CT‐MV

Technical Schedule Particulars of Current Transformer MV

No. Particulars Unit Technical Requirement Offered

1 Manufacturer
2 Manufacturer's Code N° 
3 Type 
4 Standard IEC
5 Rated Voltage  kV 24
6 Power Frequency Voltage(r.m.s) kV 50
7 Lightning Impulse Withstand Voltage (Peak) kV 125
8 Insulation Material Cycloaliphatic Epoxy Resin
9 Primaries Current A 15‐30, 20‐40, 25‐50
10 Secondary Current A 5
11 Accuracy Class 30 VA Class 0.5
12 Rated Frequency Hz 50
13 Short Circuit Thermal Current kV ‐
14 Rated Continuous Thermal Current % 120
15 Number of Core N° 1
16 Material of Core Copper
17 Diameter:
18 ‐ Height mm
19 ‐ Width mm
20 ‐ Depth mm
21 Temperature °C +45
22 Air Humidity % 90
23 Weight Kg

Technincal Office 1/1