Академический Документы
Профессиональный Документы
Культура Документы
A. LIMITATIONS OF USE:
1) UL Listing
UL File Numbers: E18964/ E51461
3) Locations:
Dry, damp, wet per article 310-8 of the 2008 NEC.
4) Wiring Methods:
In conduit or approved raceway and, in sizes 1/0 AWG and larger, in cable tray
per article 392.3 (B) (1).
B. APPLICATION CONDITIONS:
Preparation
A. Immediately prior to pulling cable into conduit or duct, any dirt, scale, water, or other
foreign substances should be removed. This can be accomplished by the use of
mandrels and duct cleaners which are available from several sources.
B. Whenever the cable to be pulled will enter a manhole or be installed in cable trays,
auxiliary pulleys may be required to ensure that the bending radius is sufficiently
large.
The following recommendations should be followed whenever cables must be pulled, whether
into conduit, duct, cable tray, or an open trench. This will increase the likelihood of a successful
pull; however, these recommendations are not expected to cover every situation which might be
encountered.
Methods of Gripping Cables
A. Basketweave pulling grip – This is a device consisting of a woven metal mesh with
loops at one end for attachment to the pulling line. It acts similarly to a “Chinese
finger grip” in that as the tension is increased, it will grip more tightly. They are
generally used with light to medium weight cables on relatively short pulls.
B. Pulling eye – Pulling eyes are connected directly to the conductor (s). Commercially
available eyes are generally applied by crimping them tightly around the conductor.
This necessitates having the correct size eye and crimping dies available for each
range of wire size to be pulled. Medium to heavy cables and/or long pulling lengths
will require the use of pulling eyes.
C. Forming the conductor into a loop – This method has been used for all types of pulls.
Care must be taken to ensure that the method of forming the loop will withstand the
tension required to pull the cable.
D. Swivels – A swivel should be used with all methods of attachment to ensure free
rotation.
The PVC and Nylon are thermoplastic materials and may stiffen at temperatures lower
than -10ºC (14ºF) per 2008 NEC article 310.13.
• During winter months, it is better to store the cable indoors with controlled
temperature of 65ºF or higher. If you did store it outside, please bring the reel
inside in a heated room (65ºF) for 24 hours prior to the installation.
• Install the cable as soon as possible after removing it from the storage area.
• Do not impact the cable when it is very cold by dropping the cable end on the
floor or by dropping an object on the cable
5) PULLING LUBRICANTS:
AIW recommends the use of pulling lubricants to reduce the coefficient of friction. The
lubricant must be removed from the cable where the terminations or splices are to be
made. It is incumbent upon the user of any lubricant to verify its suitability for their
particular application.
Generous amounts of lubricant should be applied to both the cable and conduit to
reduce friction in conduit or duct pulls.*
TABLE I
MAXIMUM PULLING TENSIONS FOR TFFN & THHN 1 / C WIRES & CABLES
NOTES:
1. All values rounded to nearest pound.
2. The above pulling tensions are based on pulling by the conductors. Do not exceed either
1,000 pounds or the value listed above when pulling by the jacket.
3. The values 2 thru 61 cables include a reduction factor to account for unequal tensions
during installation.
Product Specification
TABLE II
CONDUCTOR
SIZE 1 CABLE 2 CABLES 3 CABLES 4 CABLES
10 AWG 83 138 208 249
9 AWG 105 174 262 314
8 AWG 132 220 330 396
6 AWG 210 350 525 630
4 AWG 335 555 835 1,000
2 AWG 530 885 1,325 1,590
NOTES:
1. All values rounded to nearest pound.
2. The above pulling tensions are based on pulling by the conductors. Do not exceed either 1,000
pounds or the value listed above when pulling by the jacket.
3. The values 2 thru 4 cables include a reduction factor to account for unequal tensions during
installation.
* Although the conductor (s) will withstand the tension given, it is recommended that the tension not
exceed 6,000 pounds on single conductor cable or 7,000 pounds on multi-conductor cables when pulling
by the conductors.