MULTIPLES OF CURRENT SETTING, C

100
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 .2 .2
1000 1000 Fixed Hi-Range Instantaneous
900 900 50/60 Hz Operation Only
800 800
700 700

TIME IN SECONDS
600 Long-time 600
.1 .1
500 Delay Bands 500 .09 Insulated Case .09
.08 Circuit Breaker .08
400 400 .07 Total Clearing .07
Time
.06 .06
300 300
.05 .05

.04 Application .04


200 200 Determines
End of Curve
.03 .03

4 .02 .02
100 100
90 90
80 80
70 70
60 60
3 .01 .01
TIME IN SECONDS

50 50 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10
40 40 MULTIPLES OF BREAKER SHORT-TIME RATING, H
2 Maximum Total
30 Clearing Time 30
Breaker Short-time Rating (H)
Type Max. Frame Amps (Amps. rms symmetrical)

20 20 ICCB 800 25,000


1600, 2000 30,000
1 2500, 3000, 4000 42,000
1.5

Minimum Total
10 2.0 Clearing Time 10
Short-
9 time 9
8 8
7 2.5 7
6 6
5 5
12 t In
3.0 MULTIPLES OF INSTANTANEOUS PICKUP
4 4 4 4

3 4.0 3 3 3

Instantaneous Pickup Settings in multiples of rating plug amps (X):


Pickup Settings on trip units without Short-time function:
2 2 2 2
12 t Out 5.0 For (S) = 150 thru 3000 amps: 1.5 to 10.0, in increments of 0.5
For (S) = 4000 amps: 1.5 to 9.0, in increments of 0.5
Pickup Settings on trip units with Short-time function:
For (S) = 150 thru 2000 amps: 1.5 to 15.0, in increments of 0.5
For (S) = 2500 thru 3000 amps: 1.5 to 13.0, in increments of 0.5
For (S) = 4000 amps: 1.5 to 9.0, in increments of 0.5
1 1 1
.9 7.0 .9 .9 .9
.8 .8 .8 .8
.7 .7 .7 .7
GES-9866

GES-9866
.6 9.0 .6 .6 .6
.5 .5 .5 .5
Max Application
.4 .4 .4 .4
Determines
End of Curve
.3 .3 .3 .3
Int

.2 .2 .2 .2

Min

.1 .1 .1 .1
.09 .09 .09 .09
.08 .08 .08 .08

TIME IN SECONDS
.07 .07 .07 .07
.06 .06 .06 .06
.05 .05 .05 .05

.04 .04 .04 .04

.03 .03 .03 .03

.02 .02 .02 .02


Application
Determines
End of Curve

.01 .01 .01 .01


.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30
100

MULTIPLES OF CURRENT SETTING, C MULTIPLES OF INSTANTANEOUS PICKUP

Insulated Case Circuit Breakers


GES-9866
GE Consumer & Industrial -
Electrical Distribution Types TP, THP, TC, THC
Available Ratings (Amperes) Molded Case Circuit Breakers Adjustments
Breaker Current Rating Plug
Type Model Frame Sensor (S) (X) R-Frame Long-time Function Current Settings (C):
0.50 to 1.0 in 0.05 increments
MCCB TRL/TRP 1600 1000
1600
400, 600, 800, 1000
600, 800, 1000, 1200, 1600 with MicroVersaTrip PlusTM multiples of rating plug amps (X).
Delay Bands: 1, 2, 3 and 4.
2000
ICCB TP/THP/ 800
2000
200
800, 1000, 1200, 1600, 2000
100, 150, 200 or MicroVersaTrip PMTM Short-time Function Pickup Settings:
TC/THC 400
800
150, 200, 225, 250, 300, 400
300, 400, 500, 600, 700, 800 Digital RMS Trip Units 1.5 to 9.0 in 0.5 increments
1600 1000 400, 600, 800, 1000 multiples of current setting (C).
1600 600, 800, 1000, 1200, 1600
2000 2000 800, 1000, 1200, 1600, 2000 Long-time Delay, Short-time Delay, and Delay Bands: MIN, INT, MAX; I2t In/Out
2500 1000
2000
400, 600, 800, 1000
800, 1000, 1200, 1600, 2000
Instantaneous Time-Current Curves Instantaneous Function:
2500 1600, 2000, 2500 See Curves above.
3000 3000 2000, 2500, 3000 Curves apply at 50 through 400 Hertz S: Current Sensor Amps
4000 4000 1500, 2000, 2500, 3000, 4000
and from -20°C to 55°C breaker ambient X: Rating Plug Amps
Voltage Ratings: 600 Vac, maximum C: Current Setting Amps
Note: Operation above 60 Hertz requires thermal
H: Breaker Short-time Rating Amps
and interrupting derating of the circuit breaker.

02.93 1M