HomeWorks QS Palladiom HVAC Solution


Add a Palladiom HVAC solution to a HomeWorks QS system for convenient HomeWorks QS Palladiom
Thermostat
and aesthetically pleasing control of temperature and for intuitive heating
and cooling adjustments.
On
Heat Set

Features
Auto

HomeWorks QS Palladiom Thermostat


• Aesthetically coordinates with Palladiom keypads.
• Available in plastic, glass and metal finishes. See Colors and Finishes at
the end of the document for more information.
• Backlit screen and buttons that include Dynamic Backlight Management
(DBM) to automatically adjust backlight intensity based on ambient lighting
conditions.
• Displays temperature in Fahrenheit or Celsius.
• Uses Lutron QS link for power and communication with other QS devices.
• Ships with a sealed wallbox for use in new or existing constructions,
specifically for hollow walls that may have air movement in the wall cavity.
• IEC SELV / PELV NECR Class 2 for 24 – 30 V-
• IEC ELV / NECR Class 2 for 31 – 36 V-
HomeWorks QS
• IEC, cULus, and NOM compliant. Palladiom HVAC
HomeWorks QS Palladiom HVAC Controller Controller
• Works with many residential HVAC systems.
• Uses 12 – 24 V~ / 24 V- and common wiring from HVAC equipment
transformer or other 12 – 24 V~ / 24 V- IEC PELV/NECR Class 2 supply.
• Supports an optional wired remote temperature sensor to allow for flexibility
regarding thermostat installation location. The wired remote temperature
sensor is used instead of the internal thermostat sensor.
• IEC and cULus compliant.
System
• System features programmed in HomeWorks QS software.
• 7-day programmable schedule.
• Schedule events based on time of day or astronomic time. HVAC Equipment
• Local hold button disables system timeclock events.
• Select alternate setpoints to save energy while on vacation.
• Local fail safe feature continues operation if communication with the
HomeWorks QS system is interrupted.
• Monitor and control thermostat settings via Lutron Connect mobile device.

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 1 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Model Numbers
HQWT-T-HW-XXX*-A – HomeWorks QS Palladiom thermostat
SMC55-RESI – HomeWorks QS Palladiom HVAC controller (includes wire harness LR-HVAC-WIRE-120)
LR-TEMP-FLSH – Wired flush mount sensor (optional remote temperature sensor)
* “XXX” in the model number represents color / finish code. See Colors and Finishes section at the end of the document for more information.

Compatibility
The HomeWorks QS Palladiom HVAC controller works with residential HVAC systems including:
• Conventional forced air systems using gas, electric, or oil heat, as well as compressor-based cooling-only as
split systems or packaged units.
• Fan coil units
• Hydronic or electric underfloor / radiant heating (see Underfloor Heating Systems on page 3)
• Specific VRV / VRF systems (see VRV / VRF Systems on page 3)

Typical System Configurations


Control wiring is done via conventional isolated relays for stage capacity control. Typical system
configurations are:

Heat / Cool Stages (Relays)


• 1 heat / 1 cool conventional (W1, Y1, G)
• 1 heat conventional (with or without fan [G]) (W1)
• 1 cool conventional (Y1, G)

Fan Coil Units


• 2-pipe, On / Off valve, 3-speed fan with changeover sensor (valve, G1,G2,G3)
• 2-pipe, On / Off valve, 0 – 10 V controlled fan with changeover sensor (valve, 0 – 10 V fan)
• 2-pipe, 0 – 10 V valve, 3-speed fan with changeover sensor (0 – 10 V valve, G1, G2, G3)
• 2-pipe, 0 – 10 V valve, 0 – 10 V controlled fan with changeover sensor (0 – 10 V valve, 0 – 10 V fan)
• 4-pipe, On / Off valve, 3-speed fan (hot valve, cold valve, G1, G2, G3)
• 4-pipe, On / Off valve, 0 – 10 V controlled fan (hot valve, cold valve, 0 – 10 V fan)
• 4-pipe, 0 – 10 V valve, 3-speed fan (0 – 10 V hot valve, 0 – 10 V cold valve, G1, G2, G3)
• 4-pipe, 0 – 10 V valve, 0 – 10 V controlled fan (0 – 10 V hot valve, 0 – 10 V cold valve, 0 – 10 V fan)

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 2 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


VRV/VRF Systems
The HomeWorks QS Palladiom thermostat can be used to control the VRV / VRF systems listed below.

MitsubishiR VRF Systems


 equires one of these hardware options:
R
) HomeWorks QS Palladiom thermostat with HomeWorks QS processor and CoolAutomationT interface.*
See Application Note #650 (048650) at www.lutron.com
) HomeWorks QS Palladiom thermostat with HomeWorks QS Palladiom HVAC controller and MitsubishiR
thermostat controller interface.* See Application Note #585 (048585) at www.lutron.com

LGR VRF Systems


 equires one of these hardware options:
R
) HomeWorks QS Palladiom thermostat with HomeWorks QS processor and CoolAutomationT interface.*
See Application Note #650 (048650) at www.lutron.com
) HomeWorks QS Palladiom thermostat with HomeWorks QS Palladiom HVAC controller and LGR thermostat
controller interface.* See Application Note #627 (048627) at www.lutron.com

DaikinR VRV Systems


Requires:
) HomeWorks QS Palladiom thermostat with HomeWorks QS processor and CoolAutomationT interface.*
See Application Note #650 (048650) at www.lutron.com

Underfloor Heating Systems


Requires:
) HomeWorks QS Palladiom thermostat with HomeWorks QS processor and Heatmiser interface.* See
Heatmiser HVAC Integration with HomeWorks QS document.

* Provided by others.

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 3 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


System Diagram

Wireless router
(by others) HomeWorks Palladiom
Lutron QS Palladiom keypad
Connect thermostat
Bridge Heat

Auto
Set
On

Ethernet
connection

HomeWorks QS HVAC
processor equipment
(by others)

HomeWorks QS
QS link 1 Palladiom HVAC
controller link 2

HomeWorks QS
Lutron Connect Palladiom HVAC
mobile device controller signals
application HomeWorks QS
Palladiom HVAC
controller 3, 4

1
 or wiring details, see QS Link section on page 12.
F
2
For wiring details, see HomeWorks QS Palladiom HVAC Controller Link section on page 13.
3
For more information when using a HomeWorks QS Palladiom HVAC controller and a 3rd party interface in VRV / VRF systems, refer to either Application Note #585 (048585)
or Application Note #627 (048627) at www.lutron.com
4
For more information when using a CoolAutomationT interface in VRV / VRF systems, see Application Note #650 (048650) at www.lutron.com

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 4 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Technical Specifications
HomeWorks QS Palladiom Thermostat

Model Number HQWT-T-HW-XXX*-A

Regulatory Approvals IEC, cULus, and NOM compliant.


24 – 30 V- IEC SELV / PELV / NECR Class 2
Operating Voltage 31 – 36 V- IEC ELV / NECR Class 2
Power provided by QS link power supply.
Typical Power Consumption 10 mA at 24 V-
60 mA at 24 V-
Maximum Power Test conditions: Backlight on full.
Consumption 3 Power Draw Units (PDUs). For more information, see Power Draw Units
on the QS Link (P/N 369405).
Ambient operating temperature: 32 °F to 104°F (0 °C to 40 °C)
Environment 5% to 90% relative humidity (non-condensing). Indoor use only.
IP20 Rating
Thermostat communicates with the HomeWorks QS system via 4-wire
Communications QS link protocol. It also communicates with the HomeWorks QS Palladiom
HVAC controller via 3-wire HomeWorks QS Palladiom HVAC controller link.
Temperature display range: 32 °F to 99 °F (0 °C to 37 °C)
Temperature setpoint range: 50 °F to 90 °F (10 °C to 32 °C) (programmable)
Room Temperature Sensor
Accuracy: At 70 °F: < +/− 1 °F
At 25 °C: < +/− 0.5 °C
Should power be interrupted, the thermostat will retain all settings when
Power Failure Memory
power is restored.
Mount on a clean, dry, interior wall approximately 4 ft to 5 ft (1.2 m to 1.5 m)
Mounting
above the floor. See Mounting section for more information.
IEC SELV / PELV / NECR Class 2: 24 – 30 V-
Wiring IEC ELV / NECR Class 2: 31 – 36 V-
22 AWG (0.5 mm2) and 18 AWG (0.75 mm2) solid wiring.
www.lutron.com/TechnicalDocumentLibrary/warranty.pdf
Warranty www.lutron.com/TechnicalDocumentLibrary/Intl_warranty.pdf
Warranty only valid if installed by a properly trained climate control specialist.

* “XXX” in the model number represents color / finish code. See Colors and Finishes section at the end of the document for more information.

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 5 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Technical Specifications (continued)
HomeWorks QS Palladiom HVAC Controller

Model Number SMC55-RESI


Regulatory Approvals IEC and cULus compliant.
12 – 24 V~ 50 / 60 Hz +/−10%
Operating Voltage
24 V- +/−10%
2 A resistive load at 240 V~ or 30 V-
Note: If fan or valves exceed these ratings, interposing relays must be used
Maximum Relay Rating between the HomeWorks QS Palladiom HVAC controller and the HVAC unit.
Note: Do not connect directly to inductive or capacitive loads.
For more information, refer to the installation instructions.

Maximum Power
4 W / 6 VA
Consumption
Ambient operating temperature: −4 °F to 131°F (−20 °C to 55 °C)
Environment 10% to 90% relative humidity (non-condensing). Indoor use only.
IP20 Rating
HomeWorks QS Palladiom HVAC controller communicates with the
Communications
HomeWorks QS Palladiom thermostat using a 3-wire Modbus protocol.
Should power be interrupted, the HomeWorks QS Palladiom HVAC controller
Power Failure Memory
will retain system configuration settings when power is restored.
Intended for DIN rail mounting in an enclosure. See Mounting section for
Mounting
more information.
HomeWorks QS Palladiom HVAC Controller: LR-HVAC-WIRE-120 required
wire harness (included). For relay outputs, use wires at least 20 AWG
(0.5 mm2) with a temperature rating of at least 176 °F (80 °C).
Wiring
Wired Flush Mount Sensor: IEC SELV / PELV / NECR Class 2;
22 AWG (0.5 mm2) twisted, shielded pair wiring. Maximum wire length is
100 ft (30.5 m).
www.lutron.com/TechnicalDocumentLibrary/warranty.pdf
Warranty www.lutron.com/TechnicalDocumentLibrary/Intl_warranty.pdf
Warranty only valid if installed by a properly trained climate control specialist.

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 6 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Dimensions
All dimensions shown as: in (mm)

HomeWorks QS Palladiom Thermostat


Front View Side View
1.1
4.0
(28)
(102)
0.6
(14)

3.7 2.6
(94) (66)

0.6
(14)
0.7
(18)
0.4
(10)

Rear View

2.6
(66)

2.6
(66)

2.36
(60)

Continued on the next page...

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 7 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Dimensions (continued)
All dimensions shown as: in (mm)

Wallboxes and Wallbox Adapters


Sealed Wallbox (WBOX-HPT-Q1) and Corresponding Wallbox Adapter (included)
Both the sealed wallbox and corresponding wallbox adapter are included with the thermostat for use with hollow walls that may have
air movement in the wall cavity.

Rear View Front View Side View


Wallbox Adapter
2.75 2.0
(70) (51)

2.75
(70)

1.8
Wiring gaskets (46)

EBB-1-SQ (sold separately) and Corresponding Wallbox Adapter (included)


Square, metal wallbox (sold separately) for use with solid masonry or poured concrete walls with no airflow. Corresponding wallbox
adapter included with the thermostat.

Front View Front View


Side View
Wallbox Adapter
2.36 Minimum
2.75 (60) 1.38
(70) (35)

Wallbox

Maximum
0.125
(3)
2.36
(60) 3.46
(88) Conduit connector
Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 8 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Dimensions (continued)
All dimensions shown as: in (mm)

HomeWorks QS Palladiom HVAC Controller

Front View Side View

3.4 0.2
(87) (5)

2.75 2.4
(70) (62)

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 9 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Mounting
HomeWorks QS Palladiom Thermostat

• Mount on a clean, dry, interior wall.


• Mount approximately 4 ft to 5 ft (1.2 m to 1.5 m) above the floor.
• Mount on a wall without pipes, chimneys, or ducts.
• Mount on a wall with good visibility and control access.
• Do not mount on an exterior wall, close to a window, next to a door, or areas with drafts.
• Do not mount in direct airflow from supply and return registers / grilles.
• Do not expose to water (e.g., drips or splashes) or mount in a damp area.
• Do not mount within 4 ft (1.2 m) of heating sources (e.g., direct sunlight, light bulbs, etc.).
• Do not mount in areas with poor circulation (e.g., niches, alcoves, behind curtains, or behind doors).
• Do not mount within 0.75 in (19 mm) of Palladiom keypads.
Note: If it is not possible to follow these guidelines, the use of an indoor remote temperature sensor is recommended. For more
information, see Remote Temperature Sensor section on page 24.
ll
id e Wa
Outs
Inside Wall


4 ft to 5 ft
(1.2 m to 1.5 m)

Continued on the next page...


Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 10 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Mounting (continued)

HomeWorks QS Palladiom HVAC Controller


The HomeWorks QS Palladiom HVAC controller is intended for DIN rail mounting and requires a 4 DIN wide
mounting location. For DIN rail installation, follow the steps below:

1 2 3

Minimum Clearances
The HomeWorks QS Palladiom HVAC controller has been designed as an IP20 product and must be installed
in an enclosure (by others) with the clearances shown below.
All dimensions shown as: in (mm)

0.8 0.8
(20) (20)

3.2
(80)

1.6 1.6
(40) (40)
0.8 0.8
(20) (20)

Note: Multiple HomeWorks QS Palladiom HVAC controllers can be mounted next to each other.

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 11 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Wiring
QS Link Link Wiring < 500 ft (153 m)
• Use IEC SELV / PELV / NECR Class 2 (24 – 30 V-) Rear View
or IEC ELV / NECR Class 2 (31 – 36 V-) wiring to HomeWorks QS
Palladiom HVAC
connect the thermostat to the QS link for power and 1 2 3 4 controller link
communication. 1 2 3 4

• Connect two 22 AWG (0.5 mm2) ­shielded, twisted


pair wires to terminals 3 and 4. Shielding (drain) of
the twisted pair wires must be connected together
as shown, but do not connect the shielding to
earth / ground or the thermostat and do not allow it to
IEC ELV / NECR Data link
contact the grounded wallbox. Class 2 or IEC One twisted,
• Connect the appropriate size wires to terminals 1 and PELV / SELV NECR
Drain / 
shielded pair
Class 2 22 AWG
2 for power, according to your link length (see table One or two Shield (0.5 mm2)
below). 18 AWG 3: MUX (Purple)
• Connect Drain / Shield as shown. Do not connect to (1.0 mm2) 4: _ (White)
Ground (Earth) or the thermostat. Connect the bare 1: C
 ommon (Black)
2: V + (Red)
drain wires and cut off the outside shield.
Link Wiring 500 ft to 2000 ft (153 m to 610 m)
Note: Use appropriate wire connecting devices as
specified by local codes. 1 2 3 4
1 2 3 4

IEC ELV / Data link


NECR Class 2 One twisted,
or IEC PELV / shielded pair
Drain / 22 AWG
SELV NECR
shield (0.5 mm2)
Class 2
One 18 AWG 3: MUX (Purple)
(1.0 mm2) One or two 4: _ (White)
1: C
 ommon 12 AWG (2.5 mm2)
(Black)
QS Link Wire Sizes (check compatibility in your area) 2: V + (Red)

QS Link Wiring Length Wire Gauge Lutron Cable Part Number

Power (terminals 1 and 2)


1 pair 18 AWG (1.0 mm2) GRX-CBL-346S (non-plenum)
< 500 ft (153 m)
Data (terminals 3 and 4) GRX-PCBL-346S (plenum)
1 twisted, shielded pair 22 AWG (0.5 mm2)
Power (terminals 1 and 2)
1 pair 12 AWG (4.0 mm2)
500 ft to 2000 ft This will not fit in terminal. Connect as shown GRX-CBL-46L (non-plenum)
(153 m to 610 m) above. GRX-PCBL-46L (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm2)
Continued on the next page...
Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 12 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Wiring (continued)
HomeWorks QS Palladiom HVAC controller link
• The HomeWorks QS Palladiom HVAC controller Link Wiring < 500 ft (153 m)
comes with a 3-wire harness in the Rear View
LR-HVAC-WIRE-120 package. This is to be used on
the HomeWorks QS Palladiom HVAC controller link to
1 2 3
the thermostat.
• The 3-wire harness can be extended using one QS link
18 AWG (1.0 mm2) or 12 AWG (4.0 mm2) wire and 1
pair 22 AWG (0.5 mm2) twisted, shielded wire. See
table below and diagrams to right.
• Do not connect the drain / shield wire to earth / ground
Data link IEC ELV / NECR
or to the thermostat and do not allow it to contact the One twisted, Class 2 or IEC
grounded wallbox shielded pair PELV / SELV NECR
22 AWG Drain /  Class 2
(0.5 mm2) shield One 18 AWG
−: _ (Black) (1.0 mm2)
+: MUX (White) G: Common (Gray)

HomeWorks QS Palladiom HVAC Controller Link Wire Sizes (check compatibility in your area)
1 2 3

HomeWorks QS
Palladiom HVAC
Wire Gauge Lutron Cable Part Number
Controller Link Wiring
Length
Power (COM [G])
One 18 AWG (1.0 mm2) GRX-CBL-346S (non-plenum)
< 500 ft (153 m)
Data (MUX and _) GRX-PCBL-346S (plenum)
One twisted, shielded pair 22 AWG (0.5 mm2)

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 13 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Wiring (continued)
HomeWorks QS Palladiom HVAC controller link (continued)
HomeWorks QS
processor

Common QS Link Relay Terminals


Power and SPST(NO) 2 A 240 V~ maximum relays
V+
communication Terminal Conventional Fan Coil Unit
MUX
#5 Heat stage 1 (W1) Hot valve (HVALVE)
_
Heat valve
#5
Heating stage 1 transformer (RH)
#6 #6
transformer (RH) or Valve
1 2 3 4
HomeWorks #7 transformer (R)
QS Palladiom
#8 Cooling /
thermostat Fan transformer
#7 compressor
#9 (RFAN)
transformer (RC)
#10
Gray (G) Com Compressor
#8 Fan high (G3)
#11 stage 1 (Y1)
White (+) MUX
#12 Compressor
#9 Fan medium (G2)
Black (−) _ stage 2 (Y2)
#10 Fan (G) Fan low (G1)

#11 Heat stage 2 (W2) Cold valve (CVALVE)

HomeWorks QS Heating stage 2 Cold valve


#12
Palladiom HVAC transformer (RH2) transformer (RC)
controller

Controller Power (from HVAC system transformers)


Not used 24 V~ IEC / SELV / PELV / NECR Class 2
AO
4 G 3 5
Red (RH) Heat transformer
Gray /Red (C) Common
White (heat)
Black (common)
Green (fan) Black Isolated common (for changeover sensor, remote
Yellow (cool) Black temperature sensor, etc.)
Blue / Red (changeover sensor)
Wire harness for 0–10 V- Blue (remote temperature sensor)
valves and fan controls
Optional signal wires

Note: Wire harnesses can be extended using 18 AWG or 22 AWG (1.0 mm2 or 0.5 mm2) wire. Use twisted pair, shielded cables to
extend analog I / O and HomeWorks QS Palladiom HVAC controller links. See previous page.
Note: All terminal blocks are removable.

Continued on the next page...


Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 14 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Wiring (continued)
Signal Wiring Guide
Terminal Description
W1 1st stage heat relay
HVALVE Hot valve for 4-pipe fan coil units
RH Heating power – Connect to secondary side of heating system transformer 1
R Valve transformer
RC Cooling / compressor power – Connect to secondary side of cooling system transformer 2
RFAN Fan transformer
Y1 1st stage compressor relay
G (G3, G2, G1) Fan relay (fan high, fan medium, and fan low for fan coil units)
CVALVE Cold valve for 4-pipe fan coil units
Valve Single valve control for 2-pipe fan coil units
C Required common wire from secondary side of transformer

 Heat stage 1 transformer for conventional systems.


1

 Compressor and fan transformer.


2

Cable Type

2x 2x 2x 2x
AWG 24 to 14 22 to 14
Wire 24 to 18 24 to 16 22 to 18 20 to 16
Size 2x 2x 2x 2x
mm2 0.2 to 2.5 0.25 to 2.5
0.2 to 1.0 0.2 to 1.5 0.25 to 1.0 0.5 to 1.5
4.4 to 5.3 in-lb
(0.5 to 0.6 N•m)
0.28 in
(7 mm)

ø 0.14 in
(4 mm)

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 15 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


HomeWorks QS Palladiom HVAC Controller Wiring Diagrams (continued)
Conventional Systems

Diagram 1: 1 heat stage / 1 cool stage system (1 transformer)


24 V~
W 5 Heat 1 transformer
RH 6 24 V~
RC 7 L1 (hot)
Y1 8 Compressor L2
Common
Y2 9
G 10 Fan
W2 11
RW2 12

Controller power*
4 G 3
AO
5
RH

Diagram 2: 1 heat stage / 1 cool stage system (2 transformers)


Cooling
W 5 Heat 1 transformer
RH 6 24 V~
RC 7 L1 (hot)
Y1 8 Compressor L2
Common**
Y2 9 (for fan /
G 10 Fan compressor)
W2 11
RW2 12
24 V~
L1 (hot)
L2
Common
(for heat)
Controller power* Heating
4 G 3
AO
5
RH transformer

* If the signal source from the HVAC system is not 12 – 24 V~ / 24 V-, use a separate supply to power the HomeWorks QS Palladiom HVAC controller.
** In a two transformer system it is not necessary to connect the compressor common wires.

Continued on the next page...


Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 16 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


HomeWorks QS Palladiom HVAC Controller Wiring Diagrams (continued)
Conventional Systems (continued)

Diagram 3: Heat only system with no fan


24 V~
W 5 Heat 1 transformer
RH 6 24 V~
RC 7 L1 (hot)
Y1 8 L2
Common
Y2 9
G 10
W2 11
RW2 12

Controller power*
AO
4 G 3 5
RH

Diagram 4: Heat only system with fan


24 V~
W 5 Heat 1 transformer
RH 6 24 V~
RC 7 L1 (hot)
Y1 8 L2
Common
Y2 9
G 10 Fan
W2 11
RW2 12

Controller power*
AO
4 G 3 5
RH

* If the signal source from the HVAC system is not 12 – 24 V~ / 24 V-, use a separate supply to power the HomeWorks QS Palladiom HVAC controller.

Continued on the next page...


Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 17 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


HomeWorks QS Palladiom HVAC Controller Wiring Diagrams (continued)
Conventional Systems (continued)

Diagram 5: Cool only system


24 V~
W 5 transformer
RH 6 24 V~
RC 7 L1 (hot)
Y1 8 Compressor L2
Common
Y2 9
G 10 Fan
W2 11
RW2 12

Controller power*
4 G 3
AO
5
R

* If a secondary transformer is available to power the auxiliary heat, connect the auxiliary transformer to pin 12 (RW2).
** If the signal source from the HVAC system is not 12 – 24 V~ / 24 V-, use a separate supply to power the HomeWorks QS Palladiom HVAC controller.

Continued on the next page...


Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 18 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


HomeWorks QS Palladiom HVAC Controller Wiring Diagrams (continued)
Fan Coil Units
2-pipe Systems
Diagram 6: 2-pipe system, On / off valve, 3-speed fan, changeover sensor
24 V~
Valve 5 Valve transformer
R 6 24 V~
RFAN 7 L1 (hot)
G3 8 Fan high L2
Common
G2 9 Fan medium
G1 10 Fan low
11
12

Controller power*
AO (RH)
4 G 3 5

Common

Changeover sensor†

Diagram 7: 2-pipe system, On / off valve, 0 – 10 V controlled fan, changeover sensor
24 V~
Valve 5 Valve transformer
R 6 24 V~
RFAN 7 L1 (hot)
G3 8 L2
Common
G2 9
G1 10
11
12

Controller power*
AO (RH)
4 G 3 5

Common
Common
0–10 V-**
Fan Changeover sensor†
* If the signal source from the HVAC system is not 12 – 24 V~ / 24 V-, use a separate supply to power the Palladiom HVAC controller.
** When using 0–10 V- fan or valve control, a different power supply must be used to power the Palladiom HVAC controller and the 0–10 V- fan/valve actuators. For more
information, see Application Note #651 (048651) at www.lutron.com

 Semitec 103AT or equivalent – NTC 10 k at 25 °C

Continued on the next page... Customer Assistance:


1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 19 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


HomeWorks QS Palladiom HVAC Controller Wiring Diagrams (continued)
Fan Coil Units (continued)
2-pipe Systems (continued)
Diagram 8: 2-pipe system, 0 – 10 V valve, 3-speed fan, changeover sensor
24 V~
Valve 5 transformer
R 6 24 V~
RFAN 7 L1 (hot)
G3 8 Fan high L2
Common
G2 9 Fan medium
G1 10 Fan low
11
12

Controller power*
AO (RH)
4 G 3 5

Valve Common
0–10 V-**
Common
Changeover sensor†

Diagram 9: 2-pipe system, 0 – 10 V valve, 0 – 10 V controlled fan, changeover sensor
24 V~
Valve 5 transformer
R 6 24 V~
RFAN 7 L1 (hot)
G3 8 No relay L2
output used. Common
G2 9
G1 10
11
12

Controller power*
AO (RH)
4 G 3 5

Valve Common
0–10 V-** Common
Fan Changeover sensor†
* If the signal source from the HVAC system is not 12 – 24 V~ / 24 V-, use a separate supply to power the Palladiom HVAC controller.
** When using 0–10 V- fan or valve control, a different power supply must be used to power the Palladiom HVAC controller and the 0–10 V- fan/valve actuators. For more
information, see Application Note #651 (048651) at www.lutron.com

 Semitec 103AT or equivalent – NTC 10 k at 25 °C

Continued on the next page... Customer Assistance:


1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 20 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


HomeWorks QS Palladiom HVAC Controller Wiring Diagrams (continued)
Fan Coil Units (continued)
4-pipe Systems

Diagram 10: 4-pipe system, On / off valve, 3-speed fan


24 V~
HVALVE 5 Hot valve transformer
RH 6 24 V~
RFAN 7 L1 (hot)
G3 8 Fan high L2
Common
G2 9 Fan medium
G1 10 Fan low
CVALVE 11 Cold valve
RC 12

Controller power*
AO (RH)
4 G 3 5

Common

Diagram 11: 4-pipe system, On / off valve, 0 – 10 V controlled fan


24 V~
HVALVE 5 Hot valve transformer
RH 6 24 V~
RFAN 7 L1 (hot)
G3 8 L2
Common
G2 9
G1 10
CVALVE 11 Cold valve
RC 12

Controller power*
AO (RH)
4 G 3 5

Common
Common
0–10 V-**
Fan

* If the signal source from the HVAC system is not 12 – 24 V~ / 24 V-, use a separate supply to power the Palladiom HVAC controller.
** When using 0–10 V- fan or valve control, a different power supply must be used to power the Palladiom HVAC controller and the 0–10 V- fan/valve actuators. For more
information, see Application Note #651 (048651) at www.lutron.com

Continued on the next page... Customer Assistance:


1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 21 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


HomeWorks QS Palladiom HVAC Controller Wiring Diagrams (continued)
Fan Coil Units (continued)
4-pipe Systems (continued)
Diagram 12: 4-pipe system, 0 – 10 V valve, 3-speed fan
24 V~
HVALVE 5 transformer
RH 6 24 V~
RFAN 7 L1 (hot)
G3 8 Fan high L2
Common
G2 9 Fan medium
G1 10 Fan low
CVALVE 11
RC 12

Controller power*
AO (RH)
4 G 3 5

Hot valve Common


Common
0–10 V-**

Cold valve

Diagram 13: 4-pipe system, 0 – 10 V valve, 0 – 10 V controlled fan


24 V~
HVALVE 5 transformer
RH 6 24 V~
RFAN 7 L1 (hot)
G3 8 No relay L2
output used. Common
G2 9
G1 10
CVALVE 11
RC 12

Controller power*
AO (RH)
4 G 3 5

Hot valve Common


Common
0–10 V-**
Fan
Cold valve
* If the signal source from the HVAC system is not 12 – 24 V~ / 24 V-, use a separate supply to power the Palladiom HVAC controller.
** When using 0–10 V- fan or valve control, a different power supply must be used to power the Palladiom HVAC controller and the 0–10 V- fan/valve actuators. For more
information, see Application Note #651 (048651) at www.lutron.com

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 22 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


User Interface
Display backlighting 1 System off 2 °F / °C indicator
Heating on 3, 4
Schedule on / off (hold) 5
Auxiliary heat on 6
Auto Off Heat setpoint 7
Only AUTO On
Cooling on  3, 4
Aux Heat On Set
OFF
Cool On
Room temperature
Auto Set
On
Auto Auto Cool setpoint 7
Fan mode  8
Local hold button 9
Auto High

Raise room setpoint


Medium Low

Select system heat, cool, Lower room setpoint


only aux, auto, or off 8

Dynamic Backlight Management (DBM)


Change fan mode sensor location

1
 urns on when any button is pressed. Turns off after 10 seconds of inactivity (programmable). Dynamic Backlight Management (DBM) automatically adjusts backlight intensity
T
based on ambient lighting conditions.
2
Room temperature and “OFF” are shown when system is off.
3
Icons are animated when system is actively heating / cooling.
4
Icons flash if system is temporarily delayed for HVAC equipment protection.
5
Indicates HVAC system timeclock event status.
6
“Aux” indicates that auxiliary heat is running with the other heat stages. “Only Aux” indicates that auxiliary heat is running without the other heat stages (emergency heat).
7
Display shows the heat or cool setpoint. The first raise/lower button press activates the LCD backlight. Additional raise/lower button presses adjust the setpoint.
8
Applicable modes are configurable via the HomeWorks QS software.
9
Enables / disables HVAC system timeclock events.

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 23 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Remote Temperature Sensor
If it is not possible to follow the recommended mounting guidelines on page 10, use an indoor remote
temperature sensor for proper temperature control. The internal thermostat sensor must be disabled through
advanced programming via the thermostat. See the thermostat programming guide.

Wired Flush Mount Sensor (LR-TEMP-FLSH) Front View Side View


) Flush mount on wall in the area to be controlled. 0.75
) Field paintable to match decor. (19)
0.75 4
(19) (102)
Wiring
Use 22 AWG (0.5 mm2) twisted, shielded pair wiring. Maximum wire length: 100 ft (30.5 m)

HomeWorks QS Palladiom
HVAC controller

Isolated common Wired flush


mount sensor
Remote temperature sensor

Mounting
Use appropriate mounting instructions from the Mounting section on page 10.

Wall Self threading


Sensor
wall insert

Wall
0.5 in (13 mm)
ide
Outs
pilot hole

Inside Wall

Wired flush
mount sensor HomeWorks
QS Palladiom
thermostat
4 ft to 5 ft
(1.2 m to 1.5 m)

HomeWorks QS Palladiom
HVAC controller

Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)
www.lutron.com/support 24 +44.(0)20.7680.4481 (Europe)
product specifications 3691033b 05.03.2017

HomeWorks QS Palladiom HVAC Solution


Colors and Finishes
Architectural Matte Finishes Architectural Metal Finishes

Almond Bright Brass


AL BB

Beige Bright Chrome


BE BC

Black Bright Nickel


BL BN

Brown Satin Brass


BR SB

Gray Satin Chrome


GR SC

Ivory Satin Nickel


IV SN

Light Almond
LA

Sienna
SI

Taupe
TP

White
WH

Glass Finish

Clear Black Glass


CBL

Clear White Glass


CWH

• Due to printing limitations, colors and finishes shown cannot be guaranteed to perfectly match actual
product colors.
• Color chip keychains are available for more precise color matching:
- Architectural Matte Finishes: AM-CK-1
- Architectural Metal Finishes: AMTL-CK-1

Lutron, )Lutron, HomeWorks, and Palladiom are trademarks of Lutron Electronics Co. Inc., registered in the U.S. and other countries.
Mitsubishi is a registered trademark of Mitsubishi Electric Corporation.
CoolAutomation is a trademark of CoolAutomation Ltd.
LG is a registered trademark of LG Corp.
Daikin is a registered trademark of Daikin Industries, Ltd.
NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.