Salwico SE3000+
User’s guide
çConsilium
The contents of this document are subject to revision without notice due to continued progress in methodology,
design and manufacturing. Consilium Marine assumes no legal responsibility for any error or damage resulting
from the usage of this document.
Contents
Contents ........................................................................................ i
Chapter 1: General ...................................................................... 2
Front view ............................................................................................ 3
Side view (right) ................................................................................... 3
Chapter 2: Functions ................................................................... 4
Power time-out .................................................................................... 4
Powered loop ....................................................................................... 4
Short-circuit loop .................................................................................. 4
Battery and power supply supervision.................................................. 4
Loop test.............................................................................................. 4
Loop unit test ....................................................................................... 4
Chapter 3: Menus ........................................................................ 5
General................................................................................................ 5
Power on ............................................................................................. 5
Battery ................................................................................................. 5
Error messages ................................................................................... 5
Chapter 4: Tests .......................................................................... 6
Loop test.............................................................................................. 6
Loop unit test ....................................................................................... 8
Technical data............................................................................ 10
Weight ............................................................................................... 10
Dimension.......................................................................................... 10
Adapter requirements ........................................................................ 10
Battery ............................................................................................... 10
User’s Guide Chapter 1: General 2
Salwico SE3000
Chapter 1: General
In your hand you now have a small hand hold test device for Salwico Fire
Alarm Systems, the SE3000. With SE3000 you may execute two different
tests, a loop test and a loop unit test. Before you make a test connect the test
probes to the loop, the SE3000 thereafter checks the loop to see if it is under
power. If this is not the case SE3000 connects itself to the loop and starts
testing.
If the loop is under power an error message is displayed and the SE3000 does
not connect itself to the loop.
The loop test automatically boots the complete loop and searches all addresses
on the loop. All the information found about the addresses are saved in a list,
which you can print out or scroll through on the display.
The loop unit test searches for the manually requested address and
immediately displays all information found about the unit.
User’s Guide Chapter 1: General 3
Salwico SE3000
Front view
2 3 4
1
5
1. +24VDC Adapter
2. Earth
3 Loop -
4 Loop +
5 RS232
User’s Guide Chapter 2: Functions 4
Salwico SE3000
Chapter 2: Functions
Power time-out
SE3000 is shut down 3 minutes after the last key is pressed or the last test is
executed.
Powered loop
SE3000 can not execute a test on a loop if it is under power. Therefore
SE3000 always starts with a check of the loop to see if it is under power. The
test is not executed if this is the case. An error message is displayed and it
remains displayed until the error has disappeared.
Short-circuit loop
The communication test is interrupted when SE3000 detects a short-circuit
and an error message is displayed. The error message remains displayed until
the next communication test is executed.
Loop test
When a loop test is performed SE3000 starts at address 1 and searches the
complete loop for all the loop units and their IDs. If a loop unit does not
answer SE3000 tries to recommunicate with it several times.
Each time the test device detects a short-circuit isolator it restarts the loop test
from address 1. The loop test continues until all short circuit isolators have
been activated. If a short circuit is caused by the activation of a short circuit
isolator SE3000 can keep track of all answering addresses by using this
method. An error message is displayed.
When the loop test is finished you may look at a list or a printout including all
the answering loop units and their IDs. You may at any time interrupt the loop
test by pressing the EXIT key (F4).
Chapter 3: Menus
General
The SE3000 has two main menus, one for loop test and one for loop unit test.
You select the appropriate menu by pressing MORE (F4) repeatedly. All
messages are displayed on line one and each message remains displayed until
the error is not present in the system anymore. If there are more than one error
message the SE3000 alternatively displays each error message for 2 seconds.
Power on
At power the program name and version are displayed on line 1 for SE3000 1.00
a few seconds.
Battery
The remaining capacity of the battery is displayed in percent. (In 60%
this example the capacity is 60% of full capacity.) This message is
alternatively displayed with the error message.
Error messages
The loop is already under power. LOOP IS POWERED
The battery voltage is to low. Charge the battery. No tests can be BATTERY DISCHARGED
started and the keys are locked.
This message is displayed the last 30 seconds before the SE3000 is POWER TIMEOUT 24
running out of power.
User’s Guide Chapter 4: Tests 6
Salwico SE3000
Chapter 4: Tests
Loop test
CHECK LOOP
CHECK MORE
No units found
SE3000 can not find any units, all address have been searched.
NO UNITS FOUND
OK
Address error
The communication is bad or two units have the same address. ADDR:3 2(5)
ADDRESS ERROR
- + PRINT OK
Unknown ID
SE3000 has found a unit with an unknown ID (for instance 110). ADDR:5 4(5)
UNKNOWN TYPE 110
- + PRINT OK
User’s Guide Chapter 4: Tests 7
Salwico SE3000
Wrong address
SE3000 tests for wrong addresses after it has searched the loop ADDR:255 5(5)
and all short-circuit isolators have been activated. The wrong
addresses are address 0 and 151 - 255. If a wrong address is found WRONG ADDRESS
it is displayed. - + PRINT OK
Printout
You can make a printout of the list if you have a printer or a
computer connected to SE3000. Press PRINT.
CHECK LOOP
CHECK MORE
User’s Guide Chapter 4: Loop unit test 8
Salwico SE3000
SE3000 remains connected to the loop until you end this test by
using the EXIT key.
Next unit
When you want to go to the next unit, use the - and + keys.
User’s Guide Chapter 4: Loop unit test 9
Salwico SE3000
Short-circuit isolator
When SE3000 detects a short-circuit isolator the menu on line four ADDR:4(..º.....)
is changed. You may now control the short-circuit isolator by
using the SET/RES key (F3). The key has a toggling function. KS 2 NOT ACTIVE
- + SET EXIT
Technical data
Weight
1.1 kg (including adapter and test cables)
Dimension
196 x 100 x 40 mm
Adapter requirements
Power 24 VDC 1A ( 25 W )
Plug dimension 2.1 mm
Polarity Of no importance
Battery
Size: 12V/1900 mAh
Charging time: 3 hours (automatically)