Академический Документы
Профессиональный Документы
Культура Документы
A R T I C LE I N FO A B S T R A C T
Keywords: Integrating micro-encapsulated phase change material (PCM) in mortar could enlarge thermal storage capacity
Micro-encapsulated PCM of building thermal mass, however the reduction of conductivity would slow down thermal response. This article
Ventilated mortar blocks proposes a new method by integrating ventilation loops in floor heating phase change material mortar blocks to
Thermal energy storage enhance the energy flexibility, and achieve thermal management. Experiment was carried out to test the thermal
Thermal management
and energy performance of a series of ventilated cement based mortar blocks integrated with micro encapsulated
Space heating performance
phase change material. The amount of phase change material in each block was the same but the distribution
patterns were different, including upper concentrated, lower concentrated and evenly distributed. Three heating
scenarios including single heating, ventilation-heating and intermittent heating were conducted. Results in-
dicated that the distribution of phase change material had strong influence on the thermal storage and heating
performance. In single heating scenario, compared to pure mortar block, phase change material blocks could
increase 11.4% − −18% heating power consumption. In ventilation-heating mode, the outlet air temperature was
higher than the space air, which confirmed the inner space ventilation potential. Ventilation could also prolong
the required heating time and enlarge 7.4% − 13% power consumption of phase change material mortar block,
and reduce 22.7% − 25.6% cooling time. Especially in intermittent heating mode, the space heating performance
of partially concentrated phase change material blocks were much better. Thus, the thermal storage capacity and
energy extraction flexibility of the ventilated mortar blocks integrated with phase change material were vali-
dated, and partially distributed phase change material mortar blocks showed better thermal performance than
evenly distributed phase change material mortar block.
1. Introduction mass and other building heating, ventilation and cooling (HVAC) sys-
tems to manage energy demand [12] and achieve active interaction
Under the emergency of energy shortage and environmental pollu- with surrounding energy network [13], including shifting energy de-
tion, and with the demand of cleaner and sustainable development, mand [14], increasing energy demand flexibility [15,16] and pene-
increasing shares of renewable energy is penetrated in energy system trating more renewable energy [17]. Wang et al. [18] carried out nu-
[1,2]. In IEA report, wind and solar will satisfy 6% and 4% of global merical simulation to study the effect of building thermal mass on the
power demand in 2023 [3]. However the fluctuation and uncertainty of operation flexibility and wind power penetration in a district heating
these renewable energy source would affect the stability of energy network. It was found that building thermal mass could reduce 36.3%
system [4,5], and lead to a surge of infrastructure investment [6]. As a wind power penalty cost, which was resulted from the increase of
competitive alternative compared to other high investment energy re- system flexibility. Similar investigations were made by Heinen et al. [9]
serves, building thermal inertia was reconsidered and has been thought and Alahivl et al. [19]. Fully considering the effect of building thermal
to open up new opportunities for energy system planning and devel- mass could significantly improve the flexibility of both energy networks
opment [7,8], which was always ignored [9]. In this trend, the concept and residential buildings. And accordingly, analyse and improve the
”energy flexible building” arises, as Annex 67 proposed and in- thermal performance of building thermal mass is the basic to achieve
vestigated [10,11]. In this program, the core is to use building thermal flexible operation of energy systems [20], and provide characterization
⁎
Corresponding author.
E-mail address: jyq7245@sina.com (Y. Jiang).
https://doi.org/10.1016/j.enconman.2019.112288
Received 3 September 2019; Received in revised form 11 November 2019; Accepted 12 November 2019
0196-8904/ © 2019 Published by Elsevier Ltd.
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
for optimized control [21]. heating and heat recovery phase [36], which greatly influence the
In most residential buildings, concrete and mortar are the main thermal comfort, and affects the operation flexibility and energy man-
structural thermal mass material [22]. As recently proposed, in- agement [38,39]. This issue would be the same for PCM mortar, and the
tegrating PCM into cement mortar is a fascinating method to improve increase of heat capacity and the reduction of thermal conductivity of
the thermal and energy performance [23], for example, increasing PCM mortar should be dialectically treated and balanced [40,41]. To
thermal capacity, reducing energy demand and improve thermal com- overcome these issues, flexible measures should be adopted. Com-
fort [24]. Pure PCM is faced with leakage issue when directly in- monly, in order to increase the thermal response and operation flex-
corporated with cement, so PCM is usually absorbed in lightweight ibility of thermal storage devices such as PCM tanks, integrating addi-
aggregates or encapsulated in solid polymer shell [25,26]. Compared to tional forced energy extraction systems, such as hydronics systems [42],
lightweight PCM aggregates, the technique of encapsulated PCM is ventilation systems [43] or the combination of both methods [44] were
much more mature and the cost is lower. The leakage of PCM and the adopted. Such systems have been successfully applied in building, for
reduction of compressive strength are comparatively small than the example, the ventilation ceiling [45], floor hydronic radiant system
former [27]. Research on thermal performance and structural strength [46] and ventilation wall,etc. This provides inspiring renovation ap-
of mortar samples integrated with micro encapsulated PCM is abun- proach of building heating system to achieve effective and flexible use
dant, and growing research is focusing on the actual dynamic thermal of structural thermal mass. Cinzia et al. [47] used thermal box to test
performance in small scale experiment, even in actual buildings the thermal and energy performance of a ventilated brick wall. Venti-
[28,29]. Kheradmand et al. [30] embedded three kinds of micro en- lation was validated to efficiently reduce the thermal load. Ref [48] put
capsulated PCM with different melting temperature (10 °C, 26 °C and forward a internal ventilation concrete wall which was filled with PCM,
28 °C ) in plastering mortar block and formed a cubic. Under typical and a small scale experiment confirmed the thermal and energy man-
summer conditions, the inner temperature fluctuation reduced 2.6 °C , ageable character of the designed system. Chen et al. [49] built a
and the energy demand reduced nearly 5 times compared to pure ventilation wall with air channels which were connected to solar col-
mortar cubic. Similar PCM mortar cubic was built by Rasoul et al. [31], lectors. The thermal storage capacity and heat release capacity of the
and different amount of PCM was added. The PCM mortar could sig- passive wall were both enhanced, and the indoor thermal environment
nificantly reduce indoor heat loss, which was resulted from the increase was improved. Whiffen et al. [50] integrated PCM in active ventilation
of heat capacity and the reduction of thermal conductivity. thermal mass system, the prototype experimental result confirmed the
In most current research, the PCM is evenly distributed inside the energy saving potential and relative good thermal conductivity. Com-
mortar mix. In fact, the position and the distribution of PCM in cement pared to other building structures, floor is not directly interacted with
structure is also an interesting and meaningful problem. C. Li et al. [32] outdoor environment, thus has lower thermal loss and is promising to
made two kinds of PCM wallboard: hybrid and multi-layer using three be used as thermal storage. Ref. [51] proposed a under-floor electric
types of phase change materials with different phase change tempera- heating system coupled with duct-less air supply and 15 mm shape-
tures. For the passive wallboard, the multi-layer PCM wallboard per- stabilized PCM plates. PCM and ventilation could effectively shift the
formed better in both delaying heat transfer and releasing heat. Li et al. heating electricity consumption to low price period. Navarro et al. [52]
[33] studied the effect of different positions of PCM layer in the wall. designed a ventilation floor with PCM inside the air duct, and a solar
When the PCM was installed closer to the exterior surface, the heat collector was installed to heat the air. The active system could achieve
transfer reduction was more significant. Similar conclusion was drawn 20% energy saving compared to conventional heat pump heating
by Cao et al. [34]. Yun et al. [35] tested the performance of electric system. Coupled with building thermal conditioning systems, and by
heating PCM floor by changing the position of macro packaged PCM improving the energy flexibility, the thermal storage capacity of floor
fabric. The author emphasized that when the PCM board was placed could be effectively used, and the energy demand flexibility would be
underneath the electrical panel, the heating time was reduced and the enhanced.
heating energy efficiency was increased. From these research, the po- Except for the performance of mortar, the heat transfer between
sition of PCM is an important influencing factor for the thermal per- duct air and the PCM mortar is also another important issue, which
formance of PCM mortar, and would be carefully designed in this re- would influence the heat extraction efficiency. Many factors would
search. influence heat transfer in air flow channel, including the air flow rate
Relevant studies indicated that fully use building thermal mass [53,54], the thermal property of fluid [55,56], the internal structure of
could remarkably increase energy flexibility comprehensively con- channel [57,58], the length of channel [59], the thickness of air channel
sidering the response speed, the amount of energy saving and the ac- [60], etc. Park et al. [61] built a simplified model for the hollow core
tually shifted energy [36,37]. However, the high thermal inertia of ventilated slab system, and the air mass flow rate was fixed. By opti-
thermal mass still make some indicators worse, especially for the mized control, the indoor thermal comfort was improved but energy
2
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
consumption was reduced. Ahmed et al. [62] simulated the thermal each mortar blocks the same. Three kinds of mortar blocks were de-
performance of a hollow ventilation slab which was integrated with signed with different distribution of PCM, and another common cement
micro-encapsulated PCM. They found that the thermal mass, ventilation mortar block without PCM was made as control experiment. The ma-
rate, property of PCM would all influence the thermal performance of terial distribution of each mortar block is shown in Fig. 2. In block B,
ventilation PCM slabs. And with the increasing of ventilation speed, the the micro-encapsulated PCM was evenly distributed, while in block C
heat transfer rate was significantly increased. Sun et al. [63] validated and D, the PCM was concentrated on the upper and lower half of the
that for the PCM ventilation slab, temperature and velocity of inlet air block respectively. In order to make such blocks, four kinds of com-
had great influence on the energy charging speed and the amount of posites were prepared, and their compositions are listed in Table 2. For
heat storage. Laaouatni et al. [48] found that air ventilation in PCM the common mortar mixture, the water-cement mass ratio was 1: 2 , and
thermal storage unit would delay the occurrence of peak temperature. the cement-aggregate mass ratio was 1: 3. While for the PCM mortar
Yang et al. [64] simulated the air heating performance of a ventilation mixture, a practical method was adopted: the volume of added PCM
tube which was surrounded by PCM. With the increase of air volume powder was the same as the replaced sand, and this method could
flow rate, the outlet air temperature and heating capacity increased, but maximally reduce the reduction of structural strength [65,31]. It was
the surface temperature of tube remain almost constant. Research on observed that the PCM used here has strong absorption of water. In
the influence of ventilation parameter on the thermal performance of order to maintain the workability of mortar mixture, after initial test,
ventilated thermal mass provide guidance for this experiment. extra amount of water was added in mortar mixture 2 and 3, which
From literature review, many investigations have been made on the doubled the weight of PCM powder. All the materials were weighted by
thermal response character and energy flexibility of structural PCM electronic weigher with an accuracy of 0.1 g .
cement mortar. And much effort has been made on using auxiliary Fig. 3 shows the procedure of mortar blocks in this experiment, and
forced ventilation or hydronics system to increase energy flexibility. four steps were included. The first step was mixing. First, the cement
This provides foundation and research direction for the innovation use and sand were mixed and stirred for 5 min. Second, the water was
of the existed building thermal mass. However, nearly all research focus added and mixed for 2 min to homogenize the mixture. In the last, the
on the effective use of PCM and ventilation system in wall. When in- PCM powder and additional water were added to the mixture and
tegrated in electric floor heating system, little research is made to in- continued to mixing for another 2 min. This could maximally reduce
vestigate the thermal and energy performance of mortar combined with the damage of PCM capsules and prevent the leakage of paraffin wax.
micro-encapsulated PCM and ventilation loops. Actually, as the change The second step was perfusion. The mixed mortar mud was cast into
of application scenarios, some important parameters should be recon- a square mould with an inner space size of
sidered, for example, the better distribution of mirco-encapsulated PCM 500 mm × 500 mm × 30 mm . Four ventilation copper tubes, with an
in floor structure, and the better ventilation mode based on the con- inner diameter of 10 mm and wall thickness of 1 mm , were placed and
sideration of energy storage and extraction, etc. fixed in the mould in advance, and the positioning error was ± 1mm .
This paper would conduct an experimental study to test the thermal This could prevent the position shifting of tubes caused by the dumping
storage and thermal management character of a series of cement mortar and vibration of mortar. The inner walls of the mould were evenly
blocks, which are integrated with PCM and ventilation loops. The object brushed with oil in advance to remove the mould much more easier.
of this study is to investigate the influence of some structural and op- The third step was vibrating. The moulds were shaken for 2 min to
eration parameters on the thermal performance of PCM mortar block empty the bubbles in mortar mix as much as possible. For block C and D
and inner space, including the distribution position of PCM, the venti- where two kinds of mortar mix with the same volume were needed,
lation mode and the intermittent mode. This analyse would provide contact moulded manufacture process was adopted [28]. The inner
useful guidance for the design and application of such units and sys- space of mould was divided into upper and lower parts with equal
tems. volume and marked dimensions. After mortar mix in the lower part was
spread and shaken, the process was repeated for the upper part and
2. Materials and methodology then complete the multi-layer specimen. The last step was mould re-
moval and maintenance. The mould would be covered with plastic film
2.1. Materials and kept in the lab with the air temperature of 23 ± 1 °C . For mortar
block A, the specimens were removed from the mould after 24 h, then it
In this experiment, the cement was 32.5 ordinary Portland cement, would be packaged in plastic bags and placed in the lab for another
and the aggregate was standard sand, which had been filtered through a 28 days. While for block B, C and D, the higher ratio of water and the
sieve with an aperture of 4.5 mm . No additional plasticizer agent and PCM had strong influence on the hardening process, and the specimens
antifoaming admixture were added. The micro encapsulated phase
change material TH-ME28 used in cement mortar was commercially
available from Saimo Co. Ltd (Hebei, China), whose core was paraffin
wax and was micro encapsulated by polymer shell. The thermal prop-
erties of the used PCM, including melting temperature, solidification
temperature, melting latent heat and solidifying latent heat were ob-
tained by differential scanning calorimeter (DSC). Fig. 1 shows both the
melting and solidifying curves of test PCM sample. It could be observed
that the melting range is between 25 °C and 30 °C , and the solidifying
range is between 18 °C and 22 °C. The phase change range is close to
residential thermal comfort range, especially for floor heating system.
The other thermal and physical properties of PCM are listed in Table 1,
among them, the relative small density is quite promising to reduce the
weight of cement mortar.
3
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
Table 1
Properties of PCM.
Item Average Density (kg/m3 ) Peak melting Melting Peak solidification Solidification
diameter (μm ) temperature (°C ) latent heat (kJ/kg) temperature (°C ) latent heat (kJ/kg)
Table 2
Mass and proportion of mix compositions.
Item Material Composite 1 Composite 2 Composite 3 Composite 4 Sum of
composite 3 and 4
4
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
were demoulded after 72 h and tested after 28 days. system of air pump to modify the air supply volume. The temperature of
the cold air that flow through the air pump would rise about 10 °C, so a
recooling strategy was adopted. The air came from the cold source was
2.3. Thermal test
separated into two parts, one part flowed through the pump, the air-air
heat exchanger, the value in turn and finally flowed into the air duct.
2.3.1. System description
The other part was used to cool down the air in the air -air heat ex-
In this experiment, the mainly focus is the thermal performance of
changer. The air supply loops were all well insulated by polyethylene
different mortar blocks and their influence on indoor thermal en-
pipe to reduce to minimum heat loss.
vironment. The thermal mass of building envelopes was not considered.
The lower surface of mortar block was heated by residential elec-
Furthermore, the air ventilated through the block was directly ex-
trothermal film, and the rated heating power was 55 W. In actual op-
hausted and not circulated inside the test unit in current stage. Guided
eration, it was observed that the heating power would keep at 64 ± 1 W.
by these ideas, an artificial environment chamber was built referring to
The power to heat ratio was assumed to be 1 for all experiments. To
GB/T 13754 − 2008. The inner ventilation experiment would be carried
maximally reduce the heat loss of mortar blocks, a 50 mm high density
out as follow-up work. Fig. 4 shows the simplified system schematic
polyethylene foam board, whose thermal conductivity λ was 0.025
diagram, which mainly consists of the test unit, the chamber, the inner
W/m·K , was placed underneath the electrothermal film and used to
temperature control system and the duct air supply system. Fig. 5 gives
thermal insulate the four sides of the mortar block. To confirm the re-
some pictures of the experimental system. The test unit was a steel box
lative small heat loss, the proportion of the accumulated heat dissipated
with a size of 1500 mm × 1500 mm × 1000 mm . The dimension was
from the lower insulation board (Ql , calculated by Eq. 1) to the total
designed based on following consideration. In our heating experiment,
supplied heating power (Qs ) was calculated. Considering the fact that
the Grashof number (Gr) exceeded 5000, meaning the free convective
for these blocks, the height is far smaller than the width, so the heat loss
flow within the test unit was disordered, and entered self-stimulated
from side surfaces could be ignored [67]. The uncertainty analysis of Ql
status [66]. So the heat transfer of free convective flow within the unit
in this paper was referred to Ref [68]. In current experiment, the un-
would be not influenced by the dimension. Based on this fact, the test
certainty of Ql was 1.5%.
unit was designed as a scaling model referring to an actual room with
n
dimension of 4000 mm × 4000 mm × 2800 mm . The inner walls of the
unit were evenly painted with non-mentallic matt paint, and the surface
Ql = ∑ (Tins, u, i − Tins, d, i ) λAΔt / δ
i=1 (1)
emissivity was above 0.9. Each side of unit box was sealed with tape to
prevent the external air entering the box.
To keep a uniform outside thermal environment of the test unit, a 2.3.2. Parameter measurement
top orifice ventilation system was built in the chamber, and the unit Fig. 6 shows the arrangement of temperature sensors. The surface
was placed in the middle of the chamber and 20 cm above the ground. temperature, including the mortar block, the electrothermal film, the
The chamber was well insulated to guarantee a stable inner thermal insulation board and the wall of test unit, were all measured by surface
environment. The thermal conditioning system inside the chamber was probe sensors. Air temperature sensors were arranged at the height of
controlled by a PID controller, which monitored the temperature of 50 cm and 75 cm in the test unit separately to verify vertical tem-
return air. perature stratification. Especially, the air temperature sensors were
The duct air supply system consisted of cold air source, a pressur- specially handled by covering cylindrical aluminium caps to prevent
ized air pump, an air-air heat exchanger, an air separator and four air direct thermal radiation from heating surface. The inlet and outlet
flow value. A frequency modulator was installed in the power supply temperature of ventilation ducts were measured by 8 armoured tube
Fig. 4. Schematic of system. 1) Duct air supply system; 2) Air shunt; 3) Mortar block; 4) Air interflow; 5) Test unit; 6) Indoor air ventilation and control devices; 7)
Top orifice ventilation system; 8) Environment chamber.
5
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
temperature sensors. The above temperature sensors were all Pt1000 2.3.3. Experiment description
with an accuracy of 0.02 °C in the range of 0 °C – 50 °C . And they were In order to test the thermal performance of the mortar block, three
all calibrated by CTR5000 temperature calibration equipment (in- experiments were executed. As suggested in JGJ142 − 2012, the average
cluding standard thermometer and silicone oil bath) in the temperature surface temperature of the mortar block, Tu , was taken as the control
range of − 10 °C–60 °C. The detail of temperature sensor calibration signal. For the set of ambient temperature, in current experiment,
could refer to [69,70]. thermal mass and thermal insulation of envelops were not considered. If
The total air volume flow rate was measured by mass flow meter the ambient temperature was set at a low level, even below zero, the
MF5712, whose range was 0 − 200 L/min and the uncertainty was thermal storage and space heating performance would be hard to be
± (2.0 + 0.5FS) . The flow rate of each air flow branch was measured observed. Actually, the current research focused on horizontally com-
and adjusted by LZJ − 10 rotor flow meter with an range of 160 − 1600 pare the thermal storage and heating performance of the four mortar
L/h and an uncertainty of 2.5FS . Each rotor flow meter was equipped blocks, and comprehensively considering the demand experimental
with air valve to balance the air flow rate of four loops. The in- time, the air temperature in the chamber was kept at 16 °C to guarantee
stantaneous power and the total energy consumption of the electro- a heating scenario. The air velocity around the test unit was 0.5 m/s.
thermal film was measured by PZEM − 014 power monitoring device. In the first experiment, a single heating test was carried out to test
The accuracy was 0.5% . All the parameters were collected by data ac- the thermal storage character of mortar block. Initially, the mortar
quisition instrument Agilent 34980A every 10 s and transmitted to block was naturally cooled down, which usually took about 3 h. When
computer. Tu reached 18 °C , the electrothermal film was turned on to heat the
mortar block. Afterwards when Tu reached 30 °C , the electrothermal
6
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
film was turned off and the experiment would be ceased when Tu was in the cooling stage, the descent rate of average temperature on the left
cooled to 18 °C again. side (Tl ), which was close to the duct air inlet, was higher than the right
In the second experiment, different ventilation modes with different side (Tr ). For block C, the maximum temperature deviation between left
ventilation starting time and volume flow rate were conducted to test and right sides was 1.5 °C , which was the highest among the four blocks.
the thermal performance of mortar block. In ventilation mode 1, the For other blocks A, B and D, the temperature deviation was approxi-
duct started to ventilate after the electrothermal film was turned off. In mately 0.9 − 1.2 °C . Thus ventilation has influence on the surface
ventilation mode 2, the duct was ventilated through the whole ex- temperature distribution of mortar block.
periment. The initial inlet temperature was controlled at 16.5 °C for For ventilation mode 2 where the air duct was ventilated through
each experiment. The heating strategy was the same as experiment 1. the whole experiment, compared to the scenario without ventilation,
Different power frequency of the air pump, including 50 Hz, 40 Hz and the demand heating time was extended. The prolonged demand heating
30 Hz were implemented to change the volume flow rate. And it was time of block C was the longest, which was about 600 s. While block D
observed that the corresponding mean volume flow rate (q) of supply has the shortest demand heating time extension. Moreover, for each
air were 55.1 L/min, 45.1 L/min and 30.6 L/min respectively. mortar block, the cooling period was nearly the same for both venti-
The third experiment was to test the thermal and space heating lation modes. Furthermore, the uneven distribution of surface tem-
performance of mortar blocks in intermittent heating mode. The total perature appeared from the start of duct ventilation. Block C had the
heating time was 240 min for each block. 3 kinds of strategies with maximal temperature deviation between the two sides, which was
different intermittent heating period: 20 min, 40 min and 60 min were 2.0 °C. And for other blocks, the deviation were between 1.3 °C to 1.7 °C,
adopted. When reaching the set total heating time, the mortar blocks which were all higher than ventilation mode 1.
would be naturally cooled down, resemble experiment 1. Fig. 13 shows the average inlet and outlet temperature of the four
air ducts of each mortar block in two ventilation modes. Influenced by
3. Experiment result and discussion the heating of mortar, the inlet air temperature (Tin ) maximally in-
creased about 0.2 °C during the experiment. For each block, the outlet
3.1. Reproducibility test air temperature in ventilation mode 2 (Tout,2 ) was higher than mode 1
(Tout,1). In ventilation mode 1, Tout rise immediately after the air pump
In order to verify experimental reproducibility, experiment 1 and 3 was turned on. After about 2000 s, Tout reached the peak and slowly
were repeated four times for each mortar block. Fig. 7 and 8 present the decreased with naturally cooling of mortar block. It was observed that
variation of Tu and the center temperature at the height of 50 cm block D had the quickest duct air heating rate, indicating that the
(Ts, c,50 ), which were described by the mean temperature and the error temperature of inside copper tube was the highest. Block B and C had
bar. The error bar was formulated by standard deviation. For the same the slowest heating rate. And the maximal temperature difference be-
block, the maximum deviation of Tu and Ts, c,50 was 0.21 °C and 0.28 °C, tween Tout and Tin was about 2.0 °C for block A and B, 2.3 °C for block C
which showed a relative good reproducibility of this experiment. Fur- and 2.5 °C for block D. In ventilation mode 2, Tout increased with the
thermore, thermal performance difference of the four mortar blocks heating of mortar blocks. For block A and B, the maximal temperature
could be initially observed. And more detailed testing results would be difference between Tout and Tin were about 2.7 °C. While for block C and
given later. D, it was about 3.2 °C . And Tout peaked at 5000 and 4200 s for mortar D
and A respectively, which were the slowest and the quickest among the
3.2. Single heating test four blocks. Block B and C had similar Tout peak time. This indicating
that the inside material distribution has strong influence on the heating
Fig. 9–12 show the measured Tu of each block, and Tu,1 is the mortar rate of inside copper tube. It should also be noticed that the final outlet
surface temperature in single heating test. For the heating stage, block temperature was still higher than the inlet temperature, so the thermal
A took about 3130 s, which was the shortest among the four mortar energy in mortar blocks was not fully extracted. Restricted by the preset
blocks. Block B and C consumed similar heating time, and it was about control strategy, the left stored thermal energy in the mortar would be
3600 s. While block D consumed the longest heating time, which was not fully used.
about 3880 s and 24% longer than the pure cement mortar A. For the Take mortar block B for example, Fig. 14 presents Tout of block B
cooling stage, it took about 16830 s for PCM block C to cool down to under different ventilation rate. For both ventilation modes, the
18 °C , which was the most enduring among the blocks. The cooling time
of block D and block B decreased orderly, and block A had the shortest
cooling duration, which was 12.5% shorter than block C. Heating hys-
teresis could be observed for each block, and the highest Tu of block D
was 0.5 °C higher than block A.
According to heat transfer principle, under the same heating flux,
the temperature deviation between the upper and lower surface (Tu -Td )
is in proportion to the thermal resistance. From block A to D, the de-
viation were 2.69 °C, 5.44 °C, 5.96 °C and 8.55 °C . It could be found that
block B and C have similar thermal resistance, and block D has the
highest equivalent thermal resistance.
In Fig. 9–12, Tu,2 and Tu,3 are the mortar surface temperature in
ventilation mode 1 and 2. The power frequency of air pump in each
experiment was set at 50 Hz. For ventilation mode 1, the demand
cooling time reduced a lot. Compared to naturally cooling, the cooling
period reduced by 19%, 22.7%, 23.2% and 25.6% from block A to D re-
spectively. So regarding to the cooling stage, mortar D is the most
sensitive to duct ventilation. Especially, the temperature distribution on
mortar surface was influenced by duct ventilation. As shown in figures, Fig. 7. Reproducibility test: Tu of four mortar blocks.
7
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
8
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
from reproducibility test. was the most significant which slowed down the inside heating process.
In single heating test, compare the three PCM blocks, although the So under the current heating control strategy, the heating energy of
amount of PCM were nearly the same, the energy consumption were a block D increased a little.
little different. Block B and C consumed similar heating power, and In ventilation–heating test, the heating energy consumption of each
11.4% higher than block A. And block D consumed the most energy, block in mode 2 increased. This might be caused by the fact that air
which was 18.0% larger than block A. For block D, due to the fact that took out the heat in mortar blocks, and increased the thermal resistance
the PCM was concentrated on the lower part, the heat absorption effect in the vertical direction inside the block. Compared to single heating
9
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
4. Conclusion
In this study, a series of new mortar blocks for floor heating that
combined ventilation loops and micro-encapsulated phase change ma-
terial are made. A specially designed thermal testing system is also built
to evaluate both thermal and the space heating performance of these
blocks. Three influencing factors, including the distribution of PCM, the
ventilation and the intermittent heating duration are investigated in
experiments. Although the results in current small scale experiment are
hard to be generalized in real scale building, they prove encouraging
flexibility of this new ventilated PCM block towards practical applica-
tion. The overall results show that the micro encapsulated PCM could
significantly enhance the thermal storage performance, and the venti-
lation duct inside the mortar blocks could increase the thermal release
flexibility. Following are the main conclusions and findings:
Fig. 14. Tout of mortar block B under different ventilation rate.
1)Although the amount of added PCM for each mortar block is only
test, the energy consumption of block A and B increased 8.2% and 7.4%. about 0.8 kg, it significantly changes the thermal performance in
The increase of block C and D were 13.0% and 12.5% respectively. both heating and cooling stages. The thermal performance is highly
In summary, the distribution of material inside the mortar block and related to the distribution of PCM, which was always ignored by
the ventilation mode have certain influence on the heating energy related research. If PCM is concentrated on the lower part, the
consumption. On the condition of the same amount of PCM, when the heating period and electricity consumption increase most among the
PCM is evenly distributed, the increase of heating energy is nearly the PCM mortar blocks. In naturally cooling scenario, the upper con-
same as pure mortar block. However when the PCM is partially centrated PCM block extend the cooling period most.
10
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
all have influence on the outlet temperature of air duct. The evenly
distributed PCM mortar block shows nearly the same duct air
heating performance as the pure mortar block, and both are poorly
than the partially concentrated PCM mortar blocks. Although the
maximal outlet air temperature increases as the increasing of ven-
tilation rate, the growing trend is tapering off.
5)In intermittent heating mode, the four blocks show different space
heating performance. For the block where PCM is concentrated on
the upper part, the temperature at the center of the test unit is
maximal, and exceeds 18 °C for the longest time. However for the
evenly distributed PCM block, the space heating performance is
relatively poor.
Fig. 17. Ts, c,50, Ts, c,75, Ts, ave,50 and Ts, ave,75 of block C.
11
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
12
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
13
J. Guo, et al. Energy Conversion and Management 205 (2020) 112288
https://doi.org/10.1016/j.cma.2019.02.025. URL:http://www.sciencedirect.com/ cylindrical pcm-to-air heat exchanger (pahe) for free ventilation cooling in fluctu-
science/article/pii/S0045782519300969. ating ambient environments. Sustain. Cities Soc. 2019;51:101764https://doi.org/
[57] Sheikholeslami M, Jafaryar M, Hedayat M, Shafee A, Li Z, Nguyen TK, Bakouri M. 10.1016/j.scs.2019.101764. http://www.sciencedirect.com/science/article/pii/
Heat transfer and turbulent simulation of nanomaterial due to compound turbulator S2210670719315483.
including irreversibility analysis. Int. J. Heat Mass Transf. 2019;137:1290–300. [65] Pilehvar S, Cao VD, Szczotok AM, Valentini L, Salvioni D, Magistri M, Pamies R,
https://doi.org/10.1016/j.ijheatmasstransfer.2019.04.030. URL:http://www. Kjüniksen A-L. Mechanical properties and microscale changes of geopolymer con-
sciencedirect.com/science/article/pii/S0017931019301255. crete and portland cement concrete containing micro-encapsulated phase change
[58] Li Z, Shafee A, Ramzan M, Rokni HB, Al-Mdallal QM. Simulation of natural con- materials. Cem. Concr. Res. 2017;100:341–9. https://doi.org/10.1016/j.cemconres.
vection of fe3o4-water ferrofluid in a circular porous cavity in the presence of a 2017.07.012. URL:http://www.sciencedirect.com/science/article/pii/
magnetic field. Eur. Phys. J. Plus 2019;134(2):77. https://doi.org/10.1140/epjp/ S0008884617300352.
i2019-12433-5. [66] J. Holman, Heat Transfer, tenth ed., 2010.
[59] Dardir M, Panchabikesan K, Haghighat F, Mankibi ME, Yuan Y. Opportunities and [67] Frazzica A, Brancato V, Palomba V, Rosa DL, Grungo F, Calabrese L, Proverbio E.
challenges of pcm-to-air heat exchangers (pahxs) for building free cooling appli- Thermal performance of hybrid cement mortar-pcms for warm climates application.
cations-a comprehensive review. J. Energy Storage 2019;22:157–75. https://doi. Sol. Energy Mater. Sol. Cells 2019;193:270–80. https://doi.org/10.1016/j.solmat.
org/10.1016/j.est.2019.02.011. URL:http://www.sciencedirect.com/science/ 2019.01.022. URL:http://www.sciencedirect.com/science/article/pii/
article/pii/S2352152X18307096. S0927024819300327.
[60] Sardari PT, Grant D, Giddings D, Walker GS, Gillott M. Composite metal foam/pcm [68] Wang Y, Shen C, Tang Z, Yao Y, Wang X, Park B. Interaction between particulate
energy store design for dwelling space air heating. Energy Convers. Manage. fouling and precipitation fouling: Sticking probability and deposit bond strength.
2019;201:112151https://doi.org/10.1016/j.enconman.2019.112151. URL:http:// Int. J. Heat Mass Transf. 2019;144:118700https://doi.org/10.1016/j.
www.sciencedirect.com/science/article/pii/S0196890419311574. ijheatmasstransfer.2019.118700. URL:http://www.sciencedirect.com/science/
[61] Park B, Krarti M. Optimal control strategies for hollow core ventilated slab systems. article/pii/S0017931019330297.
J. Build. Eng. 2019;24:100762https://doi.org/10.1016/j.jobe.2019.100762. [69] Shen C, Wang Y, Zhao Z, Jiang Y, Yao Y. Decoupling analysis on the variations of
URL:http://www.sciencedirect.com/science/article/pii/S2352710218310428. liquid velocity and heat flux in the test of fouling thermal resistance. Int. J. Heat
[62] Faheem A, Ranzi G, Fiorito F, Lei C. A numerical study on the thermal performance Mass Transf. 2018;123:227–38. https://doi.org/10.1016/j.ijheatmasstransfer.2018.
of night ventilated hollow core slabs cast with micro-encapsulated pcm concrete. 02.099. URL:http://www.sciencedirect.com/science/article/pii/
Energy Build. 2016;127:892–906. https://doi.org/10.1016/j.enbuild.2016.06.014. S0017931017335846.
URL:http://www.sciencedirect.com/science/article/pii/S0378778816305035. [70] Shen C, Wang Y, Tang Z, Yao Y, Huang Y, Wang X. Experimental study on the
[63] Sun X, Chu Y, Medina MA, Mo Y, Fan S, Liao S. Experimental investigations on the interaction between particulate fouling and precipitation fouling in the fouling
thermal behavior of phase change material (pcm) in ventilated slabs. Appl. Therm. process on heat transfer tubes. Int. J. Heat Mass Transf. 2019;138:1238–50. https://
Eng. 2019;148:1359–69. https://doi.org/10.1016/j.applthermaleng.2018.12.032. doi.org/10.1016/j.ijheatmasstransfer.2019.04.136. URL:http://www.sciencedirect.
URL:http://www.sciencedirect.com/science/article/pii/S1359431118362124. com/science/article/pii/S0017931019302777.
[64] Yang D, Shi R, Wei H, Du J, Wang J. Investigation of the performance of a
14