliance with the attached specification
and is submitted for the SMLA approval”.
Bidder must sign and stamp all the pages of specification and its attachments
and provide with the compliance statement.
Page 6 / 6