CONTRACT TITLE CONTRACT No. #REF!
DESIGN DATA:
ROOM TEMPERATURE 23.0 (SUMMER)
ROOM TEMPERATURE 21.0 (WINTER)
OUTSIDE SUMMER 31.0 (db C) 22.0 (wb C)
OUTSIDE WINTER -8.0 (db C) -8.0 (wb C)
POPULATION 450
FLOOR AREA 891 (sqm)
SUMMER PSYCHOMETRICS:
LIGHTING GAIN 15 (W/sqm)
PEAK LIGHTING LOAD 13,365 (W)
% LIGHTING GAIN TO RETURN AIR 40 (%)
RA CEILING TEMP. RISE 1.6 (Deg C)
RECIRCULATION TEMPATURE 24.6 (Deg C)
SUPPLY FAN PRESSURE 750 (Pa)
SUPPLY FAN GAIN 0.97 (Deg C) (FOR MOTOR WITHIN AIR STREAM DIVIDE FAN TOTAL PR
MIXED TEMPERATURE 28.2 (Deg C)
COOLING COIL (ON COIL) 28.2 (db C) 20.5 (wb C)
COOLING COIL (OFF COIL) 12.0 (db C) 11.5 (wb C)
TOTAL COOLING LOAD 198,111 (W)
CHW TEMP. DIFF. 6.0 (K)
CHW FLOW RATE 7.899 (l/s)
ESTIMATED CHW PIPE SIZE 100
WINTER PSYCHOMETRICS:
COIL FROST MAIN
HEATING COIL (ON COIL) -8.0 (db C) 13.7 (db C)
HEATING COIL (OFF COIL) 8.0 (db C) 21.0 (db C)
TOTAL HEATING LOAD 58,752 (W) 57,283 (W)
LTHW TEMP. DIFF. 11.0 (K) 11.0 (K)
LTHW FLOW RATE 1.278 (l/s) 1.246 (l/s)
ESTIMATED LTHW PIPE SIZE 50 50
10:09:41 472092470.xls 04/24/2020
PUMP DATA:
PRIMARY PUMPS #VALUE! (l/s) #VALUE! ESTIMATED PIPE SIZE
TENANTS PUMPS #VALUE! (l/s) #VALUE! ESTIMATED PIPE SIZE
LANDLORD PUMPS #VALUE! (l/s) #VALUE! ESTIMATED PIPE SIZE
10:09:41 472092470.xls 04/24/2020
PUMP DATA:
PRIMARY PUMPS #VALUE! (l/s) #VALUE! ESTIMATED PIPE SIZE
TENANTS PUMPS 1.697 (l/s) 50 ESTIMATED PIPE SIZE
LANDLORD PUMPS #VALUE! (l/s) #VALUE! ESTIMATED PIPE SIZE
10:09:42 472092470.xls 04/24/2020
RUNNING DATA:
HEVACOMP HEATING LOAD 0 (kW)
10% SPARE CAPACITY ON NET AREA 0 (kW)
HEVACOMP INFILTRATION LOAD 0 (kW)
% INFILTRATION TO WHOLE BUILDING 60 (%)
ACTUAL LOSS + MARGIN 0 (kW)
START UP DATA:
% MORNING BOOST 20 (%)
PREHEAT LOAD 0 (kW)
VENTILATION DATA:
AHU01 #VALUE! (kW)
AHU02 0 (kW)
AHU03 116 (kW)
VENTILATION LOAD #VALUE! (kW)
HWS DATA:
HWS LOAD 0 (kW)
PUMP DATA:
MINIMUM PRIMARY FLOW #VALUE! (l/s)