Академический Документы
Профессиональный Документы
Культура Документы
I DELTA PHASE Ns
PHASE
=T =
I STAR ND
For an internal fault at fraction ‘h’ from neutral,
h x VP
Fault Current, I F =
R
1 of 10
October 2002, IEEMA Journal, Page 28 to 33
Rated Phase voltage on star side = VP
h x Ns
Effective Turns Ratio, TE =
ND
= h xT
PHASE
I DELTA
= TE
I STAR PHASE
= h xT
I DELTA PHASE = h x T x I STAR PHASE
VP
I STAR PHASE = I F = h x
R
VP
I DELTA PHASE = h 2 x T x
R
For terminal fault on star side (h = 1),
VP
I STAR MAX =
R
VP
I DELTA MAX = T x
R
Expressing the fault current in terms of maximum current,
I STAR PHASE = h x I STAR MAX v h ……………………(1)
The graphs of equations (1) and (2) are shown in Fig 2. It can be seen that for faults
close to neutral (h < 0.3), current on delta side is too small.
2 of 10
October 2002, IEEMA Journal, Page 28 to 33
2.1 Example
Transformer rating: 10 MVA, 11 kV (Delta) / 6.6 kV (Star), NGR = 4.354 :
6600
VP =
3
= 3810 V
10000
I STAR RATED =
3 x6.6
= 875 A
10000
I DELTA RATED =
3 x11
= 524 A
3810
Turns Ratio, T =
11000
= 0.3464
For terminal fault on star side (h = 1),
3810
I STAR MAX =
4.354
= 875 A
The ground fault current is limited to rated current.
,DELTAMAX = 0.3464 x 875
= 303 A
The current magnitudes on delta and star windings, as a function of fault location ‘h’,
are given in Table I.
,F = h x 3810 A ,DEL = h x T x ,F A
Table I
h ,F / ,FMAX ,DEL / ,DELMAX
4.354 T = 0.3464
0.05 43.8 0.05 0.76 0.003
0.06 52.5* 0.06 1.09 0.004
0.10 87.5 0.10 3.03 0.010
0.12 105.0* 0.12 4.37 0.014
0.20 175.0 0.20 12.12 0.040
0.45 393.8 0.45 61.3* 0.203
0.50 437.5 0.50 75.78 0.250
0.63 551.3 0.63 120.3* 0.397
0.90 787.6 0.90 245.54 0.810
1.00 875.0 1.00 303.10 1.000
3 of 10
October 2002, IEEMA Journal, Page 28 to 33
2.2 Sensitivity of differential protection (87)
A ground fault on star side gets reflected as line to line fault on delta side (Fig 1).
CT ratio on delta side = 600 / 1
CT ration on star side = 1000 / 1
If pick up is set at 10%,
Minimum Pick up current, ,P = 600 x 0.1
= 60 A.
For faults up to 45% from neutral, current on delta side is less than 60 A. Thus only
about 55% of winding is protected by differential.
If for any reason pick up is increased to 20%,
Minimum Pick up current, ,P = 600 x 0.2
= 120 A.
For faults up to 63% from neutral, current on delta side is less than 120 A. Thus only
about 27% of winding is protected by differential.
2.3 Sensitivity of REF protection (64)
The scheme is shown in Fig 3.
For faults up to 6% from neutral, current on star side is less than 50 A (Table I).
Almost 94% of winding is protected and only about 6% of winding remains
unprotected. For fault at 6% from neutral, current on delta side is too low (about 1 A)
and differential will not definitely pick up.
Thus it is concluded that REF offers much more sensitive protection than differential
for internal faults on star winding in case of resistance grounded system.
Only for faults very near to terminal, sensitivity of differential is comparable to REF.
5 of 10
October 2002, IEEMA Journal, Page 28 to 33
3.0 Solidly grounded system
Consider the same transformer analyzed for resistance grounded system. In case of
solidly grounded neutral, ground fault current magnitude will be very high (kA). For
an internal fault at fraction ‘h’ from neutral, the fault current is a function of leakage
reactance which itself is a complex function of ‘h’. A detailed analysis leads to Fig 5,
which shows the star and delta currents. As the fault point is shifted from terminal to
neutral, the fault current on star side initially decreases but at about 35% from
neutral the fault current starts rising before abruptly falling to zero near the neutral.
Assume for terminal fault on star winding, the ground fault current is limited to 10 x
,RATED .
,STARMAX = 10 x 875 A
= 8.75 kA
,DELTAMAX = 8.75 x 0.3464
= 3.03 kA
6 of 10
October 2002, IEEMA Journal, Page 28 to 33
The current magnitudes on star and delta windings, as a function of fault location ‘h’,
are given in Table II.
,F - kA ,DEL = h x T x
Table II
h
STAR
,F / ,F MAX ,DEL / ,DEL MAX
IF A
0.05 3.33 0.38 58* 0.019
0.1 3.15 0.36 109 0.036
0.2 2.54 0.29 176 0.058
0.3 1.93 0.22 200 0.066
0.35 1.93 0.22 233 0.076
0.4 2.01 0.23 279 0.092
0.8 5.95 0.68 1649 0.544
1.0 8.75 1.00 3031 1.000
7 of 10
October 2002, IEEMA Journal, Page 28 to 33
No part of delta winding has voltage to neutral / ground less than 0.5 pu. In star
winding voltage varies from 1.0 pu at terminal to 0 at neutral. The corresponding
figure for delta winding is 1.0 pu at terminal to 0.5 pu at midway of winding. Hence
the range of variation of fault current magnitude is also less in delta compared to
star. For a fault at middle of delta winding, voltage is 0.5 pu and the impedance is
also 0.5 pu. For the transformer considered in previous examples,
0.5
Fault Current, I F =
0.5
= 1 pu
= 524 A
8 of 10
October 2002, IEEMA Journal, Page 28 to 33
Current through each phase (Fig 7), ,F = 262 A
P
9 of 10
October 2002, IEEMA Journal, Page 28 to 33