Technical Datasheets
Revision 2
BRISTOL reserves the right to make changes at any time without prior notice. 1
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Table of Contents
Page
Easy Flow & Power Flow Systems 4
HFC-227ea Clean Agent 6
HFC-227ea Storage Cylinder 7
Agent Storage Label 8
Cylinder Discharge Valve 9
Nitrogen Inlet Valve 10
Pneumatic Actuation Valve 11
Solenoid Cutter with Adapter 12
Monitoring Devices 14
A. Pressure Gauge with Integrated Pressure Switch
B. Pressure Operated Switch
Nitrogen Cylinder 15
Propellant Storage Label 16
Nitrogen Valve 17
Nitrogen Actuation Valve 18
Pipe Adapter 19
Connection Flexible Hoses 20
Union Elbow 21
Adapter 22
Check Valve 23
Manifold Welding Socket 24
Manifold Relief Device 25
Nitrogen Actuation Tube 26
Actuation Tube 27
Actuation Tube Devices 28
A. Check Valve
B. Relief Valve
System Actuation Kit 30
Selector Valve 33
Discharge Nozzles 34
Nozzle Escutcheon 35
.
BRISTOL reserves the right to make changes at any time without prior notice. 2
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Table of Contents
Page
Mounting Brackets 36
Extinguishant Control Panel 37
Hold-Off Switch 40
Smoke Detector 41
Heat Detector 44
Fire Alarm Bell 46
Selectable Candela Evacuation Signals Manual Pull 47
Station 49
Civil Defense Approval & UL Certificate 50
Specification & Compliance 52
BRISTOL reserves the right to make changes at any time without prior notice. 3
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Easy Flow System (EFS) is developed for total flooding automatic gaseous fire extinguishing system. EFS utilizes clean and
safe fire extinguishing agent heptaflouropropane (HFC-227ea) popularly known by its trade name FM-200™. Since the
enforcement of Montreal Protocol in 1989, HFC-227ea had been developed and became widely regarded as one of the
most cost-effective replacement for Halon 1301 as fire extinguishing agent.
In EFS, the agent is stored in cylindrical storage cylinder and pressurized with nitrogen to about 25 bar. This kind of
system is also commonly known as standard flow system.
BRISTOL reserves the right to make changes at any time without prior notice. 4
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Conventional installation of the clean agent fire extinguishing system is constrained by the size of protected area and
distance for agent delivery. This is because for such protected area, the quantity of agent becomes insufficient for fire
extinguishing when the agent and the propelling nitrogen are contained in a single cylinder and pressurized to about 25
bar. To overcome this limitation, recently Bristol Fire Engineering L.L.C. started the development of Power Flow System
(PFS) in which a separate cylinder is added to contain the propelling nitrogen. The two cylinders are interconnected by
suitable tube, hose and valves such that during discharge the high-pressure nitrogen superpressurizes and pushes the
extinguishing agent like a gas piston in order to sustain the required pressure and agent mass flow rate. PFS configuration
enables the system to discharge more than 95% of the extinguishing agent over a wider protected area requiring longer
agent flow distances within 10 seconds.
BRISTOL reserves the right to make changes at any time without prior notice. 5
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
HFC-227ea provides superior fire protection in a wide HFC-227ea system shall be used on the following Class of
range of applications from sensitive electrical equipment Hazards:
to industrial applications using flammable liquids. HFC-
Class A & C: Electrical and Electronic Hazards
227ea is ideal for applications where clean-up of other
media presents a problem, where weight versus Telecommunications Facilities
suppression potential is a factor, where an electrically High value assets, where the associated
non-conductive medium is needed and where people down-time would be costly
compatibility is an overriding factor. When environmental
impact is a consideration, HFC-227ea is particularly Class B: Flammable liquids and gases
useful. It has zero ozone depleting potential, low global HFC-227ea systems shall “NOT” be used on fires involving
warming potential and a short atmospheric lifetime. the following materials:
These characteristics make it suitable not only for new
installations of total flooding systems, but also for Halon Chemicals or mixtures of chemicals that
1301 replacement applications. are capable of rapid oxidation in the
absence of air. (Examples include:
Cellulose Nitrate and Gunpowder)
Features and Benefits: Reactive metals such as Lithium,
• Colorless, odorless, liquefied compressed gas Sodium, Potassium, Magnesium,
Titanium, Zirconium, Uranium, and
• Stored as a liquid Plutonium
• Electrically non-conductive Metal hydrides such as Sodium Hydride
• Discharges as a gaseous vapor (due to its relatively low and Lithium Aluminum Hydride
boiling point) Chemicals capable of undergoing auto-
• Zero ozone depleting potential thermal decomposition.
BRISTOL reserves the right to make changes at any time without prior notice. 6
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Basically, both FM-200® EFS and FM-200® PFS utilize identical agent
containers. The containers have two threaded openings.
Technical Information
Material Carbon Steel (SG365; thickness 5.0)
Working Pressure 34.5 bar (500 psi)
Burst Test Pressure 69.0 bar (1,000 psi)
Hydraulic Test Pressure 137.9 bar (2,000 psi)
Paint Specification Red Polyester Powder Coated
BRISTOL reserves the right to make changes at any time without prior notice. 7
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Technical Information
U104-ASL
BRISTOL reserves the right to make changes at any time without prior notice. 8
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Technical Information
Gauge Port
1/8" NPT
(Low Pressure Router)
Needle Cylinder Port M38 x P1 .5
U110-CA063; U110-CA063N
U102-DV40 40
U100-CA089; U100-CA089N
56
U100-CA115; U100-CA115
U102-DV50 50
U100-CA175; U110-CA175N
BRISTOL reserves the right to make changes at any time without prior notice. 9
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Technical Information
Weight 1.7 kg
Inlet/Outlet Diameter 20 mm
Thread connection
M38x1 .5
with Flexible Hose
U110-CA063N; U100-CA089N
Cylinder Application
U100-CA115N; U100-CA175N
BRISTOL reserves the right to make changes at any time without prior notice. 10
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Technical Information
BRISTOL reserves the right to make changes at any time without prior notice. 11
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
DESCRIPTION
TECHNICAL INFORMATION
Approvals for use with
EFS/PFS..................................................................................... UL
Device approvals .............................................................. c-UL-us
Use of device ...................................................... Releasing device
Electrical rating ......................................................... 24VDC, 1.7A
Material
For Pilot Cylinder Valve For Master Cylinder Valve Needle .................................................................. Stainless steel
(P/N:SCTA-01) (P/N:SCTA-02) Enclosure/Frame .......................................................... Zinc alloy
Gross weight ............................................................... 2 kg (4.4 lb.)
Listed compatible releasing panel................. Potter PFC-4110RC
ORDERING INFORMATION
Specify part number and description when ordering.
Part/Model No. Description
U300-SCT Solenoid Cutter
SCTA-01 Adapter for pilot cylinder valve
Actual product may differ from the images shown.
SCTA-02 Adapter for master cylinder valve
BRISTOL reserves the right to make changes at any time without prior notice. 12
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
BRISTOL reserves the right to make changes at any time without prior notice. 13
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Monitoring Devices
A. Pressure Gauge with Integrated Pressure Switch
Technical Information
Position NC
Technical Information
Connection G 1/2”
Protection IP65
BRISTOL reserves the right to make changes at any time without prior notice. 14
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Nitrogen Cylinder
Technical Information
Seamless MnH
Material
Steel Tube
Steel Plate Thickness 7.0mm
Internal
Valve Empty Weight Fill Pressure FM-200 Container
Model No. Volume
(mm) (kg) (bar) Combination
(L)
U201-NC60 60 U110-CA063N
U201-NC70 70 U110-CA089N
68 U202-NV20 74.5
U110-CA115N
U201-NC80 80
U110-CA175N
BRISTOL reserves the right to make changes at any time without prior notice. 15
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Technical Information
BRISTOL reserves the right to make changes at any time without prior notice. 16
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Nitrogen Valve
Technical Information
Gauge Port
1/8" NPT
(Low Pressure Router)
Needle Cylinder Port M38 x P1 .5
Weight 1.4 kg
Inlet/Outlet Diameter 20 mm
U201-NC80
BRISTOL reserves the right to make changes at any time without prior notice. 17
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Technical Information
BRISTOL reserves the right to make changes at any time without prior notice. 18
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Pipe Adapter
Single System
Technical Information
BRISTOL reserves the right to make changes at any time without prior notice. 19
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Technical Information
At one end, the flexible hose (SOA) has external metric threads and
U203-FH50 is connected to a union elbow while the other end has external pipe
FIG. 11. UNION ELBOW threads (PT) and is connected to the check valve or socket.
Technical Information
BRISTOL reserves the right to make changes at any time without prior notice. 20
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Union Elbow
Technical Information
FIG. 12. UNION ELBOW Hydraulic Test Pressure SS bar (797. 7 psi)
125 (U401-UB125)
Length
225 (U401-UB225)
Inlet/Outlet Diameter 50 mm
BRISTOL reserves the right to make changes at any time without prior notice. 21
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Adapter
Technical Information
BRISTOL reserves the right to make changes at any time without prior notice. 22
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Check Valve
The check valve inlet has internal pipe threads (PT) and is
connected to the flexible hose (SOA) while the outlet has
external metric threads and is connected to the manifold
(supplied separately) via the manifold welding socket.
U500-CV50
Technical Information
FIG. 14. CHECK VALVE
Body Material Brass (C3771)
Inlet/Outlet Diameter 50 mm
BRISTOL reserves the right to make changes at any time without prior notice. 23
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Technical Information
BRISTOL reserves the right to make changes at any time without prior notice. 24
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
U500-RVD20 INSTALLATION
FIG. 28. PRESSURE RE LIEF DEVICE 20A Important Notes::
Appropriately tighten the device via the hex nut on the body
(not the safety plug) ensure leak-free connection
Technical Information
Material
BRISTOL reserves the right to make changes at any time without prior notice. 25
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
The nitrogen actuation tube for open the nitrogen valve use
by FM-200 discharge pressure deliver to nitrogen valve
when agent discharge from FM-200® valve.
Technical Information
BRISTOL reserves the right to make changes at any time without prior notice. 26
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Actuation Tube
Selector Valve and Pressure Switch Actuation Tube
Technical Information
Length 3,000 mm
BRISTOL reserves the right to make changes at any time without prior notice. 27
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
INSTALLATION
U500-ICV06 Important Notes::
FIG. 27. CHECK VALVE 6A
Refer to the system installation drawings for the location of
check valves in the actuation tubing system
Properly install the check valve with the arrow pointing to the
direction of flow
Ensure that the flared end of the copper tube are thoroughly
clean
Technical Information
Material
BRISTOL reserves the right to make changes at any time without prior notice. 28
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
B. Relief Valve 6A
The Relief Valve 6A is used for bleeding off pressure that may build-
up in the pneumatic actuation tubing if very small amount of leak in
the pilot cylinder valve occurs.
INSTALLATION
Important Notes::
U500-RV06
Refer to the system installation drawings for the location of
FIG. 28. RELIEF VALV E 6A
relief valve in the actuation tubing system
Ensure that the flared end of the copper tube are thoroughly
clean
Technical Information
Material
Spring Steel
BRISTOL reserves the right to make changes at any time without prior notice. 29
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
A. Solenoid Cutter
The solenoid cutter is fitted with PUSH button that is and should
only be used for emergency manual activation should the
electronics fail.
CAUTION!
BRISTOL reserves the right to make changes at any time without prior notice. 30
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
B. Actuation Cylinder
C. Pressure Switch
The pressure switch is then used to allow the flow of electricity via
U300-PST electrical wires to activate the discharge alarm (system).
FIG. 21. PRESSURE SW ITCH NOTE:
FM-200 PFS® requires the use of UL Listed pressure switch for use
in hazardous location that is compatible with the system operating
pressure and fire alarm panel. The designer is strongly advised to
refer to the pressure switch manual for compatibility information.
BRISTOL reserves the right to make changes at any time without prior notice. 31
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Technical Information
Box
Solenoid Cutter
Voltage 24Vdc
Current 1.7A
Actuation Cylinder
Actuator Valve
Pressure Switch
Housing Polyethylene
BRISTOL reserves the right to make changes at any time without prior notice. 32
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Selector Valve
Diameter
Inlet/Outlet
Model No. Inlet/Outlet L1 L2 H1 H2
Connector
(mm)
BRISTOL reserves the right to make changes at any time without prior notice. 33
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Discharge Nozzles
The discharge nozzle is available in two types with varied sizes each
intended for a specific area of enclosure/hazard.
The 180° nozzle is designed for sidewall installations, while the 360°
nozzle is installed at the location in the center of enclosure.
U700 SERIES
Technical Information
FIG. 22. 360 DEGREE TYPE NOZZLE
U701 SERIES
BRISTOL reserves the right to make changes at any time without prior notice. 34
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Nozzle Escutcheon
Technical Information
15mm (1/2" )
U702-RNE20 55 33 10
20mm (3/4" )
32mm (1 1/4" )
U702-RNE40 77 52 10
40mm (1 1/2" )
BRISTOL reserves the right to make changes at any time without prior notice. 35
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Mounting Brackets
Size 40 x 40 x 3,000 mm
Hole 10 x 30 mm
Hole Pitch 50 mm
Weight 2 kg/m
U116 SERIES
BRISTOL reserves the right to make changes at any time without prior notice. 36
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Features:
Three initiation circuits as standard
Designed and manufactured to the highest standards in a quality controlled environment and with UL and FM approvals, the
Sigma A-XT releasing panel offers outstanding value and performance for all small to medium fixed firefighting installations.
With three initiation circuits as standard, release can be configured to activate from any combination of detection zone inputs
to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling
void, room and floor void applications.
The extensive configuration options of the Sigma A-XT allow the functionality of the system to be extensively modified.
The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until
release for added user safety.
The countdown timer is duplicated on up to seven remote status units to provide local indication of the system status.
With all of the electronics mounted on a single, easily removable, steel plate Sigma A-XT panels are both robust and easy to
install.
Sigma A-XT is supplied in an enclosure that matches the design and color of the Elite RS range and is available in standard red
or optional grey.
BRISTOL reserves the right to make changes at any time without prior notice. 37
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Cont… K1810-13
Technical Information
Construction 1.2mm mild sheet steel
IP Rating IP30
Finish Epoxy powder coated
Color - lid & box Red RAL 3002 (optional grey BS 00 A 05 semi-matt)
Mains supply 230V AC or 115V AC
Mains supply fuse 1.6 Amp (F1.6A L250V)
Power supply rating 3 Amps total including battery charge 28V +/- 2V
Maximum ripple current 200 millivolts
Battery type (Yuasa NP) Two 12 Volt 7Ah sealed lead acid in series
BRISTOL reserves the right to make changes at any time without prior notice. 38
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Cont… K1810-13
Technical Information
Extinguishant release output Fused at 1 Amp
Extinguishant release delay Adjustable 0 to 60 seconds (in 5 second steps)
Extinguishant release duration Adjustable 60 to 300 seconds (in 5 second steps)
SIL, AL, FLT, RST inputs Switched -ve, max resistance 100 Ohms
Zone normal threshold 8K ohms to 1K ohm
Detector alarm threshold 999 ohms to 400 ohms
Call point alarm threshold 399 ohms to 100 ohms
Short circuit threshold 99 ohms to 0 ohms
Monitored inputs normal threshold 8K ohms to 1K ohm
Monitored inputs alarm threshold 999 ohms to 100 ohms
Monitored inputs Short circuit threshold 99 ohms to 0 ohms
Status unit/Ancillary board connection Two wire RS485 connection
Status unit power output Fused at 500mA with electronic fuse
BRISTOL reserves the right to make changes at any time without prior notice. 39
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Hold-Off Switch
K1823-10
Technical Information
K1823-10 Construction 1.2mm mild sheet steel
IP Rating IP30
Weight 1kg
BRISTOL reserves the right to make changes at any time without prior notice. 40
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Smoke Detector
CD-P1A/CD-P1AN
APPLICATION
Low profile, 2.0" high (with base) The CD-P1A/CD-P1AN photoelectric smoke detector utilizes
two bicolored LEDs for indication of status. In a normal standby
2 or 4 wire base compatibility, relay bases available condition the LEDs flash Green every 3 seconds. When the
detector senses smoke and goes into alarm the status LEDs will
Highly stable operation, RF/Transient protection
latch on Red.
Low standby current, 45μA at 24VDC
The detector utilizes an infrared LED light source and silicon
Two built-in power/alarm LEDs photo diode receiving element in the smoke chamber. In a
normal standby condition, the receiving element receives no
Non-directional smoke chamber light from the pulsing LED light source. In the event of a fire,
smoke enters the detector smoke chamber and light is
Vandal resistant security locking feature
reflected from the smoke particles to the receiving element.
Built-in magnetic go/no go detector test feature The light received is converted into an electronic signal.
Removable smoke labyrinth for cleaning or replacement Signals are processed and compared to a reference level, and
when two consecutive signals exceeding the reference level are
Highly resistant to false alarms caused by steam received within a specified period of time, the time delay circuit
triggers the SCR switch to activate the alarm signal. The status
LEDs light continuously during the alarm period.
BRISTOL reserves the right to make changes at any time without prior notice. 41
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Cont… CD-P1A/CD-P1AN
Technical Information
Light Source GaAlAs Infrared Emitting Diode
Rated Voltage 17.7 - 30.0 VDC
Working Voltage 15.0 - 33.0 VDC
Maximum Voltage 42 VDC
Supervisory Current 45μA @ 24 VDC
Surge Current 160μA max. @ 24VDC
Alarm Current 150mA max. @ 24 VDC
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, CD-P1A/CD-P1AN photoelectric smoke detectors.
The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel.
The base shall permit direct interchange with CD-M2 photoelectric/heat detector, and/or CD-HS4C/4D fixed temperature/
rate-of-rise heat detectors. The base shall be appropriate twist lock base CD-4 , CD-6 , CD-4R, or CD-xxxxx.
The smoke detector shall have two flashing status LED's for visual supervision. When the detector is in standby condition the
LED's will flash Green. When the detector is outside the UL listed sensitivity window the LED's will flash Red. When the
detector is actuated, the flashing LED's will latch on Red. The detector may be reset by actuating the control panel reset
switch.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated. The vandal-resistant,
security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field removable
when not required.
BRISTOL reserves the right to make changes at any time without prior notice. 42
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Cont… CD-P1A/CD-P1AN
BRISTOL reserves the right to make changes at any time without prior notice. 43
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Heat Detector
CD-HS4D
APPLICATION
Latching LED base available Automatic heat detectors shall be fixed temperature rated at
135°F for areas where ambient temperatures do not exceed
120°F and 190°F where ambient temperatures exceed 120°F
Technical Information but not 160°F. The fixed temperature element shall consist
of a bi-metallic disc and actuator shaft. Electrical contacts
Response 135° ± 7.5°F
shall be normally open, rated at 100mA @ 60VDC.
Temperature 190° ± 7.5°F Heat detectors shall be installed in accordance with National
Contact Fire Protection Association Standard 72, the spacing assigned
N/O Contacts 100mA max. @ 60 V by Underwriters Laboratories, and in accordance with the
Rating rules and regulations set forth by the local authorities having
Maximum jurisdiction. Automatic heat detectors shall be Underwriters
95% RH Non-Condensing Laboratories listed.
Humidity
BRISTOL reserves the right to make changes at any time without prior notice. 44
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Cont… CD-HS4D
COMPATIBLE BASES
The CD-xxxxx is a 6" base featuring a current limiting resistor, latching annunciator output and a latching circuit so the alarm
LED will remain lit until the control panel has been reset. Heat detectors are not recognized as proper detection for life
safety protection, therefore they should be utilized only for the protection of property.
BRISTOL reserves the right to make changes at any time without prior notice. 45
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
APPLICATION
STANDARD FEATURES
Technical Information
UL Listed ; UL 464 - S1529
Operating Voltage 24.0 VDC
CSFM Listed - 7135-0410:0209 Alarm Current 100mA
Product Compliance - NFPA 72 dB at 10ft. 96dB
0500-07170 B6-24 B6-24 6 Fire Alarm Bell, 6", 24V, Coil Driven
BRISTOL reserves the right to make changes at any time without prior notice. 46
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
STANDARD FEATURES
The HEC24 Series has a minimal operation current and has a Switch for continuous or temporal 3 (not available on
minimum flash rate of 1Hz regardless of input voltage. whoop tone)
The HEC24 Series is shipped with the standard 4" metal Surface mount with the (surface mount box)
mounting plate which incorporates the popular Slide feature
Silence horn while strobes remain flashing
that allows the installer to easily test for supervision. The
product also features a locking mechanism which secures the Faceplate available in red or off-white
product to the bracket without any screws showing.
Tamperproof re-entrant grill
The HEC24 Series appliances are UL 464 and UL 1971 listed
for use with fire protective systems and are warranted for
three years from date of purchase.
15(UL 1971)
HEC24-1575WR 0500-05800 124 VDC 70 - 82 100
75(UL 1638)
BRISTOL reserves the right to make changes at any time without prior notice. 47
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
Cont… HEC24-1575WR
Whoop 82 69* 56
NOTES:
• Operating temperature: 32°to 120°F (0° to 49° C). The HEC24 Series is not listed for outdoor use.
• The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output
rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.
• For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave
Rectified]) power, see installation manual. 12VDC models are DC only.
• Not recommend using a coded or pulsing signaling circuit with any of our strobe products (see Technical Bulletin 014).
*Operating the horn in this mode at this voltage will result in not meeting the minimum UL reverberant sound level
required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use
the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always
private mode).
1
RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the
listed voltage range (16-33VDC for 24VDC units) (8-17VDC for 12VDC units). For strobes the UL max current is
usually at the minimum listed voltage (16VDC for 24VDC units) (8VDC for 12VDC units). For audible the max current
is usually at the maximum listed voltage. For unfiltered FWR ratings, see installation manual.
.
BRISTOL reserves the right to make changes at any time without prior notice. 48
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-02
STANDARD FEATURES
Technical Information
Contact (1) Form A
Contact Rating 10A @ 120 VAC
Operating Temperature -30°F (-35 °C) ~ 150°F (66°C)
DESCRIPTION
HPS-DAK-SR is a dual action (lift & pull) fire suppression release manual pull station. HPSDAK-SR model is
constructed of a solid die cast housing and comes in glossy red. The back switch plate is plated steel. The
electrical switch is rated for 10 Amps @ 120 VAC normally open contact rating. All models are connected via
terminal block connections.
BRISTOL reserves the right to make changes at any time without prior notice. 49
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-01
BRISTOL reserves the right to make changes at any me without prior no ce. 48
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-01
BRISTOL reserves the right to make changes at any me without prior no ce. 49
FM-200™ (HFC-227ea) EFS & PFS Product Datasheet BFE/FM200/EPFS/000-01
BRISTOL reserves the right to make changes at any me without prior no ce. 50