Document history 1

Safety Notes 2

Introduction 3
MindSphere
Overview of MindConnect
Elements 4
Getting Connected to MindSphere Mounting and installing
5
MindConnect Elements

Connecting MindConnect
Elements 6
Getting Started
Onboarding MindConnect
Elements 7
Configuring data in Asset
Manager 8

Configuring protocols 9

Firmware update 10
Visual analysis of assets in
Fleet Manager 11

Appendix A

02/2020
V1801.Feb/2020.1
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
indicates that minor personal injury can result if proper precautions are not taken.

NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG V1801.Feb/2020.1 Copyright © Siemens AG 2020.


Division Digital Factory Ⓟ 03/2020 Subject to change All rights reserved
Postfach 48 48
90026 NÜRNBERG
GERMANY
Table of contents

1 Document history .................................................................................................................................... 7


2 Safety Notes ........................................................................................................................................... 9
2.1 General safety instructions ....................................................................................................... 9
2.2 Notes on usage .......................................................................................................................12
3 Introduction ........................................................................................................................................... 13
3.1 Getting Started ........................................................................................................................13
3.2 Purpose of this document .......................................................................................................13
3.3 Functional overview of MindSphere........................................................................................14
3.4 Working with MindSphere .......................................................................................................15
3.5 Data model in "Asset Manager" ..............................................................................................16
4 Overview of MindConnect Elements ...................................................................................................... 18
5 Mounting and installing MindConnect Elements..................................................................................... 20
5.1 Checking package upon delivery ............................................................................................20
5.2 Mounting MindConnect Nano .................................................................................................21
5.2.1 Permitted mounting positions and surrounding temperature ..................................................22
5.2.2 Connecting the protective earth ..............................................................................................23
5.3 Mounting MindConnect IoT2040 .............................................................................................23
5.3.1 Permitted mounting positions and surrounding temperature ..................................................23
5.3.2 Mounting types ........................................................................................................................24
5.4 LED lights of MindConnect Elements .....................................................................................25
5.4.1 LED lights of MindConnect Nano ............................................................................................25
5.4.2 LED lights of MindConnect IoT2040 .......................................................................................26
5.4.3 Troubleshooting ......................................................................................................................29
5.5 USB commands ......................................................................................................................32
6 Connecting MindConnect Elements....................................................................................................... 38
6.1 Commissioning MindConnect Element ...................................................................................38
6.2 Firewall/Proxy rules for MindSphere .......................................................................................42
6.3 Connecting MindConnect Nano to MindSphere network........................................................43
6.4 Connecting MindConnect IoT2040 to MindSphere network ...................................................45
6.5 Connecting Port X2 P1 for MindConnect Element .................................................................46
6.6 MindConnect network plan .....................................................................................................47
7 Onboarding MindConnect Elements ...................................................................................................... 50
7.1 Overview of onboarding MindConnect Element .....................................................................50

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 3
Table of contents

7.2 Logging in to MindSphere ...................................................................................................... 51


7.3 Creating an asset ................................................................................................................... 51
7.4 Enable connection to MindConnect Element ......................................................................... 53
7.5 Configuring network settings.................................................................................................. 55
7.6 Transferring configuration to MindConnect Element ............................................................. 57
8 Configuring data in Asset Manager ....................................................................................................... 62
8.1 Creating an aspect and variables .......................................................................................... 63
8.2 Creating a type in Asset Manager.......................................................................................... 65
8.3 Adding a data source and data points ................................................................................... 67
8.3.1 Adding a data source ............................................................................................................. 67
8.3.2 Adding data points ................................................................................................................. 69
8.4 Mapping an aspect to a data source ...................................................................................... 71
9 Configuring protocols ............................................................................................................................ 74
9.1 Overview of S7 protocol ......................................................................................................... 74
9.2 Overview of OPC UA protocol ............................................................................................... 80
9.3 Overview of Modbus TCP protocol ........................................................................................ 84
9.4 Overview of Modbus RTU protocol ........................................................................................ 87
9.5 Overview of SIMATIC I/O Shield............................................................................................ 92
9.6 Overview of SYSTEM protocol .............................................................................................. 94
9.7 Overview of Rockwell protocol ............................................................................................. 105
10 Firmware update ..................................................................................................................................108
10.1 Manual firmware update of MindConnect Element .............................................................. 108
10.2 Firmware update in Asset Manager ..................................................................................... 109
11 Visual analysis of assets in Fleet Manager ...........................................................................................112
11.1 Overview visual analysis ...................................................................................................... 112
11.2 Selecting assets ................................................................................................................... 112
11.3 Viewing aspects ................................................................................................................... 114
11.4 Viewing events ..................................................................................................................... 116
A Appendix .............................................................................................................................................118
A.1 Data center locations ........................................................................................................... 118
A.2 Quality code settings ............................................................................................................ 118
A.2.1 Using quality code ................................................................................................................ 118
A.2.2 Quality codes OPC UA and S7 protocol .............................................................................. 119
A.2.3 Quality codes Modbus protocol............................................................................................ 121
A.2.4 Quality codes SIMATIC I/O Shield ....................................................................................... 122
A.2.5 Quality codes SYSTEM protocol.......................................................................................... 122
A.2.6 Quality codes Rockwell protocol .......................................................................................... 123
A.3 Technical specifications of MindConnect Nano ................................................................... 123

Getting Connected to MindSphere


4 Getting Started, 02/2020, V1801.Feb/2020.1
Table of contents

A.4 Technical specifications of MindConnect IoT2040 ...............................................................126


A.5 Offline buffer .........................................................................................................................129
A.6 Read performance MindConnect Elements ..........................................................................129
A.7 Firewall Settings....................................................................................................................131
A.8 ESD guideline .......................................................................................................................133
A.9 Return of defect hardware ....................................................................................................135
A.10 List of abbreviations ..............................................................................................................136
Glossary ............................................................................................................................................. 138

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 5
This document provides an overview of the MindConnect devices to connect your assets to
MindSphere.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 6
Document history 1
Version Date Changes Link
V1801.Feb/2020.2 2020-02-20 Update of USB commandos. USB commands (Page 32)
Added new command re-
stricted device configuration.
Update of OPC UA protocol. Overview of OPC UA proto-
You can now activate events col (Page 80)
and alarms.
Update of Modbus TCP Overview of Modbus TCP
protocol. Added optional protocol (Page 84)
data source parameter.
Update of Modbus RTU Overview of Modbus TCP
protocol. Added optional protocol (Page 84)
data source parameter.
V1801.Jan/2020.1 2020-01-08 Added Rockwell protocol Overview of Rockwell proto-
section. col (Page 105)
Update of quality codes for Quality codes Rockwell
Rockwell protocol. protocol (Page 123)
V1801.Dec/2019.1 2019-12-02 Update of Connecting Mind- Connecting MindConnect
Connect Nano to Mind- Nano to MindSphere network
Sphere network. (Page 43)
Added note for Proxy IP Configuring network settings
address. (Page 55)
Added note for limitations for Adding data points
data points. (Page 69)
Update of Modbus TCP Overview of Modbus TCP
protocol. protocol (Page 84)
Update of SYSTEM protocol. Overview of SYSTEM pro-
tocol (Page 94)
V1801.Oct/2019.1 2019-10-02 Update of SYSTEM protocol. Overview of SYSTEM pro-
tocol (Page 94)
V1801.Aug/2019.1 2019-08-07 You can now use NTLM Configuring network settings
Authentication in the proxy (Page 55)
configuration.
V1801.Jun/2019.1 2019-06-13 Update of S7 protocol chap- Overview of S7 protocol
ter. (Page 74)
Update of Modbus protocol Overview of Modbus TCP
chapter. protocol (Page 84)
You can now use hysteresis Adding data points
in the data point configura- (Page 69)
tion.
V1801.Mai/2019.1 2019-05-15 Added new chapter "Mind- MindConnect network plan
Connect network plan". (Page 47)
Update of Read performance Read performance Mind-
of MindConnect Elements Connect Elements
(Page 129)

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 7
Document history

Version Date Changes Link


Added Modbus protocol Configuring protocols
section for Modbus TCP and (Page 74)
Modbus RTU.
V1801.Mar/2019.1 2019-03-18 Added note for Firmware Firmware update
update. (Page 108)
V1801.Feb/2019.1 2019-02-11 Added health status to data Adding data points
point section. (Page 69)
Added SYSTEM protocol Overview of SYSTEM pro-
section. tocol (Page 94)
Update of S7 protocol sec- Overview of S7 protocol
tion. (Page 74)
Update of OPC UA section. Overview of OPC UA proto-
col (Page 80)
V1801.Jan/2019.1 2019-01-14 Update of S7 protocol sec- Overview of S7 protocol
tion. (Page 74)
Update of technical specifi- Technical specifications of
cations. MindConnect Nano
(Page 123)
V1801.Dec/2018.1 2018-12-17 Added new topic Regions in Data center locations
MindSphere. (Page 118)
Added chapter Firmware Firmware update
update. (Page 108)
Added chapter Return of Return of defect hardware
defect hardware. (Page 135)
Update of Notes on usage. Notes on usage (Page 12)
Added section Calculation of Read performance Mind-
buffer time. Connect Elements
(Page 129)
Added chapter USB com- USB commands (Page 32)
mandos.
V1801.CW.EU1.K1203 2018-12-03 Updated section configuring Configuring protocols
protocols. (Page 74)
Added new chapter Read Read performance Mind-
performance of MindConnect Connect Elements
Elements. (Page 129)
V1801.K1113 2018-11-13 Added new protocols Mod- Configuring protocols
bus and SIMATiC I/O Shield. (Page 74)

Getting Connected to MindSphere


8 Getting Started, 02/2020, V1801.Feb/2020.1
Safety Notes 2
2.1 General safety instructions

WARNING
Life-threatening voltages are present with an open control cabinet
When you install the device in a control cabinet, some areas or components in the open
control cabinet may be carrying life-threatening voltages.
If you touch these areas or components, you may be killed by electric shock.
Switch off the power supply to the cabinet before opening it.

System expansions

NOTICE
Damage through system expansions
Device and system expansions may be faulty and can affect the entire machine or plant.
The installation of expansions can damage the device, machine or plant. Device and
system expansions may violate safety rules and regulations regarding radio interference
suppression. If you install or exchange system expansions and damage your device, the
warranty becomes void.

Note the following for system expansions:


Only install system expansion devices designed for this device. Contact your technical
support team or the team where you have purchased your PC to find out which system
expansion devices may safely be installed.
Observe the information on electromagnetic compatibility (EMC). Refer to the chapter
Technical specifications of MindConnect Nano (Page 123)/Technical specifications of
MindConnect IoT2040 (Page 126).

NOTICE
"Open Type" UL508
Note that the device is classified as "Open Type" for use in the area of Industrial Control
Equipment (UL508).
Installation of the device in an enclosure complying with UL508 is a prerequisite for
approval or operation in accordance with UL508.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 9
Safety Notes
2.1 General safety instructions

Battery and rechargeable battery

WARNING
Risk of explosion and release of harmful substances
Improper handling of lithium batteries can result in an explosion of the batteries.
Explosion of the batteries and the released pollutants can cause severe physical injury.
Worn batteries jeopardize the function of the device.
Note the following when handling lithium batteries:
• Replace used batteries in good time; see the section "Replacing the backup battery" in
the operating instructions.
• Replace the lithium battery only with an identical battery or types recommended by the
manufacturer.
• Do not throw lithium batteries into fire, do not solder on the cell body, do not recharge,
do not open, do not short-circuit, do not reverse polarity, do not heat above 100°C and
protect from direct sunlight, moisture and condensation.

Strong high-frequency radiation

NOTICE
Observe immunity to RF radiation
The device has an increased immunity to RF radiation according to the specifications on
electromagnetic compatibility in the technical specifications.
Radiation exposure in excess of the specified immunity limits can impair device functionality
resulting in malfunctions and therefore injuries or damages.
Read the information on immunity to RF radiation in the technical specifications.

ESD Guideline
Electrostatic sensitive devices can be labeled with an appropriate symbol.

Getting Connected to MindSphere


10 Getting Started, 02/2020, V1801.Feb/2020.1
Safety Notes
2.1 General safety instructions

NOTICE
Electrostatic sensitive devices (ESD)
When you touch electrostatic sensitive components, you can destroy them through voltages
that are far below the human perception threshold.
If you work with components that can be destroyed by electrostatic discharge, observe the
ESD Guideline. Refer to the chapter ESD guideline (Page 133).

Open Source Software


Siemens will identify the open source software components contained in MindConnect Nano
and MindConnect IoT2040, including the applicable license text and will include such license
text(s) in or provide them together with MindConnect Nano/ Iot2040. Should the license(s)
applicable to any part of the open source software require the distribution of the open source
software’s source code and build scripts together with MindConnect Nano/IoT2040 (or,
alternately, an offer to make the source code and build scripts available upon request), then
Siemens will provide such source code or such offer to customer together with MindConnect
Nano. No license fee is charged to customer for the use of such open source software.
Customer acknowledges and agrees that Siemens provides no warranties, express or
implied, and no indemnification for the open source software itself. Customer hereby accepts
that the open source software is subject to the specific license terms included in or provided
together with MindConnect Nano. To the extent there is a conflict between these terms and
the open source specific license terms, such terms shall prevail with regard to the open
source software.

Industrial Security
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks. In order to protect plants,
systems, machines and networks against cyber threats, it is necessary to implement – and
continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’
products and solutions only form one element of such a concept. Customer is responsible to
prevent unauthorized access to its plants, systems, machines and networks. Systems,
machines and components should only be connected to the enterprise network or the
internet if and to the extent necessary and with appropriate security measures (e.g. use of
firewalls and network segmentation) in place.
Additionally, Siemens’ guidance on appropriate security measures should be taken into
account. For more information about industrial security, please visit
http://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends to apply product updates as soon as available and to
always use the latest product versions. Use of product versions that are no longer supported,
and failure to apply latest updates may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed under: http://www.siemens.com/industrialsecurity.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 11
Safety Notes
2.2 Notes on usage

2.2 Notes on usage

NOTICE
Possible functional restrictions in case of non-validated plant operation.
The device is tested and certified on the basis of the technical standards. In rare cases,
functional restrictions can occur during plant operation.
Validate the correct functioning of the plant to avoid functional restrictions.
Mindsphere provides a highly reliable system, however the MindConnect can be affected
by system internal incidents.

Note
Use in an industrial environment without additional protective measures.
This device was designed for use in a normal industrial environment according to IEC
60721-3-3.

Note
Firmware MiniWeb versions
The connection to a SIMOCODE, SIMOTION, SINAMICS OPC UA Server cannot
reestablish automatic if the used Firmware has a MiniWeb version is less than V5.1. It's
recommended to upgrade to a new Firmware version of the SIMOCODE, SIMOTION,
SINAMICS device.

Getting Connected to MindSphere


12 Getting Started, 02/2020, V1801.Feb/2020.1
Introduction 3
3.1 Getting Started
This manual gives you an overview of MindSphere with MindConnect Nano and
MindConnect IoT2040, enabling you to commission these devices and start working with
MindSphere.

Basic knowledge requirements


● General knowledge about personal computers is required.
● General knowledge in the field automation control engineering is recommended.

Scope of validity of this document


This manual is valid for MindSphere and MindConnect Elements:
● MindConnect Nano
● MindConnect IoT2040

Convention
The term “device” is used to refer to MindConnect Nano and MindConnect IoT2040. The
terms for MindSphere can be found in Glossary in the Appendix of this documentation.
The configuration parameters should be extracted out of the text or tables
and depend respectively on the needs and constellation of the individual system.

Internet address
Click the following link to find MindSphere documentation: MindSphere Documentation Area
(http://documentation.mindsphere.io)

3.2 Purpose of this document


This Getting Started provides you with information to become familiar with commissioning
the device MindConnect Nano or IoT2040 (MindConnect Elements) and working with
MindSphere.
By using the examples given in this manual, you will be able to develop or change your
service. You will know how to access and configure the data from your assets as well as
create and answer requests.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 13
Introduction
3.3 Functional overview of MindSphere

You will work through typical steps involved in configuring MindConnect Elements and your
asset data. You will become familiar with the tools that MindSphere provides for
configuration and visualization of assets and aspects.

3.3 Functional overview of MindSphere


This part of Getting Started outlines the functional overview of MindSphere.
MindSphere offers the means to monitor asset status as well as support maintenance and
services. This requires sensor data, the tools to collect and transfer data as well as intelligent
software that offers the monitoring and support functions.
MindConnect Elements provide the hardware for collecting data from assets and transferring
it into MindSphere, which includes hosting via a web user interface.

With MindSphere and MindConnect Elements you can:


● Create and manage users and customers
● Create, manage and change assets in MindSphere
● Onboard MindConnect Elements to MindSphere in order to collect data from your assets
and transfer it to MindSphere
● Collect data from data sources (S7, OPC UA) via MindConnect Elements
● Visualize the uploaded data (timeseries)
● Display datapoints and open events of an asset
● Manage the connected assets and automate rules

Getting Connected to MindSphere


14 Getting Started, 02/2020, V1801.Feb/2020.1
Introduction
3.4 Working with MindSphere

3.4 Working with MindSphere


This part of the Getting Started provides you with a brief summary of instructions described
in detail in this manual.

Requirements
● Internet connection and newest version of your internet browser(e. g. Google chrome or
Firefox) for online user interface
● Internet connection for MindConnect Nano/IoT2040 device
● Provide standard HTTPS capabilities for MindConnect Nano/IoT2040 - outbound HTTPs
connection(s) on port 443
● Link to the online Launchpad with user and password data as supplied by Siemens
● Device (PC, tablet etc.) with minimum screen resolution of 1024x768

Configuring steps

Prepare MindConnect Elements for MindSphere


1. Mount MindConnect Nano/IoT2040 on your physical asset.
2. Connect MindConnect Elements to power supply and the Internet.

Onboard MindConnect Elements


1. Log in to your MindSphere account.
2. Configure your asset and MindConnect Element which is mounted to your physical asset.
3. Configure network settings of MindConnect Elements and proxy as needed to establish
Internet connection to MindSphere.
4. Upgrade to the newest firmware version.
5. Establish the initial connection (onboarding) by transferring the configuration manually by
USB stick.

Configure data collection with Asset Manager


1. Log in to MindSphere with your account.
2. Create an asset in Asset Manager.
3. Configure the data points you want to use.
4. MindConnect Nano/IoT2040 receives the configuration from MindSphere via an existing
Internet connection.
5. MindConnect Nano/IoT2040 starts the data acquisition.
6. The timeseries can be displayed in Fleet Manager.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 15
Introduction
3.5 Data model in "Asset Manager"

Visual analysis of assets with Fleet Manager


1. Monitor assets in different views.
2. Monitor aspects and events.

3.5 Data model in "Asset Manager"


This chapter describes the data model of Asset Manager within MindSphere. The data model
will show you what processes are necessary to connect and use your asset data in
MindSphere.

Definition asset
An asset is a digital representation of a machine or an automation system with one or
multiple automation units (e.g. PLC) connected to MindSphere.
MindSphere data collection and data provisioning is based on so called (virtual) assets. This
can be anything like a pump, motor, PLC, an entire tool machine, a production line, a robot,
a crane, a car, a wind turbine and so on. The data of an asset is collected and sent to
MindSphere to make that data available for further processing and analytics.

Definition aspect
Aspects are a data modeling mechanisms for assets. Aspects group related data points
based on their logical association. For example: The pump skid has an aspect e.g.
"Energy_consumption" that contains the data points: "power", "current", "voltage" etc. Aspect
is specified in Asset Manager and its name can be freely chosen, but should have
conjunction to datapoints and a physical asset. An aspect can consist of several variables.

Getting Connected to MindSphere


16 Getting Started, 02/2020, V1801.Feb/2020.1
Introduction
3.5 Data model in "Asset Manager"

Data model
The following graphic shows the data model in Asset Manager:

In Asset Manager devices like MindConnect Nano are defined as the data source. The
device sends data points to MindSphere. These data points must be connected to the
aspects and variables. Asset Manager uses aspects and variables as data containers.
Within MindSphere you add data points to a data source to collect the data, for example from
a control unit. In the next step you have to link the data points to the respective variables of
an aspect.
To enable data connecting and in order to use your data in MindSphere you have to fulfill the
following processes:
● Onboarding (Page 50): Onboarding is the process of attaching a MindConnect Element to
MindSphere.
● Data mapping (Page 71): Data mapping matches variables of an aspect with the
respective data points of a data source.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 17
Overview of MindConnect Elements 4
MindConnect Elements, MindConnect Nano and MindConnect IoT2040, are embedded
industrial PCs. They are able to connect to MindSphere, collect data from the field and
transfer it encrypted to MindSphere.

MindConnect Nano
MindConnect Nano is a preconfigured Industrial PC that allows connectivity to MindSphere.
The device supports the transmission of data encrypted through a secured Internet
connection to MindSphere. MindConnect Nano allows fast and easy IoT connectivity of
machines and systems. For more information refer to chapter Technical specifications of
MindConnect Nano (Page 123). The following graphic shows the MindConnect Nano:

Getting Connected to MindSphere


18 Getting Started, 02/2020, V1801.Feb/2020.1
Overview of MindConnect Elements

MindConnect IoT2040
MindConnect IoT2040 has a compact design and can also be used for collecting and
transferring data to MindSphere in smaller production environments. The device supports the
transmission of encrypted data over a secured Internet connection to enable cloud-based
applications and services. For more information refer to chapter Technical specifications of
MindConnect IoT2040 (Page 126). The following graphic shows the MindConnect IoT2040:

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 19
Mounting and installing MindConnect Elements 5
5.1 Checking package upon delivery
1. When accepting a delivery, please check the package for visible transport damage.
2. If any transport damage is present at the time of delivery, submit a complaint at the
shipping company in charge. Have the shipper confirm the transport damage
immediately.
3. Unpack the device at its installation location.
4. Keep the original packaging in case you have to transport the unit again.

Note
Damage to the device during transport and storage
If a device is transported or stored without packaging, shocks, vibrations, pressure and
moisture may impact the unprotected unit. Damaged packaging indicates that ambient
conditions may have already had a massive impact on the device.
The device may be damaged.
Do not dispose of the original packaging. Pack the device during transportation and
storage.

5. Check the content of the packaging and any accessories you may have ordered for
completeness and damage.

Getting Connected to MindSphere


20 Getting Started, 02/2020, V1801.Feb/2020.1
Mounting and installing MindConnect Elements
5.2 Mounting MindConnect Nano

6. If the content of the package is incomplete, damaged or does not match your order,
inform the responsible delivery service immediately.

WARNING
Electric shock and fire hazard due to damaged device
A damaged device can be under hazardous voltage and trigger a fire in the machine or
plant. A damaged device has unpredictable properties and states.
Death or serious injury could occur.
Make sure that the damaged device is not inadvertently installed and put into operation.
Label the damaged device and keep it locked away. Return the device for immediate
repair.

NOTICE
Damage from condensation
If the device is subjected to low temperatures or extreme fluctuations in temperature
during transportation, for example in cold weather, moisture could build up on or inside
the HMI device.
Moisture causes a short circuit in electrical circuits and damages the device. In order to
prevent damage to the device, proceed as follows:
• Store the device in a dry place.
• Bring the device to room temperature before starting it up.
• Do not expose the device to direct heat radiation from a heating device.
• If condensation develops, wait approximately 12 hours or until the device is
completely dry before switching it on.

7. Please keep the enclosed documentation in a safe place. It belongs to the device. You
will need the documentation when you commission the device for the first time.
8. Write down the identification data of the device.

5.2 Mounting MindConnect Nano

Note
Security of MindConnect Elements
In order to ensure the security of your MindConnect Element, you should mount it in a
restricted access location e. g. lockable cabinet.
This reduces the possibility of manipulations on the device/customer data.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 21
Mounting and installing MindConnect Elements
5.2 Mounting MindConnect Nano

5.2.1 Permitted mounting positions and surrounding temperature


The following mounting positions and surrounding conditional temperature are permitted:
● Horizontal mounting position: The horizontal mounting position is the preferred position.
Maximum surrounding temperature is 60°C.
● Vertical mounting position: Maximum surrounding temperature is 50°C.

Note
> 50 °C: Install in RAL
RAL = Restricted Access Location - e.g. a lockable cabinet

Free space around the device


Please make sure there’s enough empty space around the device
● Above the device: ≥ 50 mm
● Below the device: ≥ 100 mm

Note
Maximum height
The maximum altitude to install MindConnect Nano is 4000 m.

Getting Connected to MindSphere


22 Getting Started, 02/2020, V1801.Feb/2020.1
Mounting and installing MindConnect Elements
5.3 Mounting MindConnect IoT2040

5.2.2 Connecting the protective earth

Figure 5-1 Connecting protective earth

5.3 Mounting MindConnect IoT2040

5.3.1 Permitted mounting positions and surrounding temperature


The following mounting positions and surrounding conditional temperature are permitted:
● Horizontal mounting position: The horizontal mounting position is the preferred position.
Maximum surrounding temperature is 50°C.
● Vertical mounting position: Maximum surrounding temperature is 50°C.

Note
> 50 °C: Install in RAL
RAL = Restricted Access Location - e.g. a lockable cabinet

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 23
Mounting and installing MindConnect Elements
5.3 Mounting MindConnect IoT2040

Free space around the device


Please make sure there’s enough space around the device
● Above the device: ≥ 50 mm
● Below the device: ≥ 50 mm

5.3.2 Mounting types

Note
Ensure that the mounting surface on the wall can bear four times the total weight of the
device, including attached elements.
Use only the anchors and screws specified in the operating instructions.

The following mounting types of the device are possible:

Mounting on rails

Figure 5-2 Mounting on rails

Getting Connected to MindSphere


24 Getting Started, 02/2020, V1801.Feb/2020.1
Mounting and installing MindConnect Elements
5.4 LED lights of MindConnect Elements

Wall mounting

Figure 5-3 Wall mounting

5.4 LED lights of MindConnect Elements

5.4.1 LED lights of MindConnect Nano

LED lights
The LED lights status provide information on efficient self-diagnostics. The following graphics
show the LED lights of the MindConnect Nano:

Figure 5-4 LED lights - bottom view 1

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 25
Mounting and installing MindConnect Elements
5.4 LED lights of MindConnect Elements

Figure 5-5 LED lights - bottom view 2

The following table shows the meanings of the LED lights:

LED-Name Status Description


PC ON/WD GREEN Power on
ORANGE System restart
L1-RUN/STOP ORANGE • No connection to proxy·
• No connection to MindSphere
For explanation of possible problems and respective solution, please
refer to the chapter “Troubleshooting”.
Blinking ORANGE Connection to MindSphere is being established.
Blinking GREEN Onboarding is in progress.
GREEN MindConnect Nano is onboarded to MindSphere.
L2 - ERROR Blinking ORANGE Firmware update active.
ORANGE • No connection to the data sources
For explanation of possible problems and respective solution, please
refer to the chapter “Troubleshooting”.
Blinking RED • Data loss
For explanation of possible problems and respective solution, please
refer to the chapter “Troubleshooting”.
RED Firmware update error
L3 - MAINT Blinking ORANGE USB stick is active:
• Installing USB configuration
ORANGE Onboarding failed:
• Configuration file on the USB stick is not valid
Blinking RED • USB stick Error
For explanation of possible problems and respective solution, please
refer to the chapter “Troubleshooting”.

You can find more information about LED error codes in section Troubleshooting (Page 29).

5.4.2 LED lights of MindConnect IoT2040

LED lights
The LED lights provide information on the status of the device for efficient self-diagnostics.

Getting Connected to MindSphere


26 Getting Started, 02/2020, V1801.Feb/2020.1
Mounting and installing MindConnect Elements
5.4 LED lights of MindConnect Elements

MindConnect IoT2040 features the following LED lights:

LED-Name Status Description


PWR GREEN Power on
SD GREEN Micro SD card active
USB GREEN USB Power (5V) is available
OC RED Overcurrent
USER GREEN/RED/ORANGE Programmed for MindSphere, see details below

The USER LED light is only programmed for MindSphere.

Figure 5-6 USER LED light

The following table describes the device behavior associated when a different USER LED
status is displayed

Name Status Description


USER LED Fast USB STICK ACTIVE
ORANGE
• Network diagnostics are running
Blinking
• Configuration file is being read
USER LED RED Blink- USB STICK ERROR
ing
• Read error, USB flash drive is damaged
• Configuration file is invalid (damaged, illegible or configured for a different asset)
• Write error, USB flash drive is write-protected or its memory is full.
For explanation of possible problems and respective solution, please refer to the chapter
“Troubleshooting”.
ORANGE FIRMWARE UPDATE ACTIVE
Blinking
RED FIRMWARE UPDATE ERROR
For explanation of possible problems and respective solution, please refer to the chapter
“Troubleshooting”
ORANGE NO CONNECTION TO PROXY
• Network cable is missing or damaged
• Ethernet port on MindConnect IoT2040 is damaged
• “ipconfig” of MindConnect IoT2040 is incorrect
• Firewall of MindConnect IoT2040 blocks
• Your company’s router is damaged
• Proxy is offline
• No authentication on Proxy
• Proxy configuration is invalid

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 27
Mounting and installing MindConnect Elements
5.4 LED lights of MindConnect Elements

Name Status Description


ORANGE NO CONNECTION TO CLOUD
• Proxy is invalid
• Server is offline
• An addressed server cannot be accessed
• Network problems of a provider
• No authorization
ORANGE CONNECTION TO CLOUD ESTABLISHED
Blinking LED light flashes green for a short time to indicate the onboarding process - otherwise is or-
ange
GREEN ONBOARDING IN PROGRESS
Blinking
USER LED ORANGE ONBOARDING FAILED
Flashing LED flashes red for a short time to indicate onboarding is falling
Possible reason:
• Server error
• OBT is no longer valid
For explanation of possible problems and respective solution, please refer to the chapter
“Troubleshooting”.
GREEN ONBOARDED
ORANGE NO CONNECTION TO DATA SOURCE
• Problem with network connection of your machine
• Network cable is not plugged in or is damaged
• Machine is offline
RED Blink- MindConnect IoT2040 IS LOSING DATA
ing
• MindConnect IoT2040 is offline and the data buffer is full
• Slow data transfer
For explanation of possible problems and respective solution, please refer to the chapter
“Troubleshooting”.

You can find more information about LED error codes in section Troubleshooting (Page 29).

Getting Connected to MindSphere


28 Getting Started, 02/2020, V1801.Feb/2020.1
Mounting and installing MindConnect Elements
5.4 LED lights of MindConnect Elements

5.4.3 Troubleshooting

Error Problem Possible cause Possible remedy


MCN L1-RUN/STOP MindConnect Element can- Network connection problem: • Check your configuration
IoT2040 USER LED not onboard to MindSphere connection: If configured
• Either IP address is not
ORANGE No Internet connection valid or configured IP ad- IP and Proxy are valid
dress already exists in • Check physical connec-
the network of MindCon- tion: your company’s
nect Nano router, Ethernet cables
• Either disabled or invalid etc.
configured Proxy
• Proxy is offline
• Interrupted connection
• IP address is configured
via DHCP, but there is no
internet connection.
• Firewall blocks MindCon-
nect Elements
• Your company’s router is
damaged
MCN L2 - ERROR LED Although an asset is No connection to data Check the connection be-
IoT2040 USER LED onboarded, no time series source tween MindConnect Nano
are uploaded to Fleet Man- and data sources (Plant
ORANGE
ager and Visual Analyzer. Network ports and cables -
S7/OPC UA Server)
The address of the data • Check the connection
point configuration can be between MindConnect
incorrect Nano and data sources
(Plant Network ports and
cables - S7/OPC UA
server)
• Check data sources
configuration.
• Check configuration of
each data point.
MindConnect Nano/IoT2040 • Incorrect asset configura- Check configuration of your
cannot onboard to Mind- tion asset (Network Configura-
Sphere tion).
• Not accomplished asset
configuration (Network
Connection)
Invalid ID of MindConnect Check if MindConnect Nano
Nano ID is correct.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 29
Mounting and installing MindConnect Elements
5.4 LED lights of MindConnect Elements

Error Problem Possible cause Possible remedy


MCN L2- ERROR LED Data loss MindConnect Nano/IoT2040 • Check outbound connec-
blinking RED was too long offline, so it tion
could not send data to Mind-
IoT2040 USER LED • Check Ethernet cables
Sphere and the storage is
blinking RED full. • Check Proxy (IP address,
User Authentication can
be required)
MCN L2- ERROR LED Firmware update error • Technical problems with • Make sure that you are
RED a new version of firmware using the correct firm-
IoT2040 USER LED • Incorrect firmware type ware type (MindConnect
Nano/IoT2040).
• Certificate problems,
Authentication problems • MindConnect
etc. Nano/IoT2040 will auto-
matically restart and then
firmware update will be
carried out after a while.
• If MindConnect
Nano/IoT2040 does not
restart automatically,
then restart it manually:
by switching on and off
the “power button” on
MindConnect Nano and
by switching off/on the
power supply for Mind-
Connect IoT2040.

Getting Connected to MindSphere


30 Getting Started, 02/2020, V1801.Feb/2020.1
Mounting and installing MindConnect Elements
5.4 LED lights of MindConnect Elements

Error Problem Possible cause Possible remedy


MCN L3- MAINT LED Onboarding failed • Configuration file on the • Make sure that the data
ORANGE USB stick is invalid on the USB stick still is
IoT2040 USER LED • Internal error valid. (The data, which
blinking you exported to the USB
stick, is still valid only for
7 days.). If it is expired,
use the asset configura-
tion to export a new valid
configuration to your USB
stick.
• Check asset configura-
tion and reconfigure, if it
is required and export a
new configuration to USB
stick
MCN L3-MAINT LED Problems with USB stick • Incorrect formatting of • Check format and parti-
blinking RED USB stick (no FAT or tion of the USB stick. It
IoT2040 USER LED FAT32) must be FAT or FAT32
blinking • USB stick is damaged formatted and may only
contain a single partition.
• Write error, USB stick is
write-protected or its • Try a new USB stick
memory is full.
• Configuration file is inva-
lid (damaged, illegible)
• See also below

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 31
Mounting and installing MindConnect Elements
5.5 USB commands

Error Problem Possible cause Possible remedy


Although no LED lights are Problems with USB stick: • Remove and plug an
shown (except PC ON/WD USB stick into MindCon-
• Configuration file in USB
with constant GREEN) and nect Nano
stick cannot be read or
internet connection is OK,
MindConnect Nano still can- accepted by MindCon- • Check the diagnosis file
not be onboarded to Mind- nect Nano: on the USB stick.
Sphere • Problems with configura- • Check the name of the
tion file configuration file. It must
• Configuration file is lo- have MindConnect Nano
cated in an incorrect di- ID. Do not change the
rectory. name of the downloaded
file.
• Expired configuration file
on the USB stick • Check whether the direc-
tory is valid. (Configura-
• The configuration file is
tion file must be in the
invalid or not copied to
root directory of the USB
the USB stick
stick.)
• Make sure that the data
on the USB stick is still
valid. (The data, which
you exported to the USB
stick, is still valid only for
7 days.) If it is expired,
use the asset configura-
tion to export a new valid
configuration to your USB
stick.
System Error Unknown • Switch MindConnect
Nano off and on again.
• If the problem persists,
contact your Siemens
Support/„Expert Center“.

5.5 USB commands


You can run diagnostic and maintenance USB commands on your MindConnect Element.
The following lists various USB commands and the respective JSON format:

Copy agent logs to USB stick


You can create agent runtime log files and provide them by using the USB stick.
The following command will collect all log files, put them into a .tar.gz file and copy this file to
the USB stick.
JSON format:
{

Getting Connected to MindSphere


32 Getting Started, 02/2020, V1801.Feb/2020.1
Mounting and installing MindConnect Elements
5.5 USB commands

"Commands": [

"Cmd":"CopyAgentLogsToUsbStick"

Copy archived logs to USB stick


You can retrieve archived log files from MindConnect Nano/IoT2040 by using the USB stick.
The following command will copy all archived log files to a sub directory on the USB stick
and delete the copied log files from the archive folder optionally. The USB stick should be
larger than 200 MB.
Sub directories on the USB stick will have following structure: ConBox_<BOX
ID>/<CurrentTime>Sample:ConBox_J47110815/20180318T191647
JSON format:
{

"Commands": [

"Cmd":"CopyArchivedLogsToUsbStick",

"DeleteAfterCopy":"false"

Copy system files to USB stick


For analysis purpose you can copy system files to a USB stick by providing a
ConBox_Commands.json file on the USB stick that contains the
CopySystemFilesToUsbStick command.
The following command will collect the requested system files and provide them as a
ConBox_<deviceID>_SystemFiles.tar.gz file on the USB stick.
JSON format:
{

"Commands": [

"Cmd": "CopySystemFilesToUsbStick",

"TypeOfFiles": "LinuxSystemFiles"

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 33
Mounting and installing MindConnect Elements
5.5 USB commands

System files:
Depending on the value of TypeOfFiles the .tar.gz file will contain different system files.

TypeofFiles Collected system files


LinuxSystemFiles /persistent/config/hosts
/persistent/config/interfaces
/persistent_massdata/sysmsg.log
/persistent_massdata/sysmsg.log.0
/tmp/resolv.conf
/tmp/sysinfos.info
/var/log/boot
/var/log/dmesg
/var/log/fsck.log
AgentSystemFiles /persistent_appconfig/dns.static
/persistent_appconfig/loggingconfig.ini
AllSystemFiles All Linux and Agent system files listed above.

Change system time


For the case that the system time should have been changed so that agent runtime is no
longer able to connect to MindSphere, you can retrieve the backend time to correct the
system time. The following command provides the possibility to change the system time
manually via ConBox_Commands.json file on the USB stick.
JSON format:
{

"Commands": [

"Cmd": "SetSystemTime",

"NewTime": "2017-09-19T12:34:56"

Perform factory reset


For factory reset a ConBox_Commands.json file can be provided by using the USB stick.
The network settings will be reset to their initial state on MindConnect Nano/IoT2040. All
temporary files will be then deleted. At the end the MindConnect device will be restarted
automatically.
The factory reset command is available on MindConnect Nano/IoT2040 version 03.01.00.00
b00x or later.

Getting Connected to MindSphere


34 Getting Started, 02/2020, V1801.Feb/2020.1
Mounting and installing MindConnect Elements
5.5 USB commands

JSON format:
{

"Commands": [

"Cmd": "DoFactoryReset",

"DeviceID": "_MindConnect_ID_"

You can find more information on how to set a MindConnect Element to factory settings in
chapter Manual firmware update of MindConnect Element (Page 108)

Restricted device configuration


The RestrictDeviceConfiguration command allows you to enable or disable online device
configuration changes via MindSphere user interface after the MindConnect device has been
successfully onboarded.
If you need to adapt the configuration, you have to create a new onboarding file with new e.
g. network parameter and insert this data again via USB.

Note
Make sure that all parameters are valid before exporting the configuration file to prevent
unwanted changes that can lead to invalid network settings, for example.

Note
Effects on online device configuration
There is no indication in the MindSphere asset configuration user interface that the device
configuration has been restricted on MindConnect Nano/IoT2040 device.
If you try to change restricted device settings online, a message is logged in the diagnostic
file on the MindConnect Nano / IoT2040 device that this setting could not be applied.

JSON format:
{

"Commands": [

{ "Cmd":"RestrictDeviceConfiguration",

"networkInterfaces": [

"name": "WebInterface",

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 35
Mounting and installing MindConnect Elements
5.5 USB commands

"DHCP": "true",

"IPv4": "true",

"SubnetMask": "true",

"Gateway": "true",

"DNS": "true"

},

"name": "ProductionInterface",

"DHCP": "true",

"IPv4": "true",

"SubnetMask": "true",

"Gateway": "true",

"DNS": "true"

To prevent changes of network interface settings, the following parameters can be specified
in the JSON command:

Parameter Description
name Name of the network interface.
Possible values:
• WebInterface
• ProductionInterface
DHCP • true: DHCP setting can not be changed
• false: DHCP setting can be changed (default)
IPv4 • true: IP address can not be changed
• false: IP address can be changed (default)
SubnetMask • true: Subnet mask can not be changed
• false: Subnet mask can be changed (default)
Gateway • true: Gateway address can not be changed
• false: Gateway address can be changed (default)
DNS • true: DNS address can not be changed
• false: DNS address can be changed (default)

Getting Connected to MindSphere


36 Getting Started, 02/2020, V1801.Feb/2020.1
Mounting and installing MindConnect Elements
5.5 USB commands

Note
• If you only provide some of the above mentioned parameters, then the omitted
parameters will be ignored. This means that either the last restricted device configuration
of these parameters will be used, or they will be treated as not set.
• To enable device configuration changes of specific parameters again, a JSON command
containing those parameters with value "false" can be provided via USB stick.
• To turn it off a new JSON command file needs to be provided with "false" for all
parameters.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 37
Connecting MindConnect Elements 6
This chapter shows you how to connect MindConnect Elements to the power supply and to
the Internet (for MindSphere).

6.1 Commissioning MindConnect Element

Objective
The MindConnect Elements should be connected to the power supply and commissioned.

Requirements
● The protective conductor is connected (valid only for MindConnect Nano). Refer to the
chapter Connecting the protective earth (Page 23).
● A two-core cable with a cable cross-section of 0.75 mm² to 2.5 mm².
● A slotted screwdriver with a 3 mm blade.

NOTICE
Power supply requirements
MindConnect Nano should only be connected to a 24 V DC to power supply which satisfies
the requirements of safety extra low voltage (SELV) according to IEC/EN/DIN EN/UL
60950-1.
MindConnect IoT2040 should only be connected to a 9...36 V DC power supply which
meets the requirements of safe extra low voltage (SELV) according to IEC/EN/DIN EN/UL
60950-1.
The power supply must meet the NEC class 2 or LPS requirement in accordance with
IEC/EN/DIN EN/UL 60950-1.

Note
The MindConnect Nano/IoT2040 package does not include power supply. The appropriate
power supply product from Siemens with the name SITOP can be used.

Getting Connected to MindSphere


38 Getting Started, 02/2020, V1801.Feb/2020.1
Connecting MindConnect Elements
6.1 Commissioning MindConnect Element

Procedure

CAUTION
Danger of burns
The surface of the device can reach temperatures of over 70 °C. Any unprotected contact
may cause burns.
Avoid direct contact during operation of the device. Touch the device only with appropriate
protective gloves.

1. Switch off the power supply on the device.


2. Connect the cores of the power supply.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 39
Connecting MindConnect Elements
6.1 Commissioning MindConnect Element

3. Insert the terminal at the indicated position.


– The graphic shows how to connect the power supply for MindConnect Nano:

Figure 6-1 Connecting the power supply for MindConnect Nano

– The graphic demonstrates the steps how to connect the power supply for
MindConnect IoT2040:

Getting Connected to MindSphere


40 Getting Started, 02/2020, V1801.Feb/2020.1
Connecting MindConnect Elements
6.1 Commissioning MindConnect Element

Figure 6-2 Connecting the power supply for MindConnect IoT2040

4. Power on the power supply.


– For MindConnect Nano, set the on/off switch to position "I" (ON). The "PC ON/WD"
LED lights up green.
– For MindConnect IoT2040, switch on the power supply. The graphic shows the “PWR”
LED lights up green.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 41
Connecting MindConnect Elements
6.2 Firewall/Proxy rules for MindSphere

Figure 6-3 Power on a power supply for MindConnect IoT2040

Result
MindConnect Nano/IoT2040 is now prepared and you can onboard it to MindSphere.
If the green light does not appear, refer to section Troubleshooting (Page 29) for more
information about LED messages.

6.2 Firewall/Proxy rules for MindSphere


MindConnect Element require open HTTPS and DNS ports for communication with
MindSphere. You can open port 443 to enable this.
MindConnect Element will connect to the following DNS names:
<region>.mindsphere.io
For <region> enter the area that was defined in your contract, e. g. eu1.
Mindsphere uses modern cloud principles (such as content delivery networks) to achieve
high availability/scalability. The above mentioned DNS names can be resolved to a large
range of IP addresses based on the context of the caller and the state of the backend.

Getting Connected to MindSphere


42 Getting Started, 02/2020, V1801.Feb/2020.1
Connecting MindConnect Elements
6.3 Connecting MindConnect Nano to MindSphere network

Port exceptions
For region eu2, please add the following port exception to enable the online firmware
download:
● https://mdspedgeprodstorageact.blob.core.windows.net

6.3 Connecting MindConnect Nano to MindSphere network


The following options are available for integrating the device in existing or planned system
environments and networks.

① X63 port
② PN/IE LAN X1 P1 port
③ PN/IE LAN X2 P1 port

Figure 6-4 Connections of MindConnect Nano

Note
The two network adapters are separated from each other. There is no direct connection
between the two networks possible to ensure network security. Therefore, you can not
create any configuration from the cloud to the field level (e.g. OPC UA server).

The following table explains each connection port in detail:

Port Description
X63 USB 2.0 port, high current. Configuration file on USB stick.
Required during onboarding process.
PN/IE LAN X1 P1 RJ45 Ethernet connection 1 for 10/100/1000 Mbps. Access to the Internet (to MindSphere).
Required to start onboarding process.
PN/IE LAN X2 P1 RJ45 Ethernet connection 2 for 10/100/1000 Mbps. Access to the plant network or asset (e.g. S7,
OPC UA).
Required to complete onboarding process.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 43
Connecting MindConnect Elements
6.3 Connecting MindConnect Nano to MindSphere network

Prerequisite
For 250 datapoints read per second, the upload bandwidth should be at least 0.5 Mb/s.

Procedure
Before you start onboarding, connect MindConnect Nano to MindSphere, as follows:
Insert Ethernet cable into the port labeled with X1 P1 to connect MindConnect Nano to
MindSphere.

Note
MindConnect Nano MAC address
The type plate on of the MindConnect Nano shows 2 MAC addresses. The first MAC
address belongs to port X1 P1.

Figure 6-5 Connecting the port X1 P1 for Internet (MindSphere)

Getting Connected to MindSphere


44 Getting Started, 02/2020, V1801.Feb/2020.1
Connecting MindConnect Elements
6.4 Connecting MindConnect IoT2040 to MindSphere network

6.4 Connecting MindConnect IoT2040 to MindSphere network


The following options are available for integrating the device in existing or planned system
environments and networks.

① X60 port
② PN/IE LAN X1 P1 port
③ PN/IE LAN X2 P1 port

Figure 6-6 Interfaces of MindConnect IoT2040

The following table explains each connection port in detail:

Port Description
X60 USB 2.0 port, high current. Configuration file on USB stick.
Required during onboarding process.
PN/IE LAN X1 P1 RJ45 Ethernet connection 1 for 10/100/1000 Mbps. Access to the Internet (to MindSphere).
Required to start onboarding process
PN/IE LAN X2 P1 RJ45 Ethernet connection 2 for 10/100/1000 Mbps. Access to the plant network (e.g. S7, OPC
UA).
Required to complete onboarding process.

Procedure
Before you start onboarding, connect MindConnect IoT2040 to MindSphere, as follows:
Insert Ethernet cable for Internet into the port labeled with X1 P1.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 45
Connecting MindConnect Elements
6.5 Connecting Port X2 P1 for MindConnect Element

Figure 6-7 Connecting the port X1P1 for internet (MindSphere)

Note
During the onboarding process, only one USB stick is supported. Do not plug in more than
one USB stick. The recommended USB port is the USB port with label X60.

6.5 Connecting Port X2 P1 for MindConnect Element

Objective
The MindConnect Element can now be connected to the plant network or asset.

Requirements
● An asset has been created in Asset Manager.
● The configuration has been transferred via USB stick to the MindConnect Element.

Getting Connected to MindSphere


46 Getting Started, 02/2020, V1801.Feb/2020.1
Connecting MindConnect Elements
6.6 MindConnect network plan

Procedure
To connect the MindConnect Element to your plant network or asset, insert the Ethernet
cable into the port labeled with X2 P1.
The following graphic shows the connecting port of the MindConnect Nano:

Figure 6-8 Connecting Ethernet Port X2 P1 MindConnect Nano

The following graphic shows the connecting port of the MindConnect IoT2040:

Figure 6-9 Connecting Ethernet Port X2 P1 MindConnect IoT2040

6.6 MindConnect network plan


You can set up the network plan for your MindConnect Elements in two ways. The following
scenarios show them with IP address examples:

Note
In both scenarios it is important that you set X1 and X2 in different (and not overlapping)
subnets.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 47
Connecting MindConnect Elements
6.6 MindConnect network plan

Scenario A
The following scenario shows a setup example where each network-port of the MindConnect
is connected to another switch or router.

The following table shows possible setups:

Port Exemplary configuration


X1 • IP address: 192.168.1.10
• Mask: 255.255.255.0
X2 • IP address: 192.168.3.110
• Mask: 255.255.255.0
Data source • IP address: 192.168.3.120
• Mask: 255.255.255.0

Note
• Make sure that X1 is in another and not overlapping subnet then X2.
• If you have a DHCP master in both network, you can use DHCP in both. In this case,
make sure that the DHCP masters are set up so that X1 and X2 are in another subnet.

Getting Connected to MindSphere


48 Getting Started, 02/2020, V1801.Feb/2020.1
Connecting MindConnect Elements
6.6 MindConnect network plan

Scenario B
This following scenario shows a setup example where both network-ports of the
MindConnect, are connected to the same switch or router.

The following table shows possible configuration setups:

Port Exemplary configuration


X1 • IP address: 192.168.1.10
• Mask: 255.255.255.0
X2 • IP address: 192.168.3.110
• Mask: 255.255.255.0
Data source • IP address: 192.168.3.120
• Mask: 255.255.255.0

Note
• Make sure that X1 is in another and not overlapping subnet then X2.
• You can only use DHCP for one port or subnet. The other has to be set up as static IP
address. In this case, make sure that the DHCP master is set up so that X1 and X2 are in
another subnet.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 49
Onboarding MindConnect Elements 7
7.1 Overview of onboarding MindConnect Element
This chapter describes the initial configuration of an asset and MindConnect Nano/IoT2040
in order to onboard MindConnect Nano/IoT2040 to MindSphere. Onboarding is the process
of attaching a MindConnect Element to MindSphere.
To establish the initial connection between MindConnect Nano/IoT2040 and MindSphere
(onboarding), you have to configure the essential asset and MindConnect Nano/IoT2040
data. For onboarding the full configuration is not required, although you can accomplish all
steps using Asset Manager.
The respective data to be configured for onboarding is described in the following procedure.

Requirements
● MindConnect Nano/IoT2040 is connected to the Internet and powered on.
● The connection cable for the Internet is correctly plugged into the Ethernet port for the
Internet (MindSphere).
● MindConnect Nano/IoT2040 is connected to asset or plant network.
● You have received the link to the MindSphere UI with credentials (user and password
data).
● A customer account is created.
● A standard USB device with a single partition in FAT or FAT32 is formatted.
● You have the role "mdsp:core:TenantAdmin". The user roles are set in Settings.

Note
Prepare MindConnect Elements
To prepare your MindConnect Element for MindSphere V3, you have to update the firmware
for boxes that were already connected to MindSphere V2 (SAP). For devices connecting to
MindSphere region China 1, the MindConnect Nano or IoT2040 firmware should be V3.3.0.4
or higher.
You can find more information in chapter Manual firmware update of MindConnect Element
(Page 108).

Onboarding Procedure
In order to onboard MindConnect Nano/IoT2040, you must perform the following steps:
1. Login to MindSphere. (Page 51)
2. Create an asset in Asset Manager. (Page 51)

Getting Connected to MindSphere


50 Getting Started, 02/2020, V1801.Feb/2020.1
Onboarding MindConnect Elements
7.2 Logging in to MindSphere

3. Enable connection to MindConnect Element in Asset Manager. (Page 53)


4. Configuring network settings (Page 55)
5. Transfer configuration to MindConnect Element (Page 57).

7.2 Logging in to MindSphere


To log in to MindSphere, proceed as follows:
1. Click the link provided via mail by the Siemens AG.
– The MindSphere landing page for login will appear.
2. Log in to MindSphere using the configured Authentication Provider (WebKey by default).
– You will be redirected to your personal MindSphere Launchpad.
– Depending on your offering the Launchpad Icons will be displayed.

Note
MindSphere supports English, German and Chinese languages. Therefore it is
recommended to set the browser default to English, if you use a different language.

7.3 Creating an asset


To connect your MindConnect Element in Asset Manager you need to create an asset.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 51
Onboarding MindConnect Elements
7.3 Creating an asset

Procedure
To create an asset proceed as follows:
1. Select Asset Manager from the Launchpad.
2. Click "Assets" in the navigation area.
3. To create a new asset click .
The asset type overview window is opened.

4. Select the respective asset type for your MindConnect Element, e. g. MindConnect Nano.
5. Enter a name and the data for the asset, e. g. "Wind turbine"
6. Confirm the entries with "Save".

Result
The new asset is available at the asset list.
The following graphic shows the created asset:

Getting Connected to MindSphere


52 Getting Started, 02/2020, V1801.Feb/2020.1
Onboarding MindConnect Elements
7.4 Enable connection to MindConnect Element

7.4 Enable connection to MindConnect Element


To use a MindConnect Element with MindSphere you have to enable the connection. Within
enabling the connection you can assign a MindConnect Element to an asset.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 53
Onboarding MindConnect Elements
7.4 Enable connection to MindConnect Element

Procedure
To enable the connection to the MindConnect Element proceed as follows:
1. Select the asset in the "Asset" tab.
2. In the "Connectivity" area click on the MindConnect Element plugin icon, e. g.
"MindConnect Nano".
The "Create MindConnect" screen appears.

3. Enter the unique ID from your hardware.

Result
You have enabled the connection to the MindConnect Element.

Getting Connected to MindSphere


54 Getting Started, 02/2020, V1801.Feb/2020.1
Onboarding MindConnect Elements
7.5 Configuring network settings

7.5 Configuring network settings


Network configuration of MindConnect Nano/IoT2040 requires information on the ethernet
interfaces for data acquisition (ethernet labeled with X2P1) and MindSphere (ethernet
labeled with X1P1). If your company uses a proxy server, it must also be configured to
connect MindConnect Nano/IoT2040 to MindSphere. Contact your IT administrator for
details on your local network settings.
After enabling the connection to the MindConnect Element you can edit the network
configuration. You can enter either a static IP address or use DHCP. The last option is
possible, if there is a DHCP server available in your company network.

Procedure
To configure the network setting, follow these steps:
1. Select the asset in the "Asset" tab.
2. Click on the asset icon, e. g. "MindConnect Nano".

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 55
Onboarding MindConnect Elements
7.5 Configuring network settings

3. Click next to "Status" on the button .


The following graphic shows the "Edit MindConnect" screen:

Getting Connected to MindSphere


56 Getting Started, 02/2020, V1801.Feb/2020.1
Onboarding MindConnect Elements
7.6 Transferring configuration to MindConnect Element

4. Activate DHCP if a DHCP server is available in your company network or enter the
respective information for static IP address.
The following graphic shows the IP address input fields:

5. Enter the proxy data area "Communication Settings" if necessary and click "Save".
– In this case, contact your network administrator to get the proxy data. For Proxy IP
address input field, it is also possible to define the port number e.g. 127.0.0.1:8080.
– For proxy authentication type NTLM: The domain and the username have to be
provided as "username@domain" or as "domain/username".

Note
If nothing else is configured manually, MindConnect Nano/IoT2040 will try to obtain IP
addresses for both adapters via DHCP.

6. Click on "Save", to complete the configuration.

7.6 Transferring configuration to MindConnect Element

Requirement
● A standard USB device with a single partition in FAT or FAT32 is formatted.
● You have enabled the connection to the MindConnect Element.
● You have configured the network settings.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 57
Onboarding MindConnect Elements
7.6 Transferring configuration to MindConnect Element

Procedure

WARNING
USB stick information
The configuration created in this step includes security relevant information. You can
encrypt and sign the information. Take care of the USB stick and the information flow from
MindSphere to USB stick and from USB stick to the MindConnect Element. Delete the USB
stick after use.

Getting Connected to MindSphere


58 Getting Started, 02/2020, V1801.Feb/2020.1
Onboarding MindConnect Elements
7.6 Transferring configuration to MindConnect Element

To export the configuration, follow these steps:


1. In the MindConnect settings click .
The following graphic shows the "Edit MindConnect" screen:

2. In order to encrypt the onboarding key data, activate the "Encrypted" checkbox.
3. Click on "Download Onboarding Key".
4. Save the downloaded file to the root directory of your USB stick.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 59
Onboarding MindConnect Elements
7.6 Transferring configuration to MindConnect Element

5. Insert the USB stick into the USB port of the MindConnect Element, e. g. "MindConnect
Nano"

Note
During the import of the configuration, the following LED-states are to be expected:
1. MAINT LED flashes orange
2. RUN LED blinks green
3. On-boarding result
– RUN LED green: MindConnect onboarded successfully
– MAINT LED orange: onboarding failed
The process can take up to 30 minutes. Please do not remove the USB stick during this
time.

6. After successfully importing the configuration, remove the USB stick from the
MindConnect Element.
7. Check the status of the MindConnect Element at the Overview.

Result
The connection status in Asset Manager at the overview has changed to "Onboarded". The
configuration of the asset has been transferred to the MindConnect Element. The connection
between the MindConnect Element and MindSphere is established.
Once MindConnect Nano/IoT2040 is onboarded, the connection to your asset is permanent
and your asset for data collection can be configured. This requires configuration of machine
data to be monitored. Any additional configuration (except network configuration) of the
connected asset will automatically be synchronized with your onboarded MindConnect
Nano/IoT2040.
The connection to the asset is permanent and can only be cancelled by offboarding. For this
purpose, refer to the Asset Manager documentation.

Getting Connected to MindSphere


60 Getting Started, 02/2020, V1801.Feb/2020.1
Onboarding MindConnect Elements
7.6 Transferring configuration to MindConnect Element

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 61
Configuring data in Asset Manager 8
After onboarding a MindConnect Element, you need to configure the data in Asset Manager.
You have to set up a data connection to receive data from your MindConnect Element.
In order to use the data from your MindConnect Element in MindSphere you need to map the
received data to the Asset Manager data model:

Asset Manager uses the following areas:


● Assets
● Types
● Aspects

Getting Connected to MindSphere


62 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring data in Asset Manager
8.1 Creating an aspect and variables

In order to configure data in Asset Manager you need to fulfill the following steps:
● Creating an aspect and variables (Page 63)
In this step you create aspects and variables you want to use in MindSphere.
● Creating a type in Asset Manager (Page 65)
In this step you create an asset type to enable data mapping.
● Adding a data source (Page 67)
The data source defines the reading of the data from the MindConnect Element.
● Mapping an aspect to a data source (Page 71)
In this final step you map the data of the MindConnect Element to the aspects and
variables in MindSphere.

8.1 Creating an aspect and variables


To use the data of your MindConnect Element in MindSphere you need to create aspects
and variables in Asset Manager.
Aspects are combined, pre-configured data and form the context for the evaluation of
industrial processes. An aspect can consist of several variables. Within the industry process,
assets transfer the aspects as time series data in MindSphere.
In Asset Manager you can create aspect types. Aspect types are pre-configured templates
for aspects. The advantage of aspects types is to use one type for several assets. For
example, you can create one aspect type for all generators of a wind farm with the variable
rotation speed.

Procedure
To add an aspect type in Asset Manager, e. g. "Generator", follow these steps:
1. On the start screen click "Aspects".
2. To create a new aspect click .
3. Enter your Tenant ID for the aspect, e. g. "idevdoc.generator".

Note
All custom aspects and types must be named as "<TenantID>.xxx"

4. Enter a name and description for the aspect e. g. "Generator".

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 63
Configuring data in Asset Manager
8.1 Creating an aspect and variables

5. Follow these steps for each variable, e. g. "RotationSpeed":


– Enter variable data.

Note
• The units and data types specified here will need to match exactly(also case
sensitive) with the physical data source.

Figure 8-1 Variable data

– Click "Add variable".


6. Confirm with "Save".

Getting Connected to MindSphere


64 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring data in Asset Manager
8.2 Creating a type in Asset Manager

Result
The new aspect type with its variables is available in the aspect list.

8.2 Creating a type in Asset Manager


To enable data mapping you first have to create an asset type. An asset type is a pre-
configured template for an asset. The asset type predefines which aspects are integrated
into the template. You have to link aspects to an asset type to enable the connection to a
data point.

Requirement
● You have created an aspect.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 65
Configuring data in Asset Manager
8.2 Creating a type in Asset Manager

Procedure
To create an asset type proceed as follows:
1. Click on the "Types" tab in Asset Manager.
2. Click on "BasicDevice".
3. To create a new asset type click .
4. Enter ID and name for asset type, e. g. "Wind turbine".

Note
The ID must be named as "TenantID.xxx".

5. Select an aspect type from the dropdown menu, e. g. "Generator". You can find additional
information on aspects in the chapter Creating an aspect and variables (Page 63)
6. Enter an aspect name and click "Add".
7. To save the asset type click "Save".

Getting Connected to MindSphere


66 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring data in Asset Manager
8.3 Adding a data source and data points

Result
You created a new asset type. The new asset type is now available in the presets. The
following graphic shows the new available asset type "Wind turbine" in assets.

8.3 Adding a data source and data points

8.3.1 Adding a data source


To receive the data of your MindConnect Element you need to add a data source. The data
source specifies the protocol and reading cycle that is used to transfer the data from your
asset to the MindConnect Element. Within the data source, you enter the IP address of the
asset inside of your network.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 67
Configuring data in Asset Manager
8.3 Adding a data source and data points

Requirement
● You have created an asset and an aspect.
● You have enabled the connection to the MindConnect Element.
● You have the IP address of the asset inside of your network.

Procedure
To add a data source to an asset of type MindConnect, e. g. "Generator", follow these steps:
1. Click on the asset in the "Assets" tab, e. g. "Wind turbine".
2. Click on the asset icon, e. g. "MindConnect Nano".
3. Click "Add new data sources".
– The window to enter the protocol data is opened

Note
• The default reading cycle is 86400 seconds, which is one day.
• You can find additional information on supported protocols in the chapter Configuring
protocols (Page 74).

4. Enter data source data and confirm with "Accept".


5. To save the data source click "Save".

Getting Connected to MindSphere


68 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring data in Asset Manager
8.3 Adding a data source and data points

Result
You have now created a new data source. The new data source is available at the asset
details of your MindConnect Element.
The following graphic shows the added data source:

8.3.2 Adding data points


A data point is a measurable value of an asset that can be represented numerically and
graphically. Examples of a data point are temperature or pressure. Within MindSphere you
add data points to a data source to collect the data for example from a control unit. In the
next step you have to link the data points of a data source with the respective variables of an
aspect.

Note
Limitations
One data point cannot be mapped to two variables in the same aspect.

Note
Health status
The health status shows the quality of the connection of the data point. You can click on the
status to get further information. You can find additional information about quality code in
chapter Quality code settings (Page 118).

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 69
Configuring data in Asset Manager
8.3 Adding a data source and data points

Requirement
● You have created a data source.

Procedure
To add a data point to a data source, e. g. "RotationSpeed", follow these steps:
1. Click on the asset in the "Assets" tab, e. g. "Wind turbine".
2. Click on the asset icon, e. g. "MindConnect Nano".
3. To edit the data source you have to click on "Enter Edit Mode".
– Edit functions appear next to the data source.
4. Click on "Add Datapoint".
5. Enter data point data.

Note
• The units and data types specified here will need to match exactly with the aspects
and variables. If they are different, the aspect cannot be connected to the data point.
• The protocol datatypes specify the Datapoint Address. You can find additional
information on protocol datatypes in the chapter Configuring protocols (Page 74).
• It is possible to use hysteresis value in this field. This reduces the number of read
events. The hysteresis filters signals and reduces the response to short-term signal
fluctuations. The maximum value for hysteresis can be 99999 to minimum as 0.001.

Getting Connected to MindSphere


70 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring data in Asset Manager
8.4 Mapping an aspect to a data source

6. Confirm with "Accept".


7. To save the added data point in "Edit Mode" click "Save".

Result
The new data point is available at the data source.
In order to send the changes to the device, you have to click "Apply Changes" in the
MindConnect plugin.
The following graphic shows the health status of the new data point:

8.4 Mapping an aspect to a data source


Data mapping means matching variables of an aspect with the respective data points of a
data source.
● Variables of an aspect represent the MindSphere data.
● Data points of a data source represent the data of the MindConnect Element.
To use the data of your MindConnect Element you have to map them to the respective
variables of an aspect.

Requirement
You have created an asset based on your desired aspect and asset type.

Procedure
To map a variable to a data point, e. g. "RotationSpeed", follow these steps:
1. Click on the asset in the "Assets" tab, e. g. "Wind turbine1".
2. Click on the MindConnect Element Plugin icon, e. g. "MindConnect Nano".

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 71
Configuring data in Asset Manager
8.4 Mapping an aspect to a data source

3. Click "View data mapping".


4. Select the aspect, e. g. "Generator".
5. Select the variable you want to map to the data point, e. g. "RotationSpeed".
6. Select the data point you want to map and click "Link Variable".
The following graphic shows the "Link Variable" option:

7. Select the previously created asset type and click "Accept", e. g. "Wind turbine".

Note
You can find additional information on asset types in the chapter Creating a type in Asset
Manager (Page 65).

Getting Connected to MindSphere


72 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring data in Asset Manager
8.4 Mapping an aspect to a data source

8. Select the variable you want to link, e. g. "RotationSpeed".

Note
Only units and data types that match exactly with the aspects and variables are available.
If they are different, the aspect can’t be connected to the data point (also case sensitive).

9. To link the variable click "Accept".

Result
The data point is now mapped to the variable.
The following graphic shows a mapped variable:

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 73
Configuring protocols 9
9.1 Overview of S7 protocol
The following image shows the data source input window for the S7 protocol:

You can choose between automatic and manual connection type.


● Automatic: This mode tries to find slot and rack number automatically.
● Manual: In this mode you can enter the rack and slot number manually.
For S7 connection type the PG type-programmer-type-connection is used thus you will not
be able to make use of PG connection.

Note
Symbolic access
This solution does not allow full symbolic access.

Getting Connected to MindSphere


74 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.1 Overview of S7 protocol

Requirements for S7-1200 and S7-1500


● Put/Get communication must be permitted (can be found e.g. S7-1500 -> Properties ->
Protection & Security -> Connection mechanisms).
● The “Optimized block access” of the data blocks that you want to read must be
deactivated (can be found in the data block properties).

Address format examples

Detailed examples:
Example address format DB15.DBX6.3:

DB15.DBX6.3
Area indicator Data type Offset address
DB15 - DB X 6 - 3
Datablock ad- Separator Datablock Bool Offset Byte Separator Offset Bit
dress
Reads 3rd bit of byte 6 of datablock 15

Example address format IW10:

IW10
Area indicator Data type Offset address
I W 10
Process Input Word Offset Byte
Reads a word of input starting from offset 10

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 75
Configuring protocols
9.1 Overview of S7 protocol

Overview
If you want to read data out of other areas, please replace “DB15.DB“ from the examples
with the area indicator from the list below. Attention: only certain address examples work
with Inputs and Outputs (see 2)).

S7 MindSphere
Data type Length / un- Data type Address example Description
signed/signed (length)
Bool 1 bit BOOLEA DB15.DBX6.3 2) Reads 3rd bit of byte 6 of
N (1 bit) datablock 15.
Byte 1 byte / unsigned DB15.DBB4 2) Reads an unsigned byte
USInt DB15.DBBYTE4 starting from offset 4 out of
datablock 15.
SInt 1 byte / signed
Char 1 byte / signed DB15.DBCHAR6 Reads a char starting from
offset 6 of datablock 15.
INT (4
Word 2 bytes / unsigned bytes) DB15.DBW10 2) Reads an unsigned word
UInt DB15.DBWORD10 starting from offset 10 of
LONG (8 datablock 15.
bytes)
Int 2 bytes / signed DB15.DBINT12 Reads a signed integer start-
DOUBLE ing from offset 12 out of
(8 bytes) datablock 15.
1)
DINT 4 bytes / signed DB15.DBDINT28 Reads a signed double inte-
ger starting from offset 28 of
datablock 15.
DWord 4 bytes / unsigned LONG (8 DB15.DBDW24 2) Reads an unsigned double
UDInt bytes) DB15.DBDWORD24 word starting from offset 24
DOUBLE of datablock 15.
(8 bytes)
1)

Getting Connected to MindSphere


76 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.1 Overview of S7 protocol

S7 MindSphere
Data type Length / un- Data type Address example Description
signed/signed (length)
Real 4 bytes / signed DOUBLE DB15.DBD32 2) Reads a floating-point num-
(8 bytes) DB15.DBREAL32 ber starting from offset 32 of
datablock 15.
String Length of variable, DB15.DBSTRING10 The maximum string length
max. 254 bytes (Byte10) is read first. Then
the number of bytes that
Byte10 indicates are read.
After that the number of
bytes that Byte11 indicates
are extracted from the byte
array that is the result of
second read operation.
STRING For example:
(max. 254
bytes) • (Byte10)- 30
• (Byte11)-4
• (Byte12-Byte15)-TEST
First read result: 30
Second read result: 4TEST
We will extract TEST from
the second read result by
considering Byte11's value.
String Min. 100 bytes , max. DB15.DBSTRING10,100 Reads 100 bytes of string
254 bytes starting from offset 10.
1) When DOUBLE is used for integers, they are converted to a floating-point number.
2) For the areas Inputs and Outputs only certain address examples work.

Note
Signed values
If you want to read a signed value, you have to use the respective signed datablock.
Example:
DB1831.DBW508 is unsigned. You can use DB1831.DBINT508 instead.

Area Types
S7 datapoint addresses must contain an area type.

Area indicator Area types Description


C Counter Reads Counter value of hardware.
DB Datablock Reads datablock value from hardware.
DI Instance Data Reads data directly from hardware.
I Process Input Reads Input value of Process image.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 77
Configuring protocols
9.1 Overview of S7 protocol

Area indicator Area types Description


M Memory Reads Memory value of hardware.
PI Peripheral Input Reads Input value directly from hardware.
PQ Peripheral Output Reads Output value directly from hardware.
Q Process Output Reads Input value of Process image.
T Timer Reads Timer value of hardware.

Area Number
S7 datapoint addresses must contain area number.
E.g.: DB10 (10. datablock)

Data Types
The following table shows the MindSphere data types:

MindSphere data types


Data type Length Data range
From To
BOOLEAN 1 bit True False
INT 4 bytes −2147483648 2147483647
LONG 8 bytes −9223372036854775808 9223372036854775807
DOUBLE 8 bytes - 9.99999999999999999999999999
9.99999999999999999999999999 99999999999E+125
99999999999E+125
STRING 1 - 255 bytes

The following table shows the S7 data types:

S7 data types
Data type Length Data range
From To
Bool 1 bit False True
Byte (unsigned) 1 byte 0 255
Word (unsigned) 2 bytes 0 65.535
DWord (unsigned) 4 bytes 0 4294967295
Char (signed) 1 byte −128 127
Int (signed) 2 bytes −32768 32767
DINT (signed) 4 bytes −2147483648 2147483647
Real 4 bytes +/-1,18e-38 +/-3.40e+38
String 1- 254 bytes

Getting Connected to MindSphere


78 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.1 Overview of S7 protocol

Offset
Variable types must have an offset. Offset is the starting byte number.
E.g. DW4 (a double word starting from byte 4)

String

Data type Length in bytes Format


STRING[n] or STRING n+2 ASCII character of any
length. n specifies the length
of the character string. A
maximum length of
254characters is permitted. If
no length is specified, the
default setting is 254 charac-
ters.

Data type Examples of format used


STRING[2] 'AB'
STRING[55] 'The character string can consist of up to 55 characters'

Note
You must enclose your character string in single quotation marks.

The following example shows the byte order when specifying the datatype STRING[4] with
the output value 'AB'.

* Tod

TIME_OF_DAY (Time) 32 Time is in steps of 1 ms TOD#0.0.0.0 to L TOD#1:10:3.3


TOD#23:59:59.999 L TIME_OF_DAY#1:10:3.3

* Time
Returns milliseconds.
Format

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 79
Configuring protocols
9.2 Overview of OPC UA protocol

The DT (DATE_AND_TIME) datatype saves the information on date and time of day in BCD
format.
The following table shows the properties of datatype DT:

Length (bytes) Format Range of values Example of value input


8 Date and time
(year-month-day

9.2 Overview of OPC UA protocol

OPC UA data parameter

Note
MindConnect IoT2040 connection establishment
Due to the extensive and detailed logging, system slowdowns can occur during the
connection establishment phase. It depends on the work, the device has to do.

The following image shows the data source input window for the OPC UA protocol:

Getting Connected to MindSphere


80 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.2 Overview of OPC UA protocol

For the OPCUA protocol, the data source input supports the following parameters:

Parameter Description
Protocol Shows the selected protocol type.
Name Name of the data source.
Description Add a description for data source.
Reading Cycle Enter a reading cycle for the data source.
OPC UA Server Name Enter the name of the OPC UA Server Name.
OPC UA Server IP Enter the OPC UA Server IP Address.
Address
OPC UA Authentica- You can choose between the following types:
tion Type
• NONE: No authentication enabled.
• BASIC: Enables the OPC UA BASIC authentication.
OPC UA Security You can choose between the following modes:
Mode
• NONE: No security mode
• CERTIFICATE: Enables to upload a certificate in the following formats: *.pfx, *.pf12, *.cer,
*.crt, *.der, *.p7b, *.p7r, *.spc
Enable OPC UA You can enable the transfer and takeover of events and alarms in the OPC UA protocol to Mind-
Events Sphere. Fleet Manager shows all events and alarms in the "Events" extension of the agent asset.
LImits:
• For Nanobox the proposed limit is 25 events/alarms per second.
• For IoT2040 the proposed limit is 10 events/alarms per second.

OPC UA Data Access Specification


OPC UA Data Access Specification does not specify a certain representation for OPC UA
Addresses (NodeId). A NodeId is represented by a combination of:
● NamespaceIndex
● IdentifierType
● Identifier
OPC UA Client Driver addresses have the following syntax: ns=;=.

Note
OPC browsing is not supported.

For more information refer to the table below:

Field Description
NamespaceIndex The index of the OPC UA Server namespace in which the address resides. If the index is 0, the
entire ns=;= clause is omitted.
IdentifierType The type of address. OPC UA supports the following four address types:
i A numeric address represented with 32-bit unsigned integer

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 81
Configuring protocols
9.2 Overview of OPC UA protocol

Field Description
s A string address containing characters that can be encoded using UTF-8
g A GUID address in the format of XXXXXXXX-XXXX-XXXX-XXXX-XXXXXXXXXXXX
b An opaque address (such as a byte string)
Identifier The address that is formatted as a string. This address may be numeric, string, GUID, or opaque.

Examples NodeId
Below you can see examples of an OPC UA Addresses (NodeId) representation:

String

String IdentifierType Example


ns=[id];s=[string] ns=5;s=Counter1

Attribute NodeId Value NodeId


NamespaceIndex 5
IdentifierType String
Identifier Counter1

Note
String for Identifier
The string you enter at the four Identifier will be case sensitive.

Numeric

Numeric IdentifierType Example


ns=[id];i=[number] ns=0;i=3190 OR

Attribute NodeId Value NodeId


NamespaceIndex 0
IdentifierType Numeric
Identifier 3190 [BaseEventType_LocalTime]

Guid

Guid IdentifierType Example


ns=[id];g=[guid] ns=1;g=0d4e10fa-b9e1-4842-bca6-887c7d8c31f0

Getting Connected to MindSphere


82 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.2 Overview of OPC UA protocol

Base64(Opaque)

Base64(Opaque) Iden- Example


tifierType
ns=[id];b=[base64] ns=2;b=M/RbKBsRVkePCePcx24oRA==

Datatypes Conversion
The following table shows the Datatype Conversion:

IEC61131 elementary datatypes OPC UA built-in datatypes MindSphere Type


BOOL Boolean boolean
SINT SByte int
USINT Byte int
INT Int16 int
UINT UInt16 int
DINT Int32 int
UDINT UInt32 int
LINT Int64 long
ULINT UInt64 long
BYTE Byte int
WORD UInt16 int
DWORD UInt32 int
LWORD UInt64 long
REAL Float double
LREAL Double double
STRING String string
CHAR Byte int
WSTRING String string
WCHAR UInt16 int
DT DateTime n/a
DATE_AND_TIME
DATE DateTime n/a
TOD DateTime n/a
TIME_OF_DAY
TIME Double double

Note
“NodeID“ is not a valid part of the OPC string anymore.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 83
Configuring protocols
9.3 Overview of Modbus TCP protocol

9.3 Overview of Modbus TCP protocol


MindSphere supports the Modbus protocol for the MindConnect IoT2040 and MindConnect
Nano plugin. You can select the protocol type Modbus TCP while adding a new data source
in Asset Manager.

Note
Modbus configuration
The Modbus configuration view is only visible after a successful onboarding of the
MindConnect IoT2040/Nano. The MindConnect Nano Version must be higher than V3.3.0.2.

The following picture shows the protocol selection in Asset Manager:

Figure 9-1 Modbus

For more information about how to create a new data source see chapter Adding a data
source and data points (Page 67).

Getting Connected to MindSphere


84 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.3 Overview of Modbus TCP protocol

Modbus TCP data source parameter


In order to connect a Modbus TCP device, you need to select the Modbus TCP protocol and
enter the following data source parameters:

Parameter Description
IP Address IP address of the Modbus device
Port Port number of the Modbus device (default: 502)

The following parameters are optional and can be adjusted for collecting data from slow
Modbus devices:

Parameter Description
byteTimeout You can set the timeout interval between two consecutive bytes of the same message received
from the Modbus device. If the delay between is longer than the given timeout, an error will be
generated.
Range:
500ms (default) … 2000ms
responseTimeout You can set the timeout interval used to wait for a response from the Modbus device. If the wait-
ing before receiving the response is longer than the given timeout, an error will be generated.
Range:
500ms (default) … 60000ms
responseSuspension- If a byte timout or a response timeout was detected, then this waiting time is added before the
Time next request is started. During this time any response from the Modbus device will be flushed.
Range:
0ms … 45000ms. (default: 0ms)
requestDelay You can set the time between the response from the Modbus device and the next request to this
Modbus device.
Range:
0ms (default) … 10000ms

Modbus TCP data point parameter


In order to collect the data of your Modbus TCP device, you must add new data points.
The following picture shows the data point parameter window:

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 85
Configuring protocols
9.3 Overview of Modbus TCP protocol

The following table shows the parameter of the Modbus RTU data point window:

Parameter Description
Data Type Data type supported by backend (e.g. INT).
Function Type Function type - depends on the type of the data (see manual of the Modbus device).
1: Read Coils
2: Read Inputs
3: Read Holding Registers
4: Read Input Registers
Currently function codes 1..4 are supported.
Slave Number Address/Slave number of the Modbus device.
Start Address Start address (offset) of the data.
Quantity Quantity of data to be read.
VariableType You can choose the following variable types of the Modbus data to be read:
1: char
2: unsigned char
3: short
4: unsigned short
5: long
6: unsigned long
7: float
8: double
9: ASCII-Text

Getting Connected to MindSphere


86 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.4 Overview of Modbus RTU protocol

Parameter Description
Real Type Real type - determines, if the registers of real values have to be processed in reversed order
0: Normal order
1: Reversed order
Response Address Offset of the data to return in register units.
Offset
Response Quantity Quantity of the returned data. Only for string data a value greater than 1 is supported.

Note
TCP Gateway slave number
If you are using a TCP Gateway, you must select the appropriate slave number for the
configuration of the data points.

9.4 Overview of Modbus RTU protocol


MindSphere supports the Modbus protocol for the MindConnect IoT2040 and MindConnect
Nano plugin. You can select the protocol type Modbus RTU while adding a new data source
in Asset Manager.

Note
Modbus configuration
The Modbus configuration view is only visible after a successful onboarding of the
MindConnect IoT2040/Nano. The MindConnect Nano Version must be higher than V3.3.0.2.

The following picture shows the protocol selection in Asset Manager:

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 87
Configuring protocols
9.4 Overview of Modbus RTU protocol

For more information about how to create a new data source see chapter AUTOHOTSPOT.

Modbus RTU data source parameter


In order to connect a Modbus RTU device, you need to select the Modbus RTU protocol and
enter the following data source parameters:

Parameter Description
Serial Port Available serial ports:
• COM1
• COM2
Serial Type Supported serial communication standards:
• RS232
• RS422
• RS485

Getting Connected to MindSphere


88 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.4 Overview of Modbus RTU protocol

Parameter Description
Baud rate Baud rate for serial communication:
• 9600
• 2400
• 4800
• 19200
• 38400
• 57600
• 115200
Data bits Data bits for serial communication:
• 5
• 6
• 7
• 8
Stop bits You can select the number of stop bits for serial communication:
• 1
• 2
Parity Parity for serial communication:
• Odd
• None
• Even
Termination Onboard termination:
• On
• Off

The following parameters are optional and can be adjusted for collecting data from slow
Modbus devices:

Parameter Description
byteTimeout You can set the timeout interval between two consecutive bytes of the same message received
from the Modbus device. If the delay between is longer than the given timeout, an error will be
generated.
Range:
500ms (default) … 2000ms
responseTimeout You can set the timeout interval used to wait for a response from the Modbus device. If the wait-
ing before receiving the response is longer than the given timeout, an error will be generated.
Range:
500ms (default) … 60000ms

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 89
Configuring protocols
9.4 Overview of Modbus RTU protocol

Parameter Description
responseSuspension- If a byte timout or a response timeout was detected, then this waiting time is added before the
Time next request is started. During this time any response from the Modbus device will be flushed.
Range:
0ms … 45000ms. (default: 1000ms)
For Modbus RTU it is recommended to set the value to 10000 ms. If the default value 0 ms is set,
any incoming incorrect responses will not be destroyed.
requestDelay You can set the time between the response from the Modbus device and the next request to this
Modbus device.
Range:
0ms (default) … 10000ms

Pin assignment of Modbus protocols


The following table shows the pin assignment for the Modbus RTU protocol:

Pin RS 485 RS 422 RS 232


1 Data- Transmit / receive data - TX- Transmitted data - (O) for full- Not supported
(I/O) for half-duplex mode duplex mode
2 Data+ Transmit / receive data+ TX+ Transmitted data + (O) for full- RxD Received data (I)
(I/O) for half-duplex mode duplex mode
3 - RX+ Receive data + (I) for full- TxD Transmitted data (O)
duplex mode
4 - RX- Receive data - (I) for full- Not supported
duplex mode
5 M Signal ground M Signal ground M Ground
6 - - Not supported
7 - - Not supported
8 - - Not supported
9 - - Not supported

Modbus RTU data point parameter


In order to collect the data of your Modbus RTU device, you must add new data points.
The following picture shows the data point parameter window:

Getting Connected to MindSphere


90 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.4 Overview of Modbus RTU protocol

The following table shows the parameter of the Modbus RTU data point window:

Parameter Description
Data Type Data type supported by backend (e.g. INT).
Function Type Function type - depends on the type of the data (see manual of the Modbus device).
1: Read Coils
2: Read Inputs
3: Read Holding Registers
4: Read Input Registers
Currently function codes 1..4 are supported.
Slave Number Address/Slave number of the Modbus device.
Start Address Start address (offset) of the data.
Quantity Quantity of data to be read.
VariableType You can choose the following variable types of the Modbus data to be read:
1: char
2: unsigned char
3: short
4: unsigned short
5: long
6: unsigned long
7: float
8: double
9: ASCII-Text

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 91
Configuring protocols
9.5 Overview of SIMATIC I/O Shield

Parameter Description
Real Type Real type - determines, if the registers of real values have to be processed in reversed order
0: Normal order
1: Reversed order
Response Address Offset of the data to return in register units.
Offset
Response Quantity Quantity of the returned data. Only for string data a value greater than 1 is supported.

Technical specification

Protocol Description Value Data rate


Modbus RTU - RS485 Data provider 32
Max cable length 1200 m max. 115,2 kBd
Modbus RTU - RS422 Data provider 10
Max cable length 1200 m max. 115,2 kBd
Modbus RTU - RS232 Data provider 1
Maximum cable length 900 m 2,4 kBd
300 m 4,8 kBd
152 m 9,6 kBd
15 m 19,2 kBd
5m 57,6 kBd
<2m 115,2 kBd

9.5 Overview of SIMATIC I/O Shield


SIMATIC I/O Shield device has been plugged-in to MindConnect IoT2040 and set up
according to I/O Shield operating instructions. Analog and digital input signals are connected
to SIMATIC I/O Shield connectors.
You can find more information about the SIMATIC I/O Shield Modul in the SIMATIC IOT
IOT2000 Extension Modules manual
(https://support.industry.siemens.com/cs/document/109745681/iot2000-extension-
modules?dti=0&lc=en-WW). The following picture shows the SIMATIC IOT2000 Input/output
Modul:

Getting Connected to MindSphere


92 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.5 Overview of SIMATIC I/O Shield

You can select the protocol type SIMATIC I/O Shield while adding a new data source in
Asset Manager.
The following picture shows the protocol selection in Asset Manager:

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 93
Configuring protocols
9.6 Overview of SYSTEM protocol

After selecting the protocol you can enter the parameter Name, Description and Reading
Cycle.

SIMATIC I/O Shield data point parameter


In order to collect the data of your SIMATIC I/O Shield device, you must add new data
points.
The signal that has to be recorded can be configured by specifying pin type (analog/digital)
and the pin number as it is printed on SIMATIC I/O shield device. For the analog inputs, the
read value corresponds to a percentage value between 0 and 1. The percentage value refers
to the permissible voltage range between 0-10 V. The read value must be converted
accordingly for the connected sensor.
Following inputs can be chosen:

Input Pin type Pin number Recommended data type


AI0 Analog 0 DOUBLE
AI1 Analog 1 DOUBLE
AI2 Analog 2 DOUBLE
AI3 Analog 3 DOUBLE
DI0 Digital 0 BOOLEAN
DI1 Digital 1 BOOLEAN
DI2 Digital 2 BOOLEAN
DI3 Digital 3 BOOLEAN
DI4 Digital 4 BOOLEAN

9.6 Overview of SYSTEM protocol


You can use the protocol SYSTEM to implement a system information adapter for analysis
purposes. The SYSTEM protocol can collect the following information from MindConnect
devices:
● Overall CPU load
● Overall memory consumption
● Network traffic
● Application specific data
– CPU load memory consumption
● Disk usage
You can choose the SYSTEM protocol as a data source without configuring specific system
parameters, except the reading cycle.

Getting Connected to MindSphere


94 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.6 Overview of SYSTEM protocol

After creating the data source you can configure the following categories in a new data point:
● CPU
● Memory
● Network
● Disk
The following image shows the data point input window for the SYSTEM protocol:

Each category has its own set of variables which will be described in the following.

Application information
Application provides the following available applications:
● MindEdgeRuntimeSystem/java
● DataProvider
● BoxManager
● S7 Plugin
● OPCUA Plugin
● XTools
● Mosquitto

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 95
Configuring protocols
9.6 Overview of SYSTEM protocol

The following table shows the available variables for the applications:

Variable Data type Address


Name string /application/<subcategory>/name
State string /application/<subcategory>/state
Tgid int /application/<subcategory>/tgid
Ngid int /application/<subcategory>/ngid
Pid int /application/<subcategory>/pid
PPid int /application/<subcategory>/ppid
TracerPid int /application/<subcategory>/tracerpid
Uid string /application/<subcategory>/uid
Gid string /application/<subcategory>/gid
FDSize int /application/<subcategory>/fdsize
Groups string /application/<subcategory>/groups
NStgid int /application/<subcategory>/nstgid
NSpid int /application/<subcategory>/nspid
NSpgid int /application/<subcategory>/nspgid
NSsid int /application/<subcategory>/nssid
VmPeak long /application/<subcategory>/vmpeak
VmSize long /application/<subcategory>/vmsize
VmLck long /application/<subcategory>/vmlck
VmPin long /application/<subcategory>/vmpin
VmHWM long /application/<subcategory>/vmhwm
VmRSS long /application/<subcategory>/vmrss
VmData long /application/<subcategory>/vmdata
VmStk long /application/<subcategory>/vmstk
VmExe long /application/<subcategory>/vmexe
VmLib long /application/<subcategory>/vmlib
VmPTE long /application/<subcategory>/vmpte
VmPMD long /application/<subcategory>/vmpmd
VmSwap long /application/<subcategory>/vmswap
HugetlbPages long /application/<subcategory>/hugetlbpages
Threads int /application/<subcategory>/threads
SigQ string /application/<subcategory>/sigq
SigPnd string /application/<subcategory>/sigpnd
ShdPnd string /application/<subcategory>/shdpnd
SigBlk string /application/<subcategory>/sigblk
SigIgn string /application/<subcategory>/sigign
SigCgt string /application/<subcategory>/sigcgt
CapInh string /application/<subcategory>/capinh
CapPrm string /application/<subcategory>/capprm
CapEff string /application/<subcategory>/capeff
CapBnd string /application/<subcategory>/capbnd

Getting Connected to MindSphere


96 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.6 Overview of SYSTEM protocol

Variable Data type Address


CapAmb string /application/<subcategory>/capamb
Seccomp int /application/<subcategory>/seccomp
Specula- string /application/<subcategory>/speculation_store_bypass
tion_Store_Bypass
Cpus_allowed int /application/<subcategory>/cpus_allowed
Cpus_allowed_list string /application/<subcategory>/cpus_allowed_list
Mems_allowed int /application/<subcategory>/mems_allowed
Mems_allowed_list string /application/<subcategory>/mems_allowed_list
volun- int /application/<subcategory>/voluntary_ctxt_switches
tary_ctxt_switches
nonvolun- int /application/<subcategory>/nonvoluntary_ctxt_switches
tary_ctxt_switches

CPU information
The following table shows the available variables for the category CPU information:

Variable Data type Description


LoadAvg1 double Number of processes in state R(runnable) or D(disk sleep) averaged
over 1 minute.
LoadAvg5 double Number of processes in state R(runnable) or D(disk sleep) averaged
over 5 minutes.
LoadAvg10 double Number of processes in state R(runnable) or D(disk sleep) averaged
over 15 minutes .
ProcessCount string String containing number of currently runnable processes/threads and
number of scheduling processes/threads that currently exist on the sys-
tem.
LastPidUsed long Pid of the process that was most recently created.
CurrentProcessCount long Number of currently runnable processes/threads.
Sched- long Number of scheduling processes/threads that currently exist on the sys-
uledProcessCount tem.

Disk information
Disk collects information about disk usage and provides the following subcategories:
● persistent_massdata
● persistent_appconfig
● persistent
● root

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 97
Configuring protocols
9.6 Overview of SYSTEM protocol

The following table shows the available variables for the category Disk information:

Variable Data type Address Description


Available long /disk/dev/<subcategory>/available Partition size in bytes.
Size long /disk/dev/<subcategory>/size Used space in bytes.
Used long /disk/dev/<subcategory>/used Available space in bytes.

KERNEL information
The following table shows the available variables for the category KERNEL information:

Variable Data type Address


OsRelease string /kernel/osrelease
OsType string /kernel/ostype
Version string /kernel/version

Memory information
The following table shows the available variables for the category Memory information:

Variable Data type Address Restrictions


Active long /memory/active
Active(Anon) long /memory/active(anon)
Active long /memory/active
Active(Anon) long /memory/active(anon)
Active(File) long /memory/active(file)
AnonPages long /memory/anonpages
Available long /memory/available
Bounce long /memory/bounce
Buffers long /memory/buffers
Cached long /memory/cached
CommitLimit long /memory/commitlimit
Committed_As long /memory/committed_as
DirectMap4K long /memory/directmap4k
DirectMap4M long /memory/directmap4m
Dirty long /memory/dirty
AnonHugePages long /memory/anonhugepages Only supported by MindConnect
Nano.
CmaTotal long /memory/cmatotal Only supported by MindConnect
Nano.
CmaFree long /memory/cmafree Only supported by MindConnect
Nano.
HugePages_Total long /memory/hugepages_total Only supported by MindConnect
Nano.

Getting Connected to MindSphere


98 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.6 Overview of SYSTEM protocol

Variable Data type Address Restrictions


HugePages_Free long /memory/hugepages_free Only supported by MindConnect
Nano.
HugePages_Rsvd long /memory/hugepages_Rsvd Only supported by MindConnect
Nano.
HugePages_Surp long /memory/hugepages_surp Only supported by MindConnect
Nano.
Hugepagesize long /memory/hugepagesize Only supported by MindConnect
Nano.
HighFree long /memory/highfree Only supported by MindConnect
IoT 2040.
HighTotal long /memory/hightotal Only supported by MindConnect
IoT 2040.
LowFree long /memory/lowfree Only supported by MindConnect
IoT 2040.
LowTotal long /memory/lowtotal Only supported by MindConnect
IoT 2040.
Inactive long /memory/inactive
Inactive(Anon) long /memory/inactive(anon)
Inactive(File) long /memory/inactive(file)
KernelStack long /memory/kernelstack
LowFree long /memory/lowfree
LowTotal long /memory/lowtotal
Mapped long /memory/mapped
MemFree long /memory/memfree
MemTotal long /memory/memtotal
MLocked long /memory/mlocked
NFS_Unstable long /memory/nfs_unstable
PageTables long /memory/pagetables
SHMem long /memory/shmem
SLab long /memory/slab
SReclaimable long /memory/sreclaimable
SUnreclaim long /memory/sunreclaim
SwapCached long /memory/swapcached
SwapFree long /memory/swapfree
SwapTotal long /memory/swaptotal
Unevictable long /memory/unevictable
VMAllocChunk long /memory/vmallocchunk
VMAllocTotal long /memory/vmalloctotal
VMAllocUsed long /memory/vmallocused
WriteBack long /memory/writeback
WriteBackTmp long /memory/writebacktmp

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 99
Configuring protocols
9.6 Overview of SYSTEM protocol

Network information
The following table shows the available variables for the category Network information:

Variable Data type Address Description


ArpFilter long /network/arpfilter
BusyPollRxPackets long /network/busypollrxpackets
BytesReceived long /network/bytesreceived Alias for InOctets.
BytesSend long /network/bytessend Alias for OutOctets.
DelayedAckLocked long /network/delayedacklocked Number of delayed acks further
delayed because of locked socket.
DelayedAckLost long /network/delayedacklost Number of times that quick ack
mode was activated.
DelayedAcks long /network/delayedacks Number of delayed acks sent.
EmbryonicRsTs long /network/embryonicrsts Number of resets received for
embryonic SYN_RECV sockets.
InBcastOctets long /network/inbcastoctets
InBcastPkts long /network/inbcastpkts
IncePkts long /network/incepkts
IncSumErrors long /network/incsumerrors
Inect0Pkts long /network/inect0pkts
Inect1Pkts long /network/inect1pkts
InMcastOctets long /network/inmcastoctets
InMcastPkts long /network/inmcastpkts
InNoEctPkts long /network/innoectpkts
InNoRoutes long /network/innoroutes
InOctets long /network/inoctets Bytes received.
InTruncatedPkts long /network/intrucatedpkts Number of truncated packets re-
ceived.
IpReversePathFilter long /network/ipreversepathfilter
ListenDrops long /network/listendrops Number of SYNs to LISTEN sock-
ets that were dropped.
ListenOverflows long /network/listenoverflows Number of times the listen queue
of a socket overflowed.
LockDroppedIcmps long /network/lockdroppedicmps ICMP packets dropped because
socket was locked.
OfoPruned long /network/ofopruned Packets dropped from out-of-order
queue because of socket buffer
overrun.
OutBcastOctets long /network/outbcastoctets
OutBcastPkts long /network/outbcastpkts
OutMcastOctets long /network/outmcastoctets
OutMcastPkts long /network/outmcastokts
OutOctets long /network/outoctets Bytes sent.
OutOfWindowIcmps long /network/outofwindowicmps ICMP packets dropped because
they were out-of-window.

Getting Connected to MindSphere


100 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.6 Overview of SYSTEM protocol

Variable Data type Address Description


PAWSActive long /network/pawsactive Active connections rejected be-
cause of timestamp.
PAWSEstab long /network/pawsestab Packets rejected in established
connections because of timestamp.
PAWSPassive long /network/pawspassive Passive connections rejected be-
cause of timestamp.
PruneCalled long /network/prunecalled Packets pruned from receive
queue because of socket buffer
overrun.
RcvPruned long /network/rcvpruned Packets pruned from receive
queue.
SyncookiesFailed long /network/syncookiesFailed Number of invalid SYN cookies
received.
SyncookiesRecv long /network/syncookiesrecv Number of SYN cookies received.
SyncookiesSent long /network/syncookiessent Number of SYN cookies sent.
TCPAbortFailed long /network/tcpabortfailed Number of times unable to send
RST due to no memory.
TCPAbortOnClose long /network/tcpabortonclose Connections reset due to early
user close.
TCPAbortOnData long /network/tcpabortondata Connections reset due to unex-
pected data.
TCPAbortOnLinger long /network/tcpabortonlinger Connections aborted after user
close in linger timeout.
TCPAbortOnMemory long /network/tcpabortonmemory Connections aborted due to
memory pressure.
TCPAbortOnSyn long /network/tcpabortonsync Connections reset due to unex-
pected SYN.
TCPAbortOnTimeout long /network/tcpabortontimeout Connections aborted due to
timeout.
TCPAckSkippedChal- long /network/tcpackskippedchallenge
lenge
TCPAckSkippedFin- long /network/tcpackskippedfinwait2
Wait2
TCPAck- long /network/tcpackskippedpaws
SkippedPAWS
TCPAckSkippedSEQ long /network/tcpackskippedseq
TCPAckSkippedSYN- long /network/tcpackskippedsynrecv
Recv
TCPAck- long /network/tcpackskippedtimewait
SkippedTimeWait
TCPAutoCorking long /network/tcpautocorking
TCPBacklogDrop long /network/tcpbacklogdrop
TCPChallengeAck long /network/tcpchallengeack
TCPDeferAcceptDrop long /network/tcpdeferacceptdrop
TCPDirectCopyFrom- long /network/tcpdirectcopyfrombacklog Bytes directly in process context
Backlog from backlog.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 101
Configuring protocols
9.6 Overview of SYSTEM protocol

Variable Data type Address Description


TCPDirectCopyFromP long /network/tcpdirectcopyfromprequeu Bytes directly received in process
requeue e context from prequeue.
TCPD- long /network/tcpdsackignorednoundo
SACKIGNoRedNoUn-
do
TCPD- long /network/tcpdsackignoredold
SACKIGNoRedOld
TCPDSACKOfoRecv long /network/tcpdsackoforecv DSACKs for out of order packets
received.
TCPDSACKOfoSent long /network/tcpdsackofosent DSACKs sent for out of order
packets.
TCPDSACKOldSent long /network/tcpdsackoldsent DSACKs sent for old packets.
TCPDSACKRecv long /network/tcpdsackrecv DSACKs received.
TCPDSACKUndo long /network/tcpdsackundo Congestion window recovered
without slow start using DSACK.
TCPFACKReorder long /network/tcpfackreorder Number of times reordering was
detected using FACK.
TCPFastOpenActive long /network/tcpfastopenactive
TCPFastOpenAc- long /network/tcpfastopenactivefail
tiveFailL
TCPFastOpenCooki- long /network/tcpfastopencookiereqd
eReqD
TCPFastOpenListen- long /network/tcpfastopenlistenoverflow
Overflow
TCPFastOpenPassive long /network/tcpfastopenpassive
TCPFastOpenPas- long /network/tcpfastopenpassivefail
siveFail
TCPFastRetrans long /network/tcpfastretrans Fast retransmits.
TCPForwardRetrans long /network/tcpforwardretrans Forward retransmits.
TCP- long /network/tcpfromzerowindowadv
FromZeroWindowAdv
TCPFullUndo long /network/tcpfullundo Congestion windows fully recov-
ered without slow start.
TCPHPAcks long /network/tcphpacks Predicted acknowledgments.
TCPHPHits long /network/tcphphits Packet headers predicted.
TCPHPHitsToUser long /network/tcphphitstouser Packet headers predicted and
directly queued to user.
TCPHYStartDe- long /network/tcphystartdelaycwnd
layCWND
TCPHYStartDe- long /network/tcphystartdelaydetect
layDetect
TCPHYStartTrain- long /network/tcphystarttraincwnd
CWND
TCPHYStartTrainDe- long /network/tcphystarttraindetect
tect
TCPKeepAlive long /network/tcpkeepalive Number of ACK packets sent to
keep TCP flow alive.

Getting Connected to MindSphere


102 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.6 Overview of SYSTEM protocol

Variable Data type Address Description


TCPLossFailures long /network/tcplossfailures Timeouts in loss state.
TCPLossProbeRecov- long /network/tcplossproberecovery
ery
TCPLossProbes long /network/tcplossprobes
TCPLossUndo long /network/tcplossundo Congestion windows recovered
without slow start after partial ack.
TCPLostRetransmits long /network/tcplostretransmits Retransmits lost.
TCPMD5NotFound long /network/tcpmd5notfound
TCPMD5Unexpected long /network/tcpmd5unexpected
TCPMemoryPressures long /network/tcpmemorypressures Number of times TCP ran low on
memory.
TCPMINTTLDrop long /network/tcpminttldrop
TCPMTUPFail long /network/tcpmtupfail
TCPMTUPSuccess long /network/tcpmtupsuccess
TCPOfoDrop long /network/tcpofodrop
TCPOfoMerge long /network/tcpofomerge
TCPOfoQueue long /network/tcpofoqueue
TCPOrigDataSent long /network/tcporigdatasent
TCPPartialUndo long /network/tcppartialundo Congestion windows partially re-
covered using Hoe heuristic.
TCPPrequeued long /network/tcpprequeued Packets directly queued to
recvmsg prequeue.
TCPPrequeueDropped long /network/tcpprequeuedropped Packets dropped from prequeue.
TCPPureAcks long /network/tcppureacks Acknowledgments not containing
data payload received.
TCPRcvCoalesce long /network/tcprcvcoalesce
TCPRcvCollapsed long /network/tcprcvcollapsed Packets collapsed in receive queue
due to low socket buffer.
TCPRenoFailures long /network/tcprenofailures Timeouts after reno fast retransmit.
TCPRenoRecovery long /network/tcprenorecovery Times recovered from packet loss
due to fast retransmit.
TCPRenoRecoveryFail long /network/tcprenorecoveryfail Classic Reno fast retransmits
failed.
TCPRenoReorder long /network/tcprenoreorder
TCPReqQFullDoCook- long /network/tcpreqqfulldocookies
ies
TCPReqQFullDrop long /network/tcpreqqfulldrop
TCPRetransFail long /network/tcpretransfail
TCPSACKDiscard long /network/tcpsackdiscard
TCPSACKFailures long /network/tcpsackfailures Timeouts after SACK recovery.
TCPSACKMerged long /network/tcpsackmerged
TCPSACKRecovery long /network/tcpsackrecovery Times recovered from packet loss
by selective acknowledgements.
TCPSACKRecovery- long /network/tcpsackRecoveryFails SACK retransmits failed.
Fail

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 103
Configuring protocols
9.6 Overview of SYSTEM protocol

Variable Data type Address Description


TCPSACKReneging long /network/tcpsackreneging Bad SACK blocks received.
TCPSACKReorder long /network/tcpsackreorder Number of times reordering was
detected using SACK.
TCPSACKShifted long /network/tcpsackshifted
TCPSACKShift- long /network/tcpsackshiftfallback
Fallback
TCPSchedulerFailed long /network/tcpschedulerfailed Times receiver scheduled too late
for direct processing.
TCPSlowStartRetrans long /network/tcpslowstartretrans Retransmits in slow start.
TCPSpuriousRTOS long /network/tcpspuriousrtos
TCPSpuri- long /network/tcpspuriousrtxhostqueues
ousRTXHostQueues
TCPSYNChallenge long /network/tcpsynchallenge
TCPSYNRetrans long /network/tcpsynretrans
TCPTimeouts long /network/tcptimeouts Other TCP timeouts.
TCPTimeWaitOverflow long /network/tcptimewaitoverflow
TCPToZeroWindow- long /network/tcptozerowindowadv
Adv
TCPTSReorder long /network/tcptsreorder Number of times reordering was
detected using timestamp.
TCP- long /network/tcpwantzerowindowadv
WantZeroWindowAdv
TCPWinProbe long /network/tcpwinprobe Number of ACK packets to be sent
at regular intervals to make sure a
reverse ACK packet opening back
a window has not ben lost.
TW long /network/tw
TWKilled long /network/twkilled TCP sockets finished time wait in
slow timer.
TWRecycled long /network/twrecycled Time wait sockets recycled by
timestamp.

Getting Connected to MindSphere


104 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.7 Overview of Rockwell protocol

9.7 Overview of Rockwell protocol


The following image shows the data source input window for the Rockwell protocol:

Rockwell data source parameter


In order to connect a Rockwell device, you need to select the Rockwell protocol and enter
the following data source parameters:

Parameter Description
CPU type Shows available CPU types:
• COMPACT_LOGIX
• OTHER_CPU
Currently not available:
• CONTROL_LOGIX
• FLEX_LOGIX
• MICRO_LOGIX
• SOFT_LOGIX
• PLC5
• SLC500
IP address IP address of the Rockwell controller.
Route parameters Comma separated list with rack, port, and slot numbers that
are necessary to connect to the PLC (default: 1,0)

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 105
Configuring protocols
9.7 Overview of Rockwell protocol

Rockwell data point parameter


In order to collect the data of your Rockwell device, you must add new data points.

The following table shows the data point parameter:

Parameter Description
Data Type Data type supported by backend (e.g. INT).
STRING data type is currently not supported.
Tag Name of the tag that has to be recorded.
For Rockwell controller types tag name will be validated
according to the Rockwell tag name rules.2)
2)Rockwell tag name rules can be found in Logix 5000 Controllers I/O and Tag Data
Programming Manual
The following table shows the recommended data type selection:

Rockwell data type Length Data range1) MindSphere data type


BOOL 1 bit 0 or 1 BOOLEAN
SINT 1 byte -128…+127 INT
INT 2 bytes -32,768…+32,767 INT

Getting Connected to MindSphere


106 Getting Started, 02/2020, V1801.Feb/2020.1
Configuring protocols
9.7 Overview of Rockwell protocol

Rockwell data type Length Data range1) MindSphere data type


DINT 4 bytes - INT
2,147,483,648…+2,147,483,
647
REAL 4 bytes • -3.40282347E38…- DOUBLE
1.17549435E-38 (nega-
tive values)
• 0
• -1.17549435E-38-
…3.40282347E38 (posi-
tive values)

1)Values have been taken from Logix 5000 Controllers I/O and Tag Data Programming
Manual

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 107
Firmware update 10
10.1 Manual firmware update of MindConnect Element
To prepare your MindConnect Element for MindSphere V3 please follow the next two steps:
● Set MindConnect to factory settings
● Load new firmware on your MindConnect Element

Set MindConnect to factory settings

Note
This procedure is only necessary for boxes that were already connected to MindSphere V2
(SAP). V1 cannot be upgraded.

1. Set the MindConnect back to factory settings.


2. Create a “ConBox_Commands.json” file with your favorite code editor.
Content of "ConBox_Commands.json":
{

"Commands": [

"Cmd": "DoFactoryReset",

"DeviceID": "MindConnectID"

Note
MindConnectID has to be replaced with the serial number of the device.

3. Copy the extracted/unzipped fw.tar file to a USB stick (fat32 formatted).


4. Plug the USB stick in the MindConnect hardware.
– The MindConnect will be restarted automatically.
– The network and SAL settings will be reset to their initial state on MindConnect
Element.
– All SAL and script logging files will be deleted.

Getting Connected to MindSphere


108 Getting Started, 02/2020, V1801.Feb/2020.1
Firmware update
10.2 Firmware update in Asset Manager

Load new firmware on your MindConnect Element


1. Download the firmware ZIP file from Siemens Industry Online Support Page.
– Firmware download MindConnect Nano
(https://support.industry.siemens.com/cs/ww/en/view/109745561)
– Firmware download MindConnect IoT2040
(https://support.industry.siemens.com/cs/ww/en/view/109745562)
2. Unzip the firmware on your local machine.
3. Copy the unzipped files to a USB stick.
4. Insert the USB stick into the MindConnect Element and wait until the firmware update is
complete.
– Update carried out: ERROR LED flashes orange
– MindConnect Element reboots
– MAINT LED flashes orange for a few seconds
– RUN LED orange (not connected to MindSphere)
5. Disconnect the USB stick.

10.2 Firmware update in Asset Manager


In Asset Manager you can update the firmware of your MindConnect Element.

NOTICE
Outdated version
Please keep your firmware always updated.

NOTICE
Data loss
Please note that data loss can occur during the time of the firmware update. The amount of
data loss depends on the reading and uploading cycle.

To perform a firmware update proceed as follows:


1. Select the asset in the "Asset" tab.
2. Open the MindConnect plugin.
3. Click next to "Firmware" on the button .
4. Accept the terms and conditions.
5. To select a firmware release click "Choose another firmware release".
– The "select firmware" dialog appears.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 109
Firmware update
10.2 Firmware update in Asset Manager

6. Select product and available version and click "Accept".


7. To update your firmware click "Update your firmware".

Note
Incomplete firmware update
If the connection is interrupted while the new firmware is being downloaded, note that the
downloaded content might be lost if the connection cannot be recovered via the box.
For example, if the connection is interrupted while 50% of the firmware are downloaded, the
process migth be canceled. In that case you have to click firmware update on the user
interface to restart the process.

Getting Connected to MindSphere


110 Getting Started, 02/2020, V1801.Feb/2020.1
Firmware update
10.2 Firmware update in Asset Manager

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 111
Visual analysis of assets in Fleet Manager 11
11.1 Overview visual analysis
This chapter provides a brief overview of the visual analysis of your asset, which was
configured in Asset Manager. It gives you a brief overview of how to monitor the data of a
selected asset in Fleet Manager. For more information refer to the MindSphere
documentation.

Requirements
● MindConnect Nano/IoT2040 is connected to the internet and onboarded.
● Aspects and variables are configured in Asset Manager.

Procedure
To see the visualized data in Fleet Manager, you can proceed as follows:
1. Select a required asset to view its data. (Page 112)
2. View aspects of a selected asset. (Page 114)
3. View events of a selected asset. (Page 116)

11.2 Selecting assets


Fleet Manager offers the means for viewing and simple searching/sorting/filtering of assets.
You access Fleet Manager via the MindSphere Launchpad.

Requirement
You have created assets in Asset Manager.

Procedure
To select an asset in Fleet Manager, proceed as follows:
1. In the MindSphere Launchpad, click "Fleet Manager".
The overview page of Fleet Manager appears and you can see the list with assets on the
left-hand side.
2. To view an asset, select between "Fleet" or "Hierarchy" views.

Getting Connected to MindSphere


112 Getting Started, 02/2020, V1801.Feb/2020.1
Visual analysis of assets in Fleet Manager
11.2 Selecting assets

3. To see the map view, click .


4. To quickly find the created asset e.g. "Wind turbine", choose one of the following
features:
– Select the asset that is linked to your aspect and asset type.
– Enter a required text in the searching box.

Figure 11-1 Finding the asset via the searching text

– Or click the “Filter & sort" button to restrict the asset list.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 113
Visual analysis of assets in Fleet Manager
11.3 Viewing aspects

Figure 11-2 Finding the asset "Filter & sort"

Result
The navigation displays the selected asset that corresponds to the search or filter
parameters.

11.3 Viewing aspects


After you have selected an asset to be monitored, you can open an extension to see the
status of its single aspects or events in detail in the right column. To view variables of
aspects Fleet Manager offers you the "Aspects" extension.

Requirement
You have created aspects in Asset Manager.

Getting Connected to MindSphere


114 Getting Started, 02/2020, V1801.Feb/2020.1
Visual analysis of assets in Fleet Manager
11.3 Viewing aspects

Procedure
To view variables of aspects in the "Aspect" extension, proceed as follows:
1. In the right-hand side of Fleet Manager, click the "Aspects" extension icon.
– The "Aspects" extension opens on the right-hand side.
2. Select and expand an aspect e.g. "Generator":
– Aspect "Generator" is opened.
– You can set a time frame (Time picker: day, week, and month) and see the variables,
which you want to monitor.
3. Select the dates from the last week in the calendar.
4. To show the exact measured values, move the mouse over the graph.

Result
The "Aspects" extension shows the chosen aspect of an asset.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 115
Visual analysis of assets in Fleet Manager
11.4 Viewing events

11.4 Viewing events


All events are displayed in an overview of the "Events" extension and you can influence the
view through different filter criteria. You can also assign a specific status to events. You can
find additional information on creating events in the Fleet Manager documentation.

Requirements
● You have created assets in Asset Manager.
● Events have been created and are already available.

Procedure
1. Select the required asset e.g. “Wind turbine", in the left-hand side of the window.
2. In the right-hand side, click the "Events" extension icon.
3. Click the tab "Events".

Result
The events data of asset "Wind turbine" is displayed.

Getting Connected to MindSphere


116 Getting Started, 02/2020, V1801.Feb/2020.1
Visual analysis of assets in Fleet Manager
11.4 Viewing events

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 117
Appendix A
A.1 Data center locations
You can license MindSphere on different regions in various data centers.
The following table shows the regions and the data center location for each region:

Region Data center location MindSphere infrastructure


provider
Europe 1 Frankfurt, Germany (eu1) Amazon Web Services
Europe 2 Amsterdam, Netherlands (eu2) Microsoft Azure
China 1 Shanghai, China (cn1) Alibaba Cloud

A.2 Quality code settings

A.2.1 Using quality code


The quality code measures the quality of the connection from a data provider to the
MindConnect Element. In MindSphere you can enable or disable the transmission of the
quality code.
You can switch the quality code on or off:
● TRUE: The quality code is transferred with the data to MindSphere.
● FALSE: The quality code is not transferred with the data to MindSphere. Erroneous or
bad transmissions and signal losses can not be detected by MindSphere. Instead the
value 0 will be stored for the missing data.
You can find more information about the corresponding values in chapter Quality codes OPC
UA and S7 protocol (Page 119).
Within a MindConnect Element the quality code is set by default to on. You can activate or
deactivate the quality code using the Time Series Service API
(https://developer.mindsphere.io/apis/iot-iottimeseries/api-iottimeseries-overview.html).
If you export the time series value (e.g. with Fleet Manager) you can see the data points with
its connected quality code. This helps you to analyze time ranges where no data is available.
This will avoid drawing false conclusions from a null value.
The following graphic shows a dataflow overview of the quality code:

Getting Connected to MindSphere


118 Getting Started, 02/2020, V1801.Feb/2020.1
Appendix
A.2 Quality code settings

If the data provider (e.g. S7 PLC, OPC UA Server) is not available, the MindConnect
Element or the data provider client will send up a "0" with a quality code. The value of the
quality code shows that this is not a valid data.
● If the function "Quality code" is enabled for this data point all the information can be
stored in the database. The database creates a request to Fleet Manager to show the
bad quality code information in a chart.
● If the function "Quality code" is disabled, the value 0 will be saved anyway. But you
cannot figure out if this data is valid.

A.2.2 Quality codes OPC UA and S7 protocol


The following table is based on the OPC UA standard and shows the possible quality codes
for OPC UA and S7:

Quality code Quality code Short description Long description


(hex) (dec)
0x00000000 0 GOOD Good, all items could be read.
0x00BA0000 12189696 GOOD_INCOMPLETE Good results may be incomplete - at least one
item could be read.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 119
Appendix
A.2 Quality code settings

Quality code Quality code Short description Long description


(hex) (dec)
0x002F0000 3080192 GOOD_OVERLOAD Sampling has slowed down due to resource
limitations.
0x40920000 1083310080 UNCERTAIN_INITIAL_VALUE Uncertain Initial Value - initial value.
0x80000000 -2147483648 BAD Bad - generic error.
0x800B0000 -2146762752 BAD_SERVICE_UNSUPPORTED Bad Service Unsupported - service unsupport-
ed.
0x800A0000 -2146828288 BAD_TIMEOUT Bad Timeout - Timeout occurred.
0x80100000 -2146435072 BAD_TOO_MANY_OPERATIONS Bad Too Many Operations - The request could
not be processed because it specified too many
operations.
0x801F0000 -2145452032 BAD_ACCESS_DENIED Bad Access Denied - Access denied.
0x80210000 -2145320960 BAD_IDENTITY_TOKEN_REJECT Bad Identity Token Rejected.
ED
0x80820000 -2138963968 BAD_TCP_INTERNAL_ERROR TCP internal error occurred.
0x80AB0000 -2136276992 INVALID_ARGUMENT Bad Invalid Argument - all items could not be
read.
0x80890000 -2138505216 BAD_CONFIGURATION_ERROR Lack of configuration info.
0x80340000 -2144075776 BAD_NODE_ID_UNKNOWN Bad item address.
0x80AC0000 -2136211456 BAD_CONNECTION_REJECTED Connection problem.
0x80740000 -2139881472 BAD_TYPE_MISMATCH Type conversion has problem.
0x803A0000 -2143682560 BAD_NOT_READABLE Read operation(s) has problem.
0x803B0000 -2143617024 BAD_NOT_WRITABLE Write operation(s) has problem.
0x803D0000 -2143485952 BAD_NOT_SUPPORTED Operation is not supported.
0x80130000 -2146238464 BAD_SECURITY_CHECKS_FAILE Indicates security problems.
D
0x808D0000 -2138243072 BAD_OUT_OF_SERVICE OPC service has problems.
0x80B80000 -2135425024 BAD_REQUEST_TOO_LARGE Request too large.
0x80D70000 -2133393408 BAD_BOUND_NOT_FOUND No data found to provide upper or lower bound
value.
0x80090000 -2146893824 BAD_UNKNOWN_RESPONSE An unrecognized response was received from
the server.
0x80AD0000 -2136145920 BAD_DISCONNECT The server has disconnected from the client.
0x80360000 -2143944704 BAD_INDEX_RANGE_INVALID The syntax of the index range parameter is
invalid.
0x80AF0000 -2136014848 BAD_INVALID_STATE The operation cannot be completed because
the object public String getValue() { return val-
ue; }is closed.
0x80020000 -2147352576 BAD_INTERNAL_ERROR An internal error occurred as a result of a pro-
gramming or configuration error.
0x804F0000 -2142306304 BAD_SERVER_URI_INVALID The ServerUri is not a valid URI.
0x803E0000 -2143420416 BAD_NOT_FOUND A requested item was not found or a search
operation ended without success.

Getting Connected to MindSphere


120 Getting Started, 02/2020, V1801.Feb/2020.1
Appendix
A.2 Quality code settings

Quality code Quality code Short description Long description


(hex) (dec)
0x809B0000 -2137325568 BAD_NO_DATA No data exists for the requested time range or
event filter.
0x809D0000 -2137194496 BAD_DATA_LOST Data is missing due to collection start-
ed/stopped/lost.

A.2.3 Quality codes Modbus protocol


The following table shows the possible quality codes for devices that use the Modbus
protocol:

Quality code Quality code Short description Long description


(hex) (dec)
0x00000000 0 Good No error occurred
0x80050000 -2147155968 Communication error Modbus connection reset for connection

0x80310000 -2144272384 No communication Communication with the data source is defined


but not established and there is no last known
value available
0x803A0000 -2143682560 Not readable The access level does not allow reading or
subscribing to the node
0x80790000 -2139553792 No subscription There is no subscription available for this ses-
sion
0x80AB0000 -2136276992 Invalid argument One or more arguments are invalid
0x80AB0000 -2144141312 Internal error One or more arguments are invalid
0x809E0000 -2137128960 Data unavailable Expected data is unavailable for the requested
time range due to an unmounted volume, an
offline archive or tape, or similar reason for
temporary unavailability
0x809F0000 -2137063424 Entry exists The data or event was not successfully updated
because no matching entry exists
0x803C0000 -2143551488 Out of range The value was out of range
0x80270000 -2144927744 Session not activated The session cannot be used because Acti-
vateSession has not been called
0x808B0000 -2138374144 Device failure There has been a failure in the device/data
source that generates the value that has affect-
ed the value
0x803D0000 -2143485952 Not supported The server cannot retrieve a bound for the
variable
0x80630000 -2140995584 Type definition invalid The type definition node ID does not reference
an appropriate type node
0x800D0000 -2146631680 Server not connected The operation could not complete because the
client is not connected to the server.
0x80730000 -2139947008 Write not supported The server does not support writing the combi-
nation of value status and timestamps provided

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 121
Appendix
A.2 Quality code settings

A.2.4 Quality codes SIMATIC I/O Shield


The following table shows the possible quality codes for SIMATIC I/O Shield devices:

Quality code Quality code Short description Long description


(hex) (dec)
0x00000000 0 Good No error occurred
0x80050000 -2147155968 Communication error Modbus connection reset for connection
0x802A0000 -2144731136 Request header invalid Correct HTTP Status Code when rejecting a
request because User-Agent header is invalid
0x80330000 -2144141312 Node Id invalid AIO/GPIO instance is not valid
0x803E0000 -2143420416 Not found A requested item was not found
0x80AB0000 -2136276992 Invalid argument There is an error with one or more arguments
0x80020000 -2147352576 Internal error An internal error occurred. Please check pro-
gramm or configuration
0x80030000 -2147287040 Out of memory Not enough memory for operation
0x00BA0000 12189696 Good results may be incomplete The server should have followed a reference to
a node in a remote server but did not. The re-
sult set may be incomplete
0x80730000 -2139947008 Write not supported The server does't support writing the combina-
tion of the given values
0x801F0000 -2145452032 User access denied User does not have permission for requested
operation
0x805E0000 -2141323264 Node Id exists Board info file does not exist
0x80B60000 -2135556096 Syntax error Syntax error

A.2.5 Quality codes SYSTEM protocol


The following table shows the possible quality codes for devices that use the SYSTEM
adapters:

Quality code Quality code Short description Long description


(hex) (dec)
0x00000000 0 Good No error occurred
0x803A0000 -2151284736 Not readable The access level does not allow the operation
to the Node (reading or subscribing)

Getting Connected to MindSphere


122 Getting Started, 02/2020, V1801.Feb/2020.1
Appendix
A.3 Technical specifications of MindConnect Nano

A.2.6 Quality codes Rockwell protocol


The following table shows the possible quality codes for devices that use the Rockwell
protocol:

Quality code Quality code Short description Long description


(hex) (dec)
0x00000000 0 Good No error occurred
0x80010000 -2147418112 Unexpected error An unexpected error occured
0x80020000 -2147352576 Internal error An internal error occured
0x80030000 -2147287040 Out of memory Not enough memory for operation
0x80050000 -2147155968 Communication error Connection to device failed
0x80090000 -2146893824 Unknown response Received an unsolicited message
0x800A0000 -2146828288 Timeout The operation timed out
0x800B0000 -2146762752 Service unsupported Service is not supported
0x800F0000 -2146500608 Nothing to do Nothing to send
0x801F0000 -2145452032 Access denied User does not have permission for requested
operation
0x80330000 -2144141312 Invalid tag Requested item (tag) is not known
0x805E0000 -2141323264 Node does not exist Info file does not exist
0x80630000 -2140995584 Invalid type definition The type definition does not reference an ap-
propriate type
0x80740000 -2139881472 Type mismatch Data type is not supported
0x80780000 -2139619328 Too many publish requests Pending buffer is full
0x80840000 -2138832896 Request interrupted Request interrupted
0x80850000 -2138767360 Request timeout Receive timeout occured
0x80B10000 -2135883776 No data available No more data available
0x80B60000 -2135556096 Invalid syntax Syntax error
0x80B80000 -2135425024 Request too large Buffer is too small
0x80CE0000 -2133983232 Invalid response Received an invalid reply

A.3 Technical specifications of MindConnect Nano

Functions
Field protocol – S7 Siemens S7 (for S7-3xx / S7-4xx / S7-12xx/ S7-15xx / ET-200s PLCs)
Field protocol – OPC UA Part 8 of the OPC UA specification (Data Access)
Configuration of data collection With Asset Manager in MindSphere
Data buffering Up to 500 MB buffering space for collected data
Proxy support Yes
DHCP support Yes
Security Connection outbound via HTTPS on port 443 to MindSphere only; no incoming con-
nection accepted SSL/TLS encryption of data in transit to MindSphere

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 123
Appendix
A.3 Technical specifications of MindConnect Nano

Supply voltage
Type of supply voltage 24 V
Current consumption max. 1.8 A at 24 V
Mains buffering
Mains/voltage failure stored energy 20 ms
time

Interfaces
USB port 1x USB 3.0 / 3x USB 2.0
PCIe slot 1x PCIe x1 (Disabled)
serial interface 1x COM (Disabled)
Video interfaces
Graphics interface 1x DisplayPort (Disabled)
Industrial Ethernet
Industrial Ethernet interface 2x 1000 Mbit RJ45

Monitoring functions
Status LEDs Yes
Fan No

EMC
Interference immunity against discharge of static electricity
Interference immunity against dis- ±6 kV contact discharge acc. to IEC 61000-4-2; ±8 kV air discharge acc. to IEC
charge of static electricity 61000-4-2
Interference immunity to cable-borne interference
Interference immunity on supply • ±2 kV acc. to IEC 61000-4-4, burst; ±1 kV acc. to IEC 61000-4-5, surge symmet-
cables ric;
• ±2 kV acc. to IEC 61000-4-5, surge asymmetric;
Interference immunity on signal • ±2 kV acc. to IEC 61000-4-5, surge, length > 30 m;
cables >30m
Interference immunity on signal • ±1 kV acc. to IEC 61000-4-4; burst; length < 3 m;
cables < 30m
• ±2 kV acc. to IEC 61000-4-4; burst; length > 3 m;
Interference immunity against voltage surge
asymmetric interference ±2 kV acc. to IEC 61000-4-5, surge asymmetric
symmetric interference ±1 kV acc. to IEC 61000-4-5, surge symmetric
Interference immunity against high-frequency electromagnetic fields
Interference immunity against high • 10 V/m for 80 - 1000 MHz and 1.4 - 2 GHz, 80% AM acc. to IEC 61000-4-3;
frequency radiation
• 3 V/m for 2 - 2.7 GHz, 80% AM acc. to IEC 61000-4-3;
• 10 V/m for 10 kHz - 80 MHz, 80% AM acc. to IEC 61000-4-6
Interference immunity to magnetic fields

Getting Connected to MindSphere


124 Getting Started, 02/2020, V1801.Feb/2020.1
Appendix
A.3 Technical specifications of MindConnect Nano

EMC
Interference immunity to magnetic 100 A/m; to IEC 61000-4-8
fields at 50 Hz
Emission of conducted and non-conducted interference
Interference emission via line/AC EN 61000-6-3, EN 61000-6-4, CISPR 22 Class B, FCC Class A
current cables

Degree and class of protection


IP (at the front) IP20
IP (rear) IP40
Standards, approvals, certificates
CE mark Yes
UL approval Yes
UL 508 Yes
cULus Yes
RCM (formerly C-TICK) Yes
KC approval Yes
EMC CE, EN 61000-6-4:2007, EN 61000-6-2:2005
EN 61000-6-2 Yes
Dust protection Protection against foreign bodies > 1 mm
FCC Yes
Marine approval
Germanischer Lloyd (GL) Yes
American Bureau of Shipping Yes
(ABS)
Bureau Veritas (BV) Yes

Ambient conditions
Ambient temperature during operation
Ambient temperature during opera- 0 °C up to 60 °C
tion
min. 0 °C
max. 60 °C
Ambient temperature during storage/transportation
min. -20 °C
max. 60 °C
Relative humidity
Relative humidity Tested according to IEC 60068-2-78, IEC 60068-2-30: Operation: 5% to 80% at 25
°C (no condensation), Storage: 5% to 95% at 25 °C (no condensation)
Vibrations
Vibration load in operation Tested to DIN IEC 60068-2-6: 10 Hz to 58 Hz: 0.075 mm, 58 Hz to 200 Hz: 9.8 m/s²
(1 g)

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 125
Appendix
A.4 Technical specifications of MindConnect IoT2040

Ambient conditions
Shock testing
Shock load during operation Tested according to IEC 60068-2-27: 150 m/s², 11 ms

Software
MindConnect Software Pre-installed MindConnect Software

Dimensions
Width 191 mm
Height 100 mm
Depth 60 mm

A.4 Technical specifications of MindConnect IoT2040

Functions
Field protocol – S7 Siemens S7 (for S7-3xx / S7-4xx / S7-12xx/ S7-15xx/ ET-200s PLCs)
Field protocol – OPC UA Part 8 of the OPC UA specification (Data Access)
Configuration of data collection With Asset Configuration tool in MindSphere
Data buffering Up to 500 MB buffering space for collected data
Proxy support Yes
DHCP support Yes
Security Connection outbound via HTTPS on port 443 to MindSphere only; no incoming con-
nection accepted SSL/TLS encryption of data in transit to MindSphere

Installation type/mounting
Design IoT Gateway, built-in unit
Mounting DIN rail, wall mounting

Supply voltage
Type of supply voltage DC 9…36 V, no galvanic isolation
Mains buffering
Mains/voltage failure stored energy 5 ms
time

Interfaces
USB port 1x USB 2.0, 1x USB client
Connection for keyboard/mouse USB / USB

Getting Connected to MindSphere


126 Getting Started, 02/2020, V1801.Feb/2020.1
Appendix
A.4 Technical specifications of MindConnect IoT2040

Interfaces
serial interface 2x COM ports (RS 232, RS 485)
Industrial Ethernet
Industrial Ethernet interface 2 x Ethernet (RJ45)
100 Mbps Yes
1000 Mbps No

Monitoring functions
Watchdog Yes
Status LEDs Yes

EMC
Interference immunity against discharge of static electricity
Interference immunity against dis- ±4 kV contact discharge acc. to IEC 61000-4-2; ±8 kV air discharge acc. to IEC
charge of static electricity 61000-4-2
Interference immunity against high-frequency electromagnetic fields
Interference immunity against high • 10 V/m for 80 - 1000 MHz, 80% AM acc. to IEC 61000-4-3;
frequency radiation
• 3 V/m for 1.4 - 2 GHz, 80% AM acc. to IEC 61000-4-3;
• 1 V/m for 2 - 2.7 GHz, 80% AM acc. to IEC 61000-4-3;
• 10 V for 150 kHz - 80 MHz, 80% AM acc. to IEC 61000-4-6;
Interference immunity to cable-borne interference
Interference immunity on supply • ±2 kV acc. to IEC 61000-4-4, burst;
cables
• ±1 kV acc. to IEC 61000-4-5, surge symmetric;
• ±2 kV acc. to IEC 61000-4-5, surge asymmetric;
Interference immunity on signal ±2 kV acc. to IEC 61000-4-5, surge, length > 30 m
cables >30m
Interference immunity on signal ±2 kV in accordance with IEC 61000-4-4, burst, length > 30 m
cables < 30m
Interference immunity against voltage surge
Asymmetric interference ±2 kV acc. to IEC 61000-4-5, surge asymmetric
Symmetric interference ±1 kV acc. to IEC 61000-4-5, surge symmetric
Interference immunity to magnetic fields
Interference immunity to magnetic 100 A/m; to IEC 61000-4-8
fields at 50 Hz
Emission of conducted and non-conducted interference
Emission of conducted and non- EN 61000-6-4:2007 +A1:2011
conducted interference

Degree and class of protection


IP (at the front) IP20
Standards, approvals, certificates

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 127
Appendix
A.4 Technical specifications of MindConnect IoT2040

Degree and class of protection


Approval CE (industry), UL, cULus
CE mark Yes
UL approval Yes
cULus Yes
KC approval Yes
EMC • CE
• EN 61000-6-4:2007 +A1:2011
• EN 61000-6-2:2005
• EN 61000-6-3:2007 +A1:2011
• EN 61000-6-1:2007

Ambient conditions
Ambient temperature during operation
Ambient temperature during opera- 0 °C to 50 °C
tion
min. 0 °C
max. 50 °C
Relative humidity
Relative humidity • Tested according to IEC 60068-2-78
• IEC 60068-2-30: Operation: 5 % to 85 % at 30 °C (no condensation)
• storage / transport: 5 % to 95 % at 25 / 55 °C (no condensation)
Vibrations
Vibration load in operation Tested according to IEC 60068-2-6: 5 Hz to 9 Hz: 3.5 mm; 9 Hz to 200 Hz: 9.8 m/s²
Shock testing
Shock load during operation Tested according to IEC 60068-2-27: 150 m/s², 11 ms

Software
MindConnect Software Pre-installed MindConnect Software

Dimensions
Width 144 mm
Height 90 mm
Depth 53 mm

Getting Connected to MindSphere


128 Getting Started, 02/2020, V1801.Feb/2020.1
Appendix
A.5 Offline buffer

A.5 Offline buffer


In order to calculate the buffer time for MindConnect Nano or MindConnect IoT2040 you can
use the following formula:

MindConnect Nano data buffer is 500 MB. When the buffer is at full capacity, the new
incoming data will overwrite the oldest data.
The following example shows the buffer time for a MindConnect Nano with 500 MB data
buffer:
In this case, 120 bytes is the memory needed for one data point.

A.6 Read performance MindConnect Elements


All MindConnect Elements have a clear limitation on soft limits(unmonitored number of data
points and data connections). The only fixed limit is 1050 data points. Within the soft limits,
you can configure data connections and data points without reaching the limits. For 250
datapoints read per second, the upload bandwidth should be at least 0.5 MB/s.
The following describes how to proceed if you want to exceed these limits.

Tested MindConnect limits

MindConnect Nano MindConnect IOT2040


Max mount of data points can be con- 1050 1050
figured (Fix)
Data points OPC UA / S7 / Modbus 250 30
TCP (read per second)
Connections to data providers 30 5
String data points 10 3
Data points - Modbus RTU RS485 / 20 15
RS422 - 9,6 kBd
Data points - Modbus RTU RS485 / 35 20
RS422 - 19,2 kBd
Data points - Modbus RTU RS485 / 80 30
RS422 - >= 38,4 kBd
Data points - Modbus RTU RS232 - 40 30
57,6 kBd

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 129
Appendix
A.6 Read performance MindConnect Elements

Adaptions of the limits


Subsequently listed are the parameters the influence the read performance of a
MindConnect Element. By varying one of these parameters all others will be affected as well.
These are the variables:
● Performance of MindConnect hardware
● Number of connections to data providers
● Type of connection to providers (S7 / OPC UA / Modbus / ...)
● Amount of data points per second
● Type of data points (String or no string)
● Performance of data provider (PLC, OPC Server)

Note
Reading data from a data provider will always cause an effect on it. The performance of the
data provider (PLC / OPC Server / Modbus) is one of the most important limiting factors. If
more devices (e.g. OPC server, HMIs, SCADA systems,...) are connected to this data
provider (e.g. PLC) the reading cycle can rise.

Example calculations (MindConnect Nano)


● It can be possible to read 300 data points per second out of a PLC. This is possible if the
PLC is powerful and just one data provider is used.
● It can be possible to read 1000 data points out of 30 data providers if the reading cycle
will be switched to 4sec.
● It can be possible to read out of 35 data providers if you just read 200 data points per
second.

Note
To make sure a configuration works for your setup it needs to be monitored over a longer
period of time.

System Test results


The following tables show how long it takes to read a data item from one of the devices.
These are not fixed values but an indication of how the devices would react.

Getting Connected to MindSphere


130 Getting Started, 02/2020, V1801.Feb/2020.1
Appendix
A.7 Firewall Settings

MindConnect NANO

Type MS per data point read


Min Mid Max
S7 300 1,13 1,74 3,08
S7 1500 0,37 1,60 3,89
S7 1200 3,50 5,18 7,50
S7 ET200S CPU 0,89 2,09 3,71
OPC UA @ PC1) 2,38 6,64 8,53
OPC UA@ PLC 2,66 3,27 4,69
1) OPC UA @ PC always depends on the hardware.
● Read of a string data point you have to multiply the time with 2,5 per data point
● All devices are around 75% full

MindConnect IOT2040

Type MS per data point read


Min Mid Max
S7 300 2,10 4,28 6,61
S7 1500 3,73 4,54 5,22
S7 1200 6,29 6,72 7,11
S7 ET200S CPU 1,92 5,01 8,33
OPC UA @ PC
OPC UA@ PLC 4,42 5,50 7,66

● Read of a string data point you have to multiply the time with 2,5 per data point
● All devices are around 75% full

A.7 Firewall Settings


It is recommended to use a firewall between the Internet and the MindConnect Elements,
this is also recommended for communication to the automation network.
In the direction to Automation Network a firewall supporting NAPT (in case of DMZ, see
section “List of abbreviations”) or supporting the “Ghost-Mode” is required. Siemens offers
many types of Firewalls for fulfilling these requirements.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 131
Appendix
A.7 Firewall Settings

① Corporate / Office Network with route to the internet or direct internet access, e.g. via a DSL modem
② Production / Machine Network

Getting Connected to MindSphere


132 Getting Started, 02/2020, V1801.Feb/2020.1
Appendix
A.8 ESD guideline

“Ghost-Mode”, also known as “Transparent Mode”, is used to protect individual, event


alternating, devices by dynamically taking over the IP address.

A.8 ESD guideline

What does ESD mean?


An electronic module is equipped with highly integrated components. Due to their design,
electronic components are highly sensitive to overvoltage and thus to the discharge of static
electricity. Such electronic components or modules are labeled as electrostatic sensitive
devices.
The following abbreviations are commonly used for electrostatic sensitive devices:
● ESD – Electrostatic sensitive device,
● ESD – Electrostatic Sensitive Device as a common international designation.
Electrostatic sensitive devices can be labeled with an appropriate symbol.

NOTICE
Damage to ESD from touch
Electrostatic sensitive devices, ESD, can be destroyed by voltages which are far below the
human perception limit. If you touch a component or electrical connections of a module
without discharging any electrostatic energy, these voltages may arise.
The damage to a module by an overvoltage can often not be immediately detected and only
becomes evident after an extended period of operation. The consequences are incalculable
and range from unforeseeable malfunctions to a total failure of the machine or system.
Avoid touching components directly. Make sure that persons, the workstation and the
packaging are properly grounded.

Charge
Every person without a conductive connection to the electrical potential of his/her
surroundings can be electrostatically charged.
The material with which this person comes into contact is of particular significance. The
figure shows the maximum electrostatic voltages with which a person is charged, depending
on humidity and material. These values conform to the specifications of IEC 61000-4-2.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 133
Appendix
A.8 ESD guideline

① Voltage
② Synthetic materials
③ Wool
④ Antistatic materials such as wood or concrete
⑤ Relative humidity

NOTICE
Grounding measures
There is no equipotential bonding without grounding. An electrostatic charge is not
discharged and may damage the ESD.
Protect yourself against discharge of static electricity. When working with electrostatic
sensitive devices, make sure that the person and the workplace are properly grounded.

Getting Connected to MindSphere


134 Getting Started, 02/2020, V1801.Feb/2020.1
Appendix
A.9 Return of defect hardware

Protective measures against discharge of static electricity


● Disconnect the power supply before you install or remove modules which are sensitive to
ESD.
● Pay attention to good grounding:
– When handling electrostatic sensitive devices, make sure that persons, the
workstation and devices, tools and packaging used are properly grounded. This way
you avoid static discharge.
● Avoid direct contact:
– As a general rule, do not touch electrostatic sensitive devices, except in the case of
unavoidable maintenance work.
– Hold the modules at their edge so that you do not touch the connector pins or
conductor paths. This way, the discharge energy does not reach and damage the
sensitive components.
– Discharge your body electrostatically before you take a measurement at a module. Do
so by touching grounded metallic parts. Always use grounded measuring instruments.

A.9 Return of defect hardware


In case of a defect or corrupted hardware you can find contacts and information under the
following links:

Spare part services


In case of a defect or corrupted hardware you can find detail information in the SIOS Article -
Spare Parts Services (https://support.industry.siemens.com/cs/sc/2110/spare-parts-
services?lc=en-WW).

Delivery of spare parts


For ordering, provision and delivery of spare parts you can find more information in the SIOS
Article - Delivery of Spare Parts. (https://support.industry.siemens.com/cs/sc/2112/ordering-
provision-and-delivery-of-spare-parts?lc=en-WW)

Siemens Contact Database


You can find your personal contact for spare parts in the Siemens Contact Database
(https://www.automation.siemens.com/aspa_app/?cntryid=DE&comptcid=e&lang=en).

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 135
Appendix
A.10 List of abbreviations

A.10 List of abbreviations

Abbreviation Description
DMZ Demilitarized Zone (referred to a perimeter network)
GUI Graphical User Interface
HTTPS Hyper Text Transfer Protocol Secure
IoT Internet of things
IoT2040 MindConnect IoT2040
IP Internet Protocol
LAN Local Area Network
MCN MindConnect Nano
MSU MindSphere Unit
NAPT Network Address and Port Translation
OEM Original Equipment Manufacturer
OPC UA Open Platform Communications Unified Architecture
PC Personal Computer
S7 STEP 7
UI User Interface

Getting Connected to MindSphere


136 Getting Started, 02/2020, V1801.Feb/2020.1
Appendix
A.10 List of abbreviations

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 137
Glossary

Aspect
Aspects are a data modeling mechanisms for assets. Aspects group the data points based
on logical sense. For example: The pump skid has an aspect e.g. “Energy_consumption” that
contains the data points: "power", "current", "voltage" etc.
Aspect is specified in Asset Manager and its name can be freely chosen, but should bring
together a logical grouping of data points and a physical asset.

Asset
An asset is a digital representation of a machine or an automation system with one or
multiple automation units (e.g. PLC) connected to MindSphere.
MindSphere data collection and data provisioning is based on so called (virtual) assets. This
can be anything such as a pump, motor, PLC, an entire tool machine, a production line, a
robot, a crane, a car, a wind turbine and so on. The data of an asset is collected and sent to
MindSphere to make that data available for further processing and analytics.

Asset Identifier
Asset Identifier is an identifier assigned by the manufacturer of the device, to which
MindConnect Nano will be connected. After the onboarding process, MindConnect Nano is
connected to this device. The serial number identifies the asset to which the data belongs.

Asset Manager
Asset Manager is a Web Graphical User Interface for asset configuration. According to these
configurations, the following functions are available:
Asset Configuration: assets can be created, onboarded, modified, moved, offboarded or
deleted.

Asset type
Asset type is a sort or kind of a product line made by one manufacturer.

Components
Components represent built-in functionality in MindSphere. Components are:
● Asset Manager
● Fleet Manager
● Settings
● UTC Reporting

Getting Connected to MindSphere


138 Getting Started, 02/2020, V1801.Feb/2020.1
Glossary

For the complete list and description of Components, refer to the “MindSphere”
documentation.

Data point
Data points refer to elements (variables), which allow values to be obtained from data
sources (OPC UA or S7 etc.). They are combined into a relevant aspect. For example,
“temperature” and “torque” are data points of an aspect “Energy_consumption”.
Data points are configured in "Asset Manager”. In “Fleet Manager”, their values are
visualized as time series.

Data source
A data source is a physical element of a device, which can be monitored by MindSphere.
For example: OPC UA Server, S7.

Event
In "Fleet Manager", an event is a change of a datapoint state. Events are used for the
requests. With a rule it is possible to define the request, which will be created in MindSphere
when the event is triggered.
Besides the monitoring rule, a description of event (e.g. “The limit is exceeded, this may
indicate damage in the pump”), the resulting action (e.g. “Please contact your hotline”) and
priority (urgent, important or info) can be lodged.
See also “request”, “rule".

Fleet Manager
Fleet Manager is a visualization tool which provides an overview of existing assets and their
information (asset name, customer name, location). Fleet Manager displays your configured
asset, aspects with datapoints in charts and list of all requests etc.

Last Connection
"Last Connection" status in “Asset Manager” gives the information, when a MindConnect
Element was online for the last time.

MindConnect Element
MindConnect Elements are devices for transferring data and allow connectivity to
MindSphere such as MindConnect Nano, MindConnect IoT2040 or MindConnect FB.

MindSphere
MindSphere is the Siemens Industrial IoT operation system comprising the core cloud
services and applications, whereas the MindConnect Element provides secure and easy
connectivity from the field or machine to MindSphere. In MindSphere, submitted data by a

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 139
Glossary

MindConnect Element is processed and stored for analysis and further management
purposes.
For more information, refer to the “MindSphere” documentation.

MindSphere Launchpad
MindSphere Launchpad is the entry point for components as well as for available
applications.

Online/Offline Mode in Asset Manager


Online indicates internet connection, when the MindConnect Nano/IoT2040 sends the data
to the server. Offline mode means the absence of the internet connection and the
MindConnect Nano/IoT2040 is no longer able to send data to the server.

Organization
Organization is the part of hierarchical asset configuration in Asset Manager. Within
organization, areas/assets are specified.
As the administrator (OEM), you manage organizations, their customers and assets. As the
user of an organization, you can access the assets assigned only to this organization.
In the context of MindSphere, an organization can be anything and is defined by the
administrator depending on their requirements: customer, cost center, branch etc.

Request
Requests are the messages which log asset incidents based on predefined rules.
You can create manual requests as well as requests for the regular acquisition of measured
quantities with measuring series.
See also “event", "rule".

Rule
With rules you can configure an automatic monitoring of datapoints on events. For example,
a request will be created automatically by the system, if a value exceeds or falls below a
threshold (edge trigger).
See also “event", "request".

Settings
Settings is a Web Graphical User Interface for user, organization and role configuration.

Time series
Time series is a sequence of measurements which are produced by data sources over time.
Analysis and visualization tools (e.g. Fleet Manager) can retrieve collected time series and

Getting Connected to MindSphere


140 Getting Started, 02/2020, V1801.Feb/2020.1
Glossary

present it to the user after processing. In Asset Manager, the measurements, that have to be
collected, can be specified.

Getting Connected to MindSphere


Getting Started, 02/2020, V1801.Feb/2020.1 141