Siemens Power Academy

Following Objectives are treated in the


DIGSI Advanced Training ; CFC-Part 2

1. Create a DIGSI-Project structure for a NXPLUS-


Double Busbar configuration
2. Visualization of Transformer Taps and Highvoltage in default and control
displays of the 110 kV Incoming feeder
3. Configure in DIGSI the three-position-switch of NXPLUS and all
NXPLUS-related information including allocation of I/O for
motor control, in the matrix, in default and control displays and in CFC-Charts (Part 1)
4. Configure the bay-related interlocking conditions for double busbar in the typical
“incoming feeder” (Part 2)
5. Configure the substation-related interlocking conditions for double busbar in the
typicals “incoming feeder” (Part 3) and “bus coupler” (Part 4)
6. Visualization of operational measured values and metered values using
multi-page feeder displays

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 1 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

For switching ON or OFF of all switching devices the


following
interlocking conditions shall be created by CFC:
- Release Q0-OFF
- Release Q0-ON
- Release Q1-OFF
- Release Q1-ON
- Release Q2-OFF
- Release Q2-ON
- Release Q5-OFF
- Release Q5-ON

Create a new CFC-Chart ‚Interlockings‘

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 2 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)
Feedbacks of devices: CFC-Charts Release Conditions

Q0 DP X 12

Q1 DP X8
Q2 DP X 15
Release Q0 ON
Q5 DP X 10 IntSP

Release Q0 OFF
IntSP
AND
Process information Release Q1 ON
IntSP

L2 AND Release Q1 OFF


>Door Open
IntSP
Release Q2 ON
> CB wait AND
L1 IntSP
Spring is no charged
Release Q2 OFF
L5 AND IntSP
>Fail Feed VT
Release Q5 ON
> SF 6 Lost L4 IntSP
AND
Release Q5 OFF
L6 IntSP
> High Voltage on/off
H7

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 3 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

The release condition for


- Switching Q0-OFF
is ‚>Door open‘.
Please use the following CFC-block:

Negation
(Door Open) = CR Q= Off
09.2 CFC Part 2 Bay-related Interlocking
Version: B 5_Page 4 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

The release condition for


- Switching Q0-ON
is
1.) no device is in error-position
To do the interrogation of the device position use the following
CFC-blocks

off
on

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 5 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

off
on

______
(Q0 On) XOR (Q0 Off) = Q0 N Err = Q0 Err (Negation of Q0 Err)

(Q1 On) XOR (Q1 Off) = Q1 N Err

(Q2 On) XOR (Q2 Off) = Q2 N Err

(Q5 On) XOR (Q5 Off) = Q5 N Err

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 6 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

The release for switching Q0-ON shall be build up by further conditions


2.) (Q5-OFF and Q1-ON) or (Q5-ON and Q1-OFF) i.e. Q1 and Q5 are not
permitted being ON at the same time. Please use a NAND-block.

N e g a t i o n
(Q1 On + Q5 On)

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 7 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

The release for switching Q0-ON shall be build up by


further conditions
3.) „Door closed“ and „No SF6 Lost“

Combine the information to


conditions 1-3) by using an AND-block.

___ ___ ___ ___ ________ _____ ____


Q0 Err + Q1 Err + Q2 Err + Q5 Err + (Q1 On + Q5 On) + (Door Open) + SF6 Lost =Sum CR

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 8 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

The release for switching Q0-ON shall be build up by


further conditions
4.) CB ready Spring is charged

Combine the AND-block „Sum, CR“ with another


AND-block „CR Q0 On“ and conect the Q0-relevant
information ‚CB ready Spring is charged‘ by the 2nd. block.

Connect the output of the AND-block „CR Q0 On“


with the address ‚Release Q0-ON‘

_______
Sum CR + (CB wait) = CR Q0 On
09.2 CFC Part 2 Bay-related Interlocking
Version: B 5_Page 9 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

The release condition for switching Q1-OFF/ON


shall be executed in addition to the existing conditions of
the AND-Block „Sum CR“ :
- no device is in error-position
- (Q5-OFF and Q1-ON) or (Q5-ON and Q1-OFF)
- Process information ‚door closed‘
by checking
(Q0-OFF) and (Q2-OFF) and (Q5-OFF).
Please use in preparation of the station interlocking
contions two additional AND-blocks.

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 10 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

Sum CR + (Q0 Off + Q2 Off + Q5 Off) = CR Q1 Off


I I I I
I AND 1
I I
AND 2

Sum CR + (Q0 Off + Q2 Off + Q5 Off) = CR Q1 On


I I I I
I AND 1
I I
AND 2

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 11 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

The release condition for switching Q2-OFF/ON


shall be executed in addition to the existing conditions
of the AND-Block „Sum CR“ :
- no device is in error-position
- (Q5-OFF and Q1-ON) or (Q5-ON and Q1-OFF)
- Process information ‚door closed‘
by checking
(Q0-OFF) and (Q1-OFF) and (Q5-OFF).
Please use in preparation of the station interlocking
contions two additional AND-blocks

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 12 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

Sum CR + (Q0 Off + Q1 Off + Q5 Off) = CR Q2 Off


I I I I
I AND 11
I I
AND 12

Sum CR + (Q0 Off + Q1 Off + Q5 Off) = CR Q2 On


I I I I
I AND 11
I I
AND 12

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 13 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

The release condition for switching Q5-OFF


shall be executed in addition to the existing conditions of
the AND-Block „Sum CR“ :
- no device is in error-position
- (Q5-OFF and Q1-ON) or (Q5-ON and Q1-OFF)
- Process information ‚door closed‘
by checking
(Q0-OFF) and (Q1-OFF) and (Q2-OFF).
Please use an additional AND-block

Sum CR + Q0 Off + Q1 Off + Q2 Off = CR Q5 Off

09.2 CFC Part 2 Bay-related Interlocking


Version: B 5_Page 14 Energy Sector © Siemens AG
DIGSI 4 Advanced
Siemens Power Academy

Continuous function chart


Part 2) Bay related Interlockings Incomming (General)

The release condition for switching Q5-ON


shall be executed in addition to condition ,release Q5-OFF‘
by checking the information ‚High Voltage on/off‘ and „Fail Feed
V“.
Create the condition ‚High Voltage on/off‘ out of the relevant
double point information.
Use the following DI-TO-Bool-Block:

_________
CR Q5 Off + HV Off + FailFeedVT = CR Q5 On
09.2 CFC Part 2 Bay-related Interlocking
Version: B 5_Page 15 Energy Sector © Siemens AG
DIGSI 4 Advanced