CET850 with goose

CET850
EXCHANGE DATA IN THE SUBSTATION

1. CREATE THE SCL FILE


2. ADD IEDs
3. DEFINE THE NETWORK AND IP ADDRESS
4. CREATE THE GOOSE DATA SET
5. SELECT DATA TO BE TRANSMITED
6. CREATE THE GOOSE CONTROL BLOCK
7. CREATE THE GOOSE RECEIVE
8. SELECT THE IED AND THE DATA TO BE RECEIVED
9. ASSIGN THE Gxx TO THE DATA
10. CHECK, SAVE, BUILD, EXPORT FILES
11. LOAD THE FILE WITH SFT2841 OR FTP in the IEDs

Schneider Electric - Division - Name – Date 2


OPEN CET850

Schneider Electric - Division - Name – Date 3


CREATE THE SCL FILE

FILE NEW

Schneider Electric - Division - Name – Date 4


ADD IEDs

Select the ICD file

Schneider Electric - Division - Name – Date 5


ADD IED FEEDER 1

Schneider Electric - Division - Name – Date 6


ADD IEDs

Schneider Electric - Division - Name – Date 7


CREATE THE GOOSE DATASET

In the LLNO node add a data set

Schneider Electric - Division - Name – Date 8


SELECT THE DATA TO TRANSMIT

Schneider Electric - Division - Name – Date 9


CREATE THE GOOSE CONTROL
BLOCK

Schneider Electric - Division - Name – Date 10


CREATE THE GOOSE CONTROL
BLOCK

Schneider Electric - Division - Name – Date 11


CREATE THE GOOSE RECEIVE

Schneider Electric - Division - Name – Date 12


SUSCRIBE AT THE IED PUBLISHER

Schneider Electric - Division - Name – Date 13


SELECT THE DATA YOU WANT TO
RECEIVE

Schneider Electric - Division - Name – Date 14


SELECT ALL THE DATA FROM ALL
THE PUBLISHERS

Schneider Electric - Division - Name – Date 15


ASSIGN THE Gxx TO THE DATA

Schneider Electric - Division - Name – Date 16


CHECK THE DATA IN THE GOOSE
INPUTS

Schneider Electric - Division - Name – Date 17


CHECK THE ASSIGNMENT OF
GOOSE

Schneider Electric - Division - Name – Date 18


CHECK SAVE BUILD EXPORT FILES

1
3

Schneider Electric - Division - Name – Date 19


VALIDATE

Schneider Electric - Division - Name – Date 20


SAVE THE FILE

Schneider Electric - Division - Name – Date 21


BUILD THE CID FILES

Creation of all the CID files with the


name of the IEDs

Schneider Electric - Division - Name – Date 22


EXPORT TO SFT2841

1 Creation of the .net with the name


of the SCL file

Schneider Electric - Division - Name – Date 23


SFT 2841 TO LOAD THE
CONFIGURATION
Open the SFT2841 and use the
network.net Created by CET850
name of the SCL file.net

Schneider Electric - Division - Name – Date 24


SFT 2841 TO LOAD THE CID

Select the IED by the IP address and


load the cid file created by CET850
name of the IED file.net

User name : Admin


Password : ACE850

Schneider Electric - Division - Name – Date 25


Internet explorer to check the CID file
loaded

Schneider Electric - Division - Name – Date 26


●Questions ?

Schneider Electric - Division - Name – Date 27


SCL FILES
ICD
IED (Intelligent Electronic Device) Capability Description
An ICD file exists for each type of Sepam device.
An ICD file describes the functions and communication data available in a
Sepam.
ICD files are provided in a library with SFT2841 and CET850 configuration tools,
and are used as device models in the configuration process.

IID
Instantiated IED Description
The IID file describes the project-specific configuration of a single IED in a
system.
It is used as an exchange file between the CET850 configuration tool and other IEC
61850 system configuration tools to exchange the configuration data for a single IED
instantiated specifically for a project.

Schneider Electric - Division - Name – Date 28


SCL FILES
CID
Configured IED Description
For every configured Sepam or ECI850 device there is a CID file. It
describes the operating IEC 61850 configuration of the device.
A CID file is created when a device is configured with the configuration tools. The
CID file is then loaded into the device to configure it.
A CID file for an ECI850 contains configuration information for all the Sepam
devices to which it is connected.

SCD
Substation Configuration Description
An IEC 61850 Substation Automation System has an SCD file.
An SCD file contains configuration data for the IEC 61850 system and the
communication configuration settings for all related IEC 61850 devices.

Schneider Electric - Division - Name – Date 29