Вы находитесь на странице: 1из 139

7/25/2019 Sicam Tm Io Module Eng

Preface, Table of Contents

Introduction
SICAM RTUs 1
Standard I/O Modules 2
I/O Modules Safety I/O Modules 3
Literature

DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 1/139
7/25/2019 Sicam Tm Io Module Eng

Note

Please observe Notes and Warnings for your own safety in the Preface.

Translation of the original instructions

Disclaimer of Liability Copyright


 Although we have carefull y checked the contents of this public ation Copyright © Siemens AG 2014
for conformity with the hardware and software described, we cannot
guarantee complete conformity since errors cannot be excluded. The reproduction, transmission or use of this document or its
contents is not permitted without express written authority.
The information provided in this manual is checked at regular  Offenders will be liable for damages. All rights, including rights
intervals and any corrections that might become necessary are created by patent grant or registration of a utility model or design,
included in the next releases. Any suggestions for improvement are are reserved.
welcome.
Subject to change without prior notice.
Document Label:
SICRTUs-HBIOMODULE-ENG_V2.06
Issuing date:
2014.04.11

Siemens AG Order no.: DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 2/139
7/25/2019 Sicam Tm Io Module Eng

Preface

This document is applicable to the follow ing product(s):

·  SICAM TM
·  SICAM MIC
·  SICAM EMIC

Purpose of this m anual

This manual describes the characteristics and functions of all SICAM TM 1703 input/output
modules.

It contains:

·  Functional Overviews
·  Technical Specifications
·  Interface Descriptions
·  External Circuit Elements

Target Group

The document you are reading right now is addressed to users, who are in charge of the
following engineering tasks:
·  Conceptual activities, as for example design and configuration
·  Creation of the assembly technical documentation using the designated engineering tools
·  System parameterization and system diagnostic, using the designated engineering tools
·  Technical system maintenance

Placement in the Information Landscape

Document Item number  


Common Functions Peripheral Elementes according to IEC 60870-5-101/104 DC0-011-2

 ACP 1703 Platforms – Configuration - Automation Units and Automati on Networks DC0-021-2
SICAM 1703 – AK 1703 ACP User Manual DC2-016-2

SICAM 1703 – AK 1703 ACP System Description MC2-020-2


System Element Manual PE-641x/USIO66 DC6-033-2

System Element Manual PE-641x/TCIO66 DC6-037-2


CP-60xx/CPC60 System Manual TM 1703 mic DC6-031-2
System Element Manual CP-6010/USIO36 DC6-043-2
System Element Manual AI-630x/TIPS05 DC6-019-2

SICAM RTUs, I/O Modules 3


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 3/139
7/25/2019 Sicam Tm Io Module Eng

Notes on Safety

This manual does not constitute a complete catalog of all safety measures required for 
operating the equipment (module, device) in question because special operating conditions
might require additional measures. However, it does contain notes that must be adhered to for 
your own personal safety and to avoid damage to property. These notes are highlighted with a
warning triangle and different keywords indicating different degrees of danger.

Danger 
means that death, serious bodily injury or considerable property damage will occur, if th e appropriate
precautionary measures are not carried out.

Warning
means that death, serious bodily injury or considerable property damage can  occur, if the appropriate
precautionary measures are not carried out.

Caution

means
are not that minor
carried out.bodily injury or property damage could occur, if the appropriate precautionary measures

Note
is important information about the product, the handling of the product or the respective part of the
documentation, to which special attention is to be given.

Qualified Personnel
Commissioning and operation of the equipment (module, device) described in this manual must be
performed by qualified personnel only. As used in the safety notes contained in this manual, qualified
personnel are those persons who are authorized to commission, release, ground, and tag devices,
systems, and electrical circuits in accordance with safety standards.
Use as Prescri bed
The equipment (device, module) must not be used for any other purposes than those described in the
Catalog and the Technical Description. If it is used together with third-party devices and components,
these must be recommended or approved by Siemens.

Correct and safe operation of the product requires adequate transportation, storage, installation, and
mounting as well as appropriate use and maintenance.
During operation of electrical equipment, it is unavoidable that certain parts of this equipment will carry
dangerous voltages. Severe injury or damage to property can occur if the appropriate measures are not
taken:

·  Before making any connections at all, ground the equipment at the PE terminal.
·  Hazardous voltages can be present on all switching components connected to the power supply.
·  Even after the supply voltage has been disconnected, hazardous voltages can still be present in the
equipment (capacitor storage).
·  Equipment with current transformer circuits must not be operated while open.
·  The limit values indicated in the manual or the operating instructions must not be exceeded; that also
applies to testing and commissioning.

Consider obligatory the safety rules for the accomplishment of works at electrical plants:

1. Switch off electricity all-pole and on all sides!


2. Ensure that electricity cannot be switched on again!
3. Double check that no electrical current is flowing!
4. Discharge, ground, short circuit!
5. Cover or otherwise isolate components that are still electrically active!

4 SICAM RTUs, I/O Modules


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 4/139
7/25/2019 Sicam Tm Io Module Eng

Table of Contents

1 Introd uct ion ................................................................................................................. 11

1.1 Application ..................................................................................................... 12


1.2 Modules ......................................................................................................... 13
1.2.1 Standard I/O Modules................................................................................ 13
1.2.2 Safety I/O Modules .................................................................................... 13
1.3 Systems ......................................................................................................... 14
1.3.1 SICAM TM, SICAM AK .............................................................................. 14
1.3.2 SICAM MIC ............................................................................................... 15
1.3.3 SICAM EMIC ............................................................................................. 15
1.4 I/O Modules Dimensions ................................................................................. 16
1.4.1 I/O Moduls with single module width .......................................................... 16
1.4.2 I/O Modul with double module width........................................................... 17

2 Standard I/O Modules.................................................................................................. 19

2.1 DI-6100 .......................................................................................................... 20


2.1.1 Features and Functions ............................................................................. 20
2.1.2 View .......................................................................................................... 20
2.1.3 Technical Specifications ............................................................................ 21
2.1.4 Pin Assignment and Display ...................................................................... 22

2.1.5 Block Diagram and External Circuitry ......................................................... 23


2.2 DI-6101 .......................................................................................................... 24
2.2.1 Features and Functions ............................................................................. 24
2.2.2 View .......................................................................................................... 24
2.2.3 Technical Specifications ............................................................................ 25
2.2.4 Pin Assignment and Display ...................................................................... 26
2.2.5 Block Diagram and External Circuitry ......................................................... 27
2.3 DI-6102 .......................................................................................................... 28
2.3.1 Features and Functions ............................................................................. 28
2.3.2 View .......................................................................................................... 28
2.3.3 Technical Specifications ............................................................................ 29
2.3.4 Pin Assignment and Display ...................................................................... 30
2.3.5 Block Diagram and External Circuitry ......................................................... 31
2.4 DI-6103 .......................................................................................................... 32
2.4.1 Features and Functions ............................................................................. 32
2.4.2 View .......................................................................................................... 32
2.4.3 Technical Specifications ............................................................................ 33
2.4.4 Pin Assignment and Display ...................................................................... 34
2.4.5 Block Diagram and External Circuitry ......................................................... 35

2.5 DI-6104 .......................................................................................................... 36


2.5.1 Features and Functions ............................................................................. 36

SICAM RTUs, I/O Modules 5


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 5/139
7/25/2019 Sicam Tm Io Module Eng

Table of Contents

2.5.2 View .......................................................................................................... 36


2.5.3 Technical Specifications ............................................................................37
2.5.4 Pin Assignment and Display ...................................................................... 38
2.5.5 Block Diagram and External Circuitry.........................................................39
2.6 DO-6200 ........................................................................................................ 40
2.6.1 Features and Functions ............................................................................. 40
2.6.2 View .......................................................................................................... 40
2.6.3 Technical Specifications ............................................................................41
2.6.4 Pin Assignment and Display ...................................................................... 42
2.6.5 Block Diagram and External Circuitry.........................................................43
2.7 DO-6212 ........................................................................................................ 44
2.7.1 Features and Functions ............................................................................. 44
2.7.2 View .......................................................................................................... 44

2.7.3 Technical Specifications ............................................................................45


2.7.4 Pin Assignment and Display ...................................................................... 46
2.7.5 Block Diagram and External Circuitry.........................................................47
2.8 DO-6220 ........................................................................................................ 50
2.8.1 Features and Functions ............................................................................. 50
2.8.2 View .......................................................................................................... 50
2.8.3 Technical Specifications ............................................................................51
2.8.4 Pin Assignment and Display ...................................................................... 52
2.8.5 Block Diagram and External Circuitry.........................................................53
2.9 DO-6221 ........................................................................................................ 54
2.9.1 Features and Functions ............................................................................. 54
2.9.2 View .......................................................................................................... 54
2.9.3 Technical Specifications ............................................................................55
2.9.4 Pin Assignment and Display ...................................................................... 56
2.9.5 Block Diagram and External Circuitry.........................................................57
2.10 DO-6230 ........................................................................................................58
2.10.1 Features and Functions .............................................................................58
2.10.2 View .......................................................................................................... 58
2.10.3 Technical Specifications ............................................................................ 59
2.10.4 Pin Assignment and Display ......................................................................60
2.10.5 Block Diagram and External Circuitry.........................................................61
2.11 AI-6300 ..........................................................................................................67
2.11.1 Features and Functions .............................................................................67
2.11.2 View .......................................................................................................... 67
2.11.3 Technical Specifications ............................................................................ 68
2.11.4 Pin Assignment and Display ......................................................................69
2.11.5 Block Diagram and External Circuitry.........................................................70
2.12 AI-6307 ..........................................................................................................71
2.12.1 Features and Functions .............................................................................71

2.12.2 View .......................................................................................................... 71


2.12.3 Technical Specifications ............................................................................ 72

6 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 6/139
7/25/2019 Sicam Tm Io Module Eng

Table of Contents

2.12.4 Pin Assignment and Display ...................................................................... 73


2.12.5 Block Diagram and External Circuitry ......................................................... 74
2.13 AI-6308 .......................................................................................................... 75
2.13.1 Features and Functions ............................................................................. 75
2.13.2 View .......................................................................................................... 75
2.13.3 Technical Specifications ............................................................................ 76
2.13.4 Pin Assignment and Display ...................................................................... 77
2.13.5 Block Diagram and External Circuitry ......................................................... 78
2.14 AI-6310 .......................................................................................................... 79
2.14.1 Features and Functions ............................................................................. 79
2.14.2 View .......................................................................................................... 79
2.14.3 Technical Specifications ............................................................................ 80
2.14.4 Pin Assignment and Display ...................................................................... 81

2.14.5 Block Diagram and External Circuitry ......................................................... 82


2.15 AO-6380......................................................................................................... 83
2.15.1 Features and Functions ............................................................................. 83
2.15.2 View .......................................................................................................... 83
2.15.3 Technical Specifications ............................................................................ 84
2.15.4 Pin Assignment and Display ...................................................................... 85
2.15.5 Block Diagram and External Circuitry ......................................................... 86
2.16 TE-6420 ......................................................................................................... 87
2.16.1 Features and Functions ............................................................................. 87
2.16.2 View .......................................................................................................... 87
2.16.3 Technical Specifications ............................................................................ 88
2.16.4 Pin Assignment and Display ...................................................................... 89
2.16.5 Block Diagram and External Circuitry ......................................................... 90
2.17 TE-6450 ......................................................................................................... 91
2.17.1 Features and Functions ............................................................................. 91
2.17.2 View .......................................................................................................... 91
2.17.3 Technical Specifications ............................................................................ 92
2.17.4 Pin Assignment and Display ...................................................................... 93
2.17.5 Block Diagram and External Circuitry ......................................................... 94
2.18 TE-6430 ......................................................................................................... 95
2.18.1 Features and Functions ............................................................................. 95
2.18.2 View .......................................................................................................... 95
2.18.3 Technical Specifications ............................................................................ 96
2.18.4 Pin Assignment and Display ...................................................................... 98
2.18.5 Block Diagram and External Circuitry ......................................................... 99

3 Safety I/O Modules ....................................................................................................101

3.1 DI-6170 ........................................................................................................102


3.1.1 Features and Functions ...........................................................................102

3.1.2 View ........................................................................................................103


3.1.3 Technical Specifications ..........................................................................104

SICAM RTUs, I/O Modules 7


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 7/139
7/25/2019 Sicam Tm Io Module Eng

Table of Contents

3.1.4 Pin Assignment and Display .................................................................... 105


3.1.5 Unique Module Number...........................................................................106
3.1.6 Block Diagram ......................................................................................... 107
3.1.7 External Circuit Elements ........................................................................108
3.1.7.1 Error Detection on the External Circuitry ............................................. 108
3.1.7.2 Single-Channel Sensor without Test Pulse (achievable SIL 2) ............ 109
3.1.7.3 Single-Channel Sensor without Test Pulse – Sensor supply external
(achievable SIL 2) .............................................................................. 109
3.1.7.4 Double-Channel Sensor with homogeneous Channels without Test Pulse
(achievable SIL 3) .............................................................................. 110
3.1.7.5 Double-Channel Sensor with homogeneous Channels without Test Pulse
- Sensor supply external (achievable SIL 3) ........................................ 111
3.1.7.6 Double-Channel Sensor with diverse Channels without Test Pulse
(achievable SIL 3) .............................................................................. 112

3.1.7.7 Single-Channel Sensor with Test Pulse (achievable SIL 2) ................. 113
3.1.7.8 Double-Channel Sensor with homogeneous Channels with Test Pulse
(achievable SIL 3) .............................................................................. 114
3.1.7.9 Double-Channel Sensor with homogeneous Channels with Test Pulse
(achievable SIL 3) .............................................................................. 115
3.1.7.10 Double-Channel Sensor with diverse Channels with Test Pulse
(achievable SIL 3) .............................................................................. 116
3.2 DO-6270 ......................................................................................................117
3.2.1 Features and Functions ...........................................................................117
3.2.2 View ........................................................................................................ 117
3.2.3 Technical Specifications .......................................................................... 118
3.2.4 Pin Assignment and Display .................................................................... 120
3.2.5 Unique Module Number...........................................................................121
3.2.6 Block Diagram ......................................................................................... 122
3.2.7 External Circuit Elements ........................................................................123
3.2.7.1 Error Detection on the External Circuitry ............................................. 123
3.2.7.2 Overview - Circuitry of the Output Driver ............................................. 124
3.2.7.3 Example: Two-channel circuitry with relay diversity with read-back of the
relay contact; relay without electronic.................................................. 125
3.2.7.4 Example: Two-channel circuitry with relay diversity without read-back of 
the relay contact; Relay without electronic .......................................... 126
3.2.7.5 Example: Emergency stop device 1; Relay with electronic ..................127
3.2.7.6 Example: Emergency stop device 2; Relay with electronic ..................128
3.2.7.7 Transient effects of the external circuitry with external load ................. 129
3.3 AI-6370 ........................................................................................................ 130
3.3.1 Features and Functions ...........................................................................130
3.3.2 View ........................................................................................................ 131
3.3.3 Technical Specifications .......................................................................... 132
3.3.4 Pin Assignment and Display .................................................................... 134
3.3.5 Unique Module Number...........................................................................135
3.3.6 Block Diagram ......................................................................................... 136
3.3.7 External Circuit Elements ........................................................................137

8 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 8/139
7/25/2019 Sicam Tm Io Module Eng

Table of Contents

3.3.7.1 Error Detection on the External Circuitry ............................................. 137


3.3.7.2 Circuitry Examples..............................................................................137
3.4 Fault exclusion by constructional measures ..................................................138

SICAM RTUs, I/O Modules 9


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 9/139
7/25/2019 Sicam Tm Io Module Eng

Table of Contents

10 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 10/139
7/25/2019 Sicam Tm Io Module Eng

1 Introduction

Contents

1.1 Application ..................................................................................................... 12


1.2 Modules ......................................................................................................... 13
1.3 Systems ......................................................................................................... 14
1.4 I/O Modules Dimensions ................................................................................. 16

SICAM RTUs, I/O Modules 11


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 11/139
7/25/2019 Sicam Tm Io Module Eng

Introduction

1.1 Application

The I/O modules (input/output modules) are used in the peripheral elements of the
SICAM RTUs products SICAM TM, SICAM MIC and SICAM EMIC.

SICAM TM Peripheral Elements


Peripheral Element Designation

PE-6410/USIO66 Peripheral Controller Universal Signal In-/Output (Ax-PE Bus el)

PE-6411/USIO66 Peripheral Controller Universal Signal In-/Output (Ax-PE Bus opt)

PE-6412/USIO66 Peripheral Controller Universal Signal In-/Output (Ax-PE Bus 2x opt)

PE-6410/USIO66 Peripheral Controller Turbine Controler I/O (Ax-PE Bus el)

PE-6411/TCIO66 Peripheral Controller Turbine Controler I/O (Ax-PE Bus el)

PE-6412/TCIO66 Peripheral Controller Turbine Controler I/O (Ax-PE Bus 2x opt)

SICAM MIC Peripheral Elements


Peripheral Element Designation

PE-6020/USIO66 Universal Signal In-/Output

PE-6040/USIO66 Universal Signal In-/Output

SICAM EMIC Peripheral Elements


Peripheral Element Designation

PE-6010/USIO36 Universal Signal In-/Output

12 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 12/139
7/25/2019 Sicam Tm Io Module Eng

Introduction

1.2 Modules

1.2.1 Standard I/O Modul es


I/O Module Designation Item-Number/MLFB

DI-6100 Binary Input 2x8, 24…60 VDC GC6-100 / 6MF11130GB000AA0

DI-6101 Binary Input 2x8, 110/220 VDC GC6-101 / 6MF11130GB010AA0

DI-6102 Binary Input 2x8, 24…60 VDC 1ms GC6-102 / 6MF11130GB020AA0

DI-6103 Binary Input 2x8, 110/220 VDC 1ms GC6-103 / 6MF11130GB030AA0

DI-6104 Binary Input 2x8, 220 VDC GC6-104 / 6MF11130GB040AA0

DO-6200 Binary Output Transistor 2x8, 24…60 VDC GC6-200 / 6MF11130GC000AA0

DO-6212 Binary Output Relays 8x 24…220 VDC/230 VAC GC6-212 / 6MF11130GC120AA0

DO-6220 Command Output Base Module GC6-220 / 6MF11130GC200AA0

DO-6221 Command Output Base Module with Measurement GC6-221 / 6MF11130GC210AA0

DO-6230 Command Output Relay Module GC6-230 / 6MF11130GC300AA0

 AI-6300 Analog Input 2x2 ±20 mA/ ±10 V GC6-300 / 6MF11130GD000AA0

 AI-6307 Analog Input 2x2 ±5 mA GC6-307 / 6MF11130GD070AA0

 AI-6308 Analog Input 2x2 ±2 mA/±10 V GC6-308 / 6MF11130GD080AA0

 AI-6310 Analog Input 2x2 Pt100/Ni100 GC6-310 / 6MF11130GD100AA0

 AO-6380 Analog Output 4x ±20 mA/±10 mA/±10 V GC6-380 / 6MF11130GD800AA0

TE-6420 Speed Measurement 2x2 5 VDC/24 VDC/NAMUR GC6-420 / 6MF11130GE200AA0

TE-6450 Position Acquisition 2x2 SSI/RS-422 GC6-450 / 6MF11130GE500AA0

TE-6430 Counting Pulse Inp. 2x24…60 VDC GC6-430 / 6MF11130GE300AA0

1.2.2 Safety I/O Modul es

I/O Module Designation Item-Number/MLFB

DI-6170 Binary Input 2x4, 24 VDC (S) GC6-170 / 6MF11130GB700AA0

DO-6270 Binary Output Transistor 4x, 24 VDC (S) GC6-270 / 6MF11130GC700AA0

 AI-6370 Analog Input 2x, 4… 20 mA (S) GC6-370 / 6MF11130GD700AA0

SICAM RTUs, I/O Modules 13


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 13/139
7/25/2019 Sicam Tm Io Module Eng

Introduction

1.3 Systems

1.3.1 SICAM TM, SICAM AK


The possibilities to connect peripheral control modules to SICAM TM und SICAM AK are
described in document  ACP 1703 Platforms – Configuration - Automation Units and
 Automation Networks.

Master control element Bus interface module (electrical) Bus interface module (optical)

    C     0     1     2     3     Y     S


    4     I     I     I     I
    O     S     R     E
    R
    1     X
    L     S
 
    K
    S S
    K     Y
    0     T     L
    /     L
    /     P
    C     1
    6
  -     X     K     K     M     X
    R     P
    /     P
    /     O
    C
     P
     C
   x
    R     R
    E     E     O
    E
    S
    T
    A
    H
    E
    S
    L
     P     U
    E
    P
    R
     C
     A
    3
     M    0
     A    1
    7     5
    1     6
    1
     C
     I
    X     X      M
     M      A    3
     S      T      C
     I     0
    7
     S     1

    0     1     2     5     4


    1
    3
    X     6
    X     7
    X     8
    X     9
    X     1     4
    X     1     1     D     X     R     X
    X     X     X     W     E
    0
    B     M
    I     B
    T     S     F
    O
    E
    S     0
    /     1    )
    /    O     2    )
    /     3
    /
    T
    A
    E     E    T     E    B     E     K
    H
    E
    S
    L
    U
    E     R     R    E
    (     R    F
    (     R     C 1 2 3 4 5 6
    P
    R     P    0
  -    I     P    1
  -    I     P    2
  -    I     P    3
  -    I     O
    C     L
    N     M    S     M    S     M    S     M    S     N
    2     U     C     3
    X     O
    T
    D
    V
    1
    X
    H     R    0
    6
  -
    S     W    4
    U     P    2
    P

Peripheral element with Max. 8 I/O-modules


standard I/O-modules

Peripheral control module (elektrical or optical) TS35 rail


Power supply module

Peripheral element with standard und safety I/O-modules


(only applicable for SICAM AK)

14 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 14/139
7/25/2019 Sicam Tm Io Module Eng

Introduction

1.3.2 SICAM MIC

 A TM 1703 mic system consists of a power supply module, a peripheral control module and
up to a maximum of 8 I/O-modules. The modules are mounted on a TS35 rail (DIN rail).

8 I/O-Modules max.

TS35 rail
Master Control Module

Power Supply Module

1.3.3 SICAM EMIC

 A TM 1703 emic system consists of a power supply module, a peripheral control module and

up to a maximum of 8 I/O-modules. The modules are mounted on a TS35 rail (DIN rail).

8 I/O modules max.

TS35 rail

Master control module

Power supply module

SICAM RTUs, I/O Modules 15


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 15/139
7/25/2019 Sicam Tm Io Module Eng

Introduction

1.4 I/O Modules Dimensio ns

1.4.1 I/O Moduls wit h sin gle mod ule wid th

16 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 16/139
7/25/2019 Sicam Tm Io Module Eng

Introduction

1.4.2 I/O Modul wit h dou ble modu le widt h

     5
 .
     6
     6
     3
     7

131

     6
     2
     3      1
     3
     1

SICAM RTUs, I/O Modules 17


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 17/139
7/25/2019 Sicam Tm Io Module Eng

Introduction

18 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 18/139
7/25/2019 Sicam Tm Io Module Eng

2 Standard I/O Modules

Contents

2.1 DI-6100 .......................................................................................................... 20


2.2 DI-6101 .......................................................................................................... 24
2.3 DI-6102 .......................................................................................................... 28
2.4 DI-6103 .......................................................................................................... 32
2.5 DI-6104 .......................................................................................................... 36
2.6 DO-6200 ........................................................................................................ 40
2.7 DO-6212 ........................................................................................................ 44
2.8 DO-6220 ........................................................................................................ 50

2.9 DO-6221 ........................................................................................................ 54


2.10 DO-6230 ........................................................................................................ 58
2.11 AI-6300 .......................................................................................................... 67
2.12 AI-6307 .......................................................................................................... 71
2.13 AI-6308 .......................................................................................................... 75
2.14 AI-6310 .......................................................................................................... 79
2.15 AO-6380......................................................................................................... 83
2.16 TE-6420 ......................................................................................................... 87
2.17 TE-6450 ......................................................................................................... 91
2.18 TE-6430 ......................................................................................................... 95

SICAM RTUs, I/O Modules 19


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 19/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.1 DI-6100

2.1.1 Features and Functi ons


Binary input module
·  16 inputs (2 groups of 8 each)
·  Galvanically insulated by optocouplers
·  Each group has a common return
·  Signal voltage 24…60 VDC
·  Removable screw terminals
·  Indication of function and states of the inputs via LED

2.1.2 View

20 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 20/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.1.3 Techni cal Specificati ons

Binary Inputs

16 binary inputs   ·  2 groups, 8 inputs each


·  Galvanical insulation
·  Each group has a common return of selectable polarity

Filter time 3 ms *)

Nominal voltages 24/48/60 VDC

Operating points   £ 12 V logically "0"


³ 16 V logically "1"

Rated current 1.0…1.5 mA (at 18 .. 78 V)

Input circuits 18…78 VDC


The circuits are operated by means of an external voltage

Power Supply
Operating voltage 4.7…5.1 VDC, 170 mW
The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 225 g


*)
  if the sensor voltage of a group of binary inputs is monitored for failures (Parameter 
SVM_moni t or i ng), there is a dedicated binary input for each group (IN D07 and IN D17), this input
has a filter time of 2 ms

SICAM RTUs, I/O Modules 21


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 21/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.1.4 Pin Assig nment and Display

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
I
-
6
1
0
0

22 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 22/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.1.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

IN D10…IN D17:
One-pole input with internal common
root (plus or minus)

IN D00…IN D07:
One-pole input with e xternal
common root (plus or minus)

SICAM RTUs, I/O Modules 23


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 23/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.2 DI-6101

2.2.1 Features and Functi ons


Binary input module
·  16 inputs (2 groups of 8 each)
·  Galvanically insulated by optocouplers
·  Each group has a common return
·  Signal voltage 110/220 VDC
·  Removable screw terminals
·  Indication of function and states of the inputs via LED

2.2.2 View

24 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 24/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.2.3 Techni cal Specificati ons

Binary Inputs

16 binary inputs   ·  2 groups, 8 inputs each


·  Galvanical insulation
·  Each group has a common return of selectable polarity

Filter time 3 ms *)

Nominal voltages 110/220 VDC

Operating points   £ 55 V logically "0"


³ 82.5 V logically "1"

Rated current 1.0…1.7 mA (at 82…250 V)

Input circuits 82…250 VDC


The circuits are operated by means of an external voltage

Power Supply

Operating voltage 4.7…5.1 VDC, 170 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 225 g


*)
  if the sensor voltage of a group of binary inputs is monitored for failures (Parameter 
SVM_moni t or i ng), there is a dedicated binary input for each group (IN D07 and IN D17), this input
has a filter time of 2 ms

SICAM RTUs, I/O Modules 25


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 25/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.2.4 Pin Assig nment and Display

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
I
-
6
1
0
1

26 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 26/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.2.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

IN D10…IN D17:
One-pole input with internal common
root (plus or minus)

IN D00…IN D07:
One-pole input with e xternal
common root (plus or minus)

SICAM RTUs, I/O Modules 27


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 27/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.3 DI-6102

2.3.1 Features and Functi ons


Binary input module
·  16 inputs (2 groups of 8 each)
·  Galvanically insulated by optocouplers
·  Each group has a common return
·  Signal voltage 24…60 VDC
·  Removable screw terminals
·  Indication of function and states of the inputs via LED

2.3.2 View

28 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 28/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.3.3 Techni cal Specificati ons

Binary Inputs

16 binary inputs   ·  2 groups, 8 inputs each


·  Galvanical insulation
·  Each group has a common return of selectable polarity

Filter time 3 ms *)

Nominal voltages 24/48/60 VDC

Operating points   £ 12 V logically "0"


³ 18 V logically "1"

Rated current 1.0…1.5 mA (at 18…78 V)

Input circuits 18…78 VDC


The circuits are operated by means of an external voltage

Power Supply
Operating voltage 4.7…5.1 VDC, 170 mW
The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 225 g


*)
  if the sensor voltage of a group of binary inputs is monitored for failures (Parameter 
SVM_moni t or i ng), there is a dedicated binary input for each group (IN D07 and IN D17), this input
has a filter time of 2 ms

SICAM RTUs, I/O Modules 29


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 29/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.3.4 Pin Assig nment and Display

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
I
-
6
1
0
2

30 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 30/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.3.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

IN D10…IN D17:
One-pole input with internal common
root (plus or minus)

IN D00…IN D07:
One-pole input with e xternal
common root (plus or minus)

SICAM RTUs, I/O Modules 31


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 31/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.4 DI-6103

2.4.1 Features and Functi ons


Binary input module
·  16 inputs (2 groups of 8 each)
·  Galvanically insulated by optocouplers
·  Each group has a common return
·  Signal voltage 110/220 VDC
·  Removable screw terminals
·  Indication of function and states of the inputs via LED

2.4.2 View

32 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 32/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.4.3 Techni cal Specificati ons

Binary Inputs
  ·  2 groups, 8 inputs each
16 binary inputs ·  galvanic al insulation
·  each group has a common return of selectable polarity

Filter time 3 ms *)

Nominal voltages 110/220 VDC

Operating points   £ 55 V logically "0"


³ 82.5 V logically "1"

Rated current 1.0…1.7 mA (at 82…250 V)

Input circuits 82…250 VDC


the circuits are operated by means of an external voltage

Power Supply

Operating voltage 4.7…5.1 VDC, 170mW


the voltage is picked off at the TM b us

Mechanics and Connectors

Terminals removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight approx. 225 g


*)
  if the sensor voltage of a group of binary inputs is monitored for failures (Parameter 
SVM_moni t or i ng), there is a dedicated binary input for each group (IN D07 and IN D17), this input
has a filter time of 2 ms

SICAM RTUs, I/O Modules 33


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 33/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.4.4 Pin Assig nment and Display

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
I
-
6
1
0
3

34 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 34/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.4.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

IN D10…IN D17:
One-pole input with internal common
root (plus or minus)

IN D00…IN D07:
One-pole input with e xternal
common root (plus or minus)

SICAM RTUs, I/O Modules 35


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 35/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.5 DI-6104

2.5.1 Features and Functi ons


Binary input module
·  16 inputs (2 groups of 8 each)
·  Galvanically insulated by optocouplers
·  Each group has a common return
·  Signal voltage 220 VDC
·  Removable screw terminals
·  Indication of function and states of the inputs via LED

2.5.2 View

36 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 36/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.5.3 Techni cal Specificati ons

Binary Inputs

16 binary inputs   ·  2 groups, 8 inputs each


·  Galvanical insulation
·  Each group has a common return of selectable polarity

Filter time 3 ms *)

Nominal voltages 220 VDC

Operating points   £ 110 V logically "0"


³ 165 V logically "1"

Rated current 1.1…1.5 mA (at 165…250V)

Input circuits 165…250 VDC


The circuits are operated by means of an external voltage

Power Supply

Operating voltage 4.7…5.1 VDC, 170 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 225 g


*)
  if the sensor voltage of a group of binary inputs is monitored for failures (Parameter 
SVM_moni t or i ng), there is a dedicated binary input for each group (IN D07 and IN D17), this input
has a filter time of 2 ms

SICAM RTUs, I/O Modules 37


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 37/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.5.4 Pin Assig nment and Display

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
I
-
6
1
0
4

38 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 38/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.5.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

IN D10…IN D17:
One-pole input with internal common
root (plus or minus)

IN D00…IN D07:
One-pole input with e xternal
common root (plus or minus)

SICAM RTUs, I/O Modules 39


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 39/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.6 DO-6200

2.6.1 Features and Functi ons


Binary output module
·  16 transistor outputs (2 groups of 8 each)
·  Galvanically insulated by optocouplers
·  Each group has a common return
·  Switching voltage 24…60 VDC
·  All outputs proof against continued short circuit
·  To increase switching capacity 2 outputs can be connected in parallel
·  No impact on other outputs if one is short-circuit
·  Removable screw terminals

·  Indication of function and states of the outputs via LED

2.6.2 View

40 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 40/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.6.3 Techni cal Specificati ons

Binary Outputs

16 binary outputs ·  2 groups, 8 outputs each


(transistor) ·  Galvanical insulation
·  Each group has a common return

Nominal switching voltage 24/48/60 VDC

Nominal current Due to thermal loading capacity of the module:


(resistive load) ·  0.25 A at 24, 48, and 60 VDC
(for each output, if 16 outputs are active at the same time)
·  0.35 A when connecting 2 outputs in parallel
(for each pair ot outputs, if 8 pairs of outputs are active at the
same time)
Maximum continuous current Due to electrical ratings of the transistor switch:
·  0.9 A at 18…78 VDC
(only 1 output active)

Nominal switching capacity ·  6 W at 24 VDC wh en c onnec ting in par all el: 8.4 W
(resistive load, UN ) ·  12 W at 48 VDC wh en c onnec ting in par all el 16.8 W
·  15 W at 60 VDC wh en c onn ec ting in p arallel: 2 1 W
Maximum switching c apacity 70.2 W at 78 VDC

Overload proof No

Proof against continued 10 A current limitation


short-circuit If the current limitation operates,
current is cut off after 10 µs
Cyclic reclosing
break time 300 µs
make time 10 µs

Switching cycles Unlimited

Switching frequency Max. 100 Hz

Output circuit voltage drop < 0.5 V at 0.25 A

Dynamic withstand capability   ·  Capacitive load max. 100 nF at 60V


·  Inductive   t £  500 ms (any with external free-wheeling
diode)
·  Lines Z  ³  100  W , line length up to 3 km
·  Lamps IN  £  150 mA (ION  £  1.8 A)
Output circuits 18…78 VDC
The circuits are operated by means of an external voltage

Power Supply

Operating voltage 4.7…5.1 VDC, 600 mW

The voltage is picked off at the TM b us


Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 260 g

SICAM RTUs, I/O Modules 41


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 41/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.6.4 Pin Assig nment and Display

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
O
-
6
2
0
0

42 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 42/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.6.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

OUT D10…OUT D17:


One-pole input with switched plus
and internal common root

OUT D00…OUT D07:


One-pole input with switched plus
and external common root

SICAM RTUs, I/O Modules 43


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 43/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.7 DO-6212

2.7.1 Features and Functi ons


Binary output module
·  8 relay outputs
·  Galvanically insulated
·  Switching voltage 24…220 VDC/230 VAC
·  The outputs can switch dc and ac voltages
·  Removable screw terminals
·  Indication of function and states of the outputs via LED

2.7.2 View

44 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 44/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.7.3 Techni cal Specificati ons

Binary outputs

8 binary outputs ·  8 outputs, potential-fr ee


(relay) ·  Galvanical insulation

Nominal voltage   ·  24/48/60/110/220 VDC


·  110/230 VAC

Maximum continuous current   ·  2 A


·  5 A for 1 minute
Switching capacity DC voltage
·  Min. 50 mW at 5 VDC
·  Max. acc. to diagram

 AC voltage
·  Max. 1250 VA 5 A/250 VAC, resistive load
·  M ax. 500 VA 2 A/ 250 V AC, c os j = 0.4
Switching cycles 3x104

Output circuits Max. 250 VDC / 253 VAC

The circuits are operated by means of an external voltage


Power Supply

Operating voltage 4.7…5.1 VDC, 800 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 265 g

SICAM RTUs, I/O Modules 45


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 45/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.7.4 Pin Assig nment and Display

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
O
-
6
2
1
2

46 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 46/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.7.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

OUT D04, OUT D05, OUT D06

a) 1.5-pole output with switched


minus (max. 7 commands can be
used)

a) 1.5-pole output with switched plus


(max. 7 commands can be used)

OUT D00
One-pole output with switched plus
OUT D01
One-pole output with switched minus
OUT D02 / OUT D03
2-pole output

SICAM RTUs, I/O Modules 47


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 47/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

Protection of external cir cuitry

a)  Þ RL
Si

b)  Þ Si
RL

48 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 48/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

Maximum current with and without protection

a) Numbers of used outputs Maximum current for each


output

without protection all 2A

all 5A/1min

max. 2 5A

with protection

B-charakteristic 4A/10kA all 2A

max. 2 4A

Z-charakteristic 4A/10kA all 2A

max. 2 4A

C-charakteristic 2A/10kA 1 ... 8 2A

b) Maximum current for each


 AUX Pin

without protection 5A

with protection

B-charakteristic 4A/10kA 4A

Z-charakteristic 4A/10kA 4A

C-charakteristic 2A/10kA 2A

SICAM RTUs, I/O Modules 49


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 49/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.8 DO-6220

2.8.1 Features and Functi ons


Base module for checked command output in combination with up to 7 pieces of DO-6230
(command output relay module)
·  Group and pulse output relays
·  Galvanically insulated from logic
·  Switching voltage 24…110 VDC
·  Internal checks (IC1)
·  Removable screw terminals
·  Indication of function and states of the outputs via LED
·  Output functions
 ─   Pulse commands

2.8.2 View

50 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 50/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.8.3 Techni cal Specificati ons

Processor and Memory

Processor PIC18F6527, 10 MHz

Program memory intern, FLASH 48 kByte

Main memory intern, SRAM 3936 Byte

Parameter memory intern, EEPROM 1024 Bytes

Binary Outputs

2 pulse outputs Output contacts and grouping for commands

Nominal switching voltage 24/48/60/110 VDC

Switching capacity   ·  Min. 10 µA 10 m VDC


·  Max. 60 W acc. to diagram

Maximum switching capacity / 48 W 24 VDC 2 A *)


switching voltage / maximum 57 W 48 VDC 1.2 A
switching current 60 W 60 VDC 1A
55 W 110 VDC 0.5 A
Overload proof No

Proof against continued 10 A current limitation


short-circuit If the current limitation operates,
current is cut off after 10 µs
Cyclic reclosing
break time 300 µs
make time 10 µs
8
Switching cycles   ·  Mechanical: 10
5
·  Electrical: 10 (0.5 A, 110 VDC)
5
5 x 10   (1 A, 30 VDC)
5
10 (2 A, 30 VDC)

Switching frequency Max. 100 Hz


Output circuit voltage drop < 0.5 V at 0.25 A

Dynamic withstand capability   ·  Capacitive load max. 100 nF at 60 V


·  Inductive   t £  500 ms (any with external free-wheeling
diode)
·  Lines Z  ³  100  W , line length up to 3 km
·  Lamps IN  £  150 mA (ION  £  1.8 A)
Output circuits 18 VDC…143 VDC
The circuits are operated by means of an external voltage
*)
  for module DO-6220 with version -- the following reduced values are valid: 29 W / 24 VDC / 1.2 A

SICAM RTUs, I/O Modules 51


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 51/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

Power Supply

Operating voltage 5 VDC ± 5%, 560 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 220 g

2.8.4 Pin Assig nment and Display

The process signals must be connected to two 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
O
-
6
2
2
0

52 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 52/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.8.5 Blo ck Diagram and External Circui try

See module DO-6230; Block Diagram and External Circuitry.

SICAM RTUs, I/O Modules 53


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 53/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.9 DO-6221

2.9.1 Features and Functi ons


Base module for checked command output in combination with up to 7 pieces of DO-6230
(command output relay module)
·  Group and pulse output relays
·  Galvanically insulated from logic
·  Switching voltage 24…110 VDC
·  Resistance check (RC1)
·  Removable screw terminals
·  Indication of function and states of the outputs via LED

2.9.2 View

54 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 54/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.9.3 Techni cal Specificati ons

Processor and Memory

Processor PIC18F6527, 10 MHz

Program memory intern, FLASH 48 kByte

Main memory intern, SRAM 3936 Byte

Parameter memory intern, EEPROM 1024 Bytes

Binary Outputs

2 pulse outputs Output contact and grouping for commands

Nominal switching voltage 24/48/60/110 VDC

Switching capacity   ·  Min. 10 µA 10 m VDC


·  Max. 60 W

Maximum switching capacity / 48 W 24 VDC 2 A *)


switching voltage / maximum 57 W 48 VDC 1.2 A
switching current 60 W 60 VDC 1A
55 W 110 VDC 0.5 A
Overload proof Yes

Proof against continued 10 A current limitation


short-circuit If the current limitation operates,
current is cut off after 10 µs
Cyclic reclosing
break time 300 µs
make time 10 µs
8
Switching cycles   ·  Mechanical: 10
5
·  Electrical: 10 (0.5 A, 110 VDC)
5
5 x 10   (1 A, 30 VDC)
5
10 (2 A, 30 VDC)

Switching frequency Max. 100 Hz


Output circuit voltage drop < 0.5 V at 0.25 A

Dynamic withstand capability   ·  Capacitive load max. 100 nF at 60V


·  Inductive   t £  500 ms (any with external free-wheeling
diode)
·  Lines Z  ³  100  W , line length up to 3 km
·  Lamps IN £  150 mA (ION  £  1.8 A)
Output circuits 18…143 VDC
The circuits are operated by means of an external voltage
*)
  for module DO-6221 with version -- the following reduced values are valid: 29 W / 24 VDC / 1.2 A

SICAM RTUs, I/O Modules 55


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 55/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

Power Supply

Operating voltage 5 VDC ± 5%, 1380 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 230 g

2.9.4 Pin Assig nment and Display

The process signals must be connected to two 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
O
-
6
2
2
1

56 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 56/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.9.5 Blo ck Diagram and External Circui try

See module DO-6230; Block Diagram and External Circuitry.

SICAM RTUs, I/O Modules 57


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 57/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.10 DO-6230

2.10.1 Features and Functi ons


Relay module for checked command output in combination with DO-6220 or DO-6221
·  8 relay outputs
 ─   8 pulse commands (2-pole) or 
 ─   16 pulse commands (1-pole or 1½-pole)
·  Galvanically insulated from logic
·  Switching voltage 24…110 VDC
·  Removable screw terminals
·  Indication of function and states of the outputs via LED

2.10.2 View

58 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 58/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.10.3 Techni cal Specificati ons

Processor and Memory

Processor PIC18F6527, 10 MHz

Program memory internal, FLASH 48 kByte

Main memory internal, SRAM 3936 Byte

Parameter memory internal, EEPROM 1024 Bytes

Binary Outputs

16 binary outputs ·  2 groups, 8 outputs each


(transistor) ·  Galvanical insulation
·  Each group has a common return

Nominal switching voltage 24/48/60/110 VDC

Switching capacity   ·  Min. 10 µA 10 m VDC


·  Max. 60 W

Maximum switching capacity / 48 W 24 VDC 2 A *)


switching voltage / maximum 57 W 48 VDC 1.2 A
switching current 60 W 60 VDC 1A
55 W 110 VDC 0.5 A

Overload proof No

Proof against continued No


short-circuit
8
Switching cycles Mechanical: 10
5
Electrical: 10 (0.5 A, 110 VDC)
5
5 x 10   (1 A, 30 VDC)
5
10 (2 A, 30 VDC)

Switching frequency Max. 100 Hz

Output circuit voltage drop < 0.5 V at 0.25 A

Dynamic withstand capability   ·  Capacitive load max. 100 nF at 60V


·  Inductive   t £  500 ms (any with external free-wheeling
diode)
·  Lines Z  ³  100  W , line length up to 3 km
·  Lamps IN  £  150 mA (ION  £  1.8 A)
Output circuits 18…143 VDC
The circuits are operated by means of an external voltage
*)
  if the command output base modules DO-6220 or DO-6221 with version -- are used, the following
reduced values are valid: 29 W / 24 VDC / 1.2 A

Power Supply

Operating voltage 5 VDC   ± 5%, 130 mW


The voltage is picked off at the TM b us

SICAM RTUs, I/O Modules 59


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 59/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 170 g

2.10.4 Pin Assig nment and Display

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
O
-
6
2

3
0

60 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 60/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.10.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.
1-Pole Commands, Relay Commo n Return on Min us Pole
(the brackets show the external circ uit elements with relay common return on po sitiv e pole)

Configuration Note
 At Relay common ret urn on minus p ole the parameter "P olarity" must be s et to "-" .
(At Relay common return on plus pole the parameter "Polarity" must be set to "+" )

SICAM RTUs, I/O Modules 61


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 61/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

1,5-Pole Commands, 1 Rail syst em, Relay Common Return on Minu s Pole
(the brackets show the external circuit elements with relay common return o n positi ve pole)

Configuration Note
 At Relay common ret urn on minus pole the parameter "P olarity" must be s et to "+" .
(At Relay common return on plus pole the parameter "Polarity" must be set to "-" )

62 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 62/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2-Pole Commands, Measuring i n t he Minus Circuit

Configuration Note
The parameter "Polarity" must be set to "+" .

SICAM RTUs, I/O Modules 63


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 63/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2-Pole Commands, Measuring in the Plus Circuit

Configuration Note
The parameter "Polarity" must be set to "-" .

64 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 64/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

1 and 2-Pole Commands, Measurin g in the Minus Circu it

Configuration Note

The parameter "Polarity" must be set to "+" .

SICAM RTUs, I/O Modules 65


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 65/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

1 and 2-Pole Commands, Measuring i n th e Plus Circuit

Configuration Note
The parameter "Polarity" must be set to "-" .

66 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 66/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.11 AI-6300

2.11.1 Features and Functio ns


 Analog input module
·  4 inputs (2 groups of 2 each)
·  galvanically insulated by optocouplers
·  Acquisition of currents ±20 mA
·  Acquisition of voltages ±10 V
·  Removable screw terminals
·  Function indication via LED

2.11.2 View

SICAM RTUs, I/O Modules 67


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 67/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.11.3 Techni cal Specificatio ns

 An alo g In pu ts

4 analog inputs   ·  2 groups, 2 inputs each


·  Groups are galvanically insulated from one another 
·  Voltage between 2 inputs of a group max. 4 VDC

Measuring ranges Current measurement -20…0…+20 mA


Voltage measurement -10…0…+10 V
Overrange typ. 2%

Resolution 0.013% at ±20 mA


0.025% at ±10 V

 Accuracy 0.15% at 25°C


0.4% at 0…50°C
0.5% at –20…70°C

Input impedance 122.5  W at ±20 mA

11.3 kW at ±10 V
Common mode rejection ratio

Current inputs min. 70 dB (10 Hz…1 MHz)


min. 90 dB (10 Hz…500 Hz)

Voltage inputs min. 73 dB (10 Hz…1 MHz)


min. 90 dB (10 Hz…500 Hz)

Normal mode rejection ratio

Current inputs 0 dB (10 Hz…7.5 kHz)


+20 dB/dec ade (7.5 kHz… 1 MHz)

Voltage inputs 0 dB (10 Hz…7.5 kHz)


+20 dB/dec ade (7.5 kHz… 1 MHz)

Input circuits External sensors, auxiliary voltage 18 VDC…78 VDC.


The circuits are operated by means of an external voltage
Power Supply

Operating voltage 4.7…5.1 VDC, max. 480 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 225 g

68 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 68/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.11.4 Pin Assi gnment and Displ ay

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

A
I
-
6
3
0
0

SICAM RTUs, I/O Modules 69


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 69/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.11.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

IN V2:
Connection of a 2-wire measuring
transducer with current output
IN V3:
Connection of a 4-wire measuring
transducer with voltage output, the
I/O module feeds the auxiliary
supply

IN V0:
Connection of a 3-wire measuring
transducer with current output, the
I/O module feeds the auxiliary
supply
IN V1:
Connection of a 4-wire measuring
transducer with current output, the
I/O module feeds the auxiliary
supply

70 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 70/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.12 AI-6307

2.12.1 Features and Functio ns


 Analog input module
·  4 inputs (2 groups of 2 each)
·  Galvanically insulated by optocouplers
·  Acquisition of currents ±5 mA
·  Acquisition of voltages ±10 V
·  Removable screw terminals
·  Function indication via LED

2.12.2 View

SICAM RTUs, I/O Modules 71


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 71/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.12.3 Techni cal Specificatio ns

 An alo ge In put s

4 analog inputs   ·  2 groups, 2 inputs each


·  Groups are galvanically insulated from one another 
·  Voltage between 2 inputs of a group max. 4 VDC

Measuring ranges Current measurement -5…0…+5 mA


(-2.5…0…+2.5 mA)
Voltage measurement -10…0…+10 V
Overrange typ. 2%

Resolution 0.013% at ±5 mA
(0.026% at ±2.5 mA)
0.025% bei ±10 V

 Accuracy 0.15% at 25°C


0.4% at 0…50°C
0.5% at –20…70°C

Input impedance 490 Ω at ±5 mA


11.3 kΩ at ±10 V

Common mode rejection ratio

Current inputs min. 70 dB (10 Hz…1 MHz)


min. 90 dB (10 Hz…500 Hz)

Voltage inputs min. 73 dB (10 Hz…1 MHz)


min. 90 dB (10 Hz…500 Hz)

Normal mode rejection ratio

Current inputs 0 dB (10 Hz…7.5 kHz)


+20 dB/dec ade (7.5 kHz… 1 MHz)

Voltage inputs 0 dBdB/dec ade


+20 (10
(7.5Hz…7.5 kHz)
kHz… 1 MHz)

Input circuits External sensors, auxiliary voltage 18…78 VDC


The circuits are operated by means of an external voltage

Power Supply

Operating voltage 4.7…5.1 VDC, max. 480 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 225 g

72 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 72/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.12.4 Pin Assi gnment and Displ ay

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

A
I
-
6
3
0
7

SICAM RTUs, I/O Modules 73


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 73/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.12.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

IN V2:
Connection of a 2-wire measuring
transducer with current output
IN V3:
Connection of a 4-wire measuring
transducer with voltage output, the
I/O module feeds the auxiliary
supply

IN V0:
Connection of a 3-wire measuring
transducer with current output, the
I/O module feeds the auxiliary
supply
IN V1:
Connection of a 4-wire measuring
transducer with current output, the
I/O module feeds the auxiliary
supply

74 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 74/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.13 AI-6308

2.13.1 Features and Functio ns


 Analog input module
·  4 inputs (2 groups of 2 each)
·  Galvanically insulated by optocouplers
·  Acquisition of currents ±2 mA
·  Acquisition of voltages ±10 V
·  Removable screw terminals
·  Function indication via LED

2.13.2 View

SICAM RTUs, I/O Modules 75


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 75/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.13.3 Techni cal Specificatio ns

 An alo g In pu ts

4 analog inputs   ·  2 groups, 2 inputs each


·  Groups are galvanically insulated from one another 
·  Voltage between 2 inputs of a group max. 4 VDC

Measuring ranges Current measurement -2…0…+2 mA


(-1…0…+1 mA)
Voltage measurement -10…0…+10 V
Overrange typ. 1.7%

Resolution 0.013% at ±2 mA
(0.026% at ±1 mA)
0.025% at ±10 V

 Accuracy 0.15% at 25°C


0.4% at 0…50°C
0.5% at –20…70°C

Input impedance 1225  W at ±2 mA


11.4 kW at ±10 V

Input circuits External sensors, auxiliary voltage 18 VDC…78 VDC.


The circuits are operated by means of an external voltage
Power Supply

Operating voltage 4.7…5.1 VDC, max. 480 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 225 g

76 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 76/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.13.4 Pin Assi gnment and Displ ay

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

A
I
-
6
3
0
8

SICAM RTUs, I/O Modules 77


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 77/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.13.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

IN V2:
Connection of a 2-wire measuring
transducer with current output
IN V3:
Connection of a 4-wire measuring
transducer with voltage output, the
I/O module feeds the auxiliary
supply

IN V0:
Connection of a 3-wire measuring
transducer with current output, the
I/O module feeds the auxiliary
supply
IN V1:
Connection of a 4-wire measuring
transducer with current output, the
I/O module feeds the auxiliary
supply

78 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 78/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.14 AI-6310

2.14.1 Features and Functio ns


 Analog input module
·  4 inputs (2 groups of 2 each)
·  Galvanically insulated by optocouplers
·  Acquisition of temperatures
Via PT100/NI100 resistance measurement in 2-wire, 3-wire or 4-wire technology
·  For resistance measurement one current source is assigned to each input
·  Noise rejection
·  Removable screw terminals
·  Function indication via LED

2.14.2 View

SICAM RTUs, I/O Modules 79


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 79/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.14.3 Techni cal Specificatio ns

 An alo g In pu ts

4 analog inputs   ·  2 groups, 2 inputs each


·  Groups are galvanically insulated from one another 
·  Voltage between 2 inputs of a group max. 20 VDC

Measuring range Resistance measurement 50…400  W   (Pt100, Ni100)


Overrange typ. 20%

Input impedance Approx. 2 MW

Resolution 11 mW

Noise rejection 16.7 Hz, 50 Hz, 60 Hz settable for each group

Conversion time Noise rejection for 50 Hz 120 ms


Nois e r ejec tion f or 60 Hz 100 ms
Noise rejection for 16.7 Hz 180 ms

 Accuracy 0.19% at 25°C


0.21% at 0…50°C
0.4% at -20…70°C
(because of the measuring method there is no dependence on
the accuracy of the constant-current source)

Reference current 2 mA

Connecting line impedance Sum of go-and-return line max. 40  W

Common mode rejection ratio 16.7 Hz, 50 Hz, 60 Hz…20 kHz > 100 dB
10 Hz…1 MHz > 70 dB

Normal mode rejection ratio 16.7 Hz, 50 Hz, 60 Hz > 100 dB

Input circuits The circuits are operated by means of an internal voltage


(constant-current source)

Current Outputs

4 current outputs ·  2.0 mA


(constant-current source) ·  All outputs galvanically insulated

Power Supply

Operating voltage 4.7…5.1 VDC, max. 450 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 235 g

80 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 80/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.14.4 Pin Assi gnment and Displ ay

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

A
I
-
6
3
1
0

SICAM RTUs, I/O Modules 81


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 81/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.14.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

IN V2:
Connection in 2-wire technique
IN V3:
Connection in 3-wire technique

IN V0:
Connection in 4-wire technique

82 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 82/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.15 AO-6380

2.15.1 Features and Functio ns


 Analog output module
·  4 outputs
·  Galvanically insulated by optocouplers
·  Output of currents ±20 m, ±10 mA
·  Output of voltages ±10 V
·  Removable screw terminals
·  Function indication via LED

2.15.2 View

SICAM RTUs, I/O Modules 83


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 83/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.15.3 Techni cal Specificatio ns

 An alo g Ou tp ut s

4 analog outputs   ·  All outputs galvanically insulated

Current output   ·  Max. ±20 mA on max. 500 W  load


·  Max. ±10 mA on max. 1 kW load

Voltage output Max. ±10 V on min. 1 kW load

Resolution 0.025% at ±20 mA, ±10 mA, ±10 V

Settling time 1 ms

 Accuracy 0.3% at 25°C


0.4% at 0…50°C
0.7% at -20…70°C

Output circuits The circuits are operated by means of an internal voltage

Power Supply

Operating voltage 4.7…5.1 VDC, max. 1900 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 300 g

84 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 84/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.15.4 Pin Assi gnment and Displ ay

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

A
O
-
6
3
8
0

SICAM RTUs, I/O Modules 85


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 85/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.15.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

OUT V2:
2-wire connection of a load with
current output
OUT V3:
3-wire connection of a load with
current output

OUT V0:
4-wire connection of a load with
current output
OUT V1:
2-wire connection of loads in series
with current output

86 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 86/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.16 TE-6420

2.16.1 Features and Functio ns


Period duration measurement / pulse counting
·  4 pulse inputs (2 groups of 2 each)
·  Galvanically insulated by optocouplers
·  Each group has a common return
·  Inputs are made as
 ─   Passive voltage inputs for 5 and 24 VDC
 ─   Active signal inputs acc. to DIN 19234 (NAMUR)
·  Modes
 ─   Period duration measurement for speed acquisition, for frequencies 1.2…12 kHz
 ─ 
  Pulse counting for standstill detection, for frequencies 0 Hz…12 kHz
·  Accuracy 0.1%
·  Direction of rotation recognition
·  Recognition of open-circuit
·  Removable screw terminals
·  Function indication via LED

2.16.2 View

SICAM RTUs, I/O Modules 87


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 87/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.16.3 Techni cal Specificatio ns

Pulse Inputs
4 pulse inputs   ·  2 groups, 2 inputs each
·  Groups are galvanically insulated from one another 
·  Transient filter and digital glitch suppression

Each input is wired to the terminals twice


·  As an active input according to DIN 19234 (NAMUR)
·  As a passive input with 5 VDC and 24 VDC nominal voltage

Frequency range 1.2 Hz…10 kHz

 Active Inpu t

 Active input According to DIN 19 234 (NAMUR)

No-load voltage 7.4 V

Short-circuit current 7.4 mA


Operating points   £ 0.35 mA open-circuit
£ 1.3 mA logically "1"
³ 2.0 mA logically "0"
Hysteresis between logically "1" and logically "0"

Input circuits The circuits are operated by means of an internally created


voltages.

Passiv e Input

Passive input With 5 VDC and 24 VDC nominal voltage

Nominal voltage 5 VDC Voltage range 3.5…6 VDC


Nominal power per input approx. 1 mW

Nominal voltage 24 VDC Voltage range 18…32 VDC


Nominal power per input approx. 30 mW

Operating points   £ 2.0 V logically "0"


³ 3.4 V logically "1"
Hysteresis between logically "1" and logically "0"
Open-circuit detection

Input circuits 3.5…6 VDC or 18…32 VDC


The circuits are operated by means of an external voltage.

Power Supply

Operating voltage 4.7…5.1 VDC, max. 790 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx 225 g

88 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 88/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.16.4 Pin Assi gnment and Displ ay

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

T
E
-
6
4
2
0

SICAM RTUs, I/O Modules 89


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 89/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.16.5 Blo ck Diagram and External Circui try

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

90 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 90/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.17 TE-6450

2.17.1 Features and Functio ns


 Acquisition of Gray-coded data
·  4 synchronous serial interfaces "SSI" (2 groups of 2 each)
·  galvanically insulated by optocouplers
·  the interfaces of a group have a common ground
·  acquisition of Gray-coded data from serial single-turn sensors (shaft-encoders) with a
resolution of 10 to 24 bit, for position acquisition
·  recognition of open-circuit
·  removable screw terminals
·  indication of function and interface signals via LED

2.17.2 View

SICAM RTUs, I/O Modules 91


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 91/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.17.3 Techni cal Specificatio ns

Interfaces
4 serial interfaces   ·  2 groups, 2 interfac es each
·  Groups are galvanically insulated from one another 
·  Each output is galvanically insulated by optocouplers
·  The interfaces of a group have a common ground
·  Transient filter, EMC filter, interference protection devices

Interface RS-422, synchronous

Data format Gray-code

Data width 10 .. 24 bit

Transmission rate 136.5 kHz, 273 kHz, 546 kHz

Input circuits External sensors, auxiliary voltage 18 VDC .. 78 VDC.

The circuits are operated by means of an external voltage.


Power Supply

Operating voltage 4.7 .. 5.1 VDC, max. 770 mW


The voltage is picked off at the TM b us

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 230 g

92 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 92/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.17.4 Pin Assi gnment and Displ ay

The process signals must be connected to four 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

T
E
-
6
4
5
0

SICAM RTUs, I/O Modules 93


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 93/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.17.5 Blo ck Diagram and External Circui try

94 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 94/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.18 TE-6430

2.18.1 Features and Functio ns


Module can be used in TM 1703 ACP and TM 1703 emic of system family SICAM 1703 and
offers optionally
·  2 count pulse inputs
·  or 1 count pulse input and 1 control input
·  inputs are galvanically insulated from logic circuits and ground
·  inputs are not galvanically insulated from each other 
·  input voltage range 24 to 60 V
·  all inputs are protected by EMC filter and interference protection devices
·  module functions which can be operated autonomously are supplied by backup-voltage.
Because of this counting function and counts are preserved over a supply-outage of up
to 72 hours

Function of the module is defined by the respective peripheral firmware.

2.18.2 View

SICAM RTUs, I/O Modules 95


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 95/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.18.3 Techni cal Specificatio ns

Processor and Memory

Controller PIC18F6527

Clock rate 10 MHz

Program memory internal, 48kByte FLASH

Main memory internal, 3936 Byte SRAM

Parameter memory internal, 1024Byte EEPROM (to store calibration values, serial
number)

Inputs

2 count pulse inputs   ·  Acquisition of count pulses


−  2 count pulse inputs or 
−  1 count pulse input + 1 transfer input

·  Galvanically insulated from logic circuits and ground


·  Not galvanically insulated from each other 
·  Secured by means of EMC filter and interferenc e protection
facilities
·  Autonomous module functions are supplied by backup voltage,
thus counting function and counts are preserved correctly also
over a voltage failure of up to 72 hours
Input signal frequency max. 5 kHz (each input)

Bounc e suppression C ounter frequency stage Puls e length Puls e discontinuation


5kHz >10µs >100µs
500Hz >150µs >1ms
50 Hz >1.5ms >10ms
20 Hz >3ms >25ms

Voltage level < 12 VDC logically “0”


> 18 VDC logically “1”

Input circuits 18…78 VDC


The circuits are operated with external voltage source
Nominal power per input Max. 120 mW at 24 VDC
Max. 420 mW at 60 VDC

Power supply

Operating voltage 5 VDC   ± 5 %


The voltage is picked off at the TM b us

Connection power Startup 0.6 W


Normal operation 0.15 W

Buffer elements Double-layer condensers (goldcaps)

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 220 g

96 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 96/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

Buffer time chart

 A gold cap discharching characteristic at E are wor king accurate(VCC_CAP = 2,35V)


VCC_CAP [V] 25°C/ 90% humidity - lower level
B at 40°C / 90% humid ity Until this point atcounting
work correctly circuits t have
25°C (setpoint: to
= 72 h)
C Until this point counting circuits still work corr ectly
5,0 (t = 74 h at 25°C)
D H
4,5
K
4,0

3,5

3,0
D C B  A

2,5 70°C 55°C 40°C 25°C


E

2,0

K H
1,5

 -20% to +80% at 25°C


1,0

0,5

0,0
t [h]
Caution:

SICAM RTUs, I/O Modules 97


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 97/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.18.4 Pin Assig nment and Display

The process signals must be connected to two 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

98 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 98/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

2.18.5 Blo ck Diagram and External Circui try

SICAM RTUs, I/O Modules 99


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 99/139
7/25/2019 Sicam Tm Io Module Eng

Standard I/O Modules

100 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 100/139
7/25/2019 Sicam Tm Io Module Eng

3 Safety I/O Modules

Contents

3.1 DI-6170 ........................................................................................................102


3.2 DO-6270 ......................................................................................................117
3.3 AI-6370 ........................................................................................................130
3.4 Fault exclusion by constructional measures ..................................................138

SICAM RTUs, I/O Modules 101


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 101/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1 DI-6170

The safety-I/O-module DI-6170 is a binary input module. It is used for acquisition and transfer 
of 8 binary information with 24 VDC.

3.1.1 Features and Functi ons

·  8 digital inputs (2 groups, 4 inputs each)


·  Each group has a common return
·  Signal voltage 24 VDC
·  1 Test pulse output per group; can be set by parameter [ON/OFFS]; reset obligatory
·  Current limitation per group
·  Removable screw terminals
·  Indication of function and state of the inputs via LED
·  Over-voltage protection 24 VDC (of the external power supply)
·  Under-voltage protection 24 VDC (of the external power supply)
·  Power supply
·  TM bus coupling with galvanic insulation
·  EMV Filter 
·  Setting of the I/O-module address and PBA-number 
·  LED: system LED (ready, safety, error) and process LED
·  In two-channel version
 ─   Acquisition of process signals

 ─   Over-voltage protection of the 5 VDC


 ─   Under-voltage protection of the 5 VDC
 ─   Synchronization between two CPUs
 ─   Own watchdogs

102 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 102/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.2 View

SICAM RTUs, I/O Modules 103


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 103/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.3 Techni cal Specificatio ns

Safety cl asses

 According IEC 61508 SIL3

 According IEC 62061 SIL3

 According EN ISO13849 PL d, Cat. 4

Processor and Memory

Controller PIC18 – Family (PIC18F67K22)

Clock frequency 64 MHz

Program memory Internal, 128 KByte FLASH

Main memory Internal, > 3000 Byte SRAM

Parameter memory Internal, 1024 Byte EEPROM ( to store values of c alibration,

serial number)
Power Supply

Operating voltage 18.0…31.2 VDC external supply by


SELV/PELV power supply
5 VDC internal generation
Binary Inputs

8 binary inputs   ·  2 groups, 4 inputs each


·  galvanic insulation to TM bus
·  no galvanic insulation between inputs and the groups
·  Reading of mechanical contacts
Filter time All inputs 3 ms

Rated voltage: 24 VDC

Operating points   £ 13.5 V logically "0"


³ 16.5 V logically "1"

Rated current Approx. 1.7 mA at 24 V

Input circuits Supplied by module or external

Scan rate 10 ms

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)


Peripheral connector X1, X2

Dimensions 131x63x73 mm (LxWxH, dimensions w/o DIN rail)

104 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 104/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.4 Pin Assi gnment and Displ ay

The process signals must be connected to two 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
I
-
6
1
7
0

Pin Signal Pin Signal

1 IN D00 11 COM 0+

2 IN D01 12 COM 0+

3 IN D02 13 COM 0+

4 IN D03 14 COM 0+

5 IN D04 15 COM 1+

6 IN D05 16 COM 1+

7 IN D06 17 COM 1+

8 IN D07 18 COM 1+

9 AUX V0- 19 AUX V0+

10 AUX V0- 20 AUX V0+

The abbreviations have the following meaning:

 AUX V0-, AUX V0+ .................................... Module power s upply


IN D00 bis IN D03 ...................................... binary input of group 0
IN D04 bis IN D07 ...................................... binary input of group 1
COM 0+, CO M 1+ ...................................... pulsed output f or supply of external transmitter, g roup 0/1

SICAM RTUs, I/O Modules 105


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 105/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.5 Unique Modul e Number 

The addressing of the unique module number (PBA# und IOM#) is done by means of the
rotary switch on the back side of the module.

Switch position PBA# IOM#

0 0 0

1 1 1

2 2 2

3 3 3

4 4 4

5 5 5

6 6 6

7 7 7

8 8 – 

9 9 – 

 A 10 – 

B 11 –  

C 12 –  

D 13 –  

E 14 –  

F 15 –  

106 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 106/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.6 Blo ck Diagram

SICAM RTUs, I/O Modules 107


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 107/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.7 External Circui t Elements

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

3.1.7.1 Error Detecti on on the External Circui try

Following errors are detected on the input channels by permanent tests of the I/O-module.

·  Short-circuit of the sensor voltage supply


·  Short-circuit of the inputs when sensor supply is on
·  Cross fault between inputs of different groups
(test pulse must be set; depending on sensor)

Following errors can be detected by the application:

·  Interruption of the sensor (e.g. by double, 2-channel or/and antivalent circuitry)


·  Cross fault between inputs when using 2-channel sensors

Following errors are not recognized:

·  Cross fault between inputs within a group (1-channel sensor).


 A fault exclusion must be provided. See Fault exclusion by constructional measures

108 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 108/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.7.2 Singl e-Channel Sensor wi thout Test Pulse (achievabl e SIL 2)

DI-6170

     1      0      2


     1      2      X

     1      0      1


     1      X
     0     +      1     +      2     +      3     +      4     +      5     +      6     +      7     +    -     +    -     +
     0      0      0      0      0      0      0      0      0      1      0      1      0      1      0      1      0      0      0      0
     D      D      D      D      D      D      D      D      V      V      V      V
     M      M      M      M      M      M      M      M
     N      N      N      N      N      N      N      N      X      X      X      X
     I      O      I      O      I      O      I      O      I      O      I      O      I      O      I      O      U      U
     C      C      C      C      C      C      C      C      U      U
     A      A      A      A

+ 24 VDC
(SELV/PELV)
1 cable/sensor 1 cable/sensor  

Note
·  You must provide constructional measures to exclude faults in the external circuitry
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km

3.1.7.3 Single-Channel Sensor with out Test Pulse – Sensor suppl y


external (achievable SIL 2)

DI-6170

     1      0      2


     1      2      X

     1      0      1


     1      X
     0     +      1     +      2     +      3     +      4     +      5     +      6     +      7     +    -     +    -     +
     0      0
     0      0      D
     D      0      0      0
     D      0      D
     0      0      0
     D      1      D
     0      1      0
     D      1      D
     0      1      V      0
     V      V      0
     V
     M      M      M      M      M      M      M      M      X      X
     N      N      N      N      N      N      N      N
     I      O      I      O      I      O      I      O      I      O      I      O      I      O      I      O      U      X      X
     U      U      U
     C      C      C      C      C      C      C      C      A      A
     A      A

+ 24 VDC
(SELV/PELV)

Note
·  You must provide constructional measures to exclude faults in the external circuitry
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km

SICAM RTUs, I/O Modules 109


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 109/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.7.4 Double-Channel Sensor with homo geneous Channels wit hou t


Test Pulse (achievable SIL 3)

DI-6170

     1      0      2


     1      2      X

     1      0      1


     1      X
   -     +
    +     +     +      0      0
     0      1      0      2      3      0      4      5      6      7      1      V      V
     0      0      0      0      0      0      0      0
     D      D      M      D      D      M      D      D      D      D      M      X      X
     O      O      O      U      U
     N
     I      N
     I      C      N
     I      N
     I      C      N
     I      N
     I      N
     I      N
     I      C      A      A

+ 24 VDC
(SELV/PELV)
1 cable/sensor 1 cable/sensor  

Note
·  You must provide constructional measur es to exclude faults in the external circuitry
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km
·  A check of the plausibilit y of the input must be done in the application.

110 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 110/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.7.5 Double-Channel Sensor with homo geneous Channels wit hout


Test Pulse - Sensor suppl y external (achi evable SIL 3)

DI-6170

     1      0      2


     1      2      X

     1      0      1


     1      X
   -     +
     0      0
     0      1      2      3      4      5      6      7      V      V
     0      0      0      0      0      0      0      0
     D      D      D      D      D      D      D      D      X      X
     U      U
     N
     I      N
     I      N
     I      N
     I      N
     I      N
     I      N
     I      N
     I      A      A

+ 24 VDC
(SELV/PELV)

Note
·  You must provide constructional measures to exclude faults in the external circuitry.
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km
·  A plausibility check of the input must be made in the application.

SICAM RTUs, I/O Modules 111


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 111/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.7.6 Double-Channel Sensor with diverse Channels witho ut Test


Pulse (achi evable SIL 3)

DI-6170

     1      0      2


     1      2      X

     1      0      1


     1      X
   -     +
    +     +     +      0      0
     0      1      0      2      3      0      4      5      6      7      1      V      V
     0      0      0      0      0      0      0      0
     D      D      M      D      D      M      D      D      D      D      M      X      X
     O      O      O      U      U
     N
     I      N
     I      C      N
     I      N
     I      C      N
     I      N
     I      N
     I      N
     I      C      A      A

+ 24 VDC
(SELV/PELV)
1 cable/sensor 1 cable/sensor  

Note
·  SIL2: Several sensors can be conducted within a single cable
·  SIL3:You must provide constructional measures to exclude faults in the external circuitry
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km
·  A plausibility check of the input must be made in the application.

112 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 112/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.7.7 Singl e-Channel Sensor with Test Puls e (achievable SIL 2)

DI-6170

     1      0      2


     1      2      X

     1      0      1


     1      X
   -     +
    +     +     +     +     +      0      0
     0      0      1      0      2      0      3      0      4      5      6      7      1      V      V
     0      0      0      0      0      0      0      0
     D      M      D      M      D      M      D      M      D      D      D      D      M      X      X
     O      O      O      O      O      U      U
     N
     I      C      N
     I      C      N
     I      C      N
     I      C      N
     I      N
     I      N
     I      N
     I      C      A      A

+ 24 VDC
(SELV/PELV)
1 cable/sensor 1 cable/sensor  

Note
·  You must provide constructional measures to exclude faults in the external circuitry
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km
·  A test pulse is only useful if switches without own power supply and own testing are used.

SICAM RTUs, I/O Modules 113


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 113/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.7.8 Double-Channel Sensor with homogeneous Channels with Test


Pulse (achi evable SIL 3)

DI-6170

     1      0      2


     1      2      X

     1      0      1


     1      X
   -     +    +
    +     +     +      0      0
     0
     0      1      0      2      3      0      4      5      6      7      1      V      V
     V
     0      0      0      0      0      0      0      0
     D      D      M      D      D      M      D      D      D      D      M      X      X
     X
     O      O      O      U     U
     U
     N
     I      N
     I      C      N
     I      N
     I      C      N
     I      N
     I      N
     I      N
     I      C      A      A
     A

+ 24 VDC
(SELV/PELV)
1 cable/sensor 1 cable/sensor  

Note
·  You must provide constructional measur es to exclude faults in the external circuitry
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km
·  A check of the plausibilit y of the input must be done in the application.
·  A test pulse is only useful if switches without own power supply and own testing are used.

114 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 114/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.7.9 Double-Channel Sensor with homogeneous Channels wit h Test


Pulse (achievable SIL 3)

DI-6170

     1      0      2


     1      2      X

     1      0      1


     1      X
    +     +    -     +
     0      1      2      3      0      4      5      6      7      1      0      0
     0      0      0      0      0      0      0      0      V      V
     D      D      D      D      M      D      D      D      D      M
     O      O      X      X
     N
     I      N      N      N      N      N      N      N      U      U
     I      I      I      C      I      I      I      I      C      A      A

+ 24 VDC
(SELV/PELV)

Note
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km
·  A check of the plausibility of the input must be done in the application.
·  A test pulse is only useful if switches without own power supply and own testing are used.

SICAM RTUs, I/O Modules 115


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 115/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.1.7.10 Double-Channel Sensor wit h di verse Channels w it h Test Pulse


(achievable SIL 3)

DI-6170

     1      0      2


     1      2      X

     1      0      1


     1      X
     0      1      2      3     +      4      5      6      7     +    -     +
     0      0      0      0      0      0      0      0      0      1      0      0
     D      D      D      D      M      D      D      D      D      M      V      V
     N      N      N      N      N      N      N      N      X      X
     I      I      I      I      O      I      I      I      I      O      U      U
     C      C      A      A

+ 24 VDC
(SELV/PELV)

Note
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km
·  A check of the plausibilit y of the input must be done in the application.
·  A test pulse is only useful if switches without own power supply and own testing are used.

116 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 116/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2 DO-6270

The safety-I/O-module DO-6270 is a binary output module. It is used for the output of 4 digital
values. Transistor output 24 VDC.

3.2.1 Features and Functi ons

·  4 Transistor-Outputs
·  Switching voltage 24 VDC
·  Removable screw terminals
·  Indication of function and state of the outputs via LED
·  Over-voltage protection 24 VDC (of the external power supply)
·  Under-voltage protection 24 VDC (of the external power supply)
·  TM bus coupling with galvanic insulation
·  EMV Filter 
·  Setting of the I/O-module address and PBA number 
·  LED: system LED (ready, safety, error) and process LED
·  Shift register chain
·  In two-channel version
 ─   Acquisition of process signals
 ─   Over-voltage protection of the 5 VDC
 ─   Under-voltage protection of the 5 VDC
 ─   Synchronization between two CPUs

 ─   Own watchdogs

3.2.2 View

SICAM RTUs, I/O Modules 117


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 117/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.3 Techni cal Specificatio ns

Safety cl asses

 According IEC 61508 SIL3

 According IEC 62061 SIL3

 According EN ISO13849 PL d, Cat. 4 (by relays without electronic)


PL d, Cat. 3 (by relays with electronic)
Processor and Memory

Controller PIC18 – Family (PIC18F67K22)

Clock frequency 64 MHz

Program memory Internal, 128 KByte FLASH

Main memory Internal, > 3000 Byte SRAM

Parameter memory Internal, 1024 Byte EEPROM ( to store values of c alibration,


serial number)

Power Supply

Operating voltage 18.0…31.2 VDC external supply by a


SELV/PELV power supply
5 VDC internal generation
Binary Outputs

4 binary outputs (transistor)   ·  The inputs, outputs and logic circuit are galvanically insulated
from TM bus and ground.
·  The output circuits are operated by means of an external
voltage.
Rated switching voltage 24 VDC

Rated current ·  Ptot = 1.2 W (at ext. load 4 x 0.5 A)


·  Ptot = 1.4 W (at ext. load 1 x 2 A)
(for ohmic load)

Maximum continuous current Based on the electrical capability of the transistor-switch:


·  4 x 0.5 A
·  1 x 2 A (only 1 output active)

Nominal switching capacity   ·  Switching capacity of the output of DO-6270, (Udd = 24 VDC)
Pout = 48 W (atIout =1 x 2 A)
·  Switching capacity of the output of DO-6270, (Udd = 31.2 VDC)
Pout max = 65 W each output (R ext=15 Ω)
Pout sum max = 80 W - the sum of all 4 outputs, (Rext = 4x50 Ω)

Not overload proof Yes

Proof against continued short- 3.5 A current limitation, 2-stage 25 A / 3.5 A


circuit

Switching cycles Unlimited

Maximum output switching F = 3 Hz (all 4 channels are equipped)


frequency

Voltage drop in output circuit   ·  Max. voltage drop in P-part (U dd = 24 VDC, each output,
RLast = 20 Ω) …40 mV
·  Max. voltage drop in N-part (U dd = 24 VDC, each output,
RLast = 20 Ω) …35 mV
Dynamic load capability   ·  Capacitive load max. 44 nF bei 200 m
·  Inductive load   t £  1 ms (arbitrary with external free-wheeling
diode)
·  Lines Z  ³  100  W , length of line up to 200 m

118 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 118/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

Output Circuits   ·  Rated voltage 24 VDC


·  Voltage range 18…31.2 VDC
·  Connected load with ohmic resitance 15 Ω <Rext < 3 kΩ
·  Output voltage „Low“………U out(L) < 5 VDC (open circuit)
·  Output voltage „High“………U out(L) < 13 VDC (open circuit)

·  Max. output permanent leakage current (U dd = 24 VDC)


Iout-leck = 1,1 mA
·  Max. output current during meadurement (T = 10 ms,
Udd = 5 VDC, R L = 15 Ω)
Ioutmax = 80 mA
Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)


Peripheral connector X1, X2

Dimensions 131x126x73 mm (LxWxH, dimensions w/o DIN rail)

Weight Approx. 420 g

SICAM RTUs, I/O Modules 119


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 119/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.4 Pin Assig nment and Display

The process signals must be connected to two 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

D
O
-
6
2
7
0

SICAM

Pin Signal Pin Signal

1 OUT D00+ 11 OUT D00+

2 OUT D00- 12 OUT D00-

3 OUT D01+ 13 OUT D01+

4 OUT D01- 14 OUT D01-

5 OUT D02+ 15 OUT D02+

6 OUT D02- 16 OUT D02-

7 OUT D03+ 17 OUT D03+

8 OUT D03- 18 OUT D03-

9 AUX V0- 19 AUX V0+

10 AUX V0- 20 AUX V0+

The abbreviations have the following meaning:

 AUX V0-, AUX V0+ .................................... Module power sup ply


OUT D00+/- to OUT D03+/- .................... Transistor outputs

120 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 120/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.5 Uniqu e Modul e Number 

The addressing of the unique module number (PBA# und IOM#) is done by means of the
rotary switch on the back side of the module.

Switch PBA# IOM#


position

0 0 0

1 1 1

2 2 2

3 3 3

4 4 4

5 5 5

6 6 6

7 7 7

8 8 – 

9 9 – 

 A 10 – 

B 11 –  

C 12 –  

D 13 –  

E 14 –  

F 15 –  

SICAM RTUs, I/O Modules 121


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 121/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.6 Bl ock Diagram

122 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 122/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.7 External Circui t Elements

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

Hint
The external circuitry is authoritative for the achievable safety-integrity level of the whole system (sensors,
circuitry, safety-modules).

3.2.7.1 Error Detecti on on the External Circui try

Following errors are detected on the output channels by permanent tests of the I/O-module.

·  Short-circuit of the actuator voltage supply


·  Missing load voltage
·  Short-circuit
·  Overcurrent
·  Overvoltage
·  Cross fault between the outputs

SICAM RTUs, I/O Modules 123


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 123/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.7.2 Overvi ew - Circui try of the Output Driver 

The achievable safety-integrity level is dependent from the connected relay (with or without
electronic). See manual SICAM RTUs – Safety, Chapter Safety-Parameter .

DO-6270

    +    -     +    -     +    -     +    -


     0      0      1      1      2      2      3      3     +
     0      0      0      0      0      0      0      0      0
     D      D      D      D      D      D      D      D      V
     T      T      T      T      T      T      T      T      X
     U      U      U      U      U      U      U      U      U
     O      O      O      O      O      O      O      O      A

     1      0      2


     1      2      X

     1      0      1


     1      X

    +    -     +    -     +    -     +    -    -    -     +
     0      0      1      1      2      2      3      3      0      0      0
     0      0      0      0      0      0      0      0      V      V      V
     D      D      D      D      D      D      D      D      X      X      X
     T      T      T      T      T      T      T      T      U      U      U
     U      U      U      U      U      U      U      U      A      A      A
     O      O      O      O      O      O      O      O

    r     r     r     r


    o
     t     o
     t     o
     t     o
     t
    a     a     a     a
    u
     t     u
     t     u
     t     u
     t
     k      k      k      k
     A      A      A      A

+ 24 VDC
(SELV/PELV)

Note
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km

124 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 124/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.7.3 Example: Two-channel cir cuit ry wit h relay div ersity wit h read-
back of t he relay contact; r elay wit hout electronic

SIL 3 SIL 3 SIL 3

DI-6170
DO-6270
HENGSTLER - H469 M1
TAKT_0      l
    s
     ) OUT_D00     e
     2     n
     Q Dext.     n
 , IN_D00     a
     1 CH 1      h
     Q     c
     (      2
    s
     l
    e G7SA IN_D01
    n COM_00
    n
     h
    a
    c IN_D02
OUT_D01
     2
Dext.
IN_D03
CH 2

H469
COM_01

     )
TAKT_1
OUT_D02     s
     l
     4     e
     Q     n
 , Dext. IN_D04     n
     3 CH 3     a
     Q      h
     (     c
    s
     l IN_D05      2
    e G7SA
    n COM_02
    n
    a
     h IN_D06
    c
     2
OUT_D03

CH 4 Dext. IN_D07

H469
COM_03
M2 Uext+
Uext+
 AUX_V+
 AUX_V+

 AUX_V-
 AUX_V-
Uext-
Uext-
+24V (SELV) +24V (SELV)

Note
·  With this circuitry you can achieve SIL 3 / Kat. 4 for the whole system.
·  You must provide constructional measures to exclude faults in the external circuitry
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km

SICAM RTUs, I/O Modules 125


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 125/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.7.4 Example: Two-channel circuit ry with relay diversity without read-


back of the relay contact; Relay with out electronic

SIL 3 SIL 2

DO-6270
HENGSTLER - H469 M1
     ) OUT_D00
     2
     Q
 ,
     1
Dext.
CH 1
     Q
     (
    s
     l
    e G7SA
    n COM_00
    n
    a
     h
    c OUT_D01
     2
Dext.
CH 2

H469
COM_01

     ) OUT_D02
     4
     Q
 , Dext.
     3 CH 3
     Q
     (
    s
     l
    e G7SA
    n COM_02
    n
    a
     h
    c
     2
OUT_D03
Dext.
CH 4

H469
COM_03
M2
Uext+

 AUX_V+

 AUX_V-

Uext-
+24V (SELV)

Note
·  With this circuitry you can achieve SIL 2 / Kat. 3 for the whole system.
·  You must provide constructional measur es to exclude faults in the external circuitry
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km

126 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 126/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.7.5 Example: Emergency stop device 1; Relay wit h electron ic

SIL 2 SIL 3

Emergency stop device (Q0) in SIL 3 circuitry


(with 2-channel circuitry)
e.g.: Siemens 3TK2820 SIL3 relay
Itot
+U

IQ0

Q0 13 23 33 41
 A1 T1 IN1 T2 IN2

3TK2820

T3 IN3 A2
14 24 42

-U

Environment temperature when using


a 3TK2820 device:

Note
·  The 3TK2820 devices are primary made for E-Stop and for protected door applications
·  With this circuitry you can achieve SIL 2 / Kat. 3 for the whole system.

·  Cyclic testing of the external circuit is off.


·  You must provide constructional measures to exclude faults in the external circuitry
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km

SICAM RTUs, I/O Modules 127


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 127/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.7.6 Example: Emergency stop device 2; Relay wit h electron ic

SIL 2 SIL 3

Emergency stop device (Q0) in SIL 3 circuitry


(with 2-channel circuitry)
e.g.: Phoenix Contact PSR-ESP4
Itot
+U

IQ0
PSR-ESP4 Q0 13 23 31
 A1 K1

LOGIK
K2
 A2 Y1 Y2
14 24 32

Q1 Q2 H1
-U

Environment temperature when using


a PSR-ESP4 device:

Note
·  The PSR-ESP4 devices are primary made for E-Stop and for protected door applic ations
·  With this circuitry you can achieve SIL 2 / Kat. 3 for the whole system.
·  Cyclic testing of the external circuit is off.
·  You must provide constructional measur es to exclude faults in the external circuitry
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km

128 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 128/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.2.7.7 Transient effects of the external cir cuit ry wi th external load

Up to a length of 100 m, the line parameter (R K, LK, CK) have only little effects against the
transient effects, which are generated by load.

 LK 
t C  = 5  ×
 R K  + 40

RK …ohmic resistance of the line [ Ω]


LK …inductance of the line [H]
CK …capacity of the [H]
tC  …transient effects time on the line without load

Example:

Type of cable RK LK CK tC
*)
Cu-wire 2 x 0,5 length100 m 6,0 Ω 2,8 mH 8,8 nF 0,0003 s

*)
  2 x 100 m

The line length (cable length) for DO-6270 is restricted to 200 m at 220 nF/km.

The test times are determined by transient effects, generated by the resistance and the
induction of the line and the external load.

 L L
4× + t C  < t  D
 R L + 40 t  D = 0,009
  [s]

tC  …transient effects time on the line without load


tD  …time between the activation of the internal measuring circuit switch and the evaluation of the current
flow
(the time t D may be m ax. 10ms!)
LL …induction of the external load [H]
RL …ohmic resistance of the external load[ Ω]

Examples:

Relay RL LL 4 L L/(RL +40)+tC


 applicable

Schrack MT (RM) Relay 24 VDC 466 Ω 0,62 H 0,0052s yes

Rexroth RD22045 valve 24 VDC 21 Ω 0,097 H 0,0067s yes


*) *)
Hengstler H-469 relay 24 VDC 1300 Ω
*) *)
Omron G7SA relay 24 VDC 1600 Ω

*)
Values will be supplied later 

The minimal and maximal resistance values of the respective relay types may not be
exceeded.

Relay type Load resistance min. Load resistance max.

classic relay 18 Ω 2,0 kΩ


(parameterized as „Relay without electronic“)

relay with integrated electronic control 2,01 kΩ Unlimited


(parameterized as „Relay with electronic“)

SICAM RTUs, I/O Modules 129


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 129/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.3 AI-6370

The safety-I/O-module AI-6370 is an analog input module. It is used for acquisition and
transfer of 4 analog values (4 to 20 mA).

Note
Proof test interval
The probability values for the certified safety components guarantee a life time of 10 years for ordinary
configurations.

3.3.1 Features and Functi ons

·  4 inputs
·  Acquisition of currents 4 to 20 mA
 ─   Live zero measurement
·  Removable screw terminals
·  Function and state indication via LED
·  Over-voltage protection 24 VDC (of the external power supply)
·  Under-voltage protection 24 VDC (of the external power supply)
·  Current limitation
·  TM bus coupling with galvanic insulation
·  Setting of the I/O-module address and PBA-number 
·  LED: system LED (ready, safety, error) and process LED
·  In two-channel version
 ─   Over-voltage protection of the 5 VDC
 ─   Under-voltage protection of the 5 VDC
 ─   Synchronization between two CPUs
 ─   own watchdogs
 ─   Antialiasing filter 
 ─   ADC
 ─   Voltage difference (REF)

130 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 130/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.3.2 View

SICAM RTUs, I/O Modules 131


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 131/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.3.3 Techni cal Specificatio ns

Safety cl asses

 According IEC 61508 SIL2

 According IEC 62061 SIL2

 According EN ISO13849 PL d, Cat. 3

Processor and Memory

Controller PIC18 – Family (PIC18F67K22)

Clock frequency 64 MHz

Program memory Internal, 128 KByte FLASH

Main memory Internal, > 3000 Byte SRAM

Parameter memory Internal, 1024 Byte EEPROM ( to store values of c alibration,

serial number)
Power Supply

Operating voltage 18.0…31.2 VDC external supply by a


SELV/PELV power supply
5 VDC internal generation
P ower c ons um pt ion of AI -6370 Appr ox. 680 mW

Power dissipation of AI-6370 Approx. 1200 mW

 An alo g In pu ts

4 analog inputs   ·  Inputs are not galvanically insulated from each other 
·  Galvanic insulation to TM bus

Measurement ranges Current measurement + 20 mA

Resolution 16 Bit at + 20 mA
 Accuracy 0.25 % at 25°C

Safety Accuracy 1%

Input impedance Ca. 195 Ω at + 20 mA

Input circuits External sensor, auxiliary voltage 24 VDC/70 mA

Mechanics and Connectors

Terminals Removable screw terminals (grid size 5.08)


Peripheral connector X1, X2

Dimensions 131x63x73 mm (LxWxH), dimensions w/o DIN rail)

132 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 132/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

Liv e Zero Measurement – Overflo w- Underflow t reatment

technological value

32000

0
measured value

0 2 3mA 20mA

data point quality descriptor 

IV (Invalid)

hysteresis
limit

OV (Overflow)

In case of currents > 20 mA, the OV-Bit is set for the process value. The process value itself is
limited to the value 32000.

In case of currents > 21,25 mA the process value itself is additionally marked as “invalid” and
the channel goes into the safety state:

·  Process value 0

·  OV-Bit set
·  IV-Bit set
·  Channel-LED dark
·  Diagnosis entry

The concerned channel remains in the safety state until the next startup.

SICAM RTUs, I/O Modules 133


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 133/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.3.4 Pin Assig nment and Display

The process signals must be connected to two 10-pin screw terminals. The pin assignment of 
the peripheral connectors is described in the following table.

A
I
-
6
3
7
0

Pin Signal Pin Signal

1 GND V00 11 n.u.

2 GND V00 12 IN V00

3 GND V00 13 n.u.

4 GND V00 14 IN V01

5 GND V00 15 n.u.

6 GND V00 16 IN V02


7 GND V00 17 n.u.

8 GND V00 18 IN V03

9 AUX V0- 19 AUX V0+

10 AUX V0- 20 AUX V0+

The abbreviations have the following meaning:

 AUX V0-, AUX V0+ .................................... Module power sup ply


GND V00 .................................................... GND for sensor 
IN V00 to IN V03 ........................................ analog input
OUT V00 to OUT V 03 ................................ power s upply for s ensor 
n.u. ............................................................. not used

134 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 134/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.3.5 Uniqu e Modul e Number 

The addressing of the unique module number (PBA# und IOM#) is done by means of the
rotary switch on the back side of the module.

Switch position PBA# IOM#

0 0 0

1 1 1

2 2 2

3 3 3

4 4 4

5 5 5

6 6 6

7 7 7

8 8 – 

9 9 – 

 A 10 – 

B 11 –  

C 12 –  

D 13 –  

E 14 –  

F 15 –  

SICAM RTUs, I/O Modules 135


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 135/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.3.6 Bl ock Diagram

136 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 136/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.3.7 External Circui t Elements

The following circuitry variants are examples, and do not relate exclusively to the depicted
inputs/outputs.

3.3.7.1 Error Detecti on on the External Circui try

Following errors are detected on the input channels by permanent tests of the I/O-module:

·  Short-circuit of the sensor voltage supply


·  Short-circuit of the inputs when sensor supply is on
·  Interruption of sensor by live zero monitoring

3.3.7.2 Circui try Examples

 AI-6370

     1      0
     2      2
     X

     1      0      1


     1      X

     0      0      0      1      1      1      2      2      3      3      3    -     +    -     +
     0      0      0      0      0      0      0      0      0      0      0      0      0      0      0
     V      V      V      V      V      V      V      V      V      V      V      V      V      V      V
     D      D      N      D      D      N      D      N      D      D      N      X      X      X      X
     I      I      I      I      U      U      U
     N      N      N      N      N      N      N      U
     A      A      A      A
     G      G      G      G      G      G      G

+ 24 VDC
(SELV/PELV)

Note
·  You must provide constructional measures to exclude faults in the external circuitry
·  The cables must be shielded and grounded (e.g. cabinet entry)
·  Maximum permitted cable length: 200 m
·  Maximum capacitive load: 220 nF/Km

SICAM RTUs, I/O Modules 137


DC6-041-2.06, Edition 05.2014

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 137/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

3.4 Fault excl usion by const ructi onal m easures

Note
Please observe the notes on fault exclusions concerning wires/cables in EN ISO 13849-2,
Table D.4

The following example shows constructional measures which usually can be used for fault
exclusions against short circuits:

·  Alu-protective tube
·  Buried cable
·  (mechanical protecting) cable tray

Field (Ex-zone) Building (Ex-free zone)

Feeder 

push-button
Terminal bo x LKS-cabinet SPS-cabinet
(On/Off/Stop)
4-pole cable
(in ALU-protective tube)
16-pole cable 96-pole cable
buried (cable tray)
Overvoltage SIL-DI
protection
Return information

12-pole cable
(in ALU-protective tube)
NS-cabinet

Feeding

Heating

Not shown in above example:

· Short-guided or clamped connection wires in the cabinet.


These prevent a short circuit with other terminals / points when a cable is disconnected.
·  Earth connection and overvoltage protection are designed regarding mutual influencing or 
common cause in a way, that by redundancy and other measures a disconnection of the
earth connection, disconnection of the neutral point, a short circuit or potential loss are
prevented.
·  Separate cable per sensor 

Note
SICAM TM has no EX-approval.

138 SICAM RTUs, I/O Modules


Edition 05.2014, DC6-041-2.06

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 138/139
7/25/2019 Sicam Tm Io Module Eng

Safety I/O Modules

--- END OF DOCUMENT ---

http://slidepdf.com/reader/full/sicam-tm-io-module-eng 139/139