DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

#REF!
CONTRACT TITLE CONTRACT No. #REF!

Calculation for GROUND FLOOR NORTH Rev. 0


Design Safety Margin 0 %
Supply Air Temperature 13.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
NEW LOUNGE 66,743 83,195 23.0 66,743 83,195 0.80 5,453
RETAIL 16,787 19,313 23.0 16,787 19,313 0.87 1,371
- - - - -
83,530 102,508 23.0 83,530 102,508 0.81 6,824
- - - - -
- - - TOTAL 13,649
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS 167,060 205,016 (W) 167,060 205,016 0.81 ###
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for FIRST FLOOR NORTH Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for FIRST FLOOR SOUTH Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
NORTH - - (W)
ZONE TOTAL - - (W)
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for SECOND FLOOR SOUTH Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
NORTH #REF! #REF! (W)
ZONE TOTAL #REF! #REF! (W)
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for THIRD FLOOR SOUTH Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
NORTH #REF! #REF! (W)
ZONE TOTAL #REF! #REF! (W)
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for FOURTH FLOOR NORTH Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for FOURTH FLOOR SOUTH Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
NORTH - - (W)
ZONE TOTAL - - (W)
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for FIFTH FLOOR NORTH Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for FIFTH FLOOR SOUTH Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
NORTH - - (W)
ZONE TOTAL - - (W)
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for SIXTH FLOOR NORTH Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for SIXTH FLOOR SOUTH Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
NORTH - - (W)
ZONE TOTAL - - (W)
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for LANDLORDS SERVICES Rev. 0


Design Safety Margin 5 %
Supply Air Temperature 12.0 (DegC)

Room Calc. Calc. Room Adjusted Adjusted RSHR Supply


Ref. Qs Qt Temp. Qs Qt Airflow
(W) (W) (DegC) (W) (W) (l/s)
22.0 - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
- - - - -
TOTALS - - (W) - - #DIV/0! ###
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF AHU01 ENERGY LOADS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0

CALCULATION FOR: AHU01 - OFFICE TEMPERED AIR


SCHEDULE OF ZONES SERVED:
ZONE FLOOR FLOOR
POPULATION (CUM/S)
7 #REF! #VALUE!
6 #REF! #VALUE!
5 #REF! #VALUE!
4 #REF! #VALUE!
3 #REF! #VALUE!
3 #REF! #VALUE!
2 #REF! #VALUE!
1 #REF! #VALUE!
TOTAL FOR ZONE #REF! #VALUE!

TOTAL FOR TENANTS #REF! #VALUE! (CUM/S)

HEAT RECOVERY EFFICIENCY 0 (%)


INSIDE SUMMER 22.0 (DEG C)
INSIDE WINTER 21.0 (DEG C)
OUTSIDE SUMMER 28.0 (DEG C)
OUTSIDE WINTER -6.0 (DEG C)

COOLING LOAD #VALUE! (kW)


HEATING LOAD #VALUE! (kW)
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF AHU02 ENERGY LOADS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0

CALCULATION FOR: AHU02 - TOILET SUPPLY AIR


SCHEDULE OF TOILETS SERVED:
FLOOR FLOOR
AIRFLOW
7 0.000
6 0.000
5 0.000
4 0.000
3 0.000
2 0.000
1 0.000
0 0.000

TOTAL FOR TOILETS 0.000 (CUM/S)

HEAT RECOVERY EFFICIENCY 0 (%)


INSIDE SUMMER 22.0 (DEG C)
INSIDE WINTER 21.0 (DEG C)
OUTSIDE SUMMER 28.0 (DEG C)
OUTSIDE WINTER -6.0 (DEG C)

COOLING LOAD 0.0 (kW)


HEATING LOAD 0.0
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF AHU03 ENERGY LOADS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
CALCULATION FOR: AHU03

DESIGN DATA:
ROOM TEMPERATURE 23.0 (SUMMER)
ROOM TEMPERATURE 21.0 (WINTER)
OUTSIDE SUMMER 31.0 (db C) 22.0 (wb C)
OUTSIDE WINTER -8.0 (db C) -8.0 (wb C)
POPULATION 450
FLOOR AREA 891 (sqm)

OUTSIDE AIR DESIGN DATA:


OUTSIDE AIR PER PERSON 8.0 (l/s) 3.600 (cum/s)
OUTSIDE AIR PER SQM 1.30 (l/s/sqm) 1.158 (cum/s)
MAX OUTSIDE AIR FLOW 3.600 (cum/s)

SELECTED OUTSIDE AIR 3.600 (cum/s)

CALCULATED HEAT LOADS:


SEASON SUMMER WINTER
DESIGN SAFETY MARGIN 0 (%) 15 (%)
HEVACOMP SENSIBLE LOAD 78,417 (W) 0 (W)
HEVACOMP TOTAL LOAD 97,394 (W) 0 (W)
ADJUSTED SENSIBLE LOAD 78,417 (W) 0 (W)
ADJUSTED TOTAL LOAD 97,394 (W) 0 (W)
RSHR 0.81 -

SUPPLY AIR FLOW RATE CALCULATION:


SEASON SUMMER WINTER
SUPPLY AIR/ROOM TEMP. DIFF. 10.0 (K) 0.0 (K)
MASS FLOW RATE 7.688 (kg/s) 7.688 (kg/s)
VOLUME FLOW RATE 6.407 (cum/s) 6.407 (cum/s)
PEAK MASS FLOW 7.688 (kg/s)
PEAK AIR FLOW 6.407 (cum/s)
RESULTANT OA 56.2 (%)

SUMMER PSYCHOMETRICS:
LIGHTING GAIN 15 (W/sqm)
PEAK LIGHTING LOAD 13,365 (W)
% LIGHTING GAIN TO RETURN AIR 40 (%)
RA CEILING TEMP. RISE 1.6 (Deg C)
RECIRCULATION TEMPATURE 24.6 (Deg C)
SUPPLY FAN PRESSURE 750 (Pa)
SUPPLY FAN GAIN 0.97 (Deg C) (FOR MOTOR WITHIN AIR STREAM DIVIDE FAN TOTAL PR
MIXED TEMPERATURE 28.2 (Deg C)
COOLING COIL (ON COIL) 28.2 (db C) 20.5 (wb C)
COOLING COIL (OFF COIL) 12.0 (db C) 11.5 (wb C)
TOTAL COOLING LOAD 198,111 (W)
CHW TEMP. DIFF. 6.0 (K)
CHW FLOW RATE 7.899 (l/s)
ESTIMATED CHW PIPE SIZE 100

WINTER PSYCHOMETRICS:
COIL FROST MAIN
HEATING COIL (ON COIL) -8.0 (db C) 13.7 (db C)
HEATING COIL (OFF COIL) 8.0 (db C) 21.0 (db C)
TOTAL HEATING LOAD 58,752 (W) 57,283 (W)
LTHW TEMP. DIFF. 11.0 (K) 11.0 (K)
LTHW FLOW RATE 1.278 (l/s) 1.246 (l/s)
ESTIMATED LTHW PIPE SIZE 50 50
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFFFF CHW DISTRIBUTION .

CONTRACT TITLE #REF! CONTRACT No. #REF!


CALCULATION FOR: WHOLE BUILDING Rev. 0
TENANT LANDLORD
CHW FLOW TEMPERATURE 11.0 6.0 (Deg C)
CHW RETURN TEMPERATURE 15.0 12.0 (Deg C)
ZONE LOADS:
FLOOR/PLANT NORTH NORTH NORTH NORTH SOUTH SOUTH SOUTH SOUTH LAND- LAND- LAND-
FLOOR FLOOR FLOOR RISER FLOOR FLOOR FLOOR RISER LORD LORD LORD
LOAD SPARE CHW CHW LOAD SPARE CHW CHW LOAD CHW RISER
(kW) (kW) (l/s) (l/s) (kW) (kW) (l/s) (l/s) (kW) (l/s) (l/s)
6 0.0 #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE!
5 0.0 #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE!
4 0.0 #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE!
3 #VALUE! #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE!
2 #VALUE! #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE!
1 0.0 #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE!
0 205.0 #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! #VALUE! 0.0 #VALUE! #VALUE!
-1 0.0 0.000 #VALUE!
AHU01 #VALUE! #VALUE!
AHU02 0.0 0.000
AHU03 198.1 7.899

TOTAL CHW FLOW #VALUE! (l/s)

PUMP DATA:
PRIMARY PUMPS #VALUE! (l/s) #VALUE! ESTIMATED PIPE SIZE
TENANTS PUMPS #VALUE! (l/s) #VALUE! ESTIMATED PIPE SIZE
LANDLORD PUMPS #VALUE! (l/s) #VALUE! ESTIMATED PIPE SIZE
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFFF CHILLER SIZING .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0

CALCULATION FOR: WHOLE BUILDING

HEVACOMP LOAD 0 (kW) DESIGN MARGIN 5 (%)


DESIGN MARGIN 0 (kW)
PLANTROOMS 0 (kW)
AHU01 LOAD #VALUE! (kW)
AHU02 LOAD 0 (kW)
AHU03 LOAD 198 (kW)
SPARE CAPACITY #VALUE! (kW)
TOTAL LOAD #VALUE! (kW)

CHILLER RATING #VALUE! (kW)

MINIMUM CHW FLOW #VALUE! (l/s)

LOAD #VALUE! (W/SQM)


10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE CONTRACT No. #REF!


#REF!
Rev. 0
Calculation for GROUND FLOOR NORTH
Design Safety Margin 10 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
NEW LOUNGE 26,140 21 28,754 5,453 25.3
RETAIL 6,099 21 6,709 1,371 25.0
- - - -
- - - -
- - 6,824 ###
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS 32,239 (W) 35,463 AVERAGE = 25.2
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for GROUND FLOOR SOUTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for FIRST FLOOR NORTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for FIRST FLOOR SOUTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for SECOND FLOOR NORTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for SECOND FLOOR SOUTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for THIRD FLOOR NORTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for THIRD FLOOR SOUTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:41 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for FOURTH FLOOR NORTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:42 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for FOURTH FLOOR SOUTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:42 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for FIFTH FLOOR NORTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:42 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for FIFTH FLOOR SOUTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:42 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for SIXTH FLOOR NORTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:42 472092470.xls 04/24/2020

DEFGFFFFFFFFF MECHANICAL CALCULATIONS .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
Calculation for SIXTH FLOOR SOUTH
Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Qs Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
21 - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:42 472092470.xls 04/24/2020

DEFGFFFFFFFFF LANDLORDS HEATLING LOADS .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for LANDLORD ZONES Rev. 0


Design Safety Margin 20 %

Room Calc. Room Adjusted Supply Supply Air


Ref. Loss Temp. Loss Airflow Temperature
(W) (DegC) (W) (l/s) (DegC)
002 18 - - -
003 - - - -
004 - - - -
005 - - - -
102 - - - -
103 - - - -
104 - - - -
105 - - - -
202 - - - -
203 - - - -
204 - - - -
205 - - - -
302 - - - -
303 - - - -
304 - - - -
305 - - - -
402 - - - -
403 - - - -
404 - - - -
405 - - - -
502 - - - -
503 - - - -
504 - - - -
505 - - - -
602 - - - -
603 - - - -
604 - - - -
605 - - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
TOTALS - (W) - AVERAGE = #DIV/0!
10:09:42 472092470.xls 04/24/2020

DEFGFFFFFFFFFFF LTHW DISTRIBUTION .

CONTRACT TITLE #REF! CONTRACT No. #REF!


CALCULATION FOR: WHOLE BUILDING Rev. 0
TENANT LANDLORD
% SPARE CAPACITY 0 % LTHW FLOW TEMPERATURE 60 82 (Deg C)
LTHW RETURN TEMPERATURE 55 71 (Deg C)
ZONE LOADS:
FLOOR/PLANT NORTH NORTH NORTH NORTH SOUTH SOUTH SOUTH SOUTH LAND- LAND- LAND-
FLOOR FLOOR FLOOR RISER FLOOR FLOOR FLOOR RISER LORD LORD LORD
LOAD SPARE LTHW LTHW LOAD SPARE LTHW LTHW LOAD LTHW RISER
(kW) (kW) (l/s) (l/s) (kW) (kW) (l/s) (l/s) (kW) (l/s) (l/s)
6 0.0 0.0 0.000 1.697 0.0 0.0 0.000 0.000 0.0 0.000 #VALUE!
5 0.0 0.0 0.000 1.697 0.0 0.0 0.000 0.000 0.0 0.000 #VALUE!
4 0.0 0.0 0.000 1.697 0.0 0.0 0.000 0.000 0.0 0.000 #VALUE!
3 0.0 0.0 0.000 1.697 0.0 0.0 0.000 0.000 0.0 0.000 #VALUE!
2 0.0 0.0 0.000 1.697 0.0 0.0 0.000 0.000 0.0 0.000 #VALUE!
1 0.0 0.0 0.000 1.697 0.0 0.0 0.000 0.000 0.0 0.000 #VALUE!
0 35.5 0.0 1.697 1.697 0.0 0.0 0.000 0.000 0.0 0.000 #VALUE!
-1 0.0 0.000 #VALUE!
AHU01 #VALUE! #VALUE!
AHU02 0.0 0.000
AHU03 116.0 2.524

PUMP DATA:
PRIMARY PUMPS #VALUE! (l/s) #VALUE! ESTIMATED PIPE SIZE
TENANTS PUMPS 1.697 (l/s) 50 ESTIMATED PIPE SIZE
LANDLORD PUMPS #VALUE! (l/s) #VALUE! ESTIMATED PIPE SIZE
10:09:42 472092470.xls 04/24/2020

DEFGFFFFFFFFF BOILER SIZING .

CONTRACT TITLE #REF! CONTRACT No. #REF!


Rev. 0
CALCULATION FOR: WHOLE BUILDING

RUNNING DATA:
HEVACOMP HEATING LOAD 0 (kW)
10% SPARE CAPACITY ON NET AREA 0 (kW)
HEVACOMP INFILTRATION LOAD 0 (kW)
% INFILTRATION TO WHOLE BUILDING 60 (%)
ACTUAL LOSS + MARGIN 0 (kW)

START UP DATA:
% MORNING BOOST 20 (%)
PREHEAT LOAD 0 (kW)

VENTILATION DATA:
AHU01 #VALUE! (kW)
AHU02 0 (kW)
AHU03 116 (kW)
VENTILATION LOAD #VALUE! (kW)

HWS DATA:
HWS LOAD 0 (kW)

BOILER DATA: RUNNING START UP


LOAD #VALUE! #VALUE! (kW)
NUMBER OF BOILERS 2 2
INDIVIDUAL BOILER RATING #VALUE! #VALUE! (kW)
LOAD #VALUE! (W/SQM)

PUMP DATA:
MINIMUM PRIMARY FLOW #VALUE! (l/s)

LTHW FLOW TEMPERATURE 82 (Deg C)


LTHW RETURN TEMPERATURE 71 (Deg C)
10:09:42 472092470.xls 04/24/2020

DEFGFFFFFFFFF TOILET EXTRACT .

CONTRACT TITLE #REF! CONTRACT No. #REF!

Calculation for TYPICAL TOILET Rev. 0

Room Room Dimensions Room Air Extract


Ref. Length Width Height Volume Changes Airflow
(m) (m) (m) (cum) per hr. (l/s)
- ? -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
Totals 0 (cum) 0
10:09:42 472092470.xls 04/24/2020

DEFGFFFFFFFFFF GAS MAIN CALCULATION .

CONTRACT TITLE BATTLE CONTRACT No. #REF!


Rev. 0
CALCULATION BASED ON CIBSE TABLE C4.45

CALCULATION FOR: WHOLE BUILDING


GAS CV 37.80
GAS FLOWRATE CALCULATION: GAS DENSITY 0.68
PLANT HEAT PLANT HEAT GAS GAS
REF. OUTPUT EFFICIENCY INPUT FLOW FLOW
(kW) (%) (kW) (l/s) (cum/hr)
B1 80 87 90 2.392 8.61
B2 80 87 90 2.392 8.61
B3 80 87 90 2.392 8.61
T Dryer 12 80 14 0.381 1.37
andrews 19 80 23 0.603 2.17
- - -
- - -
- - -
- - -

GAS MAIN SIZING:


SECTION SECTION SECTION SECTION SECTION SECTION SECTION SECTION TOTAL
GAS FLOW PIPE K PIPE PD EL PD PD
(l/s) LENGTH K VALUES DIA. (Pa) (Pa) (Pa)
1 2 8.159 3 0.00 80 #N/A #N/A #N/A #N/A
2 3 7.778 4 0.00 80 #N/A #N/A #N/A #N/A
3 4 7.175 10 0.00 50 #N/A #N/A #N/A #N/A
4 5 4.783 2 0.00 50 #N/A #N/A #N/A #N/A
5 6 2.392 2 0.00 40 #N/A #N/A #N/A #N/A
6 7 - - 0 #N/A
7 8 - - 0 #N/A
8 9 - - 0 #N/A
9 10 - - 0 #N/A
TOTAL #N/A